Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.3 LAccepted-AOC BETHAL THIRUMALA TRIVANDRUM | THIRUVANANTHAPURAM | KERALA | 695001 | L1 | Accepted-AOC L1 | |
| 2 | L2₹13.8 L+₹49,122.17 (3.70%)Rejected-Finance CB 4190 SREE CHITHRA NAGAR PANGODE THIRUMALA P O THIRUVANANTHAPURAM 695 006 | THIRUVANANTHAPURAM | THIRUVANANTHAPURAM | KERALA | 695006 | L2 | Rejected-Finance L2 |
Tender Value
₹12.3 L
EMD Value
₹30,800
Closing Date
25 Jan 2025, 5:00 pmClosed
SUPERINTENDING ENGINEER
Superintending Engineer Main office Thiruvananthapuram Corporation
ELECTRIFICATION OF NEWLY PROPOSED BUILDING EXTENSION , PROVIDING AIR CONDITIONER TO ROOF TOP HALL AND RENOVATION OF PANEL BOARD AT MUDAVANMUGAL COMMUNITY HALL IN MUDAVANMUGAL WARD
2025_LSGD_727519_1
23/E16/1626088/24/Tender
Open Tender
Electrical Works
Item Rate
120 days
Thiruvananthapuram Corporation
Please refer Tender documents.
8 documents required · 8 mandatory
₹2,760
Yes
₹30,800
Yes
16 May 2025
18 Jan 2025
28 Jan 2025
18 Jan 2025
25 Jan 2025
18 Jan 2025
Amount
1.10.1 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group A
1.14.1 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire
1.25 Supplying and fixing two module stepped type electronic fan regulator on the existingmodular plate switch box including connections but excluding modular plate etc. as required.
1.33 Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
1.56 Supplying and fixing suitable size Gl box with modular plate and cover in front onsurface or in recess, including providng and fixing 2 Nos. 3 pin 5/6 A modular socket outlets and 2 Nos. 5/6 A modular switches, connection etc. as required. (For lightplugs to be used in non residential buildings).
1.58 Supplying and fixing PVC batten/ angle holder including connection etc. as required.
OD425998/2022-2023 Supply and providing the following types and power rated lamps in the existingfittings as required B22LED bulb 10 W
OD356573/2023-2024 Supplying and fixing cast aluminium bulk head fitting with mesh guard with 7W LEDbulb and giving connection etc. as required
1.24.1 Supplying and fixing following modular switch/ socket on the existing modular plate& switch box including connections but excluding modular plate etc. as required.5/6amps switch
1.24.3 Supplying and fixing following modular switch/ socket on the existing modular plate& switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.4 Supplying and fixing following modular switch/ socket on the existing modular plate& switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.5 Supplying and fixing following modular switch/ socket on the existing modular plate& switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
1.27.1 Supplying and fixing following size/ modules, GI box alongwith modular base &cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
1.27.2 Supplying and fixing following size/ modules, GI box alongwith modular base &cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
90.10.3.15 Supply and Fixing the following modular switches & accessories in the existing frontplates and giving necessary connections as required (RoHS compliant )32A DPswitch with indicator
90.10.3.33 Supply and Fixing the following modular switches & accessories in the existing frontplates and giving necessary connections as required (RoHS compliant )25A 3pinShuttered socket
90.4.1 Supply and installation of suitable size MS rod type fan clamp in the RCC slab as perIS 732 as required.
90.4.5.4Supply, Installation, testing and commissioning of ceiling fan of following sizesincluding wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mmFRLS PVC insulated, copper conductor, single core cable etc. as required.1200mm sweep - ceiling fan complete with service value minimum 4.0(cubmeter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper windingsuitable for 230V/240V single phase AC supply
90.4.8 Charges for cutting holes suitable for accommodating exhaust fans up to 305mmsweep including plastering colour washing etc. as required.
90.4.10 Conveyance, installation , testing and commissioning of exhaust fans of size up to450mm in the existing opening, fixing necessary anchor bolts / bolt and nuts etc., as required including giving connections with the supplied wire along with the exhaustfan.
Supply of 300/305mm sweep 1400 RPM heavy duty exhaust fan working on 230 V A/C in metal frameincluding all accessories as required (PWD approved make)
90.3.20.3Supply & installation of light fittings on TW round block<br>Supply, conveyance installation testing and commissioning the light fittings offollowing types made of CRCA with 0.5mm thickness complete with all accessoriesand lamps etc. directly on wall or ceiling with PVC round block neatly painted to suitthe fitting and giving connection with required length of 16/0.20mm 3 core copperconductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 1X20W LED Lamp with box type fixture
90.15.4.5Supply Conveyance, installation, testing and commissioning of 40W LED Flood lightoutput greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip makeCree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surgeprotection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should beseperatly accessible for maintenance (LM 79&80 certificates from NABL accreditedThird party lab to be produced mentioning chip manufacturer)
90.15.4.7Supply Conveyance, installation, testing and commissioning of 100W LED Floodlight output greater than 105lumen/W 4000-6000 K withIP 66 protection LED Chipmake Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartmentshould be seperatly accessible for maintenance (LM 79&80 certificates from NABLaccredited Third party lab to be produced mentioning chip manufacturer)
2.3.4Supplying and fixing following way, single pole and neutral, sheet steel, MCBdistribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted includingearthing etc. as required. (But without MCBIRCCB/Isolator16 way, Double door
2.10.1Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCB DBcomplete with connections, testing and commissioning etc. as required.Single pole
2.11 Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
2.12.1 Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.2 Supplying and fixing following rating, four pole, 415 volts, isolator in the existingMCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.14.2Supplying and fixing following rating, double pole, (single phase and neutral), 240volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes inthe existing MCB DB complete with connections, testing and commissioning etc. asrequired.40 amps
2.15.2Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts,residualcurrent circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes inthe existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
1.17.3Supplying and drawing following sizes of FRLS PVC insulated copper conductor,single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X1.5 sq.mm
1.17.12Supplying and drawing following sizes of FRLS PVC insulated copper conductor,single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x2.5 sq. mm
1.17.21Supplying and drawing following sizes of FRLS PVC insulated copper conductor,single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x4 sq. mm
1.21.1Supplying and fixing of following sizes of medium class PVC conduit along withaccessories in surface/ recess including cutting the wall and making good the same incase of recessed conduit as required.20 mm
90.12.7.14Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps notedalong with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3 core 10 sq mm with factory made clamp
90.12.7.28Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps notedalong with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 35 sq mm with factory madeclamp
90.12.7.32Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armouredaluminium power cable, 1.1 KV grade of the following sizes using clamps notedalong with the cables, spacing of clamps not exceeding 60cms, making good thedamages , colour washing etc. as required.3.5 core 120 sq mm
90.12.7.40Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armouredaluminium power cable, 1.1 KV grade of the following sizes using clamps notedalong with the cables, spacing of clamps not exceeding 60cms, making good thedamages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
90.12.9.2Supplying, laying and jointing of the following sizes of double wall corrugated(DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in theexisting trench50/38 mm or nearest size
9.1.7 Supplying and making end termination with brass compression gland and aluminium lugs forfollowing size of PVC insulated and PVC sheathed / XLPE aluminium conductorcable of 1.1 KV grade as required.3 X 10 sq. mm (22mm)
9.1.21Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductorcable of 1.1 KVgrade as required.3 1/2X 35 sq. mm (32mm)
9.1.32Supplying and making end termination with brass compression gland and aluminiumlugs forfollowing size of PVC insulated and PVC sheathed / XLPE aluminium conductorcable of 1.1 KVgrade as required.4 X 10 sq. mm (25mm)
2.1.4Providing and fixing following capacity TP&N disconnector fuse switch unit insidethe existing panel board with ISI marked HRC fuses including drilling holes incubicle panel, making connections, etc. as required.125 Amp TP & N
2.1.5Providing and fixing following capacity TP&N disconnector fuse switch unit insidethe existing panel board with ISI marked HRC fuses including drilling holes incubicle panel, making connections, etc. as required.160 Amp TP&N
2.1.6 Providing and fixing following capacity TP&N disconnector fuse switch unit insidethe existing panel board with ISI marked HRC fuses including drilling holes incubicle panel, making connections, etc. as required.200 Amp TP&N
90.14.11.17 MCCB AccessoriesSupply and fixing kastel interlock kit up to 250A.
2.1.2 Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.63 Amp TP & N
2.1.1 Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.32 Amp TP & N
2.2.15 Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.200 Amp, 36 KA
OD202995/2023-2024 Supply and fixing AuXC - 2000 Controller with wire harness & Illuminated Push button assembly with wire harness
OD202871/2023-2024 Supply and fixing 160 A 4 pole ATS on existing panel board, connections etc.
OD427370/2022-2023 Supply and providing Red/Green/Yellow colours LED indicator
OD427371/2022-2023 Supply and providing Multifunction meter to read: V, A, F, 3 phase accuracy class 1
5.4Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick includingaccessories, and providing masonry enclosure with cover plate having lockingarrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt asrequired.
5.10Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earthelectrode including connection with brass nut, bolt, spring, washer excavation and refillingetc. as required.
90.16.1.2Supply and drawing bare earthing conductors of the following sizes along withwiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.16.1.3 Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.1.6Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required6.00 mm copper conductor (4 SWG)
90.16.2.3Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench ofsuitable size and refilling etc, as required.32 mm dia G.I pipe ( medium class)
90.16.5.2Supply of superior quality copper earth socket for the following size of earthconductor including crimping etc. as required.2.65 mm (12 SWG)
90.16.5.3Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
90.16.5.6Supply of superior quality copper earth socket for the following size of earthconductor including crimping etc. as required.6. mm ( 4 SWG)
90.14.1.2Fabrication, supply, conveyance, installation testing and commissioning of floor orwall mounting, dust and vermin proof, cubicle type MV panel board comprising ofthe following components/ devices & complying to IS 8623.Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approveddesign and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braidedcopper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc asrequired. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted anglesetc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions,folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)
90.14.2.2 Supply and providing 3mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.3.1Supply and providing heavy duty 'A' section neoprene gasket in the panel boardA' section neoprene beeding suitable for 1.60/ 2.00 mm sheet
90.14.4 Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC)
90.14.5 Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
90.14.6Supply and providing copper bus bars including finger type SMC bus bar supports inthe bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. asrequired.
90.14.11.14 MCCB AccessoriesSupply and fixing rotary handle, Direct type (including BUChandle with door interlock ) in the existing MCCB of rating up to 250 A
OD426011/2022-2023 Supply & fixing of 250, HRC Fuse Base with HRC Fuse link
MR Supply and fixing 100A, 415 V, 2 way neutral link mounted on DMC/ SMC base in the existing meter board and giving connections etc.
MRSupply, Conveyance, Installation, Testing and commissioning of wall mounting type split air conditioner unit conforming to IS fitted with rotary compressor operating on 230 / 415 V AC supply, R410A/non CFC refrigerant Capable of performing functions like cooling, dehumidifying, air circulating, filtering etc. of following capacity, micro processor control with cordless remote control etc. including electric cable, copper pipe and thermal insulation upto 4M as required with One year on site warranty, 5 year compressor warranty and one year free service. 100% copper.2.0 TR 5 Star 1phase inverter type split AC unit ( Voltas / equivalent make of PWD approved with ISI )
MR Supply of following capacity voltage stabilizer for split type AC unit with voltagerange of 175-275 V and output voltage range of 210 to 240V.4 KVA voltage stabilizer.
Supply and providing hard drawn copper refrigerant piping interconnecting the condenser unit and indoor unit with 19 mm insulations.
Supply and providing Heavy duty outdoor unit stand for fixing outdoor unit of air conditioner
2.10.1 Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
MRSupply, Conveyance, Installation, Testing and commissioning of wall mounting type split air conditioner unit conforming to IS fitted with rotary compressor operating on 230 / 415 V AC supply, R410A/non CFC refrigerant Capable of performing functions like cooling, dehumidifying, air circulating, filtering etc. of following capacity, micro processor control with cordless remote control etc. including electric cable, copper pipe and thermal insulation upto 4M as required with One year on site warranty, 5 year compressor warranty and one year free service. 100% copper.1.5TR 3 Star 1phase inverter type split AC unit ( Voltas / equivalent make of PWD approved with ISI )
90.14.11.2 MCCB AccessoriesSupply and fixing one number earth fault Relay up to 125A to 200A with CBCT.
OD202866/2023-2024 Supply of Fire Extinguisher-ABC 5 Kg Type
OD202851/2023-2024Supply and providing 100/5 A, 5 VA, accuracy class 0.5, Resin Cast Metering CT including giving necessary connections as required
R.Radhakrishnan Nair (BID ID -2076957)
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1157984.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .