| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹33.9 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹36.4 L+₹2.5 L (7.37%)Rejected-Finance 61 ABHAY GARH SCHEME AIR FORCE JODHPUR 342001 RAJ | JODHPUR | JODHPUR | RAJASTHAN | 342001 | L2 | Rejected-Finance REJECTED DUE TO L2 |
Tender Value
Refer Docs
EMD Value
₹77,000
Closing Date
10 Aug 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE SHIKARGARH
Military Engineer Services, Garrison Engineer, Shikargarh, Near ASC Supply Depot, Ratanada Jodhpur-342011
PROVN OF CERTAIN E/M SANCTIONED WORKS AT MH JODHPUR
2022_MES_536966_1
8772/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE SHIKARGARH
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE SHIKARGARH
₹77,000
Yes
5 Sept 2022
14 Jul 2022
12 Aug 2022
14 Jul 2022
10 Aug 2022
28 Jul 2022
14 Jul 2022 - 27 Jul 2022
Amount
Supply, Install, Testing and Commissioning of Solar hot water system (Evacuvated Tube Collector) based on indirect transfer of heat of capacity 200 LPD, with electrical heating back up of 2 KW complete all as specified and directed by Engineer-in-Charge. Make : TATA BP Solar System / BHEL / Best & Crompton Noval Energy, New Delhi
All as per item No. 1 above, but 300 LPD
All as per item No.1 above but 500 LPD
S&F for 500 ltr capacity rotational moulded polyethylene water storage tanks triple layered (cylindrical vertical with closed top) and in white colour hoisted and fixed in position including 20mm bore ball valves high pressure of PTMT with epoxy coated aluminium rod & high density plastic ball screwed for iron pipe all as specified in SSR Part-I complete all as specified and as directed.
All as per item No.5 above but 750 Ltrs
Supply and fix framed work such as grills, gratings, etc, with ends of bars shouldered and/or orged into spkes, framed guard bars, barred iron doors, ladders, framework of watertanks and simillar works conforming to Fe.290 Gde-E-165 all as specified and directed by Engineer-in-Charge.
M&L for PCC (1:2:4) type D-2, using stone aggregate 20mm graded, with and incl necessary form work where required and fair finish to the exposed surfaces, complete all as specified and directed by Engineer-in-Charge.
S&L 20 mm dia bore of tubes medium grade galvanised, with all fittings and fixed complete to walls and ceilings or laid in floors complete all as specified and directed by Engineer-in-Charge.
Supply and fix 20mm dia float valve for water tank made of PVC ball connecting with iron rod complete with nuts/bolts etc all as directed by Engineer-in-Charge.
S & F stop vlaves 20 mm dia cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed all as specified and directed by Engineer-in-charge.
Supply and fixing hot water pipe duly insulated with glass wool and aluminium cladding 15mm dia bore all as specified and directed by Engineer-in-Charge.
S & F stop vlaves 15 mm dia cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed
S&F Bib taps of 15mm bore CP with crutch or butterfly handle screwed down, screwed for iron pipe or for brass ferrule and fixed long body fancy type, complete all as specified and directed by Engineer-in-Charge.
M&L for sub main wiring with 3 run of 10 Sqmm FRLS, PVC insulated, unsheathed and stranded copper conductor cable with and incl 10 Sqmm (nominal area) FRLS, PVC insulated, unsheathed and stranded copper conductor cable as earth wire connected with thimble from main DB to sub main DB, drawn in to separate casing caping medium grade, ISI marked, non metallic PVC 20 mm size incl all accessories & fittings / junction boxes / inspection covers etc, and making good of disturbed surface of wall / floor/ ceiling etc as required, complete all as directed. Note : Three run of 10 Sq.mm. and one run of 10 Sq.mm (earth wire) cable. Make : Polycab / Havells / RR Kabel / KEI
M&L for sub main wiring with 2 run of 6 Sqmm FRLS, PVC insulated, unsheathed and stranded copper conductor cable with and incl 6 Sqmm (nominal area) FRLS, PVC insulated, unsheathed and stranded copper conductor cable as earth wire connected with thimble from main DB to sub main DB, drawn in to separate casing caping medium grade, ISI marked, non metallic PVC 20 mm size incl all accessories & fittings / junction boxes / inspection covers etc, and making good of disturbed surface of wall / floor/ ceiling etc as required, complete all as directed. Note : Two run of 6 Sq.mm and one run of 6 Sq.mm (green earth wire) cable. Make : Polycab / RR Kabel / KEI
All as per Srl item No 15 here-in-before, but 2 run of 4 Sqmm and one run 4 Sqmm as green earth wire
S&F of Vertical Distribution Board, double Door, suitable for 'A' Frame FP MCCB 100/160A made out of CRCA mild steel sheet surface with insulated material like polyester or with epoxy powder coating and IP 43 & IK 09 protection, VTPN 4 way, 415 volts with bus bar rating 300 Amps, dust and vermin proof, suitable for incorporation of MCB’s and MCCB etc and making all necessary connections, duly flush of wall surface, complete all as specified and directed. Make : Legrand / Schenider / Seimens / L&T
S&F of Distribution Board, double Door, made out of CRCA mild steel sheet surface with insulated material like polyester or with epoxy powder coating and IP 43 & IK 09 protection, TPN 04 way, 415 volts with bus bar rating 200 Amps, dust and vermin proof, suitable for incorporation of MCB’s and isolators etc and making all necessary connections, duly flush of wall surface, complete all as specified and directed. Make : Legrand / Schenider / Seimens / L&T
All as per item No.18 above, but of SPN DB 08 Way
All as per item No.18 above but of SPN DB 06 Way
All as per item No.18 above but of SPN 4 way DB
S&F of MCCB, A Frame, thermal adjustable magnectic setting, Ics = 75% 25 kA, 415V, 160 Amp, 4 Pole MCCB with over load and short circuit protection, complete all as directed. Make : Legrand / Schenider / Seimens / L&T
S&F of MCCB, A Frame, thermal adjustable magnectic setting, Ics = 75% 25 kA, 415V, 100 Amp, 4 Pole MCCB with over load and short circuit protection, complete all as directed. Make : Legrand / Schenider / Seimens / L&T
S&F of MCB, C Curve type, 16 kA, 100 Amp, TPN with over load and short circuit protection, complete all as directed. Make : Legrand / Schenider / Seimens / L&T
S&F of MCB, C Curve type, 10 kA, 63 Amp, TPN with over load and short circuit protection, complete all as directed. Make : Legrand / Schenider / Seimens / L&T
S&F of MCB, C Curve type, 10 kA, 63 Amp, SPN with over load and short circuit protection, complete all as directed. Make : Legrand / Schenider / Seimens / L&T
S&F of MCB, C Curve type, 10 kA, 6 to 32 Amp, Single Pole with over load and short circuit protection, complete all as directed. Make : Legrand / Schenider / Seimens / L&T
S&F of Blanking plate of plastic, suitable for distribution board complete all as directed.
S&F MCB protected socket box for AC including 16 Amps MCB SP or SPN and all as specified and directed by Engineer-in Charge.
Supply, laying, testing and commissioning of semi conducting compound conductor screened PVC bedded galvanized steel strip or wire armoured XLPE insulated heavy duty 1100 Volts grade with stranded aluminium conductor of size 120 Sqmm x 3.5 core confirming to IS 7098 Part-II, suitable for earthed system complete all as directed. Make : Polycab / Havells / RR Kabel / KEI
All as per item No.30 above but of 70 Sqmm, 3.5 Core.
All as per item No.30 above but of 35 Sqmm, 3.5 Core.
All as per item No.30 above but of 25 Sqmm, 4 Core .
All as per item No.30 above but of 16 Sqmm, 4 Core .
All as per item No.30 above but of 16 Sqmm, 2 Core .
Excavation in trenches in soft / loose soil not exceeding 1.5 mtr in depth and not exceeding 1.5 mtr wide and getting out including trimming of sides, for laying of cables & foundation of poles, stay assembly, complete all as specified and directed by Engineer-in-Charge.
Returning filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm thick, complete all as specified and directed by Engineer-in-Charge.
Removing excavated material to a distance not exc 50m and depositing where directed at a level not exc 1.5m above the starting point, complete all as specified and directed by Engineer-in-Charge.
M&L for Sand cushioning to protection of underground cables, laid 8cm before laying and 15 cm after laying of cable, and punned to form an overall layer of 18cm thick, complete all as specified and directed. Note : Punned thickness shall be measured and sand cover to UG cable, complete all as specified and directed by Engineer-in-Charge.
M&L for factory made un-reinforced pre cast concrete cable protection cover LV class type - I with size 250mm x 150mm x 40mm laid across the cable (i.e. width of cover along the length of cable) for UG cable protection on the top of the sand cushioning, complete all as specified and directed by Engr-in-Charge.
Supply and fixing / laying galvanised pipe 80mm bore medium grade fixed to pole with clamps nuts, bolts and washers or laid under road crossing or fixed to wall complete all as specified and directed.
Supply, install and testing for 2.0 TR Invertor Cassette type unit indoor / outdoor complete with cordless remote control unit, twin rotary compressor, single phase unit 220V - 240V, 50 Hz of capacity including all fittings, features and works for cutting wall etc, and make good surface match with existing complete all as specified and directed by Engineer-in-Charge.
Supply and fix Voltage stablizer for automatic operation, single phase neutrally air cooled indoor / wall mounted type and designed for input variation between 100V to 290V with output voltage stablized at 230V with accuracy of ± 2.5% and of capacity 4 KVA. Make: Volino / V Guard / Pixel
Supply and fixing of copper tubing heavy duty inner dia 6.0 mm (1/4") with insulation for refrigerant for ACs Complete all as specified and directed.
Supply and fixing of copper tubing heavy duty inner dia 13.0 mm (1/2") with insulation for refrigerant for ACs Complete all as specified and directed.
M&L for PVC insulated three core 2.5 Sqmm FRLS, unsheathed and stranded copper conductor cable to connect indoor unit to outdoor unit with suitable size of PVC conduit pipe incl all accessories & fittings / junction boxes / inspection covers and making good of disturbed surface of wall / ceiling etc as required, complete all as directed. Make : Polycab / RR Kabel / KEI
M&L for Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 metres below normal ground level, connecting to the GI earth strip 25x4 mm by means of bolts, nuts , check nuts and washers of galvanized iron and steel earth strip protected by provision of GI light grade pipe 40 mm bore including provision of concrete pit made from PCC ( 1:2:4) type B-1 (using 20 mm graded stone aggregate) with 40mm thick cover of RCC 1:2:4 reinforced with XPM (Weight not less than 4 Kg/Sqm) and frame of angle iron 40 x 40 x 6 mm and handle of 6 mm dia MS bar made to shape, GI light grade 20 mm bore pipe for watering perforated at bottom, 1.50 metre long placed on top edge of earth plate, common salt & charcoal filling, with fixing arrangement , funnel, wire mesh and earth work in hard/dense soil , returning filling in and removal of surplus soil to a distance not exceeding 50 metres, all as per electrical plate No 3 of SSR 2009 Part-I and connecting to LT Panel all as specified or indicated including testing on complete all as specified and as directed by Engineer-in-Charge.
M&L for earthing with galvanized steel earth plate electrode of size 600 x 600 x 6 mm buried directly in ground earth pit not less than 2.25 mtr below of normal ground level with top edge of earth plate should not less than 1.5 mtr below normal ground level and connected to galvanized iron earth lead wire of size 4 mm dia by means of bolts, nuts, washers of galvanized iron or steel all as shown in electrical plate No.3 of MES SSR Part I connecting to earthing test point on completion with and including 15 mm bore GI light grade protection pipe (7.5 mtr long) for earth lead GI lead wire 4mm dia (7.5 mtr long), PCC pit with cover in PCC 1:2:4 type B-1 reinforced with 8 mm dia tor bars @ 80mm C/C, 20mm dia medium grade watering pipe with funnel, wire mesh, common salt, charcoal, necessary excavation and earth work, complete all as specified and directed.
M&L Point wiring (Modular fitting) for one socket outlet 3 pin, 5 Amps on independent board complete, with 1.5 Sq mm FRLS PVC insulated un-sheathed and stranded copper conductor cable ISI marked and PVC concealed conduit ISI marked of size 20 mm dia medium grade and PVC conduit fittings such as tees, bends, elbow, reducers with and including FRLS PVC insulated unsheathed 1.5 Sqmm copper earth wire, connecting to common earth dolly with and incl Metal flush box of suitable size for fixing modular switches / sockets etc and making good surface by wall panelling etc, complete all as directed.
All as per srl item no. 50 here-in-before but of one socket outlet 3 pin, 5 Amps on same board.
All as per srl item no. 50 here-in-before but with 4 sq mm FRLS copper wire with 4 Sqmm FRLS copper earth wire complete all as specified and directed by Engineer-in-Charge.
M/L Point wiring (Modular fitting) for one socket outlet 3 pin, 5 Amps on independent board complete, with 1.5 sqmm single core PVC insulated and PVC unsheathed FRLS multistranded copper conductor cable 1100 volt grade enclosed in and including PVC casing and capping with accessories fixed on surface on walls/ceiling by means of PVC sleeves Dash-fastners and cadmium plated screws all as per ISI including PVC gang boxes for fixing of modular switches / sockets etc and making good surface by wall panelling etc, complete all as directed.
All as per srl item no. 53 here-in-before but of one socket outlet 3 pin, 5 Amps on same board.
All as per srl item no. 53 here-in-before but with 4 Sq mm FRLS copper wire with 4 Sqmm FRLS copper earth wire complete all as specified and directed by Engineer-in-Charge. Note :- Srl No 50 to 55, Make of wire : Polycab / RR Kabel / KEI
S & F Modular switch 1 way 6A , 1 module size complete all as directed.
S & F Modular switch 1 way 16A , 1 module size complete all as directed.
S & F Modular Socket , 6 A , 5 Pin , 2 module size complete all as directed.
S & F Modular Socket , 6 A / 16 A , 5 Pin , 2 module size complete all as directed.
Supply, Installation, Testing and Commissioning, of 28mm OD x 0.9mm thick medical gas Copper pipe as per BS 2871, Lloyd certified complete all as directed. Make: Mexflow/Mediflow/Kalpataru Metal/ Metalco/ Janaya/ Mandev Note: 1. Tapping from existing pipeline of any size and connect with other pipeline insert 'T' through welding / brazing including fitting with saddles, nuts & bolts, painting etc. The cost of all work shall be inclusive in the quoted item rate. 2. Leakage of pipelines are tested properly and will be maintained for one year under warranty period.
Supply and fixing of line isolation 28mm Ball valves complete all as directed. Make : Audco/RB/Legris/India/S.Nomi and Co/ Manibhadra/Metalco/MTEL
Supply and fixing of Air regulator with filter set fully assembled size 1" (25mm) complete all as directed. Make : SMC/Genetics/Blastech.
SANJOLI CONSTRUCTION COMPANY
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .