| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹1.6 CrAccepted-AOC | ₹1.6 Cr | 1 | Accepted-AOC Lowest |
| Sl No | Description | Qty | Unit | BST AIR CONDITIONING & REFRIGERATION PVT LTD L1 |
|---|---|---|---|---|
| 1.00AIR HANDLING UNIT | ||||
| 1.01 | od179774/2023_2024 : AHUs: Supply, store, installation, testing & commissioning of Floor mounted double skin Air Handling Units with thermal break profile with a minimum panel thickness of 50 mm or more with Roof canopy , AHRI / Eurovent certified unit complete with cooling coil( DX cooling coil) ,DIDW centrifugal fan with IE3 motor with minimum W/cfm, MCCB,VFD with enclosure box ( IP 21 rated for indoor and IP 55 rated for out door applications),The VFDs must have active harmonic filters to limit the harmonic distortion as per IEEE standards, cleanable fabric filtersof MERV 8 and fine filters of MERV 14, strip heaters of following capacity condensate drain pan, coil piping connections, condensate drain connections, mixing box with dampers inbuilt flexible duct connectors in Supply, return and Fresh air section . The fan should deliver the design cfm at 50 Hz or lower. The electrical power wiring from the Isolator to the unit upto 5m shall be included. HVAC contractor to check the ahu room/location sizes during the AHU selections/sizing, and shall strictly follow the AHU room/location sizing, as no changes whatsoever shall be acceptable. Air balancing to be done as per the approved shop drawings at the time of commissioning. The AHUs should meet the sound pressure levels recommended by ASHRAE. The system shall be complete in all respects of commissioning.The supplier should visit the site before procurement and shall confirm the suitability of the particular unit for particular area and confirm the external static pressure after checking the drawings. The supplier also should vouch for the performance guarranty. 6 TR,3000 CFM, 18 mm ESP, 6 RD, 9 kw Strip Heater, with mixing box ( OPTHAL ICU )<br> | 1 | no | 3,53,877 ₹3,53,877 Lowest |
| 1.02 | od179775/2023_2024 : "AHUs: Supply, store, installation, testing & commissioning of Floor mounted double skin Air Handling Units with thermal break profile with a minimum panel thickness of 50 mm or more with Roof canopy , AHRI / Eurovent certified unit complete with cooling coil( DX cooling coil) ,DIDW centrifugal fan with IE3 motor with minimum W/cfm, MCCB,VFD with enclosure box ( IP 21 rated for indoor and IP 55 rated for out door applications),The VFDs must have active harmonic filters to limit the harmonic distortion as per IEEE standards, cleanable fabric filtersof MERV 8 and fine filters of MERV 14, strip heaters of following capacity condensate drain pan, coil piping connections, condensate drain connections, mixing box with dampers inbuilt flexible duct connectors in Supply, return and Fresh air section . The fan should deliver the design cfm at 50 Hz or lower. The electrical power wiring from the Isolator to the unit upto 5m shall be included. HVAC contractor to check the ahu room/location sizes during the AHU selections/sizing, and shall strictly follow the AHU room/location sizing, as no changes whatsoever shall be acceptable. Air balancing to be done as per the approved shop drawings at the time of commissioning. The AHUs should meet the sound pressure levels recommended by ASHRAE. The system shall be complete in all respects of commissioning.The supplier should visit the site before procurement and shall confirm the suitability of the particular unit for particular area and confirm the external static pressure after checking the drawings. The supplier also should vouch for the performance guarranty. "Hence the estimate for an amount of Rs.36,81,500/- (including GST @ 18% )is submitted herewith for approval and further actions.6 TR,3000 CFM, 20 mm ESP, 6 RD, 9 kw Strip Heater, with mixing box ( MEDICAL ICU)<br> | 1 | no | 3,53,877 ₹3,53,877 Lowest |
| 1.03 | od179776/2023_2024 : "AHUs: Supply, store, installation, testing & commissioning of Floor mounted double skin Air Handling Units with thermal break profile with a minimum panel thickness of 50 mm or more with Roof canopy , AHRI / Eurovent certified unit complete with cooling coil( DX cooling coil) ,DIDW centrifugal fan with IE3 motor with minimum W/cfm, MCCB,VFD with enclosure box ( IP 21 rated for indoor and IP 55 rated for out door applications),The VFDs must have active harmonic filters to limit the harmonic distortion as per IEEE standards, cleanable fabric filtersof MERV 8 and fine filters of MERV 14, strip heaters of following capacity condensate drain pan, coil piping connections, condensate drain connections, mixing box with dampers inbuilt flexible duct connectors in Supply, return and Fresh air section . The fan should deliver the design cfm at 50 Hz or lower. The electrical power wiring from the Isolator to the unit upto 5m shall be included. HVAC contractor to check the ahu room/location sizes during the AHU selections/sizing, and shall strictly follow the AHU room/location sizing, as no changes whatsoever shall be acceptable. Air balancing to be done as per the approved shop drawings at the time of commissioning. The AHUs should meet the sound pressure levels recommended by ASHRAE. The system shall be complete in all respects of commissioning.The supplier should visit the site before procurement and shall confirm the suitability of the particular unit for particular area and confirm the external static pressure after checking the drawings. The supplier also should vouch for the performance guarranty. "6 TR,3000 CFM, 20 mm ESP, 6 RD, 9 kw Strip Heater, with mixing box ( SURGICAL ICU)<br> | 1 | no | 3,53,877 ₹3,53,877 Lowest |
| 1.04 | od179777/2023_2024 : "AHUs: Supply, store, installation, testing & commissioning of Floor mounted double skin Air Handling Units with thermal break profile with a minimum panel thickness of 50 mm or more with Roof canopy , AHRI / Eurovent certified unit complete with cooling coil( DX cooling coil) ,DIDW centrifugal fan with IE3 motor with minimum W/cfm, MCCB,VFD with enclosure box ( IP 21 rated for indoor and IP 55 rated for out door applications),The VFDs must have active harmonic filters to limit the harmonic distortion as per IEEE standards, cleanable fabric filtersof MERV 8 and fine filters of MERV 14, strip heaters of following capacity condensate drain pan, coil piping connections, condensate drain connections, mixing box with dampers inbuilt flexible duct connectors in Supply, return and Fresh air section . The fan should deliver the design cfm at 50 Hz or lower. The electrical power wiring from the Isolator to the unit upto 5m shall be included. HVAC contractor to check the ahu room/location sizes during the AHU selections/sizing, and shall strictly follow the AHU room/location sizing, as no changes whatsoever shall be acceptable. Air balancing to be done as per the approved shop drawings at the time of commissioning. The AHUs should meet the sound pressure levels recommended by ASHRAE. The system shall be complete in all respects of commissioning.The supplier should visit the site before procurement and shall confirm the suitability of the particular unit for particular area and confirm the external static pressure after checking the drawings. The supplier also should vouch for the performance guarranty. ",2200 CFM, 20 mm ESP, 6 RD, 7.5 kw Strip Heater, with mixing box (POST-OPERATIVE)<br> | 1 | no | 2,72,672 ₹2,72,672 Lowest |
| 1.05 | od179778/2023_2024 : "AHUs: Supply, store, installation, testing & commissioning of Floor mounted double skin Air Handling Units with thermal break profile with a minimum panel thickness of 50 mm or more with Roof canopy , AHRI / Eurovent certified unit complete with cooling coil( DX cooling coil) ,DIDW centrifugal fan with IE3 motor with minimum W/cfm, MCCB,VFD with enclosure box ( IP 21 rated for indoor and IP 55 rated for out door applications),The VFDs must have active harmonic filters to limit the harmonic distortion as per IEEE standards, cleanable fabric filtersof MERV 8 and fine filters of MERV 14, strip heaters of following capacity condensate drain pan, coil piping connections, condensate drain connections, mixing box with dampers inbuilt flexible duct connectors in Supply, return and Fresh air section . The fan should deliver the design cfm at 50 Hz or lower. The electrical power wiring from the Isolator to the unit upto 5m shall be included. HVAC contractor to check the ahu room/location sizes during the AHU selections/sizing, and shall strictly follow the AHU room/location sizing, as no changes whatsoever shall be acceptable. Air balancing to be done as per the approved shop drawings at the time of commissioning. The AHUs should meet the sound pressure levels recommended by ASHRAE. The system shall be complete in all respects of commissioning.The supplier should visit the site before procurement and shall confirm the suitability of the particular unit for particular area and confirm the external static pressure after checking the drawings. The supplier also should vouch for the performance guarranty. ",2400 CFM, 20 mm ESP, 6 RD, 10 kw Strip Heater, with mixing box (CSSD)<br> | 1 | no | 2,74,704 ₹2,74,704 Lowest |
| 1.06 | od179779/2023_2024 : "AHUs: Supply, store, installation, testing & commissioning of Floor mounted double skin Air Handling Units with thermal break profile with a minimum panel thickness of 50 mm or more with Roof canopy , AHRI / Eurovent certified unit complete with cooling coil( DX cooling coil) ,DIDW centrifugal fan with IE3 motor with minimum W/cfm, MCCB,VFD with enclosure box ( IP 21 rated for indoor and IP 55 rated for out door applications),The VFDs must have active harmonic filters to limit the harmonic distortion as per IEEE standards, cleanable fabric filtersof MERV 8 and fine filters of MERV 14, strip heaters of following capacity condensate drain pan, coil piping connections, condensate drain connections, mixing box with dampers inbuilt flexible duct connectors in Supply, return and Fresh air section . The fan should deliver the design cfm at 50 Hz or lower. The electrical power wiring from the Isolator to the unit upto 5m shall be included. HVAC contractor to check the ahu room/location sizes during the AHU selections/sizing, and shall strictly follow the AHU room/location sizing, as no changes whatsoever shall be acceptable. Air balancing to be done as per the approved shop drawings at the time of commissioning. The AHUs should meet the sound pressure levels recommended by ASHRAE. The system shall be complete in all respects of commissioning.The supplier should visit the site before procurement and shall confirm the suitability of the particular unit for particular area and confirm the external static pressure after checking the drawings. The supplier also should vouch for the performance guarranty. ",1600 CFM, 18 mm ESP, 6 RD, 6 kw Strip Heater, with mixing box (STERILE CORRIDOR)<br> | 1 | no | 2,38,426 ₹2,38,426 Lowest |
| 1.07 | od179780/2023_2024 : "AHUs: Supply, store, installation, testing & commissioning of Floor mounted double skin Air Handling Units with thermal break profile with a minimum panel thickness of 50 mm or more with Roof canopy , AHRI / Eurovent certified unit complete with cooling coil( DX cooling coil) ,DIDW centrifugal fan with IE3 motor with minimum W/cfm, MCCB,VFD with enclosure box ( IP 21 rated for indoor and IP 55 rated for out door applications),The VFDs must have active harmonic filters to limit the harmonic distortion as per IEEE standards, cleanable fabric filtersof MERV 8 and fine filters of MERV 14, strip heaters of following capacity condensate drain pan, coil piping connections, condensate drain connections, mixing box with dampers inbuilt flexible duct connectors in Supply, return and Fresh air section . The fan should deliver the design cfm at 50 Hz or lower. The electrical power wiring from the Isolator to the unit upto 5m shall be included. HVAC contractor to check the ahu room/location sizes during the AHU selections/sizing, and shall strictly follow the AHU room/location sizing, as no changes whatsoever shall be acceptable. Air balancing to be done as per the approved shop drawings at the time of commissioning. The AHUs should meet the sound pressure levels recommended by ASHRAE. The system shall be complete in all respects of commissioning.The supplier should visit the site before procurement and shall confirm the suitability of the particular unit for particular area and confirm the external static pressure after checking the drawings. The supplier also should vouch for the performance guarranty. "5.5 TR,2700 CFM,15 mm ESP, 6 RD, 7.5 kw Strip Heater, with mixing box (PRE-OPERATIVE )<br> | 1 | no | 3,47,926 ₹3,47,926 Lowest |
| 1.08 | od180551/2023_2024 : "AHUs:Supply, store, installation, testing & commissioning of Ceiling suspended double skin Air Handling Units with thermal break profile with a minimum panel thickness of 40 mm or more , AHRI / Eurovent certified unit complete with cooling coil( DX cooling coil) ,DIDW centrifugal fan with IE3 motor with minimum W/cfm, MCCB, VFD with enclosure box ( IP 21 rated for indoor and IP 55 rated for out door applications). The VFDs must have active harmonic filters to limit the harmonic distortion to limit the harmonic distortion as per IEEE standards , cleanable fabric filters of MERV 8 and fine filters of MERV 14, strip heaters of following capacity condensate drain pan, coil piping connections, condensate drain connections, mixing box with dampers inbuilt flexible duct connectors. The fan should deliver the design cfm at 50 Hz or lower. The electrical power wiring from the Isolator to the unit upto 5m shall be included.Isolator shall be in electrical contractors scope. HVAC contractor to check the ahu room/location sizes during the AHU selections/sizing, and shall strictly follow the AHU room/location sizing, as no changes whatsoever shall be acceptable. Air balancing to be done as per the approved shop drawings at the time of commissioning. The AHUs should meet the sound pressure levels recommended by ASHRAE. The system shall be complete in all respects of commissioning.The supplier should visit the site before procurement and shall confirm the suitability of the particular unit for particular area and confirm the external static pressure after checking the drawings. The supplier also should vouch for the performance guarranty."6 TR,1850 CFM, 15 mm ESP, 6 RD, 7 kw Strip Heater(MINOR OT) | 1 | no | 2,55,686 ₹2,55,686 Lowest |
| 1.09 | od180552/2023_2024 : "AHUs:Supply, store, installation, testing & commissioning of Ceiling suspended double skin Air Handling Units with thermal break profile with a minimum panel thickness of 40 mm or more , AHRI / Eurovent certified unit complete with cooling coil( DX cooling coil) ,DIDW centrifugal fan with IE3 motor with minimum W/cfm, MCCB, VFD with enclosure box ( IP 21 rated for indoor and IP 55 rated for out door applications). The VFDs must have active harmonic filters to limit the harmonic distortion to limit the harmonic distortion as per IEEE standards , cleanable fabric filters of MERV 8 and fine filters of MERV 14, strip heaters of following capacity condensate drain pan, coil piping connections, condensate drain connections, mixing box with dampers inbuilt flexible duct connectors. The fan should deliver the design cfm at 50 Hz or lower. The electrical power wiring from the Isolator to the unit upto 5m shall be included.Isolator shall be in electrical contractors scope. HVAC contractor to check the ahu room/location sizes during the AHU selections/sizing, and shall strictly follow the AHU room/location sizing, as no changes whatsoever shall be acceptable. Air balancing to be done as per the approved shop drawings at the time of commissioning. The AHUs should meet the sound pressure levels recommended by ASHRAE. The system shall be complete in all respects of commissioning.The supplier should visit the site before procurement and shall confirm the suitability of the particular unit for particular area and confirm the external static pressure after checking the drawings. The supplier also should vouch for the performance guarranty."3.5 TR,1400 CFM,15 mm ESP, 6 RD, 4.5 kw Strip Heater(RESUSCITATION) | 1 | no | 2,21,170 ₹2,21,170 Lowest |
Tender Value
₹1.6 Cr
EMD Value
₹50,000
Closing Date
6 Apr 2024, 4:00 pmClosed
CHIEF ENGINEER KSHB
Chief Engineers Office KSHB Trivandrum
Air handling unit, low side air distribution works sheet metal works, insulation ,air termination Controlwiring extract and fresh air fans for the Development of Government Taluk Hospital Vaikom, Kottayam District
2023_KSHB_610639_3
2023_CE_KSHB_23(Ele)
Open Tender
Electrical Works
Item Rate
150 days
VAIKOM
Please refer Tender documents.
2 documents required · 2 mandatory
₹6,195
₹50,000
14 Aug 2025
16 Mar 2024
8 Apr 2024
16 Mar 2024
6 Apr 2024
16 Mar 2024
Amount
AIR HANDLING UNIT
od180554/2023_2024 : Supply, Installation testing and commissioning of Ducted type split/package air cooled Air-conditioners each complete with air cooled condenser and evaporator with copper tubes, GSS casing, filters, cooling coils, fan motors, control wiring, refrigerant controls and accessories, including MICROPROCESSOR CONTROL with indication lamps for the operation of the system with thermostat fixed in the respective rooms to adjust the temperature according to the equipments requirements with Micro- processor control panel for each machine. Bidder to elaborate the features of Microprocessor panel.This shall facilitate all functions such as ON / OFF thermostat to compressor control, fan interlocks, HP/LP & AFT controls etc. The remote control for the unit shall be considered. The refrigerant shall be ecofriendly like R410a, R407c,R32 etc.The power cabling from local isolator / panel , to the machine shall be considered along with this line item.The control wiring between indoor unit and out door unit shall not be considered under this lineitem. Length of power cabling shall be inferred from the drawings. The system shall be complete with all respects of commissioning. The supplier should visit the site before procurement and shall confirm the suitability of the particular unit for particular area and confirm the external static pressure after checking the drawings. The supplier also should vouch for the performance guaranty.2 TR, 800 cfm, 4 mm ESP
od180555/2023_2024 : Supply, Installation testing and commissioning of Ducted type split/package air cooled Air-conditioners each complete with air cooled condenser and evaporator with copper tubes, GSS casing, filters, cooling coils, fan motors, control wiring, refrigerant controls and accessories, including MICROPROCESSOR CONTROL with indication lamps for the operation of the system with thermostat fixed in the respective rooms to adjust the temperature according to the equipments requirements with Micro- processor control panel for each machine. Bidder to elaborate the features of Microprocessor panel.This shall facilitate all functions such as ON / OFF thermostat to compressor control, fan interlocks, HP/LP & AFT controls etc. The remote control for the unit shall be considered. The refrigerant shall be ecofriendly like R410a, R407c,R32 etc.The power cabling from local isolator / panel , to the machine shall be considered along with this line item.The control wiring between indoor unit and out door unit shall not be considered under this lineitem. Length of power cabling shall be inferred from the drawings. The system shall be complete with all respects of commissioning. The supplier should visit the site before procurement and shall confirm the suitability of the particular unit for particular area and confirm the external static pressure after checking the drawings. The supplier also should vouch for the performance guaranty.3 TR, 1200 cfm, 4 mm ESP
od180556/2023_2024 : Supply, Installation testing and commissioning of Ducted type split/package air cooled Air-conditioners each complete with air cooled condenser and evaporator with copper tubes, GSS casing, filters, cooling coils, fan motors, control wiring, refrigerant controls and accessories, including MICROPROCESSOR CONTROL with indication lamps for the operation of the system with thermostat fixed in the respective rooms to adjust the temperature according to the equipments requirements with Micro- processor control panel for each machine. Bidder to elaborate the features of Microprocessor panel.This shall facilitate all functions such as ON / OFF thermostat to compressor control, fan interlocks, HP/LP & AFT controls etc. The remote control for the unit shall be considered. The refrigerant shall be ecofriendly like R410a, R407c,R32 etc.The power cabling from local isolator / panel , to the machine shall be considered along with this line item.The control wiring between indoor unit and out door unit shall not be considered under this lineitem. Length of power cabling shall be inferred from the drawings. The system shall be complete with all respects of commissioning. The supplier should visit the site before procurement and shall confirm the suitability of the particular unit for particular area and confirm the external static pressure after checking the drawings. The supplier also should vouch for the performance guaranty.3.5TR, 1400 cfm, 4 mm ESP
od180557/2023_2024 : Supply, Installation, Testing and Commissioning of DX-type Hi-wall split air conditioners, air cooled type with evaporator coil made of copper tubes, fan and fan motor air cooled condenser with copper tubes and inverter type scroll compressor , cordless remote control, GSS casing, filters, cooling coils, fan motors, and control panel. Bidder to elaborate the features of Micro- processor panel.The quote should be inclusive of control cabling from machine out door to indoor or from control panel to indoor and power cabling along with earthing.This shall facilitate all functions such as ON OFF thermostat to compressor control, fan interlocks, HP/LP & AFT controls etc. And MS base frame for outdoor units complete with epoxy painting, vibration isolation pads, supports, hangers, railing, brackets etc including civil works. Note: Apply 2 coats of epoxy primer and 2 coats of black paint, The air conditioner unit should be provided with a required voltage stabilizer and up to 5Rmt.copper piping between indoor and outdoor unit as specified. Condenser and evaporator coils shall be equipped with copper tubes. Minimum 5 star rated .The refrigerant shall be eco-friendly gasses like R-410A /R 407C/ R32. The capacities are as under.1TR
od180558/2023_2024 : Supply, Installation, Testing and Commissioning of DX-type Hi-wall split air conditioners, air cooled type with evaporator coil made of copper tubes, fan and fan motor air cooled condenser with copper tubes and inverter type scroll compressor , cordless remote control, GSS casing, filters, cooling coils, fan motors, and control panel. Bidder to elaborate the features of Micro- processor panel.The quote should be inclusive of control cabling from machine out door to indoor or from control panel to indoor and power cabling along with earthing.This shall facilitate all functions such as ON OFF thermostat to compressor control, fan interlocks, HP/LP & AFT controls etc. And MS base frame for outdoor units complete with epoxy painting, vibration isolation pads, supports, hangers, railing, brackets etc including civil works. Note: Apply 2 coats of epoxy primer and 2 coats of black paint, The air conditioner unit should be provided with a required voltage stabilizer and up to 5Rmt.copper piping between indoor and outdoor unit as specified. Condenser and evaporator coils shall be equipped with copper tubes. Minimum 5 star rated .The refrigerant shall be eco-friendly gasses like R-410A /R 407C/ R32. The capacities are as under.1.5TR
od180559/2023_2024 : Supply, Installation, Testing and Commissioning of DX-type Hi-wall split air conditioners, air cooled type with evaporator coil made of copper tubes, fan and fan motor air cooled condenser with copper tubes and inverter type scroll compressor , cordless remote control, GSS casing, filters, cooling coils, fan motors, and control panel. Bidder to elaborate the features of Micro- processor panel.The quote should be inclusive of control cabling from machine out door to indoor or from control panel to indoor and power cabling along with earthing.This shall facilitate all functions such as ON OFF thermostat to compressor control, fan interlocks, HP/LP & AFT controls etc. And MS base frame for outdoor units complete with epoxy painting, vibration isolation pads, supports, hangers, railing, brackets etc including civil works. Note: Apply 2 coats of epoxy primer and 2 coats of black paint, The air conditioner unit should be provided with a required voltage stabilizer and up to 5Rmt.copper piping between indoor and outdoor unit as specified. Condenser and evaporator coils shall be equipped with copper tubes. Minimum 5 star rated .The refrigerant shall be eco-friendly gasses like R-410A /R 407C/ R32. The capacities are as under.2TR
od180560/2023_2024 : Supply, Installation, Testing and Commissioning of DX-type Casette air conditioners, with evaporator coil made of copper tubes, fan and fan motor air cooled condenser with copper tubes and inverter type scroll compressor , cordless remote control, GSS casing, filters, cooling coils, fan motors, drain pump and control panel. Bidder to elaborate the features of Micro- processor panel.The quote should be inclusive of control cabling from machine out door to indoor or from control panel to indoor and power cabling along with earthing.This shall facilitate all functions such as ON OFF thermostat to compressor control, fan interlocks, HP/LP & AFT controls etc. And MS base frame for outdoor units complete with epoxy painting, vibration isolation pads, supports, hangers, railing, brackets etc including civil works. Note: Apply 2 coats of epoxy primer and 2 coats of black paint, The air conditioner unit should be provided with a required voltage stabilizer and up to 5Rmt.copper piping between indoor and outdoor unit as specified. Condenser and evaporator coils shall be equipped with copper tubes. Minimum 5 star rated . The refrigerant shall be eco-friendly gasses like R-410A /R 407C/ R32. The capacities are as specified under1.5TR
od180561/2023_2024 : Supply, Installation, Testing and Commissioning of DX-type Casette air conditioners, with evaporator coil made of copper tubes, fan and fan motor air cooled condenser with copper tubes and inverter type scroll compressor , cordless remote control, GSS casing, filters, cooling coils, fan motors, drain pump and control panel. Bidder to elaborate the features of Micro- processor panel.The quote should be inclusive of control cabling from machine out door to indoor or from control panel to indoor and power cabling along with earthing.This shall facilitate all functions such as ON OFF thermostat to compressor control, fan interlocks, HP/LP & AFT controls etc. And MS base frame for outdoor units complete with epoxy painting, vibration isolation pads, supports, hangers, railing, brackets etc including civil works. Note: Apply 2 coats of epoxy primer and 2 coats of black paint, The air conditioner unit should be provided with a required voltage stabilizer and up to 5Rmt.copper piping between indoor and outdoor unit as specified. Condenser and evaporator coils shall be equipped with copper tubes. Minimum 5 star rated . The refrigerant shall be eco-friendly gasses like R-410A /R 407C/ R32. The capacities are as specified under2TR
od180562/2023_2024 : OUTDOOR UNITSupply, Installation ,Testing & commissioning of Condensing unit with R-410A /R 407C/ R32gas. It should be complete with inverter type scroll compressor, air cooled condenser including MICRO-PROCESSOR CONTROL with indication lamps, remote control, temperature controller, and sensors along with the control box, its transformer, relays, necessary power and control wiring between the thermostat, controller, and the communication cabling between the out door and temp.controller , All the fittings associated with the unit like - but not limited to -filter, refrigerant, drier etc. to be considered and can not charge seperately. The rate should be inclusive everything ready for commissioning . The capacities for the same is listed under5.5 TR (MINOR OT, RESUSCITATION,CT-SCAN,POST-OPERATIVE,STERILE CORRIDOR)
od180563/2023_2024 : Supply, Installation ,Testing & commissioning of Condensing unit with R-410A /R 407C/ R32gas. It should be complete with inverter type scroll compressor, air cooled condenser including MICRO-PROCESSOR CONTROL with indication lamps, remote control, temperature controller, and sensors along with the control box, its transformer, relays, necessary power and control wiring between the thermostat, controller, and the communication cabling between the out door and temp.controller , All the fittings associated with the unit like - but not limited to -filter, refrigerant, drier etc. to be considered and can not charge seperately. The rate should be inclusive everything ready for commissioning . The capacities for the same is listed under8.5 TR (OPTHAL ICU, MEDICAL ICU,SURGICAL ICU,PRE-OPERATIVE,STERILE AREA
LOW SIDE
od181151/2023_2024 : Supply, installation, testing & commissioning of following sizes insulated PVC drain pipe' from terminal units (AHUs, split units etc.) drain pans to nearest floor drain complete with interconnection, flanges, elbows, tees, nuts, U-trap etc. The insulation shall be 9 mm thick closed cell Class O Nitrile Rubber foam insulation. ( Upto the nearest shaft)50 mm dia.
od181152/2023_2024 : Supply, installation, testing & commissioning of following sizes insulated PVC drain pipe' from terminal units (AHUs, split units etc.) drain pans to nearest floor drain complete with interconnection, flanges, elbows, tees, nuts, U-trap etc. The insulation shall be 9 mm thick closed cell Class O Nitrile Rubber foam insulation. ( Upto the nearest shaft)32mm dia.
od181153/2023_2024 : Supply, installation, testing & commissioning of following sizes insulated PVC drain pipe' from terminal units (AHUs, split units etc.) drain pans to nearest floor drain complete with interconnection, flanges, elbows, tees, nuts, U-trap etc. The insulation shall be 9 mm thick closed cell Class O Nitrile Rubber foam insulation. ( Upto the nearest shaft)25 mm dia.
od181154/2023_2024 : "Supply,Installation and commissioning of copper refrigerant piping, complete with 19mm thick closed cell Class O Nitrile Rubber Insulation , fittings, elbows, bends, supporting and clambing arrangement on walls, cable trays/trenches including necessary civil works.<br>Refrigerant piping to be measured based on the distance between the indoor and outdoor units irrespective of number of circuits. The piping will be measured as one length for suction and liquid line. Insulation will be measured along with the piping and not be claimed as extra. <br><br>"<br>
AIR DISTRIBUTION WORKS: SHEET METAL WORKS:
od181157/2023_2024 : "Supply, Fabrication, installation, testing & commissioning of Factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gasket, elbow, splitter dampers, turning vanes, access doors, hanger, supports, etc . All ducts shall be fabricated from Galvanised Sheet Steel (GSS) conforming to IS: 655-2006.<br><br>Longest side (mm) Minimum sheet thickness<br><br> For GSS For Aluminium<br>750 mm and below 0.63 0.80<br>751 mm to 1500 mm 0.80 1.00<br>1501 mm to 2250 mm 1.00 1.50<br>2251 mm & above 1.25 1.80"<br>22 Gauge (0.8MM)<br>
od181158/2023_2024 : "Supply, Fabrication, installation, testing & commissioning of Factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gasket, elbow, splitter dampers, turning vanes, access doors, hanger, supports, etc . All ducts shall be fabricated from Galvanised Sheet Steel (GSS) conforming to IS: 655-2006.<br><br>Longest side (mm) Minimum sheet thickness<br><br> For GSS For Aluminium<br>750 mm and below 0.63 0.80<br>751 mm to 1500 mm 0.80 1.00<br>1501 mm to 2250 mm 1.00 1.50<br>2251 mm & above 1.25 1.80"<br>24 Gauge (0.63MM)<br>
od181159/2023_2024 : "Supply, Fabrication, installation, testing & commissioning of factory fabricated Aluminium ducting complete with splitter dampers, turning vanes, access doors, supports, etc Ducting to be as per SMACNA standards.All ducts shall be fabricated from aluminium sheets conforming to IS:737,<br>Longest side (mm) Minimum sheet thickness<br><br> For GSS For Aluminium<br>750 mm and below 0.63 0.80<br>751 mm to 1500 mm 0.80 1.00<br>1501 mm to 2250 mm 1.00 1.50<br>2251 mm & above 1.25 1.80"<br>22 Gauge (0.8MM)<br>
AIR DISTRIBUTION WORKS: INSULATION
od181163/2023_2024 : Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class “O”) insulation on duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required.<br>Supply and Return ductwork complete running in Air-Conditioned space (Thickness-13 mm).<br>
od181164/2023_2024 : Supply and Return ductwork complete running in Non Air-Conditioned space.(Thickness-19mm). covered with 2 coats of vapor barrier<br>
od181165/2023_2024 : Supply and Return ductwork complete running in , External Roof and in Risers.(Thickness-25 mm) covered with aluminium sheets of 26 gauge.<br>
od181166/2023_2024 : Supply, Fabricating , Fixing of 26 gauge aluminium sheet cladding in the 25mm insulated duct work <br>
od181167/2023_2024 : Supply, store, installation, testing & commissioning of Acoustic Insulation for ducts and the return plenum using nitrile rubber, open cell foam, fibre free, minimum density of 140 kg/cu.m should have microban, as per ASTM G-21, ASTM E-2180, thermal conductivity not exceeding 0.047 W/m.K at 20 C, conform to class 1 rating for flame spread in accordance to BS 476 part 7, to thickness of minimum of 10mm all inline with the specificatoin and to meet the design noise criteria. The system shall be complete in all respects for commissioning. The duct insulation measured in the line item is considered as per the duct dimention. The measurement shall be taken according to that any material wastage shall not be considered during measurement . The system shall be complete in all respects for commissioning. Not to be applied in OT and ICU units.<br>Acoustic liner 10mm<br>
od181168/2023_2024 : Supply, store, installation, testing & commissioning of Under deck insulation 50 mm thick TF quality,28kg/m3 dense, EPS,Fixed by using rawl plugs GI washers etc. The system shall be complete in all respects for commissioning.<br>
AIR DISTRIBUTION WORKS: AIR TERMINATION
od181170/2023_2024 : Supply, store, installation, testing & commissioning of Grilles, Diffusers with plenums and Dampers as specified below. The system shall be complete in all respects forcommissioning.4 Way Supply Air Square Diffusers with opposed blade dampers
od181171/2023_2024 : Supply, store, installation, testing & commissioning of Grilles, Diffusers with plenums and Dampers as specified below. The system shall be complete in all respects forcommissioning.4 Way Return Air Square Diffusers
od181172/2023_2024 : Supply, store, installation, testing & commissioning of Grilles, Diffusers with plenums and Dampers as specified below. The system shall be complete in all respects forcommissioning.Exhaust air grille
od181173/2023_2024 : Supply, store, installation, testing & commissioning of Grilles, Diffusers with plenums and Dampers as specified below. The system shall be complete in all respects forcommissioning.Fresh air grille
od181174/2023_2024 : Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc., as per specifications.GI volume control damper.
od181175/2023_2024 : Supply, installation, testing and commissioning of Aluminium volume control duct damper 1.2mm x 2.4mm thick complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc., as per specifications.Aluminium volume control damper.
od181176/2023_2024 : Supply, store, installation, testing & commissioning of Fire dampers quick release fusible link , louver type, constructed out of 18 Gauge galavanised steel casing etc., in accordance with BS 476, DW 144, DW 151, DW 154 as appropriate and have Fire resistance rating.<br>
od181177/2023_2024 : Supply, store, installation, testing & commissioning of Louvers at all air intake locations and extract locations. The system shall be complete in all respects forcommissioning.The dimensions shall be referred from the shared layouts.<br>
Control Wiring
od181180/2023_2024 : Supply, store, installation, testing & commissioning of Thermostats for AHU units. The system shall be complete in all respects for commissioning.<br>
od181181/2023_2024 : Supply , installation and commissioning of power and control cabling with all necessary accessories for humidity control panel<br>
od181182/2023_2024 : Supply , installation and commissioning of power and control cabling with all necessary accessories for Thermostat <br>
od181183/2023_2024 : Supply,installation,testing and commissioning of control cum transmission wiring with suitable gauge wire in suitable PVC conduits between indoor and out door unit.<br>
EXTRACT AND FRESH AIR FANS
od181186/2023_2024 : Supply, store, installation, testing & commissioning of Axial fan with bird cowl.50 CFM
od181187/2023_2024 : Supply, store, installation, testing & commissioning of Axial fan with bird cowl.50 CFM (FRESH AIR)
od181188/2023_2024 : Supply, store, installation, testing & commissioning of Axial fan with bird cowl.75 CFM
od181189/2023_2024 : Supply, store, installation, testing & commissioning of Axial fan with bird cowl.75 CFM (FRESH AIR)
od181190/2023_2024 : Supply, store, installation, testing & commissioning of Axial fan with bird cowl.100 CFM
od181191/2023_2024 : Supply, store, installation, testing & commissioning of Axial fan with bird cowl.125 CFM
od181192/2023_2024 : Supply, store, installation, testing & commissioning of Axial fan with bird cowl.150 CFM
od181193/2023_2024 : Supply, store, installation, testing & commissioning of Axial fan with bird cowl.600 CFM
od181194/2023_2024 : Supply, store, installation, testing & commissioning of Axial fan with bird cowl.900 CFM
od181195/2023_2024 : Supply, store, installation, testing & commissioning of Inline Centrifugal Extract Fans shall be with direct driven circular section, suitable for ceiling suspension/mounting. The starters for the same should be considered in this scope. The units shall be complete with flexible duct connections at inlet and outlet. The motor shall be IP 55 rated, protected by inbuilt thermal contact relay as protection against burn-out as specified and as indicated in the technical specifications and drawings for the following and the system shall be complete in all respects for commissioning. 100 CFM,4mm ESP
od181196/2023_2024 : Supply, store, installation, testing & commissioning of Inline Centrifugal Extract Fans shall be with direct driven circular section, suitable for ceiling suspension/mounting. The starters for the same should be considered in this scope. The units shall be complete with flexible duct connections at inlet and outlet. The motor shall be IP 55 rated, protected by inbuilt thermal contact relay as protection against burn-out as specified and as indicated in the technical specifications and drawings for the following and the system shall be complete in all respects for commissioning. 200 CFM , 4mm ESP
od181197/2023_2024 : Supply, store, installation, testing & commissioning of Inline Centrifugal Extract Fans shall be with direct driven circular section, suitable for ceiling suspension/mounting. The starters for the same should be considered in this scope. The units shall be complete with flexible duct connections at inlet and outlet. The motor shall be IP 55 rated, protected by inbuilt thermal contact relay as protection against burn-out as specified and as indicated in the technical specifications and drawings for the following and the system shall be complete in all respects for commissioning. 250 CFM, 5mm ESP
od181198/2023_2024 : Supply, store, installation, testing & commissioning of Inline Centrifugal Extract Fans shall be with direct driven circular section, suitable for ceiling suspension/mounting. The starters for the same should be considered in this scope. The units shall be complete with flexible duct connections at inlet and outlet. The motor shall be IP 55 rated, protected by inbuilt thermal contact relay as protection against burn-out as specified and as indicated in the technical specifications and drawings for the following and the system shall be complete in all respects for commissioning. 300 CFM, 6mm ESP
od181199/2023_2024 : Supply, store, installation, testing & commissioning of Inline Centrifugal Extract Fans shall be with direct driven circular section, suitable for ceiling suspension/mounting. The starters for the same should be considered in this scope. The units shall be complete with flexible duct connections at inlet and outlet. The motor shall be IP 55 rated, protected by inbuilt thermal contact relay as protection against burn-out as specified and as indicated in the technical specifications and drawings for the following and the system shall be complete in all respects for commissioning. 400 CFM, 6mm ESP
od181200/2023_2024 : Supply, store, installation, testing & commissioning of Inline Centrifugal Extract Fans shall be with direct driven circular section, suitable for ceiling suspension/mounting. The starters for the same should be considered in this scope. The units shall be complete with flexible duct connections at inlet and outlet. The motor shall be IP 55 rated, protected by inbuilt thermal contact relay as protection against burn-out as specified and as indicated in the technical specifications and drawings for the following and the system shall be complete in all respects for commissioning. 650 CFM, 6mm ESP
od181201/2023_2024 : Supply, store, installation, testing & commissioning of Inline Centrifugal Extract Fans shall be with direct driven circular section, suitable for ceiling suspension/mounting. The starters for the same should be considered in this scope. The units shall be complete with flexible duct connections at inlet and outlet. The motor shall be IP 55 rated, protected by inbuilt thermal contact relay as protection against burn-out as specified and as indicated in the technical specifications and drawings for the following and the system shall be complete in all respects for commissioning. 700 CFM, 10mm ESP
od181202/2023_2024 : Supply, store, installation, testing & commissioning of Inline Centrifugal Extract Fans shall be with direct driven circular section, suitable for ceiling suspension/mounting. The starters for the same should be considered in this scope. The units shall be complete with flexible duct connections at inlet and outlet. The motor shall be IP 55 rated, protected by inbuilt thermal contact relay as protection against burn-out as specified and as indicated in the technical specifications and drawings for the following and the system shall be complete in all respects for commissioning. 725 CFM, 10mm ES<br>
od181203/2023_2024 : Supply, store, installation, testing & commissioning of Inline Centrifugal Extract Fans shall be with direct driven circular section, suitable for ceiling suspension/mounting. The starters for the same should be considered in this scope. The units shall be complete with flexible duct connections at inlet and outlet. The motor shall be IP 55 rated, protected by inbuilt thermal contact relay as protection against burn-out as specified and as indicated in the technical specifications and drawings for the following and the system shall be complete in all respects for commissioning. 850 CFM, 10mm ESP
od181204/2023_2024 : Supply, store, installation, testing & commissioning of Inline Centrifugal Extract Fans shall be with direct driven circular section, suitable for ceiling suspension/mounting. The starters for the same should be considered in this scope. The units shall be complete with flexible duct connections at inlet and outlet. The motor shall be IP 55 rated, protected by inbuilt thermal contact relay as protection against burn-out as specified and as indicated in the technical specifications and drawings for the following and the system shall be complete in all respects for commissioning. 950 CFM,10mm ESP
od181205/2023_2024 : Supply, store, installation, testing & commissioning of Inline Centrifugal Fresh air Fans with mesh filter shall be with direct driven circular section, suitable for ceiling suspension/mounting.7. The units shall be complete with flexible duct connections at inlet and outlet. The motor shall be IP 55 rated, protected by inbuilt thermal contact relay as protection against burn-out as specified and as indicated in the technical specifications and drawings for the following and the system shall be complete in all respects for commissioning. The electrical cabling and termination from the local isolator panel to the relevant Fan upto 5m to be priced under this scope.100 CFM,4mm ESP
od181206/2023_2024 : Supply, store, installation, testing & commissioning of Inline Centrifugal Fresh air Fans with mesh filter shall be with direct driven circular section, suitable for ceiling suspension/mounting.7. The units shall be complete with flexible duct connections at inlet and outlet. The motor shall be IP 55 rated, protected by inbuilt thermal contact relay as protection against burn-out as specified and as indicated in the technical specifications and drawings for the following and the system shall be complete in all respects for commissioning. The electrical cabling and termination from the local isolator panel to the relevant Fan upto 5m to be priced under this scope.400 CFM,5mm ESP
Bidder Name
BST AIR CONDITIONING & REFRIGERATION PVT LTD
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .