Staff Officer ENM
Office of the General Manager SECL Baikunthpur Area
Providing and Fixing 03 Nos NGR System at 33 KV/ 3.3 KV Power Transformer MnB Make 1000 KVA, Sl. No. PRM128097, Andrew Yule make 1600 KVA Sl. No. 12162, ETE make 1000 KVA Sl. No. 11829 at Katkona UG Mine of Katkona Sub Area.
2023_SECL_269994_1
SECL/GM/BKP/ENM/eTender/22-23/ 26
Open Tender
Civil Works - Others
Item Rate
30 days
Katkona
As per NIT
8 documents required · 8 mandatory
₹8,800
24 Jun 2023
6 Feb 2023
18 Feb 2023
7 Feb 2023
17 Feb 2023
7 Feb 2023
7 Feb 2023 - 10 Feb 2023
Amount
Item Description/ Heading : Providing and Fixing 03 Nos NGR System at 33 KV/ 3.3 KV Power Transformer M&B Make 1000 KVA, Sl. No. PRM128097, Andrew Yule make 1600 KVA Sl. No. 12162, ETE make 1000 KVA Sl. No. 11829 at Katkona UG Mine of Katkona Sub Area.
Supply and commissioning of 3.3KV, 10Amps, Restricted Neutral Grounding system (NGR) consisting of Neutral grounding resistor, stainless steel non-magnetic punched grid tuye AISI 304 grade, Max temperature rise 375 deg C, Indoor Epoxy Resin cast neural current transformer, 3.3KV 50/5A, IOT and HMI Intergace for blue tooth, for connection with mobile APP, monitoring fail safe relay, Power pack unit 1 and 2, Fuse enclosure, HRC fuses, connectors, glands, control wires and bushing studs, Buzzer (electronic), floor mounted, power coated control panel and resistance box with all accessories, Outdoor type Safety Features : 1. Resistance temperature sensor: trips the breaker if resistance temperature exceeds a set value. 2. Trip logs : LOG of last 25 trips, log can be downloaded via the mobile app 3. Temperature logs: hourly resistance temperature log for the last 24 hours. 4.Current Logs : Hourly Neutral current log for the last 24 hours. Logs can be downoaded through mobile app. 5. SMS alert to 5 registered mobile numbers. 6. Wireless communication to master controller and NGR panel as watchdog to alert the operator in case the primary breaker fails to trip
Total impact of GST for the purpose of CTC
P R ASSOCIATES
Rajneesh Electricals
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_279354.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .