| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.8 LAccepted-AOC PMC 24 528 GROUND FLOOR NEAR PAYYANUR SERVICE CO OP BANK KOTTY BRANCH PAYANNUR KANNUR KERALA 670307 | PAYYANUR | KANNUR | KERALA | 670307 | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹40.0 L+₹1.1 L (2.91%)Rejected-Finance DOOR NO XII 356 A OPP POST OFFICE RAMANTHALI POST DIST KANNUR KERALA 670 308 | RAMANTHALI | KANNUR | KERALA | 670308 | L2 | Rejected-Finance Not being lowest | |
| 3 | L3₹40.1 L+₹1.2 L (3.13%)Rejected-Finance RP IV 23 PUNNAKADAVU JN RAMANTHALI P O KANNUR 670308 | KANNUR | KANNUR | KERALA | 670308 | L3 | Rejected-Finance Not being lowest | |
| 4 | L4₹40.8 L+₹1.9 L (5.01%)Rejected-Finance | L4 | Rejected-Finance Not being lowest | |
| 5 | L5₹41.3 L+₹2.5 L (6.37%)Rejected-Finance | L5 | Rejected-Finance Not being lowest |
Tender Value
₹39 L
EMD Value
₹78,000
Closing Date
11 Sept 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE(MAINT)EZHIMALA
GARRISON ENGINEER (MAINT) MILITARY ENGINEER SERVICES INDIAN NAVAL ACADEMY POST KANNUR DIST KERALA 670 310
AS PER BOQ AND TENDER DOCUMENTS
2023_MES_615135_1
GE MAINT EZHIMALA 8603
Open Tender
Civil Works
Item Rate
180 days
EZHIMALA
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE MAINT EZHIMALA
₹78,000
Yes
5 Oct 2023
23 Aug 2023
13 Sept 2023
23 Aug 2023
11 Sept 2023
6 Sept 2023
24 Aug 2023 - 31 Aug 2023
Amount
Excavating in trenches not exc. 1.5m wide and n. exc 1.5m in depth for foundation etc getting out hard/dense soil complete all as specified and as directed.
Removing excavated material exc. 50m & depositing where directed at a level not exc. 1.5m above the starting point complete all as specified and as directed.
M&L for cement concrete in foundations, filling and mass concrete, PCC 1:3:6 type C2 (40mm graded aggregate) complete all as specified and as directed.
S&F steel work in tubular trusses in any shape flat or curved section including special shaped washer etc. complete using ERW or induction butt welded tubes conforming to I. S.1161- 1979 grade St.-240 complete all as specified and as directed.
S&F plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, without any attachment complete all as specified and as directed.
S&F of flat iron for wind ties conforming to Fe-290 Gde E-165 complete all as specified and as directed.
S&F Pre- painted galvalume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws complete all as specified and as directed. Note:- The quoted rates shall be inclusive of necessary scoffolding also.
S&F 0.5 mm thick Pre-painted galvalume aluminum zinc coating GI based Plain steel sheet 0.50mm thick of approved colour having tensile strength of 550 Mpa as in roof covering/cladding to wall,ridge etc fixed with self tapping screws , rivetting with existing roof sheets/ valley gutters, bolting on to parepat walls etc complete as specified at any height. Note:- The quoted rates shall be inclusive of necessary scoffolding also.
M&L for preparation of new steel surfaces and applying 2 coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and as directed.
Demolition of plain cement concrete of any description and in any position not otherwise specifically provided for complete all as specified and as directed.
M&L for Pre-cast cement concrete block masonry type C1 1:3:6 (using 20 mm aggregate) with solid blocks, exc. 10 cm in width and setting in cement mortar (1:6) complete all as specified and as directed.
M&L for cement concrete 1:3:6 type C-2 (using 40mm graded stone aggregate) as in foundations, filling and mass concrete complete all as specified and as directed.
M&L for providing pre cast reinforced cement concrete type B-l, 1:2:4 (20 mm graded aggregate) as in drain cover slabs comlete all as specified and as directed.
M&L for mild steel bars 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and as directed by Engr-in-Charge.
S&F PVC (SWR) pipes of 110mm dia single socketed in any length including all necessary bends, elbow, TEE etc for connection of pipes with rubber ring joints fixed to walls / floor complete all as specified and as directed.
M&L for rendering 15mm thick in CM 1:4 on fair faces of brick work or concrete surfaces finished even and smooth without using extra cement complete all as specified and as directed.
Excavating in trenches, n.exc. 1.50m wide and n.exc. 1.5m in depth, for foundation, etc. or for shafts, wells, cesspits, manholes pier holes, etc. n exc. 10 sqm on plan and n exc 1.5m in depth and getting out in soft / loose soil complete all as specified and as directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers n.exc 25cm complete all as specified and as directed.
Removing excavated material n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point complete all as specified and as directed.
S&F powder coated aluminium (minimum thickness of powder coating 50 micron) work for doors, windows, ventilators and partitions (fixed portions) with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS:1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, aluminium snap beading for glazing/ paneling, C.P. brass/ stainless steel screws all complete as per architectural drawings and the directions of Engineer-in-Charge.
S&F powder coated aluminium anodised aluminium door shutters (minimum thickness of powder coating 50 micron) , aluminium section weighing 0.55 kg/m including necessary joining cleats, glazing clips, rubber neoprene packing, handles 2 Nos in each door, hinges, anodised aluminum snap beading screws etc. complete all as specified and as directed.
S&F 5.5 mm thick sheet glass, ordinary quality and glazing with oil putty in square exc 0.5 sq. m in each pane complete all as specified and as directed.
M&L for 9 mm thick prelaminated particle board, interior grade, prelaminated both side with decorative choice lamination, fixed with screws/rubber beading to aluminium frame work complete all as specified and as directed.
S&F door closer aluminium (extruded section) body hydraulically regulated, designation No.3, universal type, suitable for door shutters of 851 to 1000 mm in width and of weight between 61 to 80 kg complete all as specified and as directed.
S&F 150 mm long mild steel barrel tower bolts of extruded section complete all as specified and as directed.
S&F floor door stopper of aluminium alloy body and tongue, anodised, with hard drawn steel spring, fixed in floor, overall length of cover plate 150mm complete all as specified and as directed.
S&F mortice lock, vertical type, size 100 mm of mild steel 4 Levers complete all as specified and as directed.
S&F anodised aluminium snap grid frame work for false ceiling, size of grid 605 x 605mm complete all as specified and as directed.
S&F hangers 6 mm dia. G.I. (upto 1200/2400 mm length) adjusting level fixed to roof slabs by means of ceilling cleats made out of G.I. flat 40 x 3 mm size 60mm long , expansion hold fasteners 12.5mm dia 40mm long and size of grid 605 x 605mm complete all as specified and as directed.
M&L for 4mm thick non asbestos fibre cement building boards fixed or laid/ inserted to timber/GI/Aluminium framework with screws complete all as specified and as directed.
M&L for preperation of newly board ceiling and applying two coats of oil bound distember / acrylic emulsion over a coat of alkali resistant primer complete all as specified and as directed.
M&L for providing and fixing stainless steel (Grade 304) railing made of hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (where ever required) and fitting the same with necessary stainless steel nuts and bolts complete, including fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size, on the top of floor or the side of waist slab with suitable arrangement complete all as specified and as directed.
Dismantling floor, hearth or wall tiling including cement mortar bedding (but not backing), removing serviceable tiles to store and rubbish off the premises complete all as specified and as directed.
Taking down chowkats with shutter (without taking off shutter from the frame) exc 1.5 Sqm but n.exc 4.00 Sqm each complete all as specified and as directed.
Taking down cement plaster of any description or thickness/ chipping of cement concrete in any situation from brick or concrete surface including raking out of joints, hacking for key scrubbing down with water to received new plaster complete all as specified and as directed.
Taking down existing water proofing treatment of any description and removal rubbish off the premises, complete all as specified and as directed.
Demolition of brick work, PCC block or stone masonry built in cement mortar complete all as specified and as directed.
Disconnecting existing tanks, setting aside (or lowering if required) for repairs, cleaning, etc. and hoisting if required reconnecting and re-fixing in position complete all as specified and as directed.
M&L for providing, cement concrete in lintels upto 1.5m clear span, cills, steps, seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates, roof slab padding, kerbs not provided for in Item 04028, water troughs and the like including weathering, slightly rounded or chamfered angles and throating, type B1, 1:2:4 using 20 mm graded aggregate complete all as specified and as directed.
M&L for applying evenly a tack coat of industrial bitumen 85/25 at the rate of 1.2 Kg per Sqm including cleaning surface for laying one layer of APP based polymeric membrane minimum weighing 4kg/sqm and minimum 4mm thick reinforced with polyester non woven fabric (wt not less than 160 gms/sqm) by torch application with two coats of aluminium reflective paint complete all as specified and as directed.
M&L for aluminium powder coated windows and ventilator shutters etc. side hung type without sash bars, aluminium section weighing not less than 0.55 Kg/m including necessary joining cleats, glazing clips rubber neoprene packing, anodised aluminium snap beading, screws, anodised aluminium fittings such as peg stays 150mm long (1 No), hinges type B-21 100mm long (2 Nos) suitable handle (1 No) etc. (minimum thickness of powder coating not less than 50 micron) complete all as specified and as directed.
S&F aluminium powder coated door frame for doors, windows, ventilators with one or more rebates including joining cleats for fixing etc. (minimum thickness of powder coating not less than 50 micron) complete all as specified and as directed.
S&F 9mm thick pre-laminated particle board exterior grade, one side decorative choice lamination and other side balancing white lamination, fixed with screws to wooden / aluminium frame work as in cupboard shutters complete all as specified and as directed.
M&L for 4mm thick sheet glass plain ordinary quality not exc 0.50 sqm in each pane and glazing with beading complete all as specified and as directed. Note:- Aluminium beading shall be measured and paid separately.
S&F aluminum anodized wire cloth 0.45 mm nominal dia of wire and average width of aperture 1.40mm and fixed with aluminum wire staples complete all as specified and as directed.
S&F aluminum (die cast) body door closer hydraulically regulated designation No 2 universal type suitable for door shutters of 701 to 850mm in width and of weight between 36 to 60 Kg complete all as specified and as directed.
S & F in mortice lock brass body, 100 mm, 4 levers vertical type complete all as specified and as directed.
S & F in repairs 200mm anodized aluminium barrel tower bolt of extruded section complete all as specified and as directed.
M & L for coloured Non-skid ceramic tiles (square/rectangular) 7 to 10 mm thick in floors, area of each tile exc.0.11 sqm but n.exc 0.18 sqm, set and jointed in neat cement slurry and pointed in white cement mixed with matching pigment over and including 10 mm thick screed bed in CM 1:6 complete all as specified and as directed.
M & L for Glazed ceramic coloured tiles 350x250x7mm / 450x300x7mm thick in vertical surfaces of stone/brick wall, set and jointed in neat cement slurry and pointed in coloured cement to match over and including 10 mm thick backing coat plaster in CM 1:4 complete all as specified and as directed.
S & F in repair vitreous china wash basin, coloured (flat back) 500x450mm excluding pillar tap, but including fixing brackets, cutting for and pinning in ends of brackets complete all as specified and as directed.
S&F in repairs pillar taps 15 mm size, cast copper alloy, chromium plated screwed down high pressure screwed for iron pipe & fixed complete all as specified and as directed.
S&F in repair vitreous china, wash down water closet (pedestal pattern), cascade type including flushing cistern with seat cover coloured, closed pattern with flat bottom and cover with chromium plated mild steel or aluminium hinging device fixed with necessary bolts complete all as specified and as directed.
S & F in repair vitreous china urinal, half stall type, coloured, with and including all fixing accessories complete all as specified and as directed.
S & F in repair vitreous china urinal partition, coloured, with and including all fixing acessories complete all as specified and as directed.
S & F in repairs 15mm bore chromium plated bib taps (fancy type), cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipes complete all as specified and as directed.
S&F in repair angular stop valve, cast copper alloy, screwed down, high pressure with crutch or butterfly handle, chromium plated, fancy type, screwed both ends for iron pipe or for union and fixed, suitable for 15 mm bore pipe complete all as specified and as directed.
S & F in repair brass chromium plated towel ring complete all as specified and as directed.
S & F in repair 20mm dia, D type, 60cm long cast copper alloy, chromium plated towel rail complete all as specified and as directed.
S & F in repair cast copper alloy, chromium plated toilet paper holder, complete all as specified and as directed.
S&F in repair chromium plated soap tray fixed with CP brass screws complete all as specified and as directed.
S & F in repair health faucet (ABS Body) mild steel chromium plated suitable for 15 mm dia pipe with 1.25 metre long flexible tube and ABS wall hook including making connections and fixed in position complete in all respect as specified.
S&F urinal spreader of PTMT any colour for fixing with 15 mm dia pipe. (Minimum weight 60gms) complete all as specified and as directed.
S & F in repairs 32mm dia PVC flexible waste pipe for urinals/WHB/ sink complete all as specified and as directed.
S & F in repair PVC connections 15mm size with PTMT nuts of length 450mm complete all as specified and as directed.
S & F in repair cast copper alloy, chromium plated waste coupling with long shank, half thread, 32 mm dia, for WHB etc. complete all as specified and as directed.
Taking up or down steel tubing and connections, 20mm dia complete all as specified and as directed.
Taking up or down steel tubing and connections, 25/32 mm dia complete all as specified and as directed.
Supplying and laying of 20 mm CPVC pipes SDR 11 & Plain CPVC SDR 11 fittings on walls/ceiling or laying in floors complete all as specified and as directed.
Supplying and laying of 25 mm CPVC pipes SDR 11 & Plain CPVC SDR 11 fittings on walls/ceiling or laying in floors complete all as specified and as directed.
Dismantling CI soil waste pipe 100mm/75 mm dia including all joints and branch pieces jointed in cement mortar complete all as specified and as directed.
S & F in repair PVC (SWR) pipes of 110 mm dia single socketed in any length with rubber ring joints fixed to walls complete all as specified and as directed.
S & F in repair PVC (SWR) pipes of 75mm dia single socketed in any length with rubber ring joints fixed to walls complete all as specified and as directed.
S & F PVC (SWR) bends any radius of bore 75mm complete all as specified and as directed.
S & F PVC (SWR) bends any radius of bore 110mm complete all as specified and as directed.
S & F in repair 75mm PVC (SWR) floor trap plain with grating including jointing with solvent cement complete all as specified and as directed.
M&L for PCC 1:2:4 type B-0 using 12.5mm graded stone aggregate as in gola junction of wall and floor or for settings floor trap/ ‘P’ trap in position and PCC padding in floor complete (work in foul condition as in shaft) all as specified and as directed.
M&L for cutting out cracks to V-section in existing roofs or terracing, cleaning out, wetting, grouting with cement and sand slurry 1:3 using water proofing compound complete all as specified and as directed.
M&L for walling of squared rubble, regular coursed, well bonded, bedded & solidly hearted, built in cement mortar 1:6 complete all as specified and as directed.
M&L for rendering on fair faces of stone masonry work or concrete surfaces 10mm thick in CM 1:4 finished even and smooth without using extra cement including mesh at joints complete all as specified and as directed.
M&L for rendering on fair faces of brick work or concrete surfaces 10 mm thick in CM 1:3 in celing finished even and smooth without using extra cement complete all as specified and as directed.
M & L for struck pointing to squared rubble, coursed or uncoursed in cement mortar 1:3 complete all as specified and as directed.
M & L for preparation of newly plastered wall surfaces and applying two coats of oil emulsion distemper over a coat of alkali resistant primer complete all as specified and as directed.
M & L for preparation of newly plastered ceiling surfaces and applying two coats of oil emulsion distemper over a coat of alkali resistant primer complete all as specified and as directed.
M & L for PCC 1:4:8 type D2 (40 mm graded aggregate) as in foundation complete all as specified and as directed.
M&L for cement concrete 1:2:4 type B1 (20mm graded aggregate as in coping) complete all as specified and as directed.
M&L for cement concrete 1:3:6 type C-2, 100 mm thick for plinth protection and finished even and smooth without using extra cement complete all as specified and as directed.
M & L for precast cement concrete 1:2:4, type B-1 (using 20 mm graded stone aggregate) in landings, perforated cover slabs (for man holes, drain etc) chullah hoods, chajjas, water troughs, mangers, shelves and similar articles with plain faces and set in cement mortar 1:4 complete all as specified and as directed.
Removing excavated material (soil) exc. 1.5 km but n exc.5.0 km and depositing where directed complete all as specified and as directed.
Supply, installing, testing and commissioning of diesel engine driven generating set 82.5 KVA with separate AMF panel (out door type & double door) with water cooled engine of suitable BHP for 66 KW power generation @ RPM 1500, brushless frame with silencer and canopy for sound less mode (sound level not exceeding level specified by central pollution control board) and all engine accessories such as self starter, alternator/dynamo and 66 kW/82.5 kVA electric alternator, 415 volts, 3 phase, 4 wire, 50 Hz, voltage regulation ± 15, insulation class H coupled to engine with suitable coupling and base frame on foundation as recommended by the manufacturer and consisting of other electrical components, fuel tank capacity as per OEM recommendations with level indicator installed on suitable steel frame with PCC foundation as per manufacturers instructions, Power Command genset Controller, fuel pipes, Dual spin on fuel filter, Dritype Aircleaner, Shutt off coil with safeties for LLOP/HWT , fuel pipes , bar metre, hour meter, oil temperature gauges, ammeter, ignition switch, radiator with cooling fan, maintanance free battery, including suitable size of copper cable leads with terminals, all mountings , accessories and necessary foundation and AVM pads complete as per manufacturers recommendations and to the satisfaction of Engr in charge.
(A) PRIME MOVER :- Suitable for driving 66KW/82.5 KVA alternator liquid cooled battery start diesel engine of adequate capacity 110 BHP confirming of BSS 649 and fuel tank suitable for 12 hrs running capacity mounted on MS frame pedestal supported with anti-vibration mounting rated for continuous running capable of taking 10% over load for one hr in any 12 hrs operaton complete with the following standard accessories :- a)Fly wheel to match with the flexible coupling b)Flexible coupling wih guard c)Air cleaner oil bath type / dry type d)Lubricating oil filter, fuel filter paper element type e)Blower type fan and radiator f)Governor for class "A" Goverming as per IS-1601 of DS 649/1958 g) Starter motor for electric start complete with dynamo altermator, lead acid batteries heavy duty of capacity 12 V 65 Ah or as per OEM recommendations, Nos & capacity as required with copper conductor leads of adequate size and length not less than 2 M including battery box all as directed. h) Hour meter and RPM indicator j) Exhaust pipe brought outside the building and lagging of entire length of exhaust pipe with 12 mm dia. k) Instrument panel duly wired comprising the following including protection for low lub oils high temperature. l) Lube oil pressure gauge m) Battery change indicator meter n) Starting switch with key o) Lub oil temperature p) Engine temperature indicator (B) ALTERNATOR : 66KW/82.5 KVA at 0.8 PF brushless self excited, self regulated 3 phase 50 Hz 415 V 1500 RPM 4 wire screen protected drip proof free from simulation problems continuous rating confirming to BS 2613 complete with automatic voltage regulator O/P voltage regulated between +/- 1% or set voltage from no load to full load.
Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables( heavy duty) 1100 volts grade with stranded aluminium conductor of size 50 sq mm 3.5 core complete all as specified and as directed.
M&L for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground, earth pit not less than 2.25 meter deep below ground level, connected to 32x6 mm size galvanised iron as earthing strip by means of bolts, nuts, check nuts, and washers of galvanised iron /steel all as shown in electric plate No 3 of SSR Part I connected to earthing test point all as specified or indicated including provn of necessary excavation and earthwork in any type of soil, PCC pit, RCC cover and 20 mm bore medium grade watering pipe, water funnel with GI wire mesh, 40 mm bore medium grade protection pipe, common salt, charcoal dust, returning filling in of soil, removal of spoil to a distance not exceeding 50 mtr etc including testing on completion complete all as specified and as directed.
M&L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required for 32x6mm galvanised iron strip complete all as specified and directed by Engr-in-charge.
Supply and spreading riddled earth for cushioning of the UG cable in trenches complete all as specified and as directed. Note:- Punned thickness shall be measured for payment purpose.
Supplying and laying un-reinforced precast concrete cable cover but Class LV, Type I, flat, size 250mm x 150mm x 40mm complete all as specified and as directed.
Excavating in post holes (or similar holes) each n exc 0.5 cu. m, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm in hard/dense soil complete all as specified and as directed.
M&L for cement concrete 1:2:4 type B1, using 20mm graded aggregate as in foundations, including rafts, footings, foundation beams, plinth beams, bases for columns, etc. basement slabs, under-reamed piles and mass concrete complete all as specified and as directed.
S&F Plates (plain or chequered) channels square cut or notched (ordinary and counter sunk) forming holes, with riveted, bolted or welded attachment (Fe-410W, Gde E-250A) complete all as specified and as directed.
Supply and fix in replacement of sheet metal enclosure double door out door type made out of 3.15mm thick MS sheet power coated of suitable size with 200 Amps rated aluminium busbar with colour code including one no MCCB 63 Amps 25 KA & one 63 Amps on load changeover switch as incomer and suitable gland for cabling, complete all as specified and directed by Engr-in-charge.
Taking down carefully copper/ aluminium point wiring (light, fan and power socket etc) complete including fittings such as switches, ceiling roses, pendent, regulators, sockets, etc including making good the existing disturbed surface using wall putty and matching colour emulsion paint complete all as specified and directed by Engineer-in-Charge.
M&L for color code point wiring FRLS PVC insulated and unsheathed cable with 1.5 sqmm copper conductor single core multistandred 1100 volt grade conforming to IS 694 drawn through PVC conduit of suitable size not less than 20mm dia medium grade, concealed /open as per site requirement with suitable size modular metal flush box fitted with modular cover plate with frame (inner/ outer plate) for mounting switches or sockets regulators etc including FRLS 1.5 sqmm earth wire copper insulated wire connected to common earth dolly including making good the existing disturbed surface using wall putty and matching colour emulsion paint complete all as specified and directed by Engineer-in-Charge for the following:- Note:- (i) Necessary PVC rigid junction boxes for identifying junction as required on site/directed by Engineer in charge for point wiring work with PVC dummy plates shall deemed to be included in the quoted rate. (ii) Same size wire shall be used for phase, neutral and earth conductor. (iii) The wiring shall be done strictly by following proper colour coding using red , blue, yellow for phase, black for neutral and green for earth leads.
(a) One light/ fan point controlled by one switch
(b) One 3 pin socket outlet 5 Amps on the same board with other switches
S&F in replacement of old unserviceable modular switch one way 6 Amps 1 module complete all as specified and directed by Engineer in charge.
S&F modular switch one way 6 Amps 1 module complete all as specified and directed by Engineer in charge.
S&F in replacement of old unserviceable modular socket 6 Amps 2/3 pin 2 module complete all as specified and directed by Engineer in charge.
S&F in repair ceiling rose, 3 terminal PVC/polycarbonate, isolated body complete all as specified and directed by Engineer in charge.
M&L for painting exhaust fan of any sweep complete with one coat of synthetic enamel suitable paint by spraying after cleaning all dust etc complete all as specified and directed by Engr-in-Charge.
M&L for dismantling/opening the exhaust fan of 300mm sweep of metal body any make removing the old defective winding carefully cleaning the inner parts and rewinding with the same gauge super enamelled copper conductor of good insulation, varnishing, drying and reassembling complete all as specified and directed by Engr-in-Charge.
Supply and fixing in repair capacitors 4 mfd, AC 440 Volts suitable for exhaust fan complete all as specified and directed by Engineer in charge.
S&F in replacement of old unserviceable wall mounted 20 W LED 4ft warm batten out put, lumen ≥ 100 lumen/watts, efficacy 100 lumen per watt,CRI > 80, CCT >3000k , internal surge protection up to 4Kv , power factor > 0.95, THD ≤10% having extruded aluminium housing provided for efficient heat dissipation with poly carbonate diffuser and integrated electronic driver with all accessories pre-wired and including connecting up 3 core flexible copper conductor cable suitable size from fitting to ceiling rose/connection terminals complete all as specified and directed by Engineer in charge. Make:- Crompton model No. CCS-103-20-65-SL-DP-WW or equivalent in Philips/ Wipro/Havells/Bajaj. Note:- LM79 report accredited by NABL certified lab should be submitted.
S&F in replacement old unserviceable wall mounted 10 W 2 ft LED batten, out put lumen ≥ 100 lumen/watts, efficacy 100 lumen per watt, life 50,000 burning hrs, aluminum body, surge protection 4kV, power factor > 0.98, THD ≤10%, extruded channel in thermally conductive material for efficient heat dissipation with Polycarbonate diffuser and integrated electronic driver making connection to ceiling rose to fitting with 3 core 1 sqmm copper conductor complete all as specified and directed by Engineer-in charge. Make:- Crompton model No. CCS-103-10-65-SL-DP-NWH or equivalent in Philips/ Wipro/Havells/Bajaj. Note:- LM79 report accredited by NABL certified lab should be submitted.
S&F recess mounted 36W luminaire 2x2 tile, output lumens greater than 110 lumen/watt, efficiency 110 lumen per watt, life 50000 burning hrs, surge protection 4kV, power factor>0.98, THD≤10%, CRI ≥80, glare free uniform illumination housing with opel diffuser with colour temp 5700K with driver making connection to ceiling rose to fitting with 3 core 1 sqmm copper conductor including making good the existing disturbed surface using wall putty and matching colour emulsion paint complete all as specified and directed by Engineer-in-Charge. Make:- Crompton Model Polaris NIO I LCTLRNE-36-FO-CDL or equivalent in Philips/Wipro/Havells/Bajaj. Note:- LM79 report accredited by NABL certified lab should be submitted.
SATHEESAN.T.K
SANDR
TAMS ASSOCIATES
PADMANABHAN. K.V
KDR CONSTRUCTION
M/s K V Ramachandran
K P DIVAKARAN
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .