Executive Engineer TLMD-7
PDD Complex Bemina Sgr
Augmentation of Grid Station Alusteng from 320MVA to 475 MVA at 220 132 kV level along with allied works
2026_PDD_331495_1
eNIT TLMD7/ 10 of 2026-27 Dated 17-11-2026
Open Tender
Electrical Works
Lump-sum
606 days
Kashmir
Please refer Tender documents.
6 documents required · 6 mandatory
₹10,000
CD A/C No. 0367010200000182
₹1.1 Cr
Office of the Chief Engineer JKPTCL Kashmir
17 Nov 2026
17 Nov 2026
11 Dec 2026
18 Nov 2026
9 Dec 2026
19 Nov 2026
18 Nov 2026 - 26 Nov 2026
27 Nov 2026
180 days
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | (A) Design,Manufacture,Supply,Packing & Forwarding,Transportation,Delivery At Site of Equipments and Material | - | - | - | - |
| 2 | Main Equipments | - | - | - | - |
| 3 | 105 MVA (ONAN/ONAF/OFAF), 220/132/11 KV Single phase Auto Transformer with OLTC, SCADA Compatible RTCC, HV and LV connectors and other required accessories and fittings ,maintenance free automatic Breathers as per detailed Technical specs, Inbuilt NCTs and other accessories ,Common NB/individual MB's , control cables and fitting With Mandatory Spares ( Current density for HV/LV/ Teritiary winding not more than 2.4 A/sq mm.Core Flux density not more than 1.5T at rated voltage) .The scope shall include first filling of transformer oil and 10 percent extra. Mandatory spares for one autotransformer bank (3X105 MVA plus 1X105MVA spare autotransformer) which shall include 1 NO.HV RIP bushing , 1 No. OIP IV bushing ,1 No neutral and tertiary bushing,2 No OTI and 2 No WTI with contacts & sensing device , 2 No. Oil cooler pump with motor ,8 Cooler fans with motor , 3 No PRV and 3 No. bucholz relay , bushing CT's for one transformer, 3 No.oil surge relay ,3 No. MOG, 1 No. air cell for conservator, 8 No oil sampling bottle .(Technical specifications as per SBD) | 4 | Nos | - | - |
| 4 | Online DGA of transformer suitable for 7 Gases technical specifications as per SBD | 4 | Nos | - | - |
| 5 | Online dehydration kit for tranformer technical specifications as per SBD | 4 | Nos | - | - |
| 6 | Design, supply, erection testing and commissioning of NIFPES for 1 Number 105MVA, 220/132kV Single Phase Spare Transformer and supply installtion of MS tank 5 KL prefabricated cylindrical 6mm thick tank capacity including carrying out all civil works as per approved drawings including installation of accesssories for retrofitting (including commisioning of existing 3 No 53.33 MVA transformer NIFPES units for connecting same to the new 3 No. 105 MVA transformers along with pipe flanges, additional N2 cylinders etc | 1 | Nos | - | - |
| 7 | 220KV Control and Relay Panel for Transformer Bay completely wired including Substation automation supporting IEDs/numerical relays including Differential relay, Directional 3 O/C 1 E/F protection and numerical communicable REF protection relay. | 1 | No | - | - |
| 8 | Marshalling kiosk with Kiosk frames Stainless steel thickness not less than 2.0 mm. Shall be provided with a degree of protection of lP: 65, with Copper Bar earthing for 132 kV and 220 kV bays. 1. Marshalling Box shall be outdoor type rigidly constructed out of stainless steel/ Aluminium and shall be dust, water & Vermin proof Sheet steel used shall be at least 2.00 mm thick cold rolled. 2. Bay Marshalling Kiosk shall have three separate distinct compartments for the following purposes: l) To receive two incoming 415 V 3 phase.63 Amps AC 1.3 supplies with Auto changeover and MCB units and distribute minimum six outgoing 415 V 3phase l6 Amps supplies controlled by MCB with fuse failure remote indication. ll) To distribute minimum 10 outgoing, 240 V, '10 Amps supplies to be controlled by MCB to be drawn from three phase incomers. lll) 200 Nos of Terminal blocks in vertical formation for interlocking facilties | 4 | No | - | - |
| 9 | IPS Tube 4' Al tube, OD 120 mm , ID 100 mm , wall thickness 10 mm, weight 9.33 kg/m | 50 | Metre | - | - |
| 10 | IPS Tube 3' Al tube, OD 90 mm , ID 78 mm , wall thickness 6 mm, weight 5.5 kg/m | 400 | Metre | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.17 MB
SBD1.pdf
Tender Documents • 1.29 MB
SB2.pdf
Tender Documents • 4.35 MB
BOQ_1125191.xls
BOQ • 0.34 MB
PBM10.pdf
PDF • 0.32 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .