Loading…
Loading…
Tender ID
Tender Value
Refer Docs
EMD Value
₹81.6 L
Closing Date
6 Apr 2026, 6:00 pmClosed
Chief General Manager (P), Gujarat Water Infrastructure Limited
Designing, Constructing, Testing and Commissioning of RCC Under Ground Sump and RCC Pump House including Works for Supply, Installation, Testing and Commissioning (SITC) of Pumping Machinery and allied Electro-Mechanical & Instrumentation works along with miscellaneous works including 10 [Ten] years of Comprehensive Operation and Maintenance [O&M] at GWIL Navda Pumping Station [NC-28 and SPP-3A Pumping Station Project], Village - Navda, Taluka - Barvala, District - Botad.
282602
08/2026
Open
Civil Works - Water Works
Works
Gandhinagar
3 documents required · 3 mandatory
₹30,000
Chief General Manager (P), Gujarat Water Infrastructure Limited
₹81.6 L
3 Mar 2026
3 Mar 2026
3 Mar 2026
6 Apr 2026
3 Mar 2026
(3) SCHEDULE - A
(4) SCHEDULE - B
(5) SCHEDULE - C
(6) SCHEDULE - D: PREAMBLE
(7) SCHEDULE - D: BREAK UP FOR INTERIM PAYMENTS
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
Name of Work: “Designing, Constructing, Testing and Commissioning of RCC Under
Ground Sump and RCC Pump House including Works for Supply, Installation,
Testing and Commissioning (SITC) of Pumping Machinery and allied Electro-
Mechanical & Instrumentation works along with miscellaneous works including
[Ten] years of Comprehensive Operation and Maintenance [O&M] at GWIL Navda
Pumping Station [NC-28 and SPP-3A Pumping Station Project], Village - Navda, Taluka
- Barvala, District - Botad.”
(1) The bidder shall quote his firm and fixed price for the entire work under this Contract,
defined in more details in various sections of this bid document.
(2) The rates and prices shall be submitted in the electronic formats given by n-procure
which is called Schedule-B. Rates and prices received in any other formats will be
rejected and the Bids will be disqualified.
(3) It will be entirely at the discretion of the Employer to accept or reject the bidder’s
proposal, without giving any reasons whatsoever and the bidder shall not be permitted
to withdraw his bid on this account.
supplied by the client.
(5) In Schedule-B the Bidder shall quote prices for the work.
(6) The bidder should quote his bid premium or rebate at the end of Schedule B and
Schedule C. The rates shall be quoted in reference to detail BOQ (Schedule B1, B2,
…... and Schedule C) in line with Volume III Price Bid. If bidder does not wish to quote
premium or rebate, he should indicate "at par" in the blank space preceding "% above
/ below" in Schedule B and Schedule C. Thereafter bidder shall work out and indicate
the Total offered bid amount both in words and figures for Total amount of Schedule B
the Total offered bid amount both in words and figures for Total amount of Schedule B
and Schedule C. For any excess over tender quantities, Extra items and variations in
quantities, refer clause no. 14 on Volume- 1B – General Condition of Contract.
The % above/ below or at par rates and prices shall be submitted in the electronic
formats given by n-procure. % above/ below or at par Rates and prices received in
any other formats will be rejected and the Bids will be disqualified.
(7) Price quoted in SUMMARY (SCHEDULE-B) shall be firm and fixed during the
pendency of the contract, except for item under- price variation clause. Each item rate
of Schedule B and Schedule C shall be worked out by applying the same %
above/below or “at par” quoted for the Total Tender amount (Total of Schedule B and
Schedule C) given in detail in Volume III Price Bid.
(8) The agency with the lowest quoted percentage rate (by considering rebate if any), will
be considered as L-1 agency. The same percentage (above/below) quoting shall be
applicable to all rates in capital works (Schedule B) and O&M works (Schedule C).
(9) Wherever for a particular item the quantities have been specified payment shall be on
unit rate basis and unit variation in quantity will be paid with pro rata basis.
(10) The prices (in percentage) shall allow for all the works covered under the bid and all
liabilities and contractual obligations whether separately specified or not.
satisfactory working/safety of the system as specified, will be carried out by contractor.
(12) Schedule ‘D gives the basis of interim payment for construction of works.
considered for financial evaluation of the bid.
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
(14) The bidder shall be deemed to have allowed in his price for provision, maintenance
and final removal of all temporary works of whatsoever nature required for
construction including temporary bunds, diverting water, pumping, de-watering etc. for
the proper execution of works. The rates shall also be deemed to include any works
and setting out that may be required to be carried out for laying out of all the works
(15) Prices shall be filled online only.
Specifications and other sections of these bid documents and these documents are to
be taken as mutually explanatory of one another.
(17) The bidder shall interpret the data furnished and carry out any additional survey work,
or investigation work required at his own cost.
(18) The prices quoted shall also include the cost of materials utilized for testing.
(19) The bidder should acquaint himself with the site conditions including the access to
Work site. The successful bidder shall have to make suitable access to work sites at
his own cost. These accesses will be used by the other contractors working for GWIL.
shall include all the equipment / materials / accessories and services required as per
(21) 1% of the value of work will be deducted from the Running bill against labour cess
which is non-refundable.
(22) Third Party Inspection / CSC agency will be deployed by GWIL and charges of the
same will be borne by GWIL.
(23) Any expenditure incurred by inspection/ CSC agency for the work misinformed by the
contractor and charges of inspection/ CSC agency without any work due to
misinformation shall be recovered from the contractor.
(24) The prices shall be quoted exclusive of GST but inclusive of all other taxes, royalties
and duties prevailing at the time of submission of the bids. Statutory variation if any
during the currency of contract shall have to borne by the agency which shall not be
reimbursed by the GWIL.
(25) The rates quoted shall be exclusive of GST, but inclusive of all other taxes, duties
which shall not be paid extra. While GST will be paid for admissible part of actual work
done at the approved tender rates and tender conditions of price variations. GST shall
be paid as per prevailing rates at the time of payment. The TDS shall be deducted at
source as per provisions of IT rules and GWIL policy.
(26) The rates should be quoted exclusive of GST but inclusive of all other taxes as per
Volume-I (B), General Conditions of Contract, Clause No.
(27) The bidder shall have to quote the rates in this tender keeping in view of the GST. The
complete responsibility of taxes, duties, levies rests with the Contractor/agency only.
(28) The process requires that the bidder shall quote his price for the work components
fix during the entire period of performance of the contract except price variation
allowed for supply of MS/DI/ pipe as per Volume-1B Clause no. 59, General condition
(29) Payment shall be made for the components, as per schedule of payment. Total cost
will be worked out on the basis of the work done of individual items/ components, and
percentage rates quoted in Price Bid.
(30) Royalties: The contractor shall be liable to pay the royalty of the quarried materials/
minerals used in the construction of works at the rates specified in the Narmada Water
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
Resources, Water Supply & Kalpsar Dept. Resolution No. GEN-2010-595- (6) - M.I.
Cell (K-1) Dt. 29-4-2011 (Gujarati Version Copy enclosed) and shall be recovered from
the running bills of the work from time to time and remaining amount if any shall be
recovered from the final bill before releasing the security deposit of the work. The
contractor shall furnish the statement showing the quantity of quarried materials /
minerals from whom purchased (with full address of the seller) and copies of the bills
for purchase to the Executive Engineer of the in charge of the work. The contractor
shall also furnish such additional information as regards royalty payment to the
competent authority.
(31) Agency shall have to take Insurance policy and intimate to GWIL along with the
evidence within time limit. In case of non-compliance entire responsibility shall be rest
with the contractor and required amount shall be recovered from any due amount of
(32) GWIL can recover penalty amount from the agency for not taking the insurance.
Though the penalty amount is recovered, responsibility of the contractor for taking
insurance shall be continued and will not be escaped from the responsibility.
Signature of contractor Chief General Manager (Project)
GWIL Gandhinagar.
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
Bidders are required to fill up all the blank spaces in this Bid Form.
CHIEF GENERAL MANAGER (PROJECT)
GWIL GANDHINAGAR.
Dear Sir/Madam,
SUB: …………………………. (Name of work)
1. Having visited the site and examined the Bid Documents, Drawings, Conditions of Contract,
including Addenda/Amendments to the above, for the execution of the above Contract, we the
undersigned offer to design, Engineer, procure, construct, complete, commission, operate and
maintain the whole of the said works for 10 years from the date of commissioning including
defects liability period as given in Conditions of Contract and in conformity with the drawings,
Documents, including Addenda Nos.__________ (insert numbers) for Lump sum fixed price of
Rupees________________________________________________) for Construction including
free trial run for two months or such other sum as may be ascertained in accordance with the
2. I/We agree that
a) if we fail to provide required facilities to the Employer’s representative or any other
person/Agency by the Employer to perform on his behalf for carrying out the inspection and
testing of materials and workmanship.
b) if we incorporate into the Works, materials before they are tested and approved by the
Engineer’s representative.
c) if we fail to deliver water of required quantity according to the conditions/stipulations of the
Contract, the Engineer will be at liberty to take any action including termination of Contract
and impose at his absolute discretion any penalties, and/or reject the work.
3. We undertake, if our Bid is accepted, to complete and deliver the works in accordance with the
Contract within _________ months, inclusive of monsoons, from the date or receipt of Letter of
Acceptance issued to us by you.
4. We agree to abide by this Bid for a period of 180 days from the Last date of submission of the
bid and it shall remain binding upon us and may be accepted at any time before the expiry of
5. In the event of our Bid being accepted, we agree to enter into a formal Contract Agreement
with you incorporating the conditions of Contract there to annex but until such agreement is
prepared this Bid together with your written acceptance thereof shall constitute a binding
Contract between us.
6. We agree, if our Bid is accepted, to furnish performance /Security in the forms and of value
specified in the Clause 1 of Volume-IB, “General Conditions of Contract”.
7. We have independently considered the amounts of liquidated damages shown in Appendix to
Bid and agree that they represent a fair estimate of the damages likely to be suffered by you in
the event of the work not being completed by us in time.
8. We understand that you are not bound to accept the lowest or any Bid you may receive.
Dated this ________________ day of __________________ month of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
(Name of the Person)
Company Seal _____________________
Duly authorized to sign Bid for and on behalf of (fill in block capitals)
Witness Signature ___________________________
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
NAME OF SCHEME - …………………………. (Name of work)
Schedule showing the approximately the materials to be supplied to the contractor from
government stores for the work to be executed and the rate at which they are to be charged.
Rate at which the material
Sr. will be charged to the Place of
Particular Qty.
No. contractor Delivery
(1) The contractor submitting the Tender shall see that the rate in Schedule-A are filled in by
the Engineer in Charge at the time of issue tender.
(2) The contractor while submitting the tender shall provide his own arrangement at his own
cost for loading, unloading, and transporting safety to the site of work the cement stipulated
(3) All the materials required for the items other than labour in Schedule-A but available with
the dept. will be issued on request to the contractor. (for use in this contract only) at
prevailing market rates or departmental issue rates whichever is higher.
(4) All the surplus materials supplied by the department as mentioned in schedule-A should be
handed over to the Department by the contractor at the Govt. stores as directed.
(5) The materials mentioned in schedule-A shall have to be checked for their correctness and
soundness by the contractor before taking the delivery of the materials from the
(6) Necessary cement will be purchased by the agency at their own cost from open market.
(7) The persons of firm submitting the Tender should see that rates in the above schedule are
filled up by the GWIL, on the issue of form prior to the submission of the Tender.
(8) Carting of above materials should be done by contractor at his own cost.
Signature of contractor Chief General Manager (Project)
GWIL Gandhinagar.
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SUMMARY (SCHEDULE-B)
Name of Scheme:
Designing, Constructing, Testing & Commissioning of RCC Under Ground Sump
and RCC Pump House including Works for Supply, Installation, Testing and
Commissioning (SITC) of Pumping Machinery and allied Electro-Mechanical &
Instrumentation works along with miscellaneous works including 10 [Ten] year of
Comprehensive Operation and Maintenance [O&M] at GWIL Navda Pumping Station
[NC 28 & SPP–3A Pumping Station Project]. Village–Navda, Taluka–Barvala,
District–Botad.
SUMMARY (SCHEDULE - B)
Sr. No. Name of Work Amount Rs.
Construction of RCC sump, Pump House, Electrical Room,
SCHEDULE B-1 Common HT Panel room, RCC Valve Chamber, RCC Road,
RCC U/G Box Conduit, RCC Chamber, Thrust block and
Pipe support block, Compound wall and fencing etc.
Campus Headwork Development Works
Construction of RMU room, Valve chambers height
SCHEDULE B-2 increase, Plastering and Painting work at valve chamber,
Chequered plate for Valve Chamber, Information sign
boards for valve chambers, Landscape and gardening work
Mechanical Works NC 28 Pump house
SCHEDULE B-3 Design, Construction, Erection, Testing & Commissioning of
Mechanical Equipment and Accessories
Mechanical Works SPP3A Pump House
SCHEDULE B-4 Design, Construction, Erection, Testing & Commissioning of
Mechanical Equipment and Accessories
Electrical & Instrumentation Works NC 28 Pump house
SCHEDULE B-5 Design, Construction, Erection, Testing & Commissioning of
Electrical & Instrumentation Equipment and Accessories
Electrical & Instrumentation Works SPP3A Pump House
SCHEDULE B-6 Design, Construction, Erection, Testing & Commissioning of
Electrical & Instrumentation Equipment and Accessories
Campus Existing Valve Modification Works
SCHEDULE B-7 SITC of new valves, Modification work of existing valves &
valve chambers at Navda HW
SCHEDULE B-8 Site Protection Works
Total SITC Amount (Rs.)
SCHEDULE - C Operation & Maintenance
Total Amount Rs.
Total Amount Rs.
I/we am/are willing to carry out the work at ______________ % above / below percent (should be
written in figure and works) of the estimated rates mentioned above. Amount of my / our tender
works out as under.
Estimated amount put to Tender Estimated amount put to Tender
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
Deduct: __________% below Add: __________% above
GWIL Page 10 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-1 - Civil Work
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
Preparing structural design of RCC Under Ground / Partially under ground / above high ground
level Reservoir of required capacity as per relevant I.S. standards and constructing the same,
including excavation in all types of soil strata (including rock) including shoring strutting if required,
for loose soil / to protect from collapse, casting 100 mm thick P.C.C. levelling course in M-15,
Refilling the pit with proper soil and disposing of the surplus stuff at all lead. Including cement
plaster in CM 1:2 with approved water proofing compound to all over inside container (i.e. walls,
base, top slab (As per drawing)/dome bottom etc. all). Including all types of labour and material
charges of lowering, laying, erecting / hosting and jointing of pipe assembly to inlet, outlet
overflow, washout and bye pass arrangement as per hydraulic design. Providing and fixing
accessories, water level indicator. RCC chambers for valves. Providing and applying three coats of
cement paint / snowcem to the out side face of structure. It also includes satisfactory water
tightness test as per relevant I.S. code and painting name of scheme and capacity on the tank as
per direction of engineer in charge.
List of Indian Standards for Design of GSR / SUMP:-
The structural design of GSR shall be in accordance with provisions relevant I.S standards
(1) I.S. 3370, Part-1 2 & 4, latest revisions
(2) I.S. 456-2000 latest revisions
(3) I.S. 1893-1984 &, Part-1 to 5 of latest revisions.
(4) I.S. 875, Part - 1 to 5, latest revisions. Rupees One
(5) I.S. 10262 - 2019 or latest revision. Crore Twenty
(6) I.S. 13920 - 2016 or latest revision. One Lac Sixty
1 General Specifications: 1.00 No Thousand One
(1) Water depth in container shall be adopted as per data of tender. Capacity shall be calculated Hundred Two
excluding free board of the reservoir. If water depth is not specified, the suitable water depth / & Paise Sixty
acceptable to field engineer in accordance with hydraulic requirement Eight only
(2) Shape of Sump (in plan) specified as per tender drawing or as per site condition.
(3) Size shall be fixed as per availability of space (land area) at site / acceptable engineer in
(4) Effect of overlapping of pressure bulbs on soil due near by structure and proposed sump
should be considered.
(5) Care shall be taken that no damage should occur to nearby existing structure. Compensation
shall be paid for the same by agency.
(6) The minimum concrete grade for RCC shall be M-30.
(7) CRS Fe-500 grade reinforcing bars confirming to I.S. 1786 / 1139 shall be considered in
(8) Minimum size (or thickness) of various components shall be provided as per tender criteria /
specifications in absence as per I.S./ Std. practice of G.W.S.S.B./GWIL Minimum dimensions
specified for various components in tender data / specifications shall be provided without fail.
(9) The safe bearing capacity (SBC) shall be referred from SBC test report. In absence of report it
shall be referred from data sheet. If poor soil is found / water table is met with during excavation
SBC shall be scientifically ascertained and design shall be revise. No extra shall be paid for
increase in quantity.
(10) The rate shall include cost of dewatering during excavation making all arrangement when
GWIL Page 11 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-1 - Civil Work
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
water table meets within depth.
(11) The structure shall be designed properly to resist uplift due to ground water table specified in
data or actual ground water table meets with during excavation. If GWT / Uplift is mentioned in
tender and during excavation it does not meet 7.5% rate shall be reduced.
(12) MS material railing with min. 5 mm FRP Coating shall be provided over sump periphery when
sump height is ≥ 1.5 meter above ground level.
(12.a) RCC staircase/RCC Steps should be provided from GL to sump top slab based on the
height of the GSR above/below the ground. (For both compartment)
(12.b) RCC Staircase with MS material railing with min. 5 mm FRP Coating to be provided inside
reservoir container. BB Masonry staircabin to be provided to cover the same with MS safety door
having locking arrangement.
(13) Appearance of structure should be aesthetically good looking acceptable to authority.
(14) Any change in size, shape, depth below GL, height above GL, water depth, F.B., size of
member etc can be permitted in exceptional case due to site condition or hydraulic design
requirement by CGM (P). No extra shall be paid for change.
(15) Any change in data, dimensions, shape, water depth, reduction in size if permitted by
competent authority and if it reduces quantity then payment shall be reduced prorate.
(16) When capacity of GSR / Sump is > 20 lakh litres two or suitable compartments acceptable to
CGM (P) shall be designed and provided.
(17) Agency shall engage qualified (at least graduate) consulting engineer for designing the
structure and he / she shall visit the site for guidance of work.
(18) 75% part rate shall be payable for concrete, reinforcement and plastering items of container
until satisfactory hydraulic testing for water tightness is performed as per tender condition. Till the
work shall be treated as incomplete.
(19) Clearing and grubbing road land including uprooting rank vegetation grass bushes, shrubs,
sapling and trees girth, removal of stumps of trees cut earlier and disposal of unserviceable
(20) Dewatering by pumping set - Dewatering by pumping set of required capacity including
temporary platform carting pumping at site and fixing the same in position including all
accessories, and fuel and labour etc. complete.
Above conditions / general specifications Sr. No. 1 to 20 are part and parcel of tender (contact)
and prevail over other provisions in tender.
RWS 55 LL Capacity
Rectangular Sump with water table (Sub soil water level above foundation) of 55 LL RWS
constructed at site situated in seismic zone III.
Designing (aesthetically) and constructing R.C.C. frame structure of pump room and panel room
as per data sheet and Specification including,1. Minimum 15 % opening for ventilation should be
provided.2. Pump room rolling shutter (Two no.), door and windows of aluminium section and
window grill of aluminium anodized should be provided (Included in Cost).3. Plinth level of Panel
2 630.00 Sqm 21,689.52 Hundred
Room should be min. 3.0 meter above existing GL4. The arrangement shall be such that suction
pipe, pump-sets, delivery pipe including all the valves and accessories shall be accommodated in
pump house.5. The control panel room, office, PLC Scada room, battery room, pantry and
toilet/WC shall be constructed. The size of these rooms shall be enough to accommodate all
GWIL Page 12 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-1 - Civil Work
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
electrical & instrumentation equipment as per norms and approved by EIC.6. Vitrified tiles shall be
provided in office, PLC Scada and battery room. For other area flooring shall be provided of
Polished kotastone or as per instructions of Engineer-in-charge. For Toilet non sleepry tiles as per
EIC. For walkway and staircase portion chequered terrazo tiles to be provided.7. China mosaic
shall be provided over top slab of pump house and panel room. 8. As per instruction of engineer-
in-charge, EOT crane girders shall be extended for loading / unloading of pump house equipment.
Two rolling shutters shall be provided in which one shall be at pump area and other will be at
electrical room. Other one rolling shutter shall be provided for the HT panel room area. The same
shall be incorporated during approval of pump house GAD.(DOUBLE ROLLING SHUTTER)9.
Approach from ground level to two side of pump house and panel area shall be provided with RCC
staircase.10.Internal RCC staircase approach provided from the pump room to panel room.
Maintenance bay area shall be enough to accommodate the pump for maintenance purpose.Note:
In case increase in pump house and panel room size due to larger size of pumping
machinery/panel, no extra payment shall be given to the contractor.For Navda PSFor pump &
piping portion :63 x 10 m with gantry structure. Minimum 10.0m clear height from plinth
level / maintenance floor level to bottom level of beam at roof slab.
(b)-------do as above---- Eighteen
For Navda panel room : 63 x 8 m without gantry structure. minimum 8.0m height including celler Thousand
3 from Finished Floor Level of Pump House to Beam bottom of Roof slab.(Which includes 3.0m ht 504.00 Sqm 18,495.62 Four Hundred
for Pipe gallery from pump floor to Beam bottom and 4.5 m ht for Electrical room from Pipe gallery Ninety Five &
slab to Beam bottom of roof slab) Paise Sixty
Common HT Panel Room of 95 sqm of minimum 4.5 m clear height from plinth level to top (roof) Thousand
slab beam bottom as per the drawing, data sheet and Specification. Nine Hundred
Construction of RCC valve chambers of different sizes for different valve. The rates shall
include construction of RCC valve chamber in M 25 concrete. Including Excavation with shoring
and strutting if required, Dewatering, rubble soling, foundation concrete(PCC) in CC M-10
(approx. corresp. to prop. 1:3:6), pedestal and vertical wall in CC M25, CRS steel all diameter FE
500 grade confirming to relevant IS, top cover of minimum 7 mm thick M.S. Chequered plate
5.1 5.00 No 8,85,829.61 Eight Hundred
including necessary supporting arrangement with nuts, bolts, locking arrangement. Including form
work, painting, C.I Step etc. Complete as per datasheet, & specification and instruction of
Engineer-In-Charge/Consultant.
For Butterfly Valves 3 nos. and for Flow Meter 2 nos. (minimum Size of 4.0m x 4.0m x5.0m
5.2 Rupees Nine
-------do as above---- for Butterfly Valve (Minimum Size of 5.0m x 5.0m x 5.5m ht) 1.00 No 9,95,667.30 Lac Ninety
GWIL Page 13 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-1 - Civil Work
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
5.3 Rupees Three
Providing and casting in situ mass cement concrete in grade M-10 (approx. corresp. to prop. 1:3:6)
using granite quartzite trap metal of size 12 mm to 25 mm incl. consolidation curing etc. complete. 17.21 Cum 3,662.00
Without Forms WorkPCC For Thrust Block and Pipe Encasing
Providing and casting in situ R.C.C in grade M-20 (proportions as per mix design or as per Table
of IS456 2000 in masses by weigh, batching ) using granite, quartzite trap metal of size 6 mm to
20 mm for RCC work, including excavation, dewatering, scaffolding cantering, form work, needle
vibrated consolidation, curing comp. up to 6 meter depth or height ( including cost of
6 482.43 Cum 8,663.08 Hundred Sixty
reinforcement and neat finishing) with cantering and shuttering/deshuttering etc. comp. for
structure for other than water retaining.
RCC for thrust block and for Support block of individual discharge pipe upto the common
Construction of RCC U/G Box Conduit. The rates shall include construction of RCC chamber in Eighty Six
M 30 concrete. along with rubble soiling, Excavation, Dewatering, PCC in CC M-15 (approx. Thousand
7.1 corresp. to prop. 1:2:4), Reinforcement in CRS FE 500 grade etc.complete as per drawings & 28.00 Rmt 86,466.19 Four Hundred
specification and instruction of Engineer-In-Charge/Consultant . Sixty Six &
For RCC U/G Box Conduit of 2.0m wide x 3.0m depth Paise
7.2 --- do as above---- for RCC U/G Box Conduit of 3.0m wide x 3.0m depth 15.00 Rmt 99,529.42 Hundred
7.3 --- do as above---- for RCC U/G Box Conduit of combined 4.4m wide x 3.0m depth 8.00 Rmt 1,45,908.85 Nine Hundred
Construction of RCC Chamber (for U/G Box Conduit) The rates shall include construction of Rupees
RCC chamber in M 30 grade concrete. Excavation with shoring and struting if required, Twenty Five
8 Dewatering, foundation concrete(PCC) in CC M-15 (approx. corresp. to prop. 1:2:4), pedestal and 1.00 No 25,34,514.68 Lac Thirty
vertical wall in CC M 30 including Reinforcement in FE 500 CRS grade, top covered slab with Four
cutout and having chequered plate etc.complete as per drawings & specification and instruction of Thousand Five
GWIL Page 14 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-1 - Civil Work
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
Engineer-In-Charge/Consultant . Hundred
For RCC Chamber for U/G Box Conduit (8.0m X6.0m X 6.1m) Fourteen &
Construction of 25cm RCC Approach Road in M20 Garde of concrete (granite quartzite trap
metal of size 6 mm to 20 mm for RCC work ) including the cost of excavtion,sorting out and
stacking of useful materials, disposing off the excavated stuff upto 50 Meter lead using casting in
situ mass cement concrete PCC 10 cm thick of grade M-10 having granite quartzite trap metal of
9 385.00 Sqm 2,849.00 Eight Hundred
size 12 mm to 25 mm incl.scaffolding centering, needle vibrated consolidation, curing, including
reinforcement (CRS Fe 500 -25 kg/cum) complete. Providing and casting in situ ordinary cement
concrete M- 150 for Kerbs / kerb blocks both side of road including formwork, curing ,finishing and
Two coats of weather proof exterior emulsion paint of approved brand and manufacture for kerb
Dismantling and Construction of compound wall M20 Garde of concrete (granite quartzite trap
metal of size 6 mm to 20 mm for rcc work) including the cost of excavation, sorting out and
stacking of useful materials, disposing off the excavated stuff upto 50 Meter lead, Brick work using
10 common burnt clay building bricks having crushing strength not less than 35 kg./Sq.Cm. in 65.00 RMT 8,104.00
foundation and plinth in Cement Mortar 1:6 (1‐ Cement : 6 ‐fine sand)(B) Conventional (upto
ton) using casting in situ mass cement concrete PCC 10 cm thick of grade M-10 having granite
quartzite trap metal of size 12 mm to 25 mm Inc. Scaffolding centering, needle vibrated
consolidation, curing, including reinforcement (CRS Fe 500 -25 kg/cum) complete.
Fencing Providing and fixing 0.6 Metre high fencing with 0.75 Meter long M.S. Angle posts 40mm
x 40 mm x6 mm and oil painting 2 coats fixed at 3.0 Mt,C/c. with Three Horizontanl lines and two
11 65.00 rmt 104.00 Hundred Four
diagonals of galvanized steel barbed wire weighting 9.38 Kg. per 100 Meter, strained and fixed to
posts including fixing the posts etc complete.
Providing & Fixing Iron gates for compound wall of required size & specification with 1 No of
R.C.C. M-20 column size 0.45 x 0.45 m including reinforcement CRS steel all diameter Fe
grade confirming to relevant IS with 20 mm thick cement plaster to all exposed surface including
excavation in all strata, P.C.C. M-10 , form work for R.C.C. work(M-20) , painting to all Iron
exposed surfaces( incl. brushing , cleaning & priming coat ) and cleaning the site etc. the site etc.
12 1.00 No 1,20,446.00 Thousand
complete as per the detailed drawing attached.(MS Gate size 7.00 mtr long and average 2.0 mtr
height ), and construction of wall(at front side at MS gate) in B.B. Masonary in C.M. 1:6 with
mm thick Cement plaster to all exposed concrete and masonary structure. For Lighting supplying
and erecting R&B approved make of 8 nos. of LED recessed mounted luminaire with rear reflector
suitable for MS Gate.
Excavation for pipe line trenches for water supply, sewerage line, manhole, etc. all with shoring
and strutting if required as per required gradient and line including safety provisions using site rails
13 and stacking excavated stuff including up to all required lead cleaning the site, including all type 2904.00 Cum 151.16
of dewatering (water incoming in pipeline trenches due to seepage, uplift ground water, rain,
surrounding water bodies, etc.) complete for all lifts and strata as specified, including soil, soft
GWIL Page 15 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-1 - Civil Work
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
murrum, Hard Murrum, boulders incl. macadam road, Soft Rock and/or masonary in CM or LM or
Lime Concrete, hard rock and/ or in C.C. 1:2:4 or with blasting and chiseling or by chiseling only.
Refilling the pipeline trenches incl. ramming, watering, consolidating, disposal of surplus stuff as
14 2225.00 Cum 22.00 Twenty Two
directed within a radius of 3.0 Km.
Pocket/core cutting in existing RCC structure (sump wall) at required locations, suitable depth
and sizes as per drawings at common wall of existing sump of NC-28 & SPP-3A, specifications
and instructions of the Engineer-in-Charge. The scope includes surveying, marking, level
checking, required staging, tools and tackles, consumables, and safe removal of core material.
15 3.00 Job 1,80,000.00 Lac Eighty
The work also includes complete finishing of the core edges, trimming, cleaning, coping/chipping
and temporary arrangements to achieve a neat profile, and making the opening to a clear
diameter of minimum 1400 mm in the existing sump wall. All works to be completed in all
respects as directed by Engineering In-charge without damaging the existing structures.
Dismantling and removal of existing 2500 mm dia. MS gravity pipeline from Collection
Chamber to NC-28 Sump, as per requirement and mentioned in tender drawing as per the
instruction of the Engineering In-charge. Including dewatering and removing of all connected
specials & fittings and fixing the pipe ends tightly with blind flanges to ensure a fully secure and
leak proof closure at both ends. This works shall be completed as per specification and as per the
instruction of Engineering In-charge by cutting, welding with proper method and stackng of
removed pipeline at the designated location in Navda H.W. campus with all lead and lift of
transportation including taking all safety measures and supply, installation, testing &
commissioning of flanged type MS fabricated specials (flanges, blind flanges, tees, bends, tapers,
distance pieces, bolts, nuts, washers, gaskets, etc.) with epoxy painting of pipes and MS specials.
Total Amount Rs.
Total Amount Rs.
GWIL Page 16 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-2 Campus Headwork Development Work
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
Brick masonry work for raised height of Valve chamber Thousand
Brick work using common burnt clay building bricks having crushing strength not less than Two
35 kg./Sq.Cm. in foundation and plinth in Cement Mortar 1:5. (1- Cement : 5 -fine sand)(B) Hundred
Conventional Forty Five &
PCC for Valve Chamber Three
Providing and casting in situ mass cement concrete in grade M-10 (approx. corresp. to prop. Thousand
1:3:6) using granite quartzite trap metal of size 12 mm to 25 mm incl. consolidation curing Six Hundred
etc. complete. Sixty Two
Plaster for Valve Chamber Rupees Two
3 Cement plaster 20 mm thick in C.M. 1:2 using water proofing compound of approved quality 234.80 Sqm 202.00 Hundred
including finishing etc. complete. Two only
Painting for Valve Chamber Hundred
Wall painting (Two coats) with plastic emulsion paint of approved brand and manufacture on Twenty &
undercoated wll surface to give an even shade including throughly brushing the surface free Paise
from mortar droppings and other foreign matter and sand papered smooth. Twenty Six
Chequered plate for Valve Chamber
5 Supplying and fixing steel chequered plate having 7 mm thickness duly painted with two 49.75 Sqm 3,531.97
coats of black japan colour (Average weight 61.1kg/sqm)
Providing and fixing at site of work M. S. iron ladder with Rly. freight, loading, unloading,
carting & all taxes etc. comp as directed including paints 2 coats etc comp. Purchasing &
supplying at site of works, with Railway freight, loading, unloading, carting, etc. complete
such as joints, channels, angles, iron rails, etc. Including Labour charges for lowering laying,
erecting, fixing, various size of M. S. section such as joints channel, angles plates etc.
Encasing for SPP-4 Outlet FM Chamber Rupees
Providing and casting in situ C.C. in grade M-15 (approx. corresp. to prop. 1:2:4) Four
(proportions as per mix design or as per Table 9 of IS456 2000 in masses by weigh batching Thousand
) using granite, quartzite trap metal of size 6 mm to 20 mm for RCC work, including Nine
GWIL Page 17 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-2 Campus Headwork Development Work
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
scaffolding centering, form work, needle vibrated consolidation, curing comp. up to 6 Hundred Six
meterdepth or height (excluding cost of reinforcement and neat finishing) with centering and only
shuttering/deshuttering etc. comp. for structure for other than water retaining. (with form
Information Board for all chambers Eight
Supplying and fixing road sign board of M.S. plates and angle iron including painting, Hundred
lettering etc. complete including fixing in C.C. 1:4:8 with necessary excavation etc. complete Seventy
as per I.R.C. type design.(i) Non -Reflective type Eight &
RMU Room of 5.1 x 8.2 m of minimum 4.5 m clear height from plinth to beam bottom at Nine
roof slab as per datasheet and Specification. Hundred
Landscape and gardening work - Providing and executing complete gardening,
landscaping, drip irrigation and outdoor garden-lighting works including clearing of
jungle/vegetation; supplying and stacking of good earth and well-decayed cow dung
manure; mixing, spreading and preparation of soil; tree-plantation including excavation,
refilling and watering; supply and planting of well-developed trees; providing and laying
10 4,000.00 Sqm 288.13 Eighty Eight
doob-grass turf with maintenance; installation of complete drip irrigation system with HDPE
piping, laterals, emitters, control valves and accessories; and complete outdoor electrical
garden-lighting works including supply, erection and commissioning of lighting fittings, poles,
foundations, cables, DWC pipes, MCBs, terminations and all associated works,
specifications and directions of the Engineer-in-Charge.
GWIL Page 18 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-3 Mechanical Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
Supply, installation, testing & commissioning of Vertical Turbine pump motor set of specified duty
parameters & guaranteed efficiency of following MOC with specified capacity vertical solid shaft CACA,
Squirrel cage, Insulated bearing at NDE side, VFD Compatible induction motor, working on three
phase AC supply with 50 Hz ± 5%, 6.6kV ± 10%, rated speed 990 RPM along with column and bowl
assembly, discharge head, base channel / RSJ, self-lubrication for line shaft bearing etc. complete as
per relevant IS/ International Standard, tender datasheet and specification.
M.O.C.: Impeller: Duplex Steel Confirming to ASTM A890 – Grade 1B, Sealing rings: AISI SS
CF8M, Bowl & Suction Bell: Cast Steel WCB, Shaft with coupling: Duplex Steel confirming to
ASTM A276 S31803/S32205, Column Pipe: M.S., Mechanical Seal, Base Plate: MS, Line Bearing:
1 Thordon type, Suction Strainer: SS316 with suitable rating motor to draw clear water from bottom of the 8.00 Set 1,28,86,650.00
sump. Flanges machined faced and having dimensions- PCD, OD, Thickness, Holes as per ISO-7005-
1 or as per manufacturer's design with companion flanges (PN 16).
Discharge Capacity (Q) 3000 m3/hr, 81 m Head (H) each at 990 RPM, 900 kW (Minimum) and as per
the relevant IS, Data sheet and detailed tender specifications. (5W + 3S), with 87% minimum
guaranteed bowl efficiency as per HIS without negative tolerance. Motor rating is minimum 900 kW
(Minimum) or suitable to above pump. Pumpmotor set should be as per relevant standard, tender data
sheet & detailed tender specifications. The item descriptions provided in the BOQ indicate the
minimum requirement only. The specifications and details mentioned in the tender datasheet and
technical specifications shall also be strictly followed.
SITC of PN-1.6, Double Flanged Dual Plate Check Valve (DPCV), conforming to API - 594 having Rupees
body, disc in graded Cast Steel of ASTM A216 Gr. WCB, spring, hinge pin, body seat, plate seat of Two Lac
S.S. AISI 316, dody seat ring of EPDM & retainer of ASTM A216 Gr. WCB. Valve seat tested to 16 Seventy
kg/cm2 and body to 24 kg/cm2. Flanges machined faced and having Dimensions- PCD, OD, One
Thickness, Holes as per ISO-7005-1. Hydraulic tests certificate & certificate of material of construction Thousand
2 of parts shall be submitted before despatch of valves as per design with companion flages, all 8.00 No. 2,71,037.33 Thirty
accessories, hardware, bolts, nuts, washers, rubber gasket, necessary mounting supports etc. Seven &
complete. (on Delivery Side) Paise
(A) -- 800 mm dia. (1 No on each delivery pipe) Three
SITC of PN-1.6, Double Flanged Modulating Type Electrically Operated Butterfly valves with
electric actuator having integral starter generally conforming to IS:13095 having body & disc in Rupees
graded Cast Steel of ASTM A216 Gr. WCB, shaft & thurst pad of stainless steel AISI 410, body seat Six Lac
ring, clamping ring, disc pin, internal hardware of SS AISI 304 and disc seal ring of EPDM. Valve seat Three
tested to 16 kg/ cm2 and body to 24 kg/ cm2, Flanges machined faced and having Dimensions- PCD, Thousand
OD, Thickness, Holes as per ISO-7005-1. Hydraulic tests certificate & certificate of material of One
construction of parts shall be submitted before despatch of valves as per design with companion Hundred
flages, all accessories, hardware, bolts, nuts, washers, rubber gasket, necessary mounting supports Seven
GWIL Page 19 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-3 Mechanical Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
800 mm dia. (0 1 Nos. on each delivery pipe)
SITC of PN-1.6, Double Flanged Modulating Type Electrically Operated Butterfly valves with
electric actuator having integral starter generally conforming to IS:13095 having body & disc in
graded Cast Steel of ASTM A216 Gr. WCB, shaft & thurst pad of stainless steel AISI 410, body seat
ring, clamping ring, disc pin, internal hardware of SS AISI 304 and disc seal ring of EPDM. Valve seat
tested to 16 kg/ cm2 and body to 24 kg/ cm2, Flanges machined faced and having Dimensions- PCD,
OD, Thickness, Holes as per ISO-7005-1. Hydraulic tests certificate & certificate of material of
construction of parts shall be submitted before despatch of valves as per design with companion
4 2.00 No. 46,18,518.00 Thousand
flages, all accessories, hardware, bolts, nuts, washers, rubber gasket, necessary mounting supports
The motorized actuator shall be mounted on top of the chamber, incorporating the extended SS shaft
and precision-aligned mounting bracket supported on a suitable rigid MS structural section including all
required material etc complete.
(A) 2000 mm dia. PN 1.6 (01 No. on Header & 01 No. on Branch Pipe)
5 (B) '-----do as above------but, 2400 mm dia. PN 1.6 (Interconnection Branch Pipe Line) 1.00 No. 53,70,363.00 Thousand
SITC of Air cushion valve as surge control device of following class and diameter with companion One Lac
flanges, accesseries, hardware, necessary mounting supports etc. & including all taxes, insurance, Eighty
transportation, freight charges, octroi, inspection charges, loading, unloading, conveyance to Thousand
Departmental stores/Contractor's own stack yard, stacking, stack yard to site transportation charges Nine
6 etc. complete. 1.00 No. 1,80,958.67 Hundred
Flanges machined faced and having Dimensions- PCD, OD, Thickness, Holes as per ISO-7005-1. Fifty Eight
300 MM (Air cusion with M.S. Body), (PN 1.6)Class-15 + 300 mm dia MS Sluice Valve PN 1.6 with & Paise
hand/wheel cap operated (PD type Short body) Sixty
SITC of PN-1.6, Double Flanged Electric Operated Sluice Valve with electrical actuator having Rupees
7 integral starter generally conforming to API 600 / equivalent standard having body, bonnet, wedge & 8.00 No. 12,44,920.67 Twelve
gland in graded Cast Steel as per ASTM A216 Gr. WCB , Stem - AISI 410, body ring & wedge ring - IS Lac Forty
GWIL Page 20 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-3 Mechanical Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
318 Gr LTB-2, packing of Graphoil Filler, internal hardware of SS AISI 304, Wedge Nut and Stem Nut Four
of IS 318 Gr LTB-2. Valve seat tested to 16 kg/ cm2 and body to 24 kg / cm2 Flanges machined faced Thousand
and having Dimensions- PCD, OD, Thickness, Holes as per ISO-7005-1. Hydraulic tests certificate & Nine
certificate of material of construction of parts shall be submitted before despatch of valves as per Hundred
design with required accessories, erection hardware, necessary mounting support, etc. Twenty &
(B) -- 800 mm dia. (01 No. on each delivery pipe) Sixty
SITC of PN-1.6, ISI mark Double Flanged Sluice Valve (Non rising) generally conforming to IS
:14846 having body, bonnet, wedge & gland in graded Cast Steel as per ASTM A216 Gr. WCB , Stem -
AISI 410, body ring & wedge ring - IS 318 Gr LTB-2, packing of Graphoil Filler, internal hardware of SS
AISI 304, Wedge Nut and Stem Nut of IS 318 Gr LTB-2. Valve seat tested to 16 kg/ cm2 and body to
24 kg / cm2 Flanges machined faced and having Dimensions- PCD, OD, Thickness, Holes as per ISO-
7005-1. Hydraulic tests certificate & certificate of material of construction of parts shall be submitted
before despatch of valves as per design with companion flages, all accessories, hardware, bolts, nuts,
washers, rubber gasket, necessary mounting supports etc.
(A) --200 mm dia. (On Delivery bypass line)
9 (B) ----- do as above ---- but, 450 mm dia. (For by pass on Common Header) 1.00 No. 2,28,073.33 Seventy
SITC of PN-1.6, Flanged High Performance, single chamber, temper proof Kinetic Air Valve Rupees
confirming to AWWA C 512 automatic Air Release Valve with Isolating PN 1.6 Manually hand wheel Sixty
operated non rising spindle type Sluice Valve, both having MOC of graded Cast Steel ASTM A216 Gr Three
WCB, for water combination type (non tempering type) having single ball, single orifice with stainless Thousand
steel SS304 ball, tamper proof air vents rolling seal mechanism for air release and anti vacuum Five
application designed for 16 kg/cm2 working pressure and tested for 24 kg/cm2 pressure. Flanges Hundred
machined faced and having Dimensions- PCD, OD, Thickness, Holes as per ISO-7005-1. Hydraulic Forty
tests certificate & certificate of material of construction of parts shall be submitted before despatch of Three &
valves. (Rate to include cost of gaskets, bolts, nut and any other materials required for jointing and its Paise
transportation etc. including all taxes and duties. With required accessories, erection hardware, Sixty
necessary mounting supports etc. Seven
GWIL Page 21 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-3 Mechanical Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
(A) 200 mm dia. (on Common Header)
Supply, installation, testing & commissioning of PN 1.6 flange ends Expansion Bellow as per Rupees
EJMA standards of overall length of minimum 300 mm, with companion flanges, accessories erection Fifty
hardware, necessary mounting supports etc. designed for 15 mm axial compression and 5 mm axial Thousand
11 extension with tie rods etc. of following MOC & pressure ratings.MOC: Bellows: SA 240 Gr. 304; 8.00 No. 50,856.00 Eight
Internal Sleeve: SA 240 Gr. 304; Weldends: IS 2062 Gr. B; Flanges: IS 2062 Gr. B, Flanges machined Hundred
faced and having Dimensions- PCD, OD, Thickness, Holes as per ISO-7005-1 & Limit Rods & Nuts: Fifty Six
CS - IS 1367. only
(A)--800 mm dia., Overall length of minimum 300 mm (For each delivery pipeline)
Supply, installation, testing & commissioning of PN 1.6 flange ends Expansion Bellow as per Rupees
EJMA standards of overall length of minimum 450 mm with companion flanges, accessories erection One Lac
hardware, necessary mounting supports etc. designed for 15 mm axial compression and 5 mm axial Eighty
extension with tie rods etc. of following MOC & pressure ratings.MOC: Bellows: SA 240 Gr. 304; Thousand
Internal Sleeve: SA 240 Gr. 304; Weldends: IS 2062 Gr. B; Flanges: IS 2062 Gr. B, Flanges machined One
faced and having Dimensions- PCD, OD, Thickness, Holes as per ISO-7005-1 & Limit Rods & Nuts: Hundred
CS - IS 1367. Fifty Two
(A)--2000 mm dia., Overall length of minimum 450 mm (01 No. For Header pipeline & 01 No. For
Supply, installation, testing & commissioning of PN 1.6 flange ends Expansion Bellow as per
EJMA standards of overall length of minimum 500 mm, with companion flanges, accessories erection
hardware, necessary mounting supports etc. designed for 15 mm axial compression and 5 mm axial
extension with tie rods etc. of following MOC & pressure ratings.MOC: Bellows: SA 240 Gr. 304;
13 1.00 No. 2,12,105.00 Thousand
Internal Sleeve: SA 240 Gr. 304; Weldends: IS 2062 Gr. B; Flanges: IS 2062 Gr. B, Flanges machined
faced and having Dimensions- PCD, OD, Thickness, Holes as per ISO-7005-1 & Limit Rods & Nuts:
CS - IS 1367. (A)--2400 mm dia., Overall length of minimum 500 mm (ForInterconnecting Branch
SITC of following type of Plain & Socket ends type Fabricated MS Specials like tee, 90° bend,
tapper, distance pipe piece, dismentling joint, bolts, nuts, washers, rubber packing, suction strainer etc,
for suction, delivery, header, bypass pipelines and suitable for above pumpsets.
M.S. pipe 168.3mm OD and above should be conforming to IS-3589/2001 and MS Pipe below 168.3 Rupees
14 mm OD should be heavy duty as per IS-1239 Part-1/2004 or latest. All specials & pipes should be 66986.00 Kg. 96.00 Ninety
painted by epoxy paint. The item also includes job connection work for connection of MS header Six only
pipeline to MS rising main pipeline.
Weight of 90° Bend
GWIL Page 22 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-3 Mechanical Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
1) Up to 300 mm dia.
2) Above 300 mm dia.
SITC of following type of Flanged Type Fabricated MS Specials flanges, blind flange, dismentling
joint, bolts, nuts, washers, rubber packing, suction strainer etc, for suction, delivery, header, bypass
pipelines and suitable for above pumpsets.
Flanges machined faced and having Dimensions - PCD, OD, Thickness, Holes as per ISO 7005-1 (PN
20). All specials & pipes should be painted by epoxy paint. The item also includes job connection work
for connection of MS header pipeline to MS rising main pipeline.
Weight of Flanges
1) Up to 300 mm dia.
2) Above 300 mm dia.
SITC of Electric Resistance Welded (Up to 400 mm) / Submerged Arc Welded (Above 400 mm)
M.S.Pipe shall be externally protected by the application of 2 to 3 coats of high-quality bituminous
paint, achieving a total dry film thickness (DFT) of 150 to 200 microns. The surface shall be thoroughly
cleaned to remove rust, scale, oil, and other contaminants to ensure proper adhesion and long-term
corrosion resistance in both above-ground and buried conditions having beveled ends plate or coil
16 conforming to IS-3589-2001 or its latest revision/ ammendment for following thickness outside diameter 200.00 rmt 11,960.00
at GWSSB/GWIL store or site anywhere in Gujarat State including all taxes, insurance, transportation,
freight charges, octroi, inspection charges, loading, unloading conveyance to Departmental
stores/Contractor's own stack yard, stacking, stack yard to site transportation charges etc. all complete.
For 813 mm OD x 8 mm thick (Delivery Pipeline)
17 ---------do as above --------for 219.1 mm OD x 4.5 mm thick ( By pass Pipeline for delivery ) 120.00 rmt 1,900.00
18 ---------do as above --------for 457.0 mm OD x 5 mm thick ( By pass Pipeline for header ) 25.00 rmt 4,330.00 Three
---------do as above --------for 2032.0 mm OD x 16 mm thick Fifty Eight
19 (Common Header Pipeline of NC-28 (165m) and Interconnection Pipeline (15m) till sump from 180.00 rmt 58,529.00 Thousand
exisitng 2500 mm dia pipeline ) Five
GWIL Page 23 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-3 Mechanical Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
20 ---------do as above --------for 2540.0 mm OD x 20 mm thick ( Branch Pipeline ) 20.00 rmt 90,893.00
21 ---------do as above --------for 323.9 mm OD x 5.6 mm thick ( for Air Cushion Valve ) 2.00 rmt 3,403.00 Four
Dredging Pump-Set : SUBMERSIBLE NON-CLOG VERTICAL PUMP:
Supply, installation, testing & commissioning of sewage submersible, non clog type suitable for working
on three phase, 50 Hz ± 3%, 415 V ± 10%, AC supply, 1450 RPM synchronous speed with 3 core flat
copper cable from pump to starter panel with cable end terminations, all supports, valves, clamps, pipe
22 fittings along with mechanical seal, bearing bush, strainer, suitable size flexible delivery pipe up to 2.00 No. 4,84,957.00
neares discharge point etc. complete set & following M.O.C: Casing: CI, Impeller: SS CF8M, Wearing
ring & Bearing bush: Bronze, TC mechanical seal, CS / SS bearing, SS shaft with sleeve, SS strainer &
Pump of Capacity of 30 HP -02 Nos. for old SPP-3A & NC -28 Existing Sump
Dredging Pump-Set: SUBMERSIBLE NON-CLOG VERTICAL PUMP:
Supply, installation, testing & commissioning of sewage submersible, non clog type suitable for working Seven
on three phase, 50 Hz ± 3%, 415 V ± 10%, AC supply, 1450 RPM synchronous speed with 3 core flat Lac
copper cable from pump to starter panel with cable end terminations, all supports, valves, clamps, pipe Ninety
23 fittings along with mechanical seal, bearing bush, strainer, suitable size flexible delivery pipe up to 1.00 No. 7,91,602.00 One
neares discharge point etc. complete set & following M.O.C: Casing: CI, Impeller: SS CF8M, Wearing Thousand
ring & Bearing bush: Bronze, TC mechanical seal, CS / SS bearing, SS shaft with sleeve, SS strainer & Six
MS motor body. Hundred
Pump of Capacity of 60 HP - For New Sump
Supply, fabrication, installation & testing of a mobile work platform with integrated staircase, Rupees
designed for safe and efficient elevated access in industrial use. The platform should be constructed Fifty Six
GWIL Page 24 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-3 Mechanical Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
using high-quality material for long term durability, corrosion resistant in harsh industrial Thousand
environmentmild with a non-slip chequered plate deck, and include guardrails on three sides for fall Fifty only
protection.The staircase must feature anti-slip treads, and the entire structure should be mounted on
four heavy-duty swivel castor wheels. Each wheel shall include a locking mechanism to ensure stability
during use. Wheel shall be made of polyurethane or equivalent material suitable for industrial use. The
platform should support a minimum load capacity of 400 kg, and be finished with epoxy paint in safety
yellow for visibility and corrosion resistance. All components must comply with relevant IS/OSHA safety
SITC of trash rack designed especially for the grab cleaner (TRCM) having approximate a width of
5700 mm (Indicative) and height of 2700mm (Indicative) (Size suitable to channel size) . Bar spacing
50 mm. Size of trash bar 100 mm x 10mm. Material: Mild Steel IS 2062 E250 Gr. A/BR. The item is to
be executed as per the data sheet and detailed technical specifications. - 1 Set
SITC of grab cleaner (TRCM) for approximately 5700mm X 2700mm (Indicative) (Size suitale to canal
size) size trash rack to clean the debris including all accessories, motors, parking hut, structural
members switches, grab bucket & superstructure above the platform. Material: Mild Steel IS 2062 E250
Gr. A/BR. The item is to be executed as per the data sheet and detailed technical specifications. -
No. Structure work and civil foundation including all accessories required to complete the job for
25 1.00 Job 67,43,000.00 Lac Forty
Installation of above trash rack mechanism (trash rack & grab cleaner) at existing canal. The item is to
be executed as per the data sheet and detailed technical specifications. The trash rack mechanism
(trash rack, grab cleaner) shall be installed at existing channel having channel height of approximately
2.7 m. The item descriptions provided in the BOQ indicate the minimum requirement only. The
specifications and details mentioned in the tender datasheet and technical specifications shall also be
strictly followed.
Trash Rack with Grab Clearner (TRCM) mounted on Existing channel
'SITC of SS Wire Mesh Screen including Embedded Guide Frame and Lifting Beam. The wire mesh
screen size shall be 3000mm (W) X 8000 mm(H) (The dimensions of screen is indicative and may very Rupees
as per the actual structural design of pump compartment walls). The wire mesh shall have square Thirty Lac
opening of 25mm X 25mm & minimum 6.00mm wire diameter (diameteris indicative as minimum only it Twenty
may change during detail engineering) . The wire mesh screen shall consist of a minimum of five (5) Thousand
segmented sections. Each segment shall be sized appropriately to ensure equal distribution across the Six
total length. An embedded guide frame shall be provided and mounted on the pump compartment wall. Hundred
Additionally, an automatic engaging and disengaging type lifting beam shall be provided for handling Forty
the wire mesh screen. The item descriptions provided in the BOQ indicate the minimum requirement Seven &
only. The specifications and details mentioned in the tender datasheet and technical specifications Paise Six
shall also be strictly followed.Material of construction of wire mesh with frame, guide frame (Channel), only
lifting beam & hardware etc : Stainless Steel Type 316(Wire Mesh At Upstream of each pumps
E.O.T. Crane: Rupees
Supply, installation, testing & commissioning double girder type fully electrically operated EOT crane Lac Thirty
with electrically operated hoist, class II duty, geared travelling trolley with required lift complete with Four
GWIL Page 25 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-3 Mechanical Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
long travel rail track (With gantry girder, ISMC & minimum 50 mm sq. bar), moving or cross girder, all Thousand
three motions electrically operated by suitable rating motor IP 54, control panel & down pendant control Two
block, brake, safety device, DSL,Support structure and cables form motor to starter panel to Pendent Hundred
Push Button & other required accessories & tested as per IS specifications. Fifty only
The item descriptions provided in the BOQ indicate the minimum requirement only. The specifications
and details mentioned in the tender datasheet and technical specifications shall also be strictly
Minimum 10 Ton Capacity or as per actual requirement (Span, Long Travel & Lift shall be as per site
Supply, installation, testing & commissioning, Minimum 2 Ton (Indicative, Actual capacity as per site
requirement) , electrically operated monorail hoist, class II duty, geared travelling trolley with minimum
16 meter lift or as per the actual site condition complete with long travel rail track, monorail all two
motions electrically operated by suitable rating motor IP 54, control panel & down pendant control
block, brake, DSL, DSL structural support ,safety device and cables from motor to starter panel to
Pendent Pushbutton, Gantry Girder ISMB & other required accessories & tested as per IS
28 Specifications. The item descriptions provided in the BOQ indicate the minimum requirement only. The 1.00 No. 6,53,500.00
specifications and details mentioned in the tender datasheet and technical specifications shall also be
strictly followed.
Hoist For-Wire Mesh Screen at Pump House (Long Travel Length & Lift shall be as per site
Supply, installation, testing, and commissioning of a pillar-mounted jib crane with a rated capacity of
Minimum 2 Ton or as per actual site requirment) and a lifting height of Minimum15 meters or as per
actual site requirment, complete with electric wire rope hoist, motorized trolley, 360° slewing
arrangement, heavy-duty steel column and jib arm designed as per IS 807/ IS 3177 standards, Rupees
equipped with limit switches, overload protection, pendant control station, required cables from motors Eight Lac
to control panel to pendent push button, corrosion-resistant finish, and suitable for 415 V, 3-phase, 50 Sixty
29 Hz power supply, including all accessories,Civil foundation, foundation bolts, and compliance with 1.00 No. 8,63,020 Three
relevant safety and electrical standards. Thousand
The item descriptions provided in the BOQ indicate the minimum requirement only. The specifications Twenty
and details mentioned in the tender datasheet and technical specifications shall also be strictly only
Jib Crane For Dredging Pump Loading Unloading (Cross Travel Length & Lift shall be as per
site requirement)
Design, Engineering, Supply, Installation, Testing & Commissioning of Capacity (R-410A /R-407c or Rupees
eco-friendly Refrigerant) Air Cooled type OUTDOOR UNITS of VRF system having hermetically sealed Seventy
scroll inverter compressor, condenser coil fabricated from Seamless Copper tube & Plate type Al. Fins Three
of Multi Row, Axial Flow, upward throw condenser fan, Condenser fan - motor unit, insulated Lac Thirty
refrigeration piping, power / control wiring, and earthing, external wiring between Indoor & Outdoor Seven
units, all system controls-safety. Each Outdoor units with High Pressure switch, Fan driver overload Thousand
GWIL Page 26 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-3 Mechanical Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
protector, Over current relay, Inverter Overload Protector & Fusible Plug. The unit shall be suitable for Nine
415 ± 10 % volts, 50 Hz, 3 phase AC supply, and IP 55 protection. The out door unit shall be installed Hundred
on M.S. platform duly painted, as per specifications. VRF / VRV AC EQUIPMENTS. Minimum 40 Tone Nine only
or as per detail engineering whichever is higher. Supply Installation Testing & commissioning AHU
Controller / distribution kit of suitable capacity for connecting multi VRF ODU to DX AHU, with a) built in
auto restart function with necessary electrical wiring & remote controller.
SITC of DX double skin Air Handling Unit working on 100% fresh air of mentioned capacities below:
Specifications : Unit shall have Double Skin wall panels, 40 mm thick sandwich PUF injected panels.
Outer skin shall be 0.6 mm pre painted sheet with 275 GSM Zn coating. Inner sheet shall be 0.6 mm
GSS, Complete with Glass view panel, marine light, limit switch, cable entry, GSS base frame. Screw
less construction with zero leakage in the panel joints. DX Coil - 6RD/8RD air cooled DX coil. DX coil
shall have 12.5 to 15 mm dia (O.D) tubes minimum 0.35 mm thick with sine wave aluminium fins firmly
bonded to copper tubes assembled in zinc coated steel frame with SS Drain tray. Direct Driven
Backward / Forward Curved Plug Fans with VFD, with Squirrel cage IE2 induction motor, Motor shall
be suitable for operation of Variable Frequency Drive operation with 415±10% volts, 3 phase AC
supply included with VFD. Each unit shall be provided with a factory assembled filter section containing
pre filters( EU-4) filters. Filter bank framework shall be fully sealed and constructed from GSS.
Minimum 25000 CFM or as per detail engineering whichever is higher.
GSS Ducting:- Supplying fabrication installation testing and commissioning of GI. Sheet metal ducting.
Zinc coated. Complete with all Standard Accessories, G.I.. Hardware, Self Adhesive elastomeric foam
gasket, Support etc as per SMACNA specification. GSS Ducting:- 20 SWG for Supply and Return Air
Duct. Minimum 60 sqmtr or as per detail engineering whichever is higher.
Providing thermal insulation to supply air ducting with 19mm.thickness nitrile rubber. Minimum 60 sqmtr
or as per detail engineering whichever is higher. Providing thermal insulation to return air ducting with
12mm.thickness nitrile rubber. Minimum 30 sqmtr or as per detail engineering whichever is higher.
Providing fresh air damper with crowl piece,bird screen and removable type prefilters. Minimum
Sqmtr or as per detail engineering whichever is higher. Providing aluminium supply air diffusers &
return air grills with volume control dampers. Minimum 3 Sqmtr or as per detail engineering whichever
is higher. Supply & fixing acoustic insulation in the Plant room/ AHU room.Minimum 160 sqmtror as per
detail engineering whichever is higher. S & I of Control Panel for DX AHU/ Packaged/ Precision AC
Units. The item descriptions provided in the BOQ indicate the minimum requirement only. The
specifications and details mentioned in the tender datasheet and technical specifications shall also be
strictly followed. For VFD Panel Room
SITC of Electrical actuator operated SS sluice gate as per relevant standard to be mounted on side Twenty
walls having size 1500 mm (W) x 2000 mm (H). The gates shall be suitable for 3m Seating & unseating Two Lac
operating water head from center line of the Gate. The sluice gate shall have flush bottom closure, Eighty Six
31 rising spindle type, self-contained with closed top frame. (Material - Stainless Steel ASTM A240 Type 1.00 No. 22,86,005.70 Thousand
316/316L) Design head as per actual site condtion. The item descriptions provided in the BOQ indicate Five &
the minimum requirement only. The specifications and details mentioned in the tender datasheet and Paise
technical specifications shall also be strictly followed. Seventy
GWIL Page 27 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-3 Mechanical Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
SITC of Electrical actuator operated SS sluice gate as per relevant standard to be mounted on side Twenty
walls having size 2000 mm (W) x 3000 mm (H). The gates shall be suitable for 3m Seating & unseating Seven
operating water head from center line of the Gate. The sluice gate shall have flush bottom closure, Lac
rising spindle type, self-contained with closed top frame. (Material - Stainless Steel ASTM A240 Type Eighty
316/316L) Design head as per actual site condtion. The item descriptions provided in the BOQ indicate One
the minimum requirement only. The specifications and details mentioned in the tender datasheet and Thousand
technical specifications shall also be strictly followed. Six
GWIL Page 28 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE -B4-Mechanical Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
Supply, installation, testing & commissioning of Vertical Turbine pump motor set of specified duty
parameters & guaranteed efficiency of following MOC with specified capacity vertical solid shaft
CACA, Squirrel cage induction motor, working on three phase AC supply with 50 Hz ± 5%,
6.6kV ± 10%, rated speed 990 RPM along with column and bowl assembly, discharge head, base
channel / RSJ, self-lubrication for line shaft bearing etc. complete as per relevant IS/ International
Standard, tender datasheet and specification. Rupees
M.O.C.: Impeller: Duplex Steel Confirming to ASTM A890 – Grade 1B, Sealing rings: AISI SS One Crore
CF8M, Bowl & Suction Bell: Cast Steel WCB, Shaft with coupling: Duplex Steel confirming Twenty
to ASTM A276 S31803/S32205, Column Pipe: M.S., Mechanical Seal, Base Plate: MS, Line Eight Lac
1 Bearing: Thordon type, Suction Strainer: SS316 with suitable rating motor to draw clear water from 9.00 Set 1,28,86,650.00 Eighty Six
bottom of the Sump. Flanges machined faced and having dimensions- PCD, OD, Thickness, Holes Thousand
as per ISO-7005-1 or as per manufacturer's design with companion flanges (PN 20). Six
Discharge Capacity (Q) 1902 m3/hr, 126 m Head (H) each at 990 RPM, 900 kW and as per the Hundred
relevant IS, Data sheet and detailed tender specifications. (6W + 3S), with 87% minimum Fifty only
guaranteed bowl efficiency as per HIS without negative tolerance. Motor rating is minimum 900 kW
or suitable to above pump. Pumpmotor set should be as per relevant standard, tender data sheet
& detailed tender specifications. The item descriptions provided in the BOQ indicate the minimum
requirement only. The specifications and details mentioned in the tender datasheet and technical
specifications shall also be strictly followed.
SITC of PN-2.0, Double Flanged Dual Plate Check Valve (DPCV), conforming to API - 594 having
body, disc in graded Cast Steel of ASTM A216 Gr. WCB, spring, hinge pin, body seat, plate seat of
S.S. AISI 316, dody seat ring of EPDM & retainer of ASTM A216 Gr. WCB. Valve seat tested to
kg/cm2 and body to 30 kg/cm2. Flanges machined faced and having Dimensions- PCD, OD,
Thickness, Holes as per ISO-7005-1. Hydraulic tests certificate & certificate of material of
construction of parts shall be submitted before despatch of valves as per design with companion
flages, all accessories, hardware, bolts, nuts, washers, rubber gasket, necessary mounting
supports etc. complete. (on Delivery Side)
(A) -- 600 mm dia. (1 No on each delivery pipe)
SITC of PN-2.0, Double Flanged Modulating Type Electrically Operated Butterfly valves with
electric actuator having integral starter generally conforming to IS:13095 having body & disc in
graded Cast Steel of ASTM A216 Gr. WCB, shaft & thurst pad of stainless steel AISI 410, body
seat ring, clamping ring, disc pin, internal hardware of SS AISI 304 and disc seal ring of EPDM.
Valve seat tested to 22 kg/ cm2 and body to 30 kg/ cm2, Flanges machined faced and having
3 Dimensions- PCD, OD, Thickness, Holes as per ISO-7005-1. Hydraulic tests certificate & 9.00 No. 4,66,394.00
certificate of material of construction of parts shall be submitted before despatch of valves as per
design with companion flages, all accessories, hardware, bolts, nuts, washers, rubber gasket,
necessary mounting supports etc.
(A) -- 600 mm dia. (01 Nos. on each delivery pipe)
GWIL Page 29 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE -B4-Mechanical Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
(B) '-----do as above------but, 1600 mm dia. PN 2.0 (on Header) Four Lac
4 The motorized actuator shall be mounted on top of the chamber, incorporating the extended SS 1.00 No. 24,72,430.00 Two
shaft and precision-aligned mounting bracket supported on a suitable rigid MS structural section Thousand
including all required material etc complete. Four
SITC of PN-2.0, Double Flanged Electric Operated Sluice Valve with electrical actuator
having integral starter generally conforming to API 600 / equivalent standard having body,
bonnet, wedge & gland in graded Cast Steel as per ASTM A216 Gr. WCB , Stem - AISI 410, body
ring & wedge ring - IS 318 Gr LTB-2, packing of Graphoil Filler, internal hardware of SS AISI
Wedge Nut and Stem Nut of IS 318 Gr LTB-2. Valve seat tested to 22 kg/ cm2 and body to 30 kg /
cm2 Flanges machined faced and having Dimensions- PCD, OD, Thickness, Holes as per ISO-
7005-1. Hydraulic tests certificate & certificate of material of construction of parts shall be
submitted before despatch of valves as per design with required accessories, erection hardware,
necessary mounting support, etc.
600 mm dia. (01 No. on each delivery pipe)
SITC of PN-2.0, Double Flanged Manual Operated Sluice Valve generally conforming to API
600 / equivalent standard having body, bonnet, wedge & gland in graded Cast Steel as per ASTM
A216 Gr. WCB , Stem - AISI 410, body ring & wedge ring - IS 318 Gr LTB-2, packing of Graphoil
Filler, internal hardware of SS AISI 304, Wedge Nut and Stem Nut of IS 318 Gr LTB-2. Valve seat
tested to 22 kg/ cm2 and body to 30 kg / cm2 Flanges machined faced and having Dimensions-
6 9.00 No. 48,288.67 Hundred
PCD, OD, Thickness, Holes as per ISO-7005-1. Hydraulic tests certificate & certificate of material
of construction of parts shall be submitted before despatch of valves as per design with required
accessories, erection hardware, necessary mounting support, etc.
(A) --200 mm dia. (On Delivery bypass line)
7 (B) ----- do as above ---- but, 450 mm dia. (For by pass on Common Header) 1.00 No. 2,42,116.67 One
SITC of PN-2.0, Flanged High Performance, single chamber, temper proof Kinetic Air Valve Rupees
confirming to AWWA C 512 automatic Air Release Valve with Isolating PN 2.0 Manually hand One Lac
GWIL Page 30 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE -B4-Mechanical Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
wheel operated non rising spindle type Sluice Valve, both having MOC of graded Cast Steel ASTM Five
A216 Gr WCB, for water combination type (non tempering type) having single ball, single orifice Thousand
with stainless steel SS304 ball, tamper proof air vents rolling seal mechanism for air release and Two
anti vacuum application designed for 22 kg/cm2 working pressure and tested for 30 kg/cm2 Hundred
pressure. Flanges machined faced and having Dimensions- PCD, OD, Thickness, Holes as per Eighty
ISO-7005-1. Hydraulic tests certificate & certificate of material of construction of parts shall be Seven only
submitted before despatch of valves. (Rate to include cost of gaskets, bolts, nut and any other
materials required for jointing and its transportation etc. including all taxes and duties. With
required accessories, erection hardware, necessary mounting supports etc.
(A) 200 mm dia. (on Common Header)
SITC of Air cushion valve as surge control device of following class and diameter with companion
flanges, accesseries, hardware, necessary mounting supports etc. & including all taxes, insurance,
transportation, freight charges, octroi, inspection charges, loading, unloading, conveyance to
Departmental stores/Contractor's own stack yard, stacking, stack yard to site transportation
9 charges etc. complete. 1.00 No. 2,07,052.00
Flanges machined faced and having Dimensions- PCD, OD, Thickness, Holes as per ISO-7005-1.
300 MM (Air cusion with M.S. Body), (PN 2.0) Class-20 + 300 mm dia MS Sluice Valve PN
with hand/wheel cap operated (PD type Short body)
Supply, installation, testing & commissioning of PN 2.0 flange ends Expansion Bellow as
per EJMA standards of overall length of minimum 300 mm, with companion flanges, accessories
erection hardware, necessary mounting supports etc. designed for 15 mm axial compression and 5 Rupees
mm axial extension with tie rods etc. of following MOC & pressure ratings.MOC: Bellows: SA 240 Thirty Nine
Gr. 304; Internal Sleeve: SA 240 Gr. 304; Weldends: IS 2062 Gr. B; Flanges: IS 2062 Gr. B, Thousand
Flanges machined faced and having Dimensions- PCD, OD, Thickness, Holes as per ISO-7005-1 only
& Limit Rods & Nuts: CS - IS 1367. (A)--600 mm dia., Overall length of minimum 300 mm (For
each delivery pipeline)
Supply, installation, testing & commissioning of PN 2.0 flange ends Expansion Bellow as per
EJMA standards of overall length of minimum 450 mm, with companion flanges, accessories Rupees
erection hardware, necessary mounting supports etc. designed for 15 mm axial compression and 5 One Lac
mm axial extension with tie rods etc. of following MOC & pressure ratings.MOC: Bellows: SA 240 Sixty Four
Gr. 304; Internal Sleeve: SA 240 Gr. 304; Weldends: IS 2062 Gr. B; Flanges: IS 2062 Gr. B, Thousand
Flanges machined faced and having Dimensions- PCD, OD, Thickness, Holes as per ISO-7005-1 Two
& Limit Rods & Nuts: CS - IS 1367. Hundred
1600 mm dia., PN-2.0 -Header - Overall length of minimum 400 mm (On Common Header for
Butterfly Valve & Flow Meter)
SITC of following type of Plain & Socket ends type Fabricated MS Specials like tee, 90° bend, Rupees
tapper, distance pipe piece, dismentling joint, bolts, nuts, washers, rubber packing, suction strainer Ninety Six
GWIL Page 31 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE -B4-Mechanical Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
etc, for suction, delivery, header, bypass pipelines and suitable for above pumpsets. only
M.S. pipe 168.3mm OD and above should be conforming to IS-3589/2001 and MS Pipe below
168.3 mm OD should be heavy duty as per IS-1239 Part-1/2004 or latest. All specials & pipes
should be painted by epoxy paint. The item also includes job connection work for connection of MS
header pipeline to MS rising main pipeline.
Weight of 90° Bend
1) Up to 300 mm dia.
2) Above 300 mm dia.
SITC of following type of Flanged Type Fabricated MS Specials flanges, blank flange,
dismentling joint, bolts, nuts, washers, rubber packing, suction strainer etc, for suction, delivery,
header, bypass pipelines and suitable for above pumpsets.
Flanges machined faced and having Dimensions - PCD, OD, Thickness, Holes as per ISO 7005-1
(PN 20). All specials & pipes should be painted by epoxy paint. The item also includes job
connection work for connection of MS header pipeline to MS rising main pipeline.
Weight of Flanges
1) Up to 300 mm dia.
2) Above 300 mm dia.
SITC of Electric Resistance Welded (Up to 400 mm) / Submerged Arc Welded (Above
mm) M.S.Pipe shall be externally protected by the application of 2 to 3 coats of high-quality
bituminous paint, achieving a total dry film thickness (DFT) of 150 to 200 microns. The surface
shall be thoroughly cleaned to remove rust, scale, oil, and other contaminants to ensure proper
adhesion and long-term corrosion resistance in both above-ground and buried conditions having
beveled ends plate or coil conforming to IS-3589-2001 or its latest revision/ ammendment for
following thickness outside diameter at GWSSB/GWIL store or site anywhere in Gujarat State
including all taxes, insurance, transportation, freight charges, octroi, inspection charges, loading,
unloading conveyance to Departmental stores/Contractor's own stack yard, stacking, stack yard to
site transportation charges etc. all complete.
For 610 mm OD x 8 mm thick (Delivery Pipeline)
15 ---------do as above --------for 219.1 mm OD x 4.5 mm thick ( By pass Pipeline for delivery ) 135.00 rmt 1,900.00
16 ---------do as above --------for 457.0 mm OD x 5 mm thick ( By pass Pipeline for header ) 25.00 rmt 4,330.00 Thousand
GWIL Page 32 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE -B4-Mechanical Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
17 ---------do as above --------for 1626.0 mm OD x 16 mm thick ( Common Header Pipeline ) 120.00 rmt 46,751.00 Seven
18 ---------do as above --------for 323.9 mm OD x 5.6 mm thick ( for Air Cushion Valve ) 2.00 rmt 3,403.00
Dredging Pump-Set: SUBMERSIBLE NON-CLOG VERTICAL PUMP:
Supply, installation, testing & commissioning of sewage submersible, non clog type suitable for
working on three phase, 50 Hz ± 3%, 415 V ± 10%, AC supply, 1450 RPM synchronous speed
with 3 core flat copper cable from pump to starter panel with cable end terminations, all supports,
19 1.00 No. 7,91,602.00 Thousand
valves, clamps, pipe fittings along with mechanical seal, bearing bush, strainer, suitable size
flexible delivery pipe up to neares discharge point etc. complete set & following M.O.C: Casing: CI,
Impeller: SS CF8M, Wearing ring & Bearing bush: Bronze, TC mechanical seal, CS / SS bearing,
SS shaft with sleeve, SS strainer & MS motor body.
Pump of Capacity of 60 HP (For new sump)
Dredging Pump-Set: SUBMERSIBLE NON-CLOG VERTICAL PUMP:
Supply, installation, testing & commissioning of sewage submersible, non clog type suitable for Rupees
working on three phase, 50 Hz ± 3%, 415 V ± 10%, AC supply, 1450 RPM synchronous speed Four Lac
with 3 core flat copper cable from pump to starter panel with cable end terminations, all supports, Eighty
valves, clamps, pipe fittings along with mechanical seal, bearing bush, strainer, suitable size Four
20 flexible delivery pipe up to neares discharge point etc. complete set & following M.O.C: Casing: CI, 2.00 No. 4,84,957.00 Thousand
Impeller: SS CF8M, Wearing ring & Bearing bush: Bronze, TC mechanical seal, CS / SS bearing, Nine
SS shaft with sleeve, SS strainer & MS motor body. Hundred
Pump of Capacity of 30 HP only
02 Nos. for old SPP-3A & NC -28 Existing Sump
Supply, installation, testing, and commissioning of a pillar-mounted jib crane with a rated capacity Rupees
21 of Minimum 2 Ton or as per actual site requirment) and a lifting height of Minimum15 meters or as 1.00 No. 8,63,020 Eight Lac
per actual site requirment, complete with electric wire rope hoist, motorized trolley, 360° slewing Sixty
GWIL Page 33 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE -B4-Mechanical Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
arrangement, heavy-duty steel column and jib arm designed as per IS 807/ IS 3177 standards, Three
equipped with limit switches, overload protection, pendant control station, required cables from Thousand
motors to control panel to pendent push button, corrosion-resistant finish, and suitable for 415 V, Twenty
3-phase, 50 Hz power supply, including all accessories,Civil foundation, foundation bolts, and only
compliance with relevant safety and electrical standards. The item descriptions provided in the
BOQ indicate the minimum requirement only. The specifications and details mentioned in the
tender datasheet and technical specifications shall also be strictly followed.Jib Crane For
Dredging Pump Loading Unloading (Cross Travel Length & Lift shall be as per site
Supply, installation, testing & commissioning double girder type fully electrically operated EOT
crane with electrically operated hoist, class II duty, geared travelling trolley with required lift
complete with long travel rail track (With gantry girder, ISMC & minimum 50 mm sq. bar), moving
or cross girder, all three motions electrically operated by suitable rating motor IP 54, control panel
& down pendant control block, brake, safety device, DSL,Support structure and cables form motor
22 to starter panel to Pendent Push Button & other required accessories & tested as per IS 1.00 No 13,34,250.00
specifications. The item descriptions provided in the BOQ indicate the minimum requirement only.
The specifications and details mentioned in the tender datasheet and technical specifications shall
also be strictly followed.
Minimum 10 Ton Capacity or as per actual requirement (Span, Long Travel & Lift shall be as per
site requirement)
Supply, installation, testing & commissioning, Minimum 2 Ton (Indicative, Actual capacity as per
site requirement) , electrically operated monorail hoist, class II duty, geared travelling trolley with
minimum 16 meter lift or as per the actual site condition complete with long travel rail track,
monorail all two motions electrically operated by suitable rating motor IP 54, control panel & down Rupees
pendant control block, brake, DSL, DSL structural support ,safety device and cables from motor to Six Lac
starter panel to Pendent Pushbutton, Gantry Girder ISMB & other required accessories & tested as Fifty Three
23 per IS Specifications. The item descriptions provided in the BOQ indicate the minimum 1.00 No. 6,53,500.00 Thousand
requirement only. The specifications and details mentioned in the tender datasheet and technical Five
specifications shall also be strictly followed. Hundred
Hoist For-Wire Mesh Screen at Pump House (Long Travel Length & Lift shall be as per site
GWIL Page 34 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
Supply, Installation, Testing and Commissioning of Outdoor Type, 72.5KV, 1250A, 31.5KA for 3Sec,
1 3Pole, 50Hz, Class-M2C2, SF6 Circuit Breaker, with Structure (25mm/KV, with terminal connectors) 3.00 Nos. 6,15,570.00
for Existing 66KV Switchyard and as per tender datasheet and technical specification.
66/6.9 kV,20000KVA Power transformers :
Design, Engineering, Procurement, Installation, Testing and Commissioning of outdoor type, three
phase, oil immersed, power transformer of required KVA & voltage ratio, copper double wound,
vector group- Dyn11, HV delta connected & LV star connected with neutral brought out connected to
provide separate earthing terminals, bushing on HV side and cable box on LV side with extended
busbar suitable for ease of multiple runs and cores cable terminations as per requirement with
standard fittings, conforming to IS: 2026 - 2011 with its latest amendment including first fill of
transformer oil & following accessories. (a) Oil conservator with filling holes with cap, magnetic oil
level gauge and prismatic oil level gauge. (b) Silica Gel dehydrating breather charged with silica gel
for Main conservator tank and OLTC conservator tank (c) Oil drain cum sampling valves with plug (d)
Oil filter valves (e) Lifting Eyes / Hooks / Lugs (f) Two earthing terminals (g) Diagram and rating plate
(h) Air release plugs (i) Pressure relief valves (j) Thermometer pockets (k) Four bi-directional plain
roller with base channel with hauling holes (l) Fixed / Separate type radiator banks with isolation
2 valves and drain plugs (m) Off circuit externally operated tapping switch (n) 100 mm stem type oil 2 Nos. 82,47,994.00
temperature indicator (o) Bucholz relay with shut off valves (p) Neutral Bushing Current Transformers
(q) 150 mm dial type oil temperature indicator with Alarm / Trip contact and 4 to 20mA Analog Output
(r) 150 mm dial type winding temperature indicator with Alarm / Tip contact and 4 to 20mA Analog
Output (s) Marshalling Cabinet (t) 150 mm dia. magnetic type oil gauge (u) Inspection cover &
Jacking lugs(v) ON LOAD TAP CHANGER +5% to -15% in steps of 1.25% with RTCC for & AVR (w)
Oil surge relay (x) Nitrogen injection fire protection system (NIFPS) and as per tender datasheet and
technical specification, Sufficient quantity of oil for first filling of complete transformer (with
accessories). The item descriptions provided in the BOQ indicate the minimum requirement only. The
specifications and details mentioned in the tender datasheet and technical specifications shall also
be strictly followed.
66/6.6 KV, Minimum 20000 KVA or as per detailed engineering whichever is higher, Max Losses as
per CBIP Manual, CEA guidelines and as per technical specification and Datasheet (Transformer &
its all accessories shall be GETCO Approved vendors only)
Control & Relay Panel Rupees
Design, Engineering, Supply, Installation, Testing and Commissioning of Simplex Indoor Type CRCA Fifteen
3 Sheet Cubicle of minimum thickness of 3mm for front & 2mm for all other sides, Gland Plate - 3mm 1 Set 15,87,500.00 Lac Eighty
Protection IP-4X Paint shade shall be 631 of IS: 5 for exterior and white for interior Control Relay Seven
Panels comprising of Indication Lamps, Voltmeter with Selector Switch, Ammeter with Selector Thousand
GWIL Page 35 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
Switch, Multifunction Meters, Numerical type microprocessor Protection Relays, Electromagnetic Five
Type Relays, Transformer Protection Relays, Semaphore indication Lamps, Circuit Breaker Control Hundred
Switches, Auxiliary Relays, Auxiliary Contactors, Test Terminal Blocks, Auto/Manual Selector only
Switches, Push Buttons, Emergency Stop Push Buttons, Annunciator, Hooter, Buzzer, MCBs, Panel
Illumination Lamp,Space Heater with Thermostate, Switch Socket, Wiring with 1.1KV PVC Copper
Flexible stranded FRLS grade wire, Earth Bus, etc. 1Nos. for 66KV Line incomer bay, 4Nos. for
66KV Transformer Feeder bay (2Nos. for New Proposed 20MVA Transformer Feeder, 2Nos. of
15MVA Transformer Feeders) including disconnecting cable from existing 12.5MVA and
15MVA Transformer and swichyard equipment and cable laying and termination of Power and
control cable from 66KV swichyard equipment to new proposed control relay panels of 66KV
line and transformer feeder. The item descriptions provided in the BOQ indicate the minimum
requirement only. The specifications and details mentioned in the tender datasheet and technical
specifications shall also be strictly followed.
Casting of transformer plinth / foundation including oil soak pit (where required) in situ reinforced
cement concrete in M 20 using granite, quartzite trap metal of size 6 mm to 20 mm for RCC work Rupees
including providing of 53 grade cement & CRS Fe-500 grade, scaffolding, entering, form work, curing Ninety
etc. complete. Thousand
RCC plinth / foundation for transformer of capacity 20000 KVA - Plinth Dimensions - 3000 x 2500 x only
500 or As per actual structure design calculation based on total weight of Transformer
Design, engineering, procurement, installation, testing and commissioning of 9.53 Ohms suitable for Six
5 6.6kV (Phase Voltage -6.6 KV),400A, 10 Sec. Neutral Grounding Resistors as per IS IEEE-32 with 2 No 2,06,500.00 Thousand
Mounting Steel Structures and as per tender datasheet and technical specification. Five
Dismantling of the existing 12.5 MVA Transformers from the plinth/foundation safely without any Twenty
damage and shifting to the place as suggested by engineer in charge within pump house premises. Six
HT Switchgear Panel (Common Panel of Power Supply for NC-28 & SPP-3A, SPP-3B Rupees
Design, engineering, procurement, installation, testing and commissioning both side extensible, type Seventy
tested, Indoor type HV Switchgear panel confirming to IS-3427, IS-2516 (Part- I & II.sec.1 ) & IEC- Three Lac
60056 & IEC-62271-100/200 for use on 3phase, 50 Hz, unearthed AC supply system and having Seventy
7 breaking/ ruptuing capacity as mentioned below complete with spring charged mechanism, ON-OFF 1 No. 73,71,716.00 One
mechanical push button, operation counters, Breaker TNC switch, Breaker L/R switch, necessary Thousand
auxiliary switches, closing coil, shunt trip, protection relays & Indicators, Push Buttons, Emergancy Seven
Push Button, Hooter, Annunciators, and accessories mentioned in tender Datasheet and Technical Hundred
Specifications etc. to complete the work in all respect. The panel shall comprise of air insulated Sixteen
GWIL Page 36 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
busbars provided with heat shrinkable PVC sleeves. The VCB trolley shall comprise of three vacuum only
interrupters with epoxy support insulators and self aligning finger type isolating contacts and
necessary mechanical interlocks, safety shutters, isolating plugs. Enclosure shall be openable from
front as well as rear end. The breaker shall be Manual cum motorised mechanism with following
accessories and accessories mentioned in as per tender datasheet and Specifications.
a) 96 x 96 mm square flush mounting type Ammeter & Volt meter with selector switches for all
b) Multi function meter for all feeders
c) Three Core cast resin type current transformer having ratio, burden and accuracy as per
requirement or as per tender specification and Datasheet (One core for metering, Second core for
protection and third core for differential protection applicable for incomer feeder), Double core, cast
resin type current transofrmers having ratio as per requirement, one core for metering & second core
for protection having required class of accuracy for outgoing feeders
d) Instantaneous under voltage relay & Temperature rise tripping Relay and relays as mentioned in
tender datasheet and specifications,
e) Feeder Protection Numerical IDMT Relay with IEC-61850 & RJ-45 port Protection, Tranformer
fault relay as mentioned in tender datasheet and specifications,
f) Comprehensive Motor Protection Relay as mentioned in tender datasheet and specifications (if
g) Electrical closing. coil & shunt trip coil operating on 110 V DC.
h) Auxiliary relay for anti pumping device.
h) Three limb, dual core, drawout type, feeder connected, cast resin insulated, Potential transformers
at line side and common bus having ratio, burden & accuracy mentioned in tender datasheet and
specifications.
i) Annunciator Windows, Hooter / Alarm bell operating on 230 AC/ 110 V DC for each feeders.
j) Cable boxes suitable to terminate 3 core XLPE cable of required size (As per design).
k) 230V AC to 110 V DC power pack for closing & tripping circuit common.
l) Breaker ON-OFF, Auto trip and spring charged indicators.
m) Phase indicating & panel illumination lamps with plug socket.
n) Space Heater with Thermostat. The item descriptions provided in the BOQ indicate the minimum
requirement only. The specifications and details mentioned in the tender datasheet and technical
specifications shall also be strictly followed.6.6 kV HV Switchgear Panel- Comprising of 2000 A,
31.5KA for 3Sec, 3Pole, Vacuum circuit breaker for 2nos. Incomer, 1no. Bus coupler, 2 Nos.
Bus PT and 10 Nos. 1250A, 3Pole O/G feeders Vacuum circuit breakers (2 nos. O/G feeders for
HT Panels of NC-28, 2Nos. O/G feeders for HT Panel of SPP-3A, 2Nos. O/G feeders for HT
Panel of SPP-3B, 2 Nos. for Bus Capacitor Panel, 2 Nos. Spare)
HT Switchgear Panel Rupees
Design, engineering, procurement, installation, testing and commissioning both side extensible, type Forty
tested, Indoor type HV Switchgear panel confirming to IS-3427, IS-2516 (Part- I & II.sec.1 ) & IEC- Three Lac
60056 & IEC-62271-100/200 for use on 3phase, 50 Hz, unearthed AC supply system and having Thirty Five
breaking/ ruptuing capacity as mentioned below complete with spring charged mechanism, ON-OFF Thousand
mechanical push button, operation counters, Breaker TNC switch, Breaker L/R switch, necessary Five
GWIL Page 37 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
auxiliary switches, closing coil, shunt trip, protection relays & Indicators, Push Buttons, Emergancy Hundred
Push Button, Hooter, Annunciators, and accessories mentioned in tender Datasheet and Technical Eighteen
Specifications etc. to complete the work in all respect. The panel shall comprise of air insulated only
busbars provided with heat shrinkable PVC sleeves. The VCB trolley shall comprise of three vacuum
interrupters with epoxy support insulators and self aligning finger type isolating contacts and
necessary mechanical interlocks, safety shutters, isolating plugs. Enclosure shall be openable from
front as well as rear end. The breaker shall be Manual cum motorised mechanism with following
accessories and accessories mentioned in as per tender datasheet and Specifications.
a) 96 x 96 mm square flush mounting type Ammeter & Volt meter with selector switches for all
b) Multi function meter for all feeders
c) Three Core cast resin type current transformer having ratio, burden and accuracy as per
requirement or as per tender specification and Datasheet (One core for metering, Second core for
protection and third core for differential protection applicable for incomer feeder), Double core, cast
resin type current transofrmers having ratio as per requirement, one core for metering & second core
for protection having required class of accuracy for outgoing feeders
d) Instantaneous under voltage relay & Temperature rise tripping Relay and relays as mentioned in
tender datasheet and specifications,
e) Feeder Protection Numerical IDMT Relay with IEC-61850 & RJ-45 port Protection, Tranformer
fault relay as mentioned in tender datasheet and specifications,
f) Comprehensive Motor Protection Relay as mentioned in tender datasheet and specifications (if
g) Electrical closing. coil & shunt trip coil operating on 110 V DC.
h) Auxiliary relay for anti pumping device.
h) Three limb, dual core, drawout type, feeder connected, cast resin insulated, Potential transformers
at line side and common bus having ratio, burden & accuracy mentioned in tender datasheet and
specifications.
i) Annunciator Windows, Hooter / Alarm bell operating on 230 AC/ 110 V DC for each feeders.
j) Cable boxes suitable to terminate 3 core XLPE cable of required size (As per design).
k) 230V AC to 110 V DC power pack for closing & tripping circuit common.
l) Breaker ON-OFF, Auto trip and spring charged indicators.
m) Phase indicating & panel illumination lamps with plug socket.
n) Space Heater with Thermostat. The item descriptions provided in the BOQ indicate the minimum
requirement only. The specifications and details mentioned in the tender datasheet and technical
specifications shall also be strictly followed The item descriptions provided in the BOQ indicate the
minimum requirement only. The specifications and details mentioned in the tender datasheet and
technical specifications shall also be strictly followed. 6.6 kV HV Switchgear Panel- Comprising of
1250 A, 26.3KA for 3Sec, Vacuum circuit breaker for 2nos. Incomer, 1no. Bus coupler, 2 Nos.
Bus PT, 8Nos. 1250A O/G feeders, 26.3KA for 3Sec, Vacuum circuit breakers (for 5W+3S
Motor feeder), 2 nos. O/G for 6.6 / 0.433 kV Auxiliary transformers
6.6/6.6kV (Unearthed) Grade Cable- Aluminium Conductor Rupees
Supply, laying, testing & commissioning 6.6 / 6.6 kV (UE) grade, XLPE insulated, stranded Thirty
GWIL Page 38 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
Aluminium conductor, galvanised steel flat strip / round wire armoured, extruded PVC type ST2 Nine Lac
sheathed, heavy duty, FRLS cable (to be laid on wall surface with necessary clamps / in existing Ninety
cable trench / cable trays / conduit / pipe sleeves at road crossing or floor as per site requirement) Five
conforming to IS: 7098 (Part- 2) & IEC: 60502 (Part-2) of following sizes: Thousand
3 Core x 400Sqmm (From 20MVA Transformer to 6.6KV HT Switchgear Common Panel) Four
---------do as above --------for 3 Core x 300 Sqmm
(From 6.6KV HT Switchgear Common Panel to NC-28 Pump House 6.6KV HT Switchgear Panel,
9.1 1 Lot 16,77,060.00 Seventy
SPP-3A Pump House 6.6KV HT Switchgear Panel, SPP-3B Pump House 6.6KV HT Switchgear
---------do as above --------for 3 Core X 240 Sqmm (From 6.6 kV VCB Panel to HT VFD Panel and
9.2 HT Soft Starter Panel to HT Motor, HT VCB Panel to HT Capacitor Bank, HT VCB Panel to Aux 1 Lot 8,00,992.50
Cable Terminations / Jointing Kits for 6.6 kV (UE) XLPE Cable One Lac
Providing & fitting heat shrink cable termination/ jointing kits for 6.6 kV (UE) grade XLPE insulated Forty Two
cable including necessary earth connectivity connection, material & consummables making the Thousand
termination / joint complete ensuring the joint resistance is within the permissble limit as per IS, of Eight
following types & sizes: Hundred
3C x 400 Sqmm (Outdoor Terminations Kit suitable for Transformer) Twenty
---------do as above --------for 3C x 400 Sqmm (Indoor Terminations Kit suitable for 6.6KV Common Thousand
HT Panel) Seven
10.2 ---------do as above --------for 3C x 300 Sqmm ( Indoor Terminations Kit suitable for 6.6KV Panel) 1 Lot 1,58,334.00 One Lac
GWIL Page 39 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
---------do as above --------for 3C x 240 Sqmm ( Indoor Termination Kit suitable for 6.6KV Panel and
10.3 1 Lot 2,87,880.00 Thousand
6.6kV AC Variable Frequency Drive (MV-VFD)
SITC of 6.6kV AC Variable Frequency Drive (MV-VFD) including delivery, installation, system
integration, commissioning. The VFD system shall be compatible with proposed squirrel cage Rupees
induction motor to be installed at Pumping Station and complete with Transformer, Rectifier device:- Forty Nine
Diode, DC link capacitor, Inverter device:- IGBT, Number of cell :-15, Number of Pulse :- 30, suitable Lac Sixty
rating of Integrated dry type Electrolytic grade Copper conductor converter input transformer with One
associated auxiliaries, harmonic filters, isolators, Blower for Cooling Air Supply including ducting Thousand
arrangement to directly discharge hot air from VFD to outside of Room, Space Heater etc. for the Five
motors having 900kW rating having speed range (10% to 100%), Frequency (5 – 50Hz). The item Hundred
descriptions provided in the BOQ indicate the minimum requirement only. The specifications and only
details mentioned in the tender datasheet and technical specifications shall also be strictly followed.
6.6 KV, 900 KW or as per motor rating
Flux Compensated Magnetic Amplifier (FCMA) Soft Starter for 900 KW (Line Side)
Supply, installation, testing & commissioning Line Side FCMA (Flux compensated magnetic amplifier) Rupees
HV soft starter panel suitable for 3 phase squirrel cage induction motor & provided with built in Seven Lac
bypass terminal with bypass device as a Vacuum Circuit breaker having Rating 6.6KV, 1250A, Thirty
3Pole, 26.3KA for 3Sec for pump control application by torque control method. Thousand
Soft Starter shall be operated on 3 phase, 50 Hz, fault Level 25 kA for 1 second with Copper bus bar Seven
& enclosure fabricated from 2 mm CRCA sheet steel, solidly earthed neutral system earthing Hundred
complete with following associated necessary equipment & accessories. The item descriptions Fifty Five
provided in the BOQ indicate the minimum requirement only. The specifications and details only
mentioned in the tender datasheet and technical specifications shall also be strictly followed.
HT Fix Capacitor Panel 395 kVAR or Suitable Rating as per Details Engineering whichever is Rupees
Higher Supply, installation, testing & commissioning of minimum 395kVAR or Suitable Rating as per Five Lac
13 Details Engineering whichever is better/Higher , 6.6 kV, 3 Ph. 31.5KA for 1 Sec., MV Capacitor Bank. 8 Nos. 5,55,500.00 Fifty Five
Along with associated equipment’s like 6.6KV, 630A, Vacuum Contactor (Class C2) of Requied Thousand
Capacity, On Delay Timers, Remote/Local Selector Switch, Indication Lamps, Push Buttons, Five
GWIL Page 40 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
Protection Relays, Ammeter, Current Transformers, HT capacitor,0.2% Series Reactor RVT, NDR, Hundred
etc., to be assembled in a Power coated Sheet metal enclosure of IP-42 as below 3Ph., 50Hz. only
comprising of APP star connected Type Capacitor unit along with discharge resister, Indoor Type,
0.2% Inrush Current Limiting , 6.6KV, 3-Ph., 150% rated current, Super Heavy Duty Long Life Low
Losses Dry Type Air core Cu Wound Series Reactor suitable, 7.2kV, 3Ph.,Off Load Isolator 630A,
STC 31.5kA/1Sec, 7.2kV HT HRC Fuse Link of suitable current rating, Residual Voltage Transformer
6.6kV/110-190V Resin Cast, Neutral Displacement Relay (Microprocessor Based Electrostatic
Relay), Indicating Lamps (On/Off)., Limit Switches, Set of interconnecting high conductivity
electrolytic grade Cu bus bars & insulated by using Colour coded heat shrinkable PVC Sleeves,
Indoor Type Standalone / Free standing, Fully Enclosed, dust & vermin proof, Powder coated CRCA
Enclosure of IP-42 with Bottom entry for Busbar duly wired with each Items.The item descriptions
provided in the BOQ indicate the minimum requirement only. The specifications and details
mentioned in the tender datasheet and technical specifications shall also be strictly followed.
HT Fix Capacitor Panel 150 kVAR or Suitable Rating as per Details Engineering whichever is
Supply, installation, testing & commissioning of minimum 150kVAR or Suitable Rating as per Details
Engineering whichever is better/Higher , 6.6 kV, 3 Ph. 31.5KA for 1 Sec., MV Capacitor Bank. Along
with associated equipment’s like Indication Lamps, Push Buttons, Protection Relays, Ammeter,
Current Transformers, HT capacitor,0.2% Series Reactor RVT, NDR, etc., to be assembled in a Rupees
Power coated Sheet metal enclosure of IP-42 as below Three Lac
3Ph., 50Hz. comprising of APP star connected Type Capacitor unit along with discharge resister, Seventy
Indoor Type, 0.2% Inrush Current Limiting , 6.6KV, 3-Ph., 150% rated current, Super Heavy Duty Eight
14 Long Life Low Losses Dry Type Air core Cu Wound Series Reactor suitable, 7.2kV, 3Ph.,Off Load 2 Nos. 3,78,784.00 Thousand
Isolator 630A, STC 31.5kA/1Sec, 7.2kV HT HRC Fuse Link of suitable current rating, Residual Seven
Voltage Transformer 6.6kV/110-190V Resin Cast, Neutral Displacement Relay (Microprocessor Hundred
Based Electrostatic Relay), Indicating Lamps (On/Off)., Limit Switches, Set of interconnecting high Eighty
conductivity electrolytic grade Cu bus bars & insulated by using Colour coded heat shrinkable PVC Four only
Sleeves, Indoor Type Standalone / Free standing, Fully Enclosed, dust & vermin proof, Powder
coated CRCA Enclosure of IP-42 with Bottom entry for Busbar duly wired with each Items. The item
descriptions provided in the BOQ indicate the minimum requirement only. The specifications and
details mentioned in the tender datasheet and technical specifications shall also be strictly followed..
(2Nos. Bus Capacitors for 20MVA Transformer No Load Compensation)
SITC of 110 V DC, Min. 200 AH or Suitable Rating as per Details Engineering whichever is Higher,
Float and Float cum Boost type Battery Charger with Battery and Integral 63A DC distribution
board. The item descriptions provided in the BOQ indicate the minimum requirement only. The
15 specifications and details mentioned in the tender datasheet and technical specifications shall also 2 Set. 6,26,000.00
be strictly followed. (For NC-28 Pump House). 2Nos. Incomer , 1Nos. Buscoupler 63A MCCB
Feeder, 12Nos. Outgoing 16A MCB Feeders, Interconnecting work of Battery charger of Common
HT Panel Room, NC-28, SPP-3B
SITC of outdoor type, three phase, oil immersed, distribution transformer of required KVA & Rupees
16 voltage ratio, copper double wound, vector group - Dyn11, HV delta connected & LV star connected 2 Nos. 11,95,051.00 Eleven
with neutral brought out connected to provide separate earthing terminals, bushing / cable box on HV Lac Ninety
GWIL Page 41 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
side and cable box on LV side suitable for cables or bus duct as per requirement with standard Five
fittings, conforming to IS: 1180 (Part-1) / 2014 with its latest amendment including first fill of Thousand
transformer oil & following accessories. Fifty One
(a) Oil conservator with filling holes with cap and prismatic oil level gauge. only
(b) Silica Gel dehydrating breather charged with silica gel
(c) Oil drain cum sampling valve with plug
(d) Oil filter valve
(e) Lifting Eyes / Hooks / Lugs
(f) Two earthing terminal
(g) Diagram and rating plate
(h) Air release plug
(i) Explosion vent with diaphragm
(j) Thermometer pocket
(k) Four bi-directional plain roller with base channel with hauling holes
(l) Fixed / Separate type radiator banks
(m) Off circuit externally operated tapping switch (For rating < 1000 kVA)
(n) 100 mm stem type oil temperature indicator (For rating < 500 kVA)
(o) Bucholtz relay with shut off valve (For rating ≥ 500 KVA)
(p) 150 mm dial type oil temperature indicator with Alarm / Trip contact (For rating ≥ 500 kVA)
(q) 150 mm dial type winding temperature indicator with Alarm / Tip contact (For rating ≥ 1000 kVA)
(r) Marshalling box (For rating ≥ 500 kVA)
(s) 150 mm dia. magnetic type oil gauge
(t) Inspection cover & Jacking lugs (For rating ≥ 1600 kVA)
For transformer having oil storage capacity for 2000 liters and higher, nitrogen injection fire protection
system (NIFPS) is to be provided. The item descriptions provided in the BOQ indicate the minimum
requirement only. The specifications and details mentioned in the tender datasheet and technical
specifications shall also be strictly followed.
With off circuit tap changer ± 10% in steps of 2.5%, Eff. Level-3, Auxiliary Transformer 6.6 kV/
0.433 kV,800 KVA or Suitable Capacity Rating Auxilary Transformer, Maximum total losses
(kW) @50%/ @100 % / % Imp (Level-3 type) shall be as per IS 1180 and its latest amendments.
Casting of transformer plinth / foundation including oil soak pit (where required) in situ reinforced
cement concrete in M 20 using granite, quartzite trap metal of size 6 mm to 20 mm for RCC work
17 including providing of 53 grade cement & CRS Fe-500 grade, scaffolding, centering, form work, 2 Set. 40,000.00
curing etc. complete.
RCC plinth / foundation for transformer of capacity 800 KVA Dimensions 1750x1750x
Supplying and fixing of GI chain link fencing of required width in mesh including strengthening with Rupees
2 mm dia GI wire/ G.I. staples/ G.I.U-nails/ nuts bolts with 2.4 m angle iron posts 50 mm x 50 mm x 6 Seven
mm placed every 3 metres center to center founded in M15 grade cement concrete Hundred
18 30cmx30cmx60cm, 0.6 metre below ground level, every 15th post, last but one end post and corner 37 Sqmtr 718.64 Eighteen
post shall be strutted on both sides and end post on one side only etc complete as required and as & Paise
per direction of Engineer-in-charge. Mesh size 50mm x 50mm made of GI wire 3.15mm dia. including Sixty Four
2Nos. Gates only
GWIL Page 42 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
LV Cables: Rupees
Supply, laying, testing & commissioning 1.1 kV grade, XLPE insulated, stranded Aluminium / Copper Seven Lac
Conductor, galvanised steel flat strip / round wire armoured, extruded PVC type ST2 sheathed, FRLS Fifty One
heavy duty cable (to be laid on wall surface with necessary clamps / in existing cable trench / cable Thousand
trays / conduit / pipe sleeves at road crossing or floor inclusive lugs & heavy duty double Two
compression brass glands with washers as per site requirement) conforming to IS:7098 (Part-1) & Hundred
IEC:60502 (Part-1) of following sizes: Seventy
3.5C X 300 sqmm Auxiliary Transformer Five only
---------do as above --------for 3.5 C x 300 Sq. mm Aluminium Conductor (From LVDB Panel to LT Thousand
APFC Panel) One
---------do as above --------for 3.5 C x 185 Sq. mm Aluminium Conductor (From LVDB Panel to Thousand
---------do as above --------for 3.5C x 50 Sq. mm Aluminium Conductor (From HVAC Panel to AC
---------do as above --------for 3.5 C x 95 Sq. mm Aluminium Conductor (From LVDB Panel to 60HP
---------do as above --------for 3.5 C x 35 Sq. mm Aluminium Conductor (From LVDB Panel to
ACDB of MCC PANEL ROOM, 30HP Dredging Pump)
GWIL Page 43 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
---------do as above --------for 3.5 C x 25 Sq. mm Aluminium Conductor (From LVDB Panel to
19.06 MOVDB, Battery Charger of NC-28, Battery Charger of Common HT Panel to Battery Charger of NC- 1 Lot 91,455.00
28, Battery Charger of Common HT Panel to Battery Charger of SPP-3B)
---------do as above --------for 4C x 16 Sq. mm Aluminium Conductor (From LVDB Panel to Thirteen
19.07 Dewatering Pumps, Exhaust Fan DB, Welding Receptacles, ACDB (COMMON HT PANEL ROOM), 1 Lot 1,13,400.00 Thousand
EOT CRANE etc.) Four
---------do as above --------for 4C x 4 Sq.mm Copper Conductor (From LVDB TO LDB of MCC
19.08 ROOM, PUMP HOUSE, COMMON HT PANEL ROOM, OUTDOOR LIGHTING, LVDB TO UPS, PLC 1 Lot 2,36,880.00
---------do as above --------for 3C x 2.5 Sq.mm Copper Conductor (For Actuators, Exhaust Fan, Thousand
External cooling fan of VFD operated Motors, Instrument Power Supply & Small Misc. Loads etc.) One
---------do as above --------for 4C x 2.5 Sq.mm Copper Conductor (For 66KV Line and transformer Rupees
feeder Current and Potential Transformers to 66KV Line, New Proposed 20MVA and existing 15MVA Three Lac
transformer feeders control Relay Panel, (From 66KV Isolators at line side and New Proposed Eighty
20MVA and existing 15MVA transformers to 66KV Line, New Proposed 20MVA and existing 15MVA One
GWIL Page 44 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
transformer feeders control Relay Panel, 6.6KV HT Panel to Each Motor LPBS, HT Panel to HT Thousand
Capacitor Panels, HT Panel to HT VFD Panels , HT Panel to Soft Starter Panel etc.) Twenty
---------do as above --------for 2C x 2.5 Sq. mm Copper Conductor Power cables (For single phase
power feeders - New Proposed 20MVA and Existing 15MVA transformer Marshalling cabinets
19.11 OLTC, RTCC, Space Heaters, HT Panels, NGR of New Proposed 20MVA and Existing 15MVA 1 Lot 3,93,750.00
transformer , NIFPS of New Proposed 20MVA, FCMA Soft Starter Panels & DC Cables - DCDB to
HT Panels, Isolators, 66KV Sf6 Circuit Breaker, Soft Starter, VFD Feeder, Outdoor CT and PT etc.)
---------do as above --------for 8C x 2.5 Sq.mm Copper Conductor (Control cables HT Panel to HT
VFD and Soft Starter Panel, Power cables for 66KKV Current and Potential Transformers of New
Proposed 20MVA and existing 15MVA transformers to New Proposed 20MVA and existing 15MVA
transformer feeders control Relay Panel and 66KV SF6 circuit breakers of Line side, New Proposed
20MVA and existing 15MVA transformers to Line side, New Proposed 20MVA and existing 15MVA
transformer feeders control Relay Panel etc.)
---------do as above --------for 12C x 2.5 Sq. mm Copper Conductor (Control cables for New Thousand
19.13 Proposed 20MVA and existing 15MVA transformers marshelling Box to New Proposed 20MVA and 1 Lot 5,61,305.08 Three
existing 15MVA transformers feeder control relay Panel) Hundred
---------do as above --------for 19C x 1.5 Sq. mm Copper Conductor (Control cables for Indication
19.14 and Signalling of SF6 Circuit breaker of 66KV Lines side, New Proposed 20MVA and existing 15MVA 1 Lot 12,09,978.00
transformers to respective control relay Panel feeders)
---------do as above --------for 19C x 2.5 Sq. mm Copper Conductor (Control cables Auxiliary Eight Lac
Transformer marshalling box to HT Panel) Seventy
GWIL Page 45 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
R. C. C. PIPE (Horizontal Cast)
Providing and supplying ISI Standard R.C.C. pipes(of Sulphate Resisting Cement) in standard
lengths of following class and diameter suitable for either collar joints or rubber ring joints including
20 20 Meter 1,485.00 Four
all taxes, insurance, transportation, freight charges, octroi, inspection charges, loading, unloading,
conveyance to departmental stores, stacking etc. (500mm Dia. - 5Nos. Pipe)
Class NP3 Test Pressure 0.7 Kg/sq.cm
Lowering, laying and jointing R. C. C. pipes in C. M. 1:1 1/2 of following diameters in proper One
21 position, grade and alignment at all level as directed by Engineer-in-charge including conveyance 20 Meter 189.00 Hundred
from stores to site of work, labour, giving hydraulic testing as per ISI code. Eighty
Cable Gland/ Terminations:Providing & fitting heavy duty brass cable glands (nickel-plated) with
washers & rubber ring conforming to IS, suitable for 3, 3½ & 4 core cables of following type & sizes:
Double Compression Brass Cable Glands300 Sq.mm"185 Sq.mm50 Sq.mm95 Sq.mm35 Sq.mm25
22 Sq.mm16 Sq.mm4 Sq.mm1.5 and 2.5 Sq. mm or as per actual size of cable. The item descriptions 1 Lot 1,68,217.00
provided in the BOQ indicate the minimum requirement only. The specifications and details
mentioned in the tender datasheet and technical specifications shall also be strictly followed to
complete the work in all respect.
Cable Terminals (Lugs)
Providing & fitting crimping type Cable Terminals (Lugs) conforming to IS of following types and sizes
300Sqmm Aluminium"
185Sqmm Aluminium
150Sqmm Aluminium Rupees
120Sqmm Aluminium Twenty
95Sqmm Aluminium Seven
50Sqmm Aluminium Thousand
35Sqmm Aluminium Four
25Sqmm Aluminium Hundred
16Sqmm Aluminium Seventy
4Sqmm Copper Four only
1.5Sqmm Copper or as per actual size of cable. The item descriptions provided in the BOQ indicate
the minimum requirement only. The specifications and details mentioned in the tender datasheet and
technical specifications shall also be strictly followed to complete the work in all respect.
24 LVDB Panel: 1.00 No. 18,92,358.80 Rupees
GWIL Page 46 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
Supply, installation, testing and commissioning LV Distribution Board (LVDB) totally enclosed, dust & Eighteen
vermin proof, indoor type, fabricated from CRCA sheet steel with minimum thickness of 3 mm for Lac Ninety
base frame / channel / gland plates, 2.0 mm for load bearing members / doors & 1.6 mm for internal Two
partitions, minimum degree of protection - IP 52 as per IS: 2147, suitable for operation on 3-Phase, 4 Thousand
Wire, 415 V, 50 Hz, Neutral effectively grounded, with strumentation compartments accomodating Three
meters, aux / protective relays, LED type indicating lamps & control MCBs as per IS: 13947, current Hundred
& voltage transformers as per IS: 2705, air insulated electrolitic grade Copper bus bar for three Fifty Eight
phase & neutral system, GI earth bus for entire length, power / control wiring using 1100 V grade, & Paise
FRLS insulated copper conductor wires conforming to IS: 694 & 8130, equipment fittings, horizontally Eighty
running busbar compartment height of minimum 300 mm, incoming & ougoing cable connections for only
1100 V grade, Aluminium / Copper conductor XLPE / PVC insulated & PVC sheathed armoured
cable. LVDB shall have required incomming / bus coupler / outgoing modules of following type &
ratings. Aluminium earth bus bar for entire length as per SLD, detail specifications & data sheet
including required testing @ factroy as per applicable IS/ IEC standards. LVDB/ PCC Panel shall be
comprising of ;
(a) 2Nos. 1250A Incomer and 1Nos. Buscoupler, 4 Pole, 1250 A, ACB (Draw-out Type) with
Microprocessor release (O / C, S / C & E / F) having breaking capacity Icu of 50 kA at 415V
with 6NO+6NC potential feee auxiliary contacts, secondary isolating contacts with all
necessary Electro Mechanical protections & interlocks etc.
(b) 2 Nos. 400 A, 3 Pole, Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free
mechanism, current limiting type with Microprocessor release (O / C, S / C & E / F) with
adjustable settings & having minimum 2NO+2NC potential free auxiliary contacts with all
necessary Electro-Mechanical protections & interlocks etc.. for LT APFC Panel Power Supply
outgoing feeder-2Nos.
(c) 2 Nos. 400 A, 4 Pole, Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free
mechanism, current limiting type with Microprocessor release (O / C, S / C & E / F) with
adjustable settings & having minimum 2NO+2NC potential free auxiliary contacts with all
necessary Electro-Mechanical protections & interlocks etc.. for SPP-3A LVDB Panel Power
Supply Outging Feeder - 2Nos. etc.
(d) 2 Nos. 250 A, 4 Pole, Air Break Fixed MCCB conforms to IS / IEC 60947-2 with trip free
mechanism, current limiting type with Microprocessor release (O / C, S / C & E / F) with
adjustable settings & having minimum 2NO+2NC potential free auxiliary contacts with all
necessary Electro-Mechanical protections & interlocks etc. (LT Panel to HVAC Panel-1Nos.
and Spare-1Nos.)
(e) 9 Nos. 160 A, 3 Pole, Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free
mechanism, current limiting type with Thermal Magnetic release (O / C, S / C & E / F) with
adjustable settings & having minimum 2NO+2NC potential free auxiliary contacts with all
necessary Electro-Mechanical protections & interlocks etc. LT Panel to 60HP Dredging Pump
Control Panel-2Nos., ACDB Common HT Panel Room-1Nos., HVAC Panel to AC Unit-5Nos,
(f) 2 Nos. 80 A, 3 Pole, Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free
mechanism, current limiting type with Thermal Magnetic release (O / C, S / C & E / F) with
GWIL Page 47 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
adjustable settings & having minimum 2NO+2NC potential free auxiliary contacts with all
necessary Electro-Mechanical protections & interlocks etc. (LT Panel to 30HP Dredging Pump
Control Panel-1Nos., Spare-1Nos. )
(g) 5 Nos. 63A, 4 Pole, Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free
mechanism, current limiting type with Thermal Magnetic with adjustable settings & having
minimum 2NO+2NC potential free auxiliary contacts with all necessary Electro-Mechanical
protections & interlocks etc. MCCB module-5 Nos for ACDB Electrical Room, ACDB Pump
House, EOT Crane, Spares etc.
(h) 6 Nos. 32A, 4 Pole , Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free
mechanism, current limiting type with Thermal Magnetic with adjustable settings & having
minimum 2NO+2NC potential free auxiliary contacts with all necessary Electro-Mechanical
protections & interlocks etc. MCCB module-6 Nos for LDBs for Electrical control room, Pump
House, Common HT Panel room, HT VFD Room, Outdoor Light DB, Spares .etc.
(i) 10 Nos. 63A, 3 Pole, Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free
mechanism, current limiting type with Thermal Magnetic with adjustable settings & having
minimum 2NO+2NC potential free auxiliary contacts with all necessary Electro-Mechanical
protections & interlocks etc. MCCB module-10 Nos for Battery Charger for NC-28 HT Panel,
Welding Receptacles, Spares etc.
(j) 15 Nos.32A 3 Pole, Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free
mechanism, current limiting type with Thermal Magnetic with adjustable settings & having
minimum 2NO+2NC potential free auxiliary contacts with all necessary Electro-Mechanical
protections & interlocks etc.
(k) 40 Nos Outgoing each with 32A DP MCB for 230V aux loads having breaking capacity
KA & confirming to IS/IEC 60898-2:2003 for Exhaust Fans, Instrumentation Load from LT
Panel to UPS, etc. Cat-III
(L) DOL / Star Delta starter suitable for local & remote operation of external cooling fan
application for cooling arrangment of VFD operated Motors consisting of MPCB, overload
relay and contactors as per Type II coordination including digital voltmeter, analogue
ammeter with selector switch, run hour meter, required protective relays & control
accessories. - 3Nos.
(M) 2 Nos. of 40kVAR No Load Compansation KVAR banks (APP type) with detuned filters,
MCCB, Power Contractor , Auto / manual control with switching on delay timer, housed in
lower most compartment of incomer/ buscoupler module(s). KVAR bank, selected based on
kva rating of associated transformer(s), The item descriptions provided in the BOQ indicate the
minimum requirement only. The specifications and details mentioned in the tender datasheet and
technical specifications shall also be strictly followed to complete the work in all respect.
Auto transformer starter suitable for local & remote pump control application consisting of Auto Rupees
Transformer (vacuum impregnated, air cooled having three (3) tappings at 50%, 65% and 80%), Twenty
incomer MCCB / MPCB, overload relay and contactors as per Type II coordination including digital Four
MFM with RS 485 communication port, analogue type ammeter with selector switch, run hour meter, Thousand
required protective relays & control accessories. Two
A. T. S. 30 HP for 30HP Dredging Pump (For Existing Sump ) Hundred
GWIL Page 48 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
25.1 ---------do as above ------- for A. T. S. 60 HP for 60HP Dredging Pump (For NC-28 sump) 1.00 Nos. 46,238.00 Two
AC POWER DISTRIBUTION BOARD:
Supply, installation, testing and commissioning LV Distribution Board (LVDB) totally enclosed, dust &
vermin proof, indoor type, fabricated from CRCA sheet steel with minimum thickness of 3 mm for
base frame / channel / gland plates, 2.0 mm for load bearing members / doors & 1.6 mm for internal
partitions, minimum degree of protection - IP 52 as per IS: 2147, suitable for operation on 3- Phase,
4 Wire, 415 V, 50 Hz, Neutral effectively grounded, with instrumentation compartments
accomodating meters, aux / protective relays, LED type indicating lamps & control MCBs as per IS:
13947, current & voltage transformers as per IS: 2705, air insulated electrolitic grade Aluminum /
Copper bus bar for three phase & neutral system, GI earth bus for entire length, power / control Rupees
wiring using 1100 V grade, FRLS insulated copper conductor wires conforming to IS: 694 & 8130, Twenty
equipment fittings, horizontally running busbar compartment height of minimum 300 mm, incoming & Five
ougoing cable connections for 1100 V grade, Aluminium / Copper conductor XLPE / PVC insulated & Thousand
PVC sheathed armoured cable. LVDB shall have required incomming / bus coupler / outgoing Six
modules of following type & ratings. Hundred
(a) 1Nos. 415VAC, 63A, 3Pole, Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free Forty &
mechanism, current limiting type with Thermal Magnetic (O / C, S / C & E / F) with adjustable settings Paise
& having minimum 2NO+2NC potential free auxiliary contacts with all necessary Electro-Mechanical Ninety
protections & interlocks etcPole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics =100% of only
(b) 20 Nos Outgoing each with 32A DP MCB for 230V aux loads having breaking capacity 10 KA &
confirming to IS/IEC 60898-2:2003. Cat-III
1Nos. For MCC Room (For Power Supply of Space Heater of HT VFD, Soft Starter Panel,
Capacitor Panel and Exhaust Fan of MCC Room)
The item descriptions provided in the BOQ indicate the minimum requirement only. The
specifications and details mentioned in the tender datasheet and technical specifications shall also
be strictly followed to complete the work in all respect.
AC POWER DISTRIBUTION BOARD: Rupees
Supply, installation, testing and commissioning LV Distribution Board (LVDB) totally enclosed, dust & Forty Nine
vermin proof, indoor type, fabricated from CRCA sheet steel with minimum thickness of 3 mm for Thousand
27 base frame / channel / gland plates, 2.0 mm for load bearing members / doors & 1.6 mm for internal 1 Nos. 49,191.46 One
partitions, minimum degree of protection - IP 52 as per IS: 2147, suitable for operation on 3- Phase, Hundred
4 Wire, 415 V, 50 Hz, Neutral effectively grounded, with instrumentation compartments Ninety
accomodating meters, aux / protective relays, LED type indicating lamps & control MCBs as per IS: One &
GWIL Page 49 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
13947, current & voltage transformers as per IS: 2705, air insulated electrolitic grade Aluminum / Paise
Copper bus bar for three phase & neutral system, GI earth bus for entire length, power / control Forty Six
wiring using 1100 V grade, FRLS insulated copper conductor wires conforming to IS: 694 & 8130, only
equipment fittings, horizontally running busbar compartment height of minimum 300 mm, incoming &
ougoing cable connections for 1100 V grade, Aluminium / Copper conductor XLPE / PVC insulated &
PVC sheathed armoured cable. LVDB shall have required incomming / bus coupler / outgoing
modules of following type & ratings.
(a) 160 A, 4 Pole, Air Break Fixed MCCB conforms to IS / IEC 60947-2 with trip free mechanism,
current limiting type with Thermal-Magnetic / Microprocessor release (O / C, S / C & E / F) with
adjustable settings & having minimum 2NO+2NC potential free auxiliary contacts with all necessary
Electro-Mechanical protections & interlocks etc. MCCB
(b) 16 Nos Outgoing each with 32A DP MCB for 230V aux loads having breaking capacity 10 KA &
confirming to IS/IEC 60898-2:2003. Category -III
(c) 12 Nos Outgoing each with 32A TP MCB for 415V aux loads having breaking capacity 10 KA &
confirming to IS/IEC 60898-2:2003. Category -III
(d) 2 Nos Outgoing each with 63A TP MCB for 415V aux loads having breaking capacity 10 KA &
confirming to IS/IEC 60898-2:2003. Category -III
1Nos. For Common HT Panel Room (For Power Supply of CRP Panel, OLTC, RTCC, Battery
Charger Panel, Transformer Marshelling Cabinet, NGR, NIFPS Panel)
The item descriptions provided in the BOQ indicate the minimum requirement only. The
specifications and details mentioned in the tender datasheet and technical specifications shall also
be strictly followed to complete the work in all respect.
AC POWER DISTRIBUTION BOARD:
Supply, installation, testing and commissioning LV Distribution Board (LVDB) totally enclosed, dust &
vermin proof, indoor type, fabricated from CRCA sheet steel with minimum thickness of 3 mm for
base frame / channel / gland plates, 2.0 mm for load bearing members / doors & 1.6 mm for internal
partitions, minimum degree of protection - IP 52 as per IS: 2147, suitable for operation on 3- Phase,
4 Wire, 415 V, 50 Hz, Neutral effectively grounded, with instrumentation compartments
accomodating meters, aux / protective relays, LED type indicating lamps & control MCBs as per IS: Rupees
13947, current & voltage transformers as per IS: 2705, air insulated electrolitic grade Aluminum / Twenty
Copper bus bar for three phase & neutral system, GI earth bus for entire length, power / control Eight
wiring using 1100 V grade, FRLS insulated copper conductor wires conforming to IS: 694 & 8130, Thousand
equipment fittings, horizontally running busbar compartment height of minimum 300 mm, incoming & Five &
ougoing cable connections for 1100 V grade, Aluminium / Copper conductor XLPE / PVC insulated & Paise
PVC sheathed armoured cable. LVDB shall have required incomming / bus coupler / outgoing Thirty One
modules of following type & ratings. only
(a) 1Nos. 415VAC, 80A, 3Pole, Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free
mechanism, current limiting type with Thermal Magnetic (O / C, S / C & E / F) with adjustable settings
& having minimum 2NO+2NC potential free auxiliary contacts with all necessary Electro-Mechanical
protections & interlocks etcPole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics =100% of
(b) 15 Nos Outgoing each with 32A TP MCB for 415V aux loads having breaking capacity 10 KA &
GWIL Page 50 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
confirming to IS/IEC 60898-2:2003. Category-III
1Nos. For Motorised Valve Distribution Board
The item descriptions provided in the BOQ indicate the minimum requirement only. The
specifications and details mentioned in the tender datasheet and technical specifications shall also
be strictly followed to complete the work in all respect.
LIGHTING DISTRIBUTION BOARD (For MCC Room, Pump House, Common HT Panel Room,
Providing and erecting Sheet Steel powder coated MCB distribution board - flush / surface mounted
fitted with busbar, neutral link, earth bar and DIN rail, Conforms to IS 8623-1 & 3, IEC 61439-1 &
without MCB to house appropriate nos. of MCBs. (The DBs should be used of same company of
MCB to be used) three phase incoming and single phase horizontal type outgoing Per phase
isolation type (PPI) sheet steel double door-16Way suitable for Providing and erecting a 415V MCB
29 Four-Pole Switch for lighting load (B curve), having a breaking capacity of 10 kA and conforming to 4 Nos. 10,208.47
IS:8828, in Distribution Board with the following capacity.
(a) 1 No. incomer with 63A FP EL+MCCB (O/L+S/C+E/F) for lighting & inductive load having 25kA
breaking capacity & conforming to IS/IEC 60898-2:2003.
(b) 16 Nos Outgoing each with 32A DP MCB for 230V aux loads having breaking capacity 10 KA &
confirming to IS/IEC 60898-2:2003. The item descriptions provided in the BOQ indicate the minimum
requirement only. The specifications and details mentioned in the tender datasheet and technical
specifications shall also be strictly followed to complete the work in all respect.
LIGHTING DISTRIBUTION BOARD (For Outdoor Lighting): Fourteen
Supplying and erecting an approved make IP55 grade, company-fabricated Timer Panel of the Thousand
following capacity for switching streetlights on/off based on time scheduling. The panel shall be made Three
30 from 16G CRCA sheet, duly epoxy powder coated inside and outside, and provided with hinged 1 Nos. 14,314.41 Hundred
doors and locking arrangements. It shall consist of a suitable size 4-Pole MCB and 4-Pole Contactor Fourteen
(Category-III), an analog time switch, auto/manual switch of the same make, suitable input and & Paise
output Bakelite terminals, and door earthing, all as approved by the Engineer-in-Charge. Forty One
Supply , Installation, Testing and Comissioning of wall mounted remote ON/OFF Local Push Button Thousand
station for Soft Starter Operated HT Motor and ON, OFF and Potentiometer for (Speed Variation) of Five
31 HT VFD Panel made out from powder quoted CRCA sheet of 16 SWG , illuminated ON/OFF push 8 Set 5,569.49 Hundred
button including making connections etc as required complete in all respect. All as per pre approved Sixty Nine
by Engineer in-charge & Paise
LV APFC PANEL Rupees
32 180 KVAR: APFC panel consisting following items. 2 Nos. 2,10,870.00 Two Lac
a) 400 A, 50 kA for 1sec. TP, TM based MCCB with spreader terminals & rotary handle Ten
GWIL Page 51 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
b) 0-400 A range analogue ammeter of 96 x 96 mm size with selector switch Thousand
c) 3nos. 400 / 5A, 10 VA CL-1.0 cast resin type current transformer Eight
d) Suitable rating of MCCB / MCB & Contractors for each capacitor bank Hundred
e) Suitable rating APP type capacitor banks (vacuum impregnated with non-PCB / non toxic oil, Seventy
internally delta connected with built in internal fuses complete with discharge resistances & terminal only
cover) of approved make in required steps with well suited detuned reactor is placed in series with
each capacitor step.Up to 170 KVAR capacity: APFC panel consisting following items.(e.g. 1 nos x
KVAR, 2 nos x 10KVAR, 1 nos x 15 KVAR & 2 nos x 20 KVAR, 2 nos x 25 KVAR, 1 nos x
KVAR). The item descriptions provided in the BOQ indicate the minimum requirement only. The
specifications and details mentioned in the tender datasheet and technical specifications shall also
be strictly followed to complete the work in all respect.
Supplying and erecting LED indoor fittings with LEDs of wattage 0.2Watt to 0.5Watt assembled on
single MCPCB,with housing used as a heatsink shall bemade of thick sheet Steel conforming to
IS:513/ CRCA/ aluminium diecast powder coated and high U.V.& corrosion resistance with diffuser
with company mark/name 160V to 270V,Power Factor more than 0.95, THD < 15%,CCT 3000 K to Rupees
6500K, Luminaire efficacy > 85 lumens/watt ,LED driver efficiency > 85 % (fitting required LM-79 & Twenty
LM-80 Certificates) (NOTE: Below description have shown ranges of Wattage capacity of LED Six
33 fittings.The item descriptions provided in the BOQ indicate the minimum requirement only. The 1.00 Lot 26,940 Thousand
specifications and details mentioned in the tender datasheet and technical specifications shall also Nine
be strictly followed to complete the work in all respect.- For Common HT Panel room, Pump House, Hundred
Electrical Panel Room, Battery Room as per the requirement of GWIL and instructions of engineer- Forty only
in-charge (Cat. III)(A) Tube Light with integral driver36-40Watts,Surge-2KV,IP-20,conventional
feetMin. 60Nos. or as per Lux level calculation and instructions of engineer-in-charge whichever is
Supplying and Erecting Of L.E.D. type High bay fixture having Power Consumption of following
watts with, Input Voltage 110 - 290 V.AC with full efficiency, Power Factor > 0.9 with 50/60 HZ,
CCVC LED Driver used for maximum power saving, Best Quality Aluminium alloy housing and
aluminium Dome for better heat dissipation, CCT Cool white (6000K), CRI 80, Beam angle >
34 1.00 Lot 68,952 Nine
degrees, working temperature -20 deg c to +55 deg c, Body IP
- For pump house area as per the requirement of GWIL and instructions of engineer-in-charge
Min. 8 Nos. or as per Lux level calculation and instructions of engineer-in-charge whichever is higher
Supplying and erecting Square/ Circular shaped Surface/ Recessed Mount Downlight with Three
provision for spring loaded mounting clips complete. IP20 Thousand
35 22-24 watts, Surge-2 KV, Cat.-III 1.00 Lot 3,816 Eight
for SCADA Room, Office Room Hundred
Min. 6Nos. or as per Lux level calculation and instructions of engineer-in-charge whichever is higher Sixteen
Point wiring for Light/ Bell with 2 sq. mm & earthwire of 1.5 sq.mm (Green) both are of ISI marked Rupees
1.1kV grade FRLS PVC insulated multistrand copper wires, in following type of pipe to be erected Twenty
GWIL Page 52 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
concealed in/ on surface on wall/ ceiling complete with 6A Modular type switch/ bell push & Seven
accessories and earth continuity of following type, erected on PVC/ Metallic box, single mounting Thousand
base frame covered with textured/ metallic front plate modules erected on/in wall/ ceiling as per pipe Nine
erected, with necessary Lamp holder/ceiling rose/ H.D.Connector as directed. Contractor has to Hundred
submit lighting layout and get it approved from competent authority before execution of this work. Six &
- (a) with medium class Rigid PVC pipe and accessories erected flushed on wall/ceiling complete- Paise
Cat. III Eighty
- For pump house, Electrical control room, instrumentation room, Common HT Panel Room, HT VFD Eight only
Room, Battery Room as per the requirement of GWIL and instructions of engineer-in-charge. Min.
Nos. or as per Detail Engineering whichever is higher
Providing and erecting Mains with 1.1KV grade FRLS PVC insulated ISI marked stranded Copper
conductor wire in following type of pipe to be erected concealed in / flushed on wall / ceiling with
1.5sq.mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of
(A) With medium class Rigid PVC pipe and accessories
c) 3 wire 1.5 sq. mm
Point wiring for Individual Plug with earthwire of 1.5 sq.mm (Green) both are of ISI marked 1.1kV
grade FRLS PVC insulated multistrand copper wires, in following type of to be erected concealed in/ Rupees
on surface of wall/ ceiling complete with Modular type switch & 5 pin Plug erected on PVC/ Metallic Eleven
box covered with appropriate front plate modules erected on/ in wall/ ceiling as per pipe erected with Thousand
following type of accessories. Contractor has to submit lighting layout and get it approved from Nine
38 competent authority before execution of this work 1.00 Lot 11,974.58 Hundred
- Modular Type Cat-III, Seventy
[III] For 6A Plug and 6 amp switch with 2-1.5 sq.mm Cu. Wire with 1.5 sq.mm (green) earthing wire Four &
from MCB DB board. CAT-III Paise Fifty
(a) with medium class Rigid PVC pipe and accessories erected flushed on wall/ceiling complete Eight only
Min. 30Nos. or as per Detail Engineering whichever is higher
Point wiring for Individual Plug with earthwire of 1.5 sq.mm (Green) both are of ISI marked 1.1kV
grade FRLS PVC insulated multistrand copper wires, in following type of to be erected concealed in/
on surface of wall/ ceiling complete with Modular type switch & 5 pin Plug erected on PVC/ Metallic
box covered with appropriate front plate modules erected on/ in wall/ ceiling as per pipe erected with
following type of accessories. Contractor has to submit lighting layout and get it approved from
competent authority before execution of this work
39 1.00 Lot 21,076.20 Seventy
- Modular Type Cat-III, With [III] For 16A Plug and 16 amp switch with 2-4 sq.mm Cu. Wire with
sq.mm (green) earthing wire from MCB DB board.
(a) with medium class Rigid PVC pipe and accessories erected flushed on wall/ceiling complete
- For pump house, Electrical control room, instrumentation room as per the requirement of GWIL and
instructions of engineer-in-charge.
Min. 30Nos. or as per Detail Engineering whichever is higher
40 Supplying & erecting single phase approved make industrial exhaust fan suitable for medium duty 40.00 No 3,304.24 Rupees
GWIL Page 53 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
ring mounted low noise operation suitable for medium duty having following dia size and maximum Three
speed in RPM Exhaust Air Fan respectively 450 mm dia 1400 RPM Cat.II Thousand
P & F of Wall cowl with Bird Screen Suitable for Outside Wall of Exhaust Fan Opening of following Thousand
size and made out from 24 SWG GI sheet as per instructions of Engineer in-charge including fixing Seven
with suitable fasteners etc. as required. All as per pre approved by Engineer in-charge. For additional Hundred
technical parameters of products/ work. Suitable for 450 mm sweep Exhaust Fan Sixty Six &
Outdoor Street Lighting with Street Light Pole allied accessories
LED Street Light :
Supplying and erecting LED street light /Flood ligh tfittings with High power White LEDs wattage of
3Watt and above assembled on single MCPCB,efficiency more than130lm/w and corrosion free High
pressure diecast aluminum housing with smooth finish powder coated and heatsink extruded
aluminium with diffuser and Polycarbonate optics/lenses,with toughened glass with company mark/
name engraved or embossed 160 to 270V,Power Factor more than 0.95,THD<10%, CCT 3000K to
5700K, Uniformity ratio>0.45, Luminaire efficacy>100lumens/watt. LED driver efficiency >85%.
(fittings required LM-79 & LM-80 certificates)(NOTE:Below description have shown ranges of
Wattage capacity of LED fittings.The Engineer incharge may select any wattage capacity between
ther anges shown.) (i) above 36 to 48 watts Cat-lll ( Min. 10 Nos. for Street Lighting or as per lux
level calculation)
Supplying & erecting Steel tubular pole (Swaged) confirming to IS-2713 (Part II)1980. Manufacturing
process of steel tubular pole should be as per IS specification.Basic steel tube should be ISI Marked.
Pole should be painted by one coat of Zinc comet Primer and two coat of Aluminium/ approved paint
to be erected on/in existing Foundation.The length of poles are as below.
(A) 7.5 mtr. Long Swaged Steel tubular pole
(i) pole as per IS code 410-SP-4 with 300X300X4mm base plate with necessary G.I. J Bolts
(Approximate Pole weight 67Kg ) Forburial erection
(ii) Add Extra for M.S.Base plate 300X300X16 mm for pole,Suitable for mounting on surface of
foundation with GI foundation bolts,with required stiffeners welded with pole.
(iii)Add Extra for PU base primer and PU Paint on pole. ( Min. 5 Nos. for (Road) Street Lighting
quantity of light fixtures as per lux level calculation )
Providing 1:2:4 cement concrete foundation & 70% PCC from bottom including excavation for the
pole of size 60x60x120cm.Deep in below ground level with plinth of 45cmx45cm (or 45cm dia x
45cm) high upper ground level with necessary curing and finishing inapproved manner. ( for 7.5 &
GWIL Page 54 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
8/8.5 mtr pole) ( Min. 5 Nos. for (Road) Street Lighting quantity of light fixtures as per lux level
Supplying & erecting approved make SMC press moulded composite FRP.loop-in,loop out
approx.2mm thick box complete with Bakelite connector strip 5way (3P+N+E),DIN rail for mounting
mob & hinged doors asper requirement having locking arrangements with mounting clamp with
nuts,bolts & washers suitable for erection on pole with cable clamps & earth bolt of following size of
300mm x 200mm x 100mm [deep] ( Min. 5 Nos. for (Road) Street Lighting quantity of light
fixtures as per lux level calculation )
Providing & erecting 240V MCB double pole switch for lighting Load (B Curve) having 10KA breaking
capacity & confirms to IS:8828 in existing box having following capacity ( Min. 5 Nos. for (Road)
Street Lighting quantity of light fixtures as per lux level calculation )
Supplying and erecting Street light pole bracket comprising main B Class GI pipe of 4.2cm/require
outside dia.complete with suitable BClass G.I.sleeve tubing of approx.45cms.length and suitable for
76.5mm/80mm/require size of pole top having nuts and bolts for fixing the brackets and having
spread of 0.5mtr.Length with 110 deg.with vertical plane and suitable welded stiffener reducer and
nipple with check nut complete painted with one coat.of Red oxide/ PU base primer and two coats of
Aluminium/ PU paint. paint with following nos of arms.[A] Single Arm bracket 1 Mtr( Min. 10 Nos. for
(Road) Street Lighting quantity of light fixtures as per lux level calculation )
Providing and layinh of PVC insulated round cable as per detailed technical specifications
conforming to IS 694, IEC 60227 / 60228. 1 R x 3 C x 2.5 mm2 with Copper Tubular lug Terminals (in
Supply, laying, testing & commissioning 1.1 kV grade, XLPE insulated, stranded Aluminium
conductor, galvanised steel flat strip / round wire armoured, extruded PVC type ST2 sheathed, heavy
duty cable (to be laid on wall surface with necessary clamps / in existing cable trench / cable trays /
conduit / pipe sleeves at road crossing or floor as per site requirement) conforming to IS: 7098 (Part-
1) & IEC: 60502 (Part-1) of following sizes: 4 Core x 10 Sqmm with Cable glands and terminal lugs (
Length of Cable of should be as per the final quantity of Light Poles as per lux calculation )
Providing & Fixing of IK08 IP-66 protected high power LED flood light system with single piece
Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to
achieve various beam angles, of high power LED of 3 to 5 watt each . Integrated potted driver as a Rupees
unique BIS R number having efficiency more than 85 % and in compliance to BIS certified and Trade One Lac
mark certificate. The System level Luminaire efficacy >=125 lm/ wt. LED driver Input Voltage AC 120 Sixty Nine
to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety .Power Factor >0.95 , Thousand
THD(I) <10% , driver current <=750mA. driver should be Phase to phase protection of 440 V for 4 Seven
Hrs. Electrical Connector , Surge Protection Min >=4KV internal and 10KV external but inside driver Hundred
compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 Forty Nine
and CCT 5700K ±355K. Manufactures Word Mark/Name Engraved/Embossing/Screen printing on & Paise
die cast housing to allow traceability/authenticity. Fixture shall be IS 10322 Complianced.OEM Must Eighteen
have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) only
Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per
pre approved by Engineer in-charge.
GWIL Page 55 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
High Power LED Flood Light Minimum lumen output 18650 lm (150W) (Min. 18 for Outdoor side
of Pump House wall Mounted as per Lux level calculation whichever is higher and instruction of
Engineer - in -charge)
Maintenance free Chemical Earthing : Rupees
Supply of UL Listed Maintenance Free Earthing System made of copper bonded rod of 10 feet (3 mtr Five
approx.) length, 17.2 mm dia. (Minimum copper bonding shall be 0.25mm, suitable for 25 kA fault Thousand
44 current) along with Rod-to-Conductor connectors, 95% pure Carbon-Based Earth enhancement 15.00 No 5,356.00 Three
material of 30kg, Pit Cover as required and as per specification. (For HV panels, MCC Panel, PLC Hundred
Panel, UPS Panel, Motors, APFC Panel,LDB,PDB etc.). Contractor has to submit earthing layout Fifty Six
and get it approved from competent authority before execution of this work only
Supplying & erecting funnel type earthing having earth plate of following size burred in specifically
prepared earth pit 3 mtr. below ground with 40 kg. charcoal and salt with alternate layers of charcoal
& salt, 20mm.dia. G.I. pipe with Funnel with a wire mesh for watering & bricks masonry block, C.I. Rupees
Cover complete as per para 7.3 of IS 3043 with necessary length of double Galvanised Iron / copper Nine
earth wire No 6 SWG bolted with lug to the plate and covered in 12 mm dia. G.I. pipe 2.5 mtr long Thousand
complete connected to the nearest switch gear with end socket as per direction & duly tested by Two
earth tester Hundred
confirming to IS (As per drawing) with following specification complete with 60 x 60 x 0.315 cm only
Copper earth plate (For Transformer neutrals & Lightning protection). Contractor has to submit
earthing layout and get it approved from competent authority before execution of this work
Supplying & erecting earth pit of minimum bore dia.150mm size approved make Earthing Electrode
consisting Pipe-in-Pipe Technology as per IS 3043-1987 made of corrosion free G.I.Pipes having Rupees
Outer pipe dia of 50mm having 80-200 Micron galvanising, Inner pipe dia of 25 mm having 200-250 Thirteen
Micron galvanising, connection terminal dia of 12mm with constant ohmic value surrounded by highly Thousand
conductive compound with high charge dissipation suitable for following type of applications.For Four
Electrical Installation 66KV Switchyard i.e.independent Earthing located inother than normal soil i.e. Hundred
Soft Rock, Marshy Soil etc..-Length of Pipe : 3 Mtrs. -Back filling Compound :2 nos Bags of 25 Kg. Fifty only
with connection to mesh earthing of Existing 66KV Switchyard as per IEEE:80
Supply and erection of required size HOT Deep Galvanised Iron Strip for earthing of 66KV
Swithcyard, HT, VCB Panel, HT Soft Starter, HT Capacitor Panel, Battery Charger, PLC Panel, LT
47 Panel, Transformer, LT APFC Panel, HT Motors, etc., using proper clamp. Contractor has to submit 1.00 Lot 65,250.00
earthing layout and get it approved from competent authority before execution of this work
Min. 1000kg or as per detailed engineering whichever is higher
Supply & erection required size Copper strip for earthing of Auxiliary Transformers, Electronics
Earthing of PLC Panel etc. using copper clamp. Contractor has to submit earthing layout and get it
approved from competent authority before execution of this work Min. 500kg or as per detailed
engineering whichever is higher
GWIL Page 56 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
SITC of Vertical Air Termination Solid aluminium with Base – 10 mm dia and 1000 mm long. Air Thousand
Termination Base tested for conditioning, Ageing Test & Lightning impulse current withstand test: Nine
100 kA of 10/350µs waveform in an accredited Third party laboratory as per 6.3 & 6.4 of IEC 62561-1 Hundred &
2017 protocol with MAST 34mm dia 3000 mm long – Cold Galvanized Paise
SITC of 8 mm dia solid Aluminium Conductor for roof top mesh grid and tested as per IEC
62561-2 conducted in the Govt. accredited third party laboratory to meet the requirement of IS/IEC
62305 with Required Accessories – Aluminium Holding clamp at every 1 mtr distance, Aluminium/SS
cross splicer at every crossing of Alu. conductor, Expansion piece with connectors at every 20 mtr
50 distance, Aluminium straight Splicer to connect conductors. All Accessories should be tested as per 1 Lot 36,495.76
IEC 62561-1:2018 Cl. 6.3 for conditioning & Ageing Test & 6.4 for Lightning impulse current
withstand test: 100 kA of 10/350µs waveform (Ageing & Electrical test) conducted in a sequence
manner & tested in the Govt. accredited Third party laboratory to meet the requirements of IS/IEC
SITC of 10 mm Hot dipped Galvanised Round Solid Conductor having smooth surface should be
tested and used exclusively for lightning protection (Vertical Riser/Down Conductor which shall be
concealed in column or flushed on) to meet the requirement of IS/IEC
Earthing stud of dimension SS–75mm OD plate with 10mm dia tail connector used in structural steel
ring earthing system to meet the requirements of IS/IEC
For interconnecting the column and the terrace AL conductor / strip / flat.
SS Cross Connector to connect earth fixing point to vertical raiser/down conductor.
51 SS Straight Splicer at every 4 mtr to connect MS conductor in column. 1 Lot 18,330.51
Bonding/Rebar Clamp at every 3 mtr suitable for interconnecting round conductor with reinforcement
inside the concrete for structural earthing system.
SS Connector – To connect external conductor 8–10 mm with earth fixing point.
Testing Requirements:
All accessories should be tested as per IEC 62561-1:2018, Clause 6.3 for Conditioning & Ageing
Test and Clause 6.4 for Lightning Impulse Current Withstand Test: 100 kA of 10/350µs waveform
(Ageing & Electrical Test) conducted in a sequence manner and tested in the Govt. accredited Third
Party Laboratory to meet the requirements of IS/IEC
SITC of Galvanized Steel Flat 25×6 mm thickness from earth electrode directly in ground as
52 required. Zinc coating: 500 g/m² (Approx. 70 micron coating) tested and used exclusively for lightning 1 Lot 3,500.85
protection earthing system and ring equipotential bonding.
GWIL Page 57 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
SITC of 14.2 mm dia, 3 mtr long Earth electrode of high tensile steel electrode with 250 micron Thousand
copper bonding and 1 bag of carbon fill-based environment-friendly backfill tested as per IEC 62561- Twenty
53 7 in NABL accredited laboratory and suitable stainless steel double-sided clamp. Eco-friendly, rust- 3 Nos. 5,027.97 Seven &
proof, heavy-duty, weather-proof polyethylene Earth Pit Chamber with the following dimensions: 254 Paise
mm dia (top), 330 mm dia (bottom) & 260 mm (height). Ninety
Providing & erecting Hot dip Galvanisied strip/ iron wire 8 to16 SWG/25x6mm GI Strip for ACDB,
DCDB, LDB, Actuator Valves, Junction Box, Outdoor Lighting Poles & LPBS etc. Contractor has to
submit lighting layout and get it approved from competent authority before execution of this work Min.
100kg or as per detailed engineering whichever is higher
Cable Trays & Accessories:
Supply & laying GI ladder type cable trays with side channels having rungs of size spaced at 250 mm
apart, fabricated from 2 mm thick sheet steel in standard length of 2.5 meter, duly hot dipped
55 galvanized after fabrication as per IS 2629-1989/ IS 4759-1984 including accessories such as 1.00 Lot 50,400.00
coupler plates/ fish plates, bends, tees, reducers, elbows, covers and electro-galvanized hardware
etc, erected on existing support as per specification and instruction of Engineer-in-charge.
150(W) x 75(H) x 2.0 mm Thick
55.1 ---------do as above --------for 300(W) x 75(H) x 2.0 mm Thick 1.00 Lot 19,400.00
55.2 ---------do as above --------for 450(W) x 75(H) x 2.0 mm Thick 1.00 Lot 65,850.00
GWIL Page 58 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
55.4 ---------do as above --------for 750(W) x 75(H) x 2.0 mm Thick 1.00 Lot 2,18,400.00 Thousand
Supply & laying GI perforated type cable trays with returned edge / flange, fabricated from 2.0 mm
thk sheet steel in the standard length of 2.5 mtrs, duly hot dipped galvanized after fabrication as per
IS 2629-1989 / IS 4759-1984 including accessories such as coupler plates/ fish plates, bends, tees,
56 1.00 Lot 1,14,000.00 Fourteen
reducers, elbows, covers and electro-galvanized hardware etc, erected on existing support as per
specification and instruction of Engineer-in-charge.
100(W) x 35(H) x 2.0 mm Thick
Providing, erecting, and fabricating the M.S. structure for mounting of Cable Trays of Switchyard, Rupees
Common HT panel room, Electrical room, Pumphouse, etc.as per site requirements, incorporating Six Lac
proper sizes of M.S. angles, squares, rounds, flats, bars, channels,Square Pipes and sections. The Eighty
work shall include cutting, welding, grinding, and finishing, duly painted with one coat of red oxide Five
57 primer. Erection on site shall be carried out as per the directions of the Engineer-in-Charge, along 1.00 Lot 6,85,125.00 Thousand
with necessary grouting, cementing, plastering, and finishing, all complete. Min. 10.5 ton or as per One
detailed engineering whichever is higher The item descriptions provided in the BOQ indicate the Hundred
minimum requirement only. The specifications and details mentioned in the tender datasheet and Twenty
technical specifications shall also be strictly followed to complete the work in all respect. Five only
Power/ Welding Receptacle: (Two for Transformer Area, Two for Pump Room)
P & F of Industrial plug and socket conforming to IEC 60309-1/2 made out of self extinguishing
engineering polymer / polyamide, nickel plated brass sleeve and pins, socket with shutter including
making connection etc as reqd. IP -67 Surface/Wall mounted socket 63 A 5 pin(3P+N+E)
GWIL Page 59 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
Fire & Safety Equipments:
Design, supply, erection, testing and commissioning of safety accessories for all electrical
equipment/ system as per tender specifications.
(a) Providing printed instruction chart both in English and Gujarati duly framed with front glasses for
treatment of person suffering from electric shock.- Min.2 Nos.
(b) Providing of pair of rubber hand gloves for working on 12 kV supply.- Min.10 Pair
(c) Supplying and erecting dielectric flooring meeting requirement of class B as per IS 15652:2006 for
all HV & LV switchgear in Common HT Panel Room, Electrical Control Room, SCADA Control Room
(d) Supplying stand First Aid Box with antiseptic cream, medicine for use on wounds due burn, crepe
bandage ,gauge bandage ,medicated ready to use bandage adhesuve tape for medicinal user , Rupees
Scissors, anti-septic solution tec-( All above contents shall be of the standard makes ).-Min.5 Nos. Four Lac
(e) Supplying & erecting FIRE bucket round bottom of 9 lit. capacity made out of 24 gauge GI sheet Eighty
with extra handle at bottom duly painted white inside & red out side with fire mark filled with dry sand Nine
& kept on exsisting stand provided or hund on wall hook.-Min.8 Nos. Thousand
(f) Suppying & erecting floor mounting stand for keeping 4 nos of fire buckets comprising 1500 mm in Four
length & 900 mm height made out of 30mmX30mmX4mm angle iron with cross supports for lags Hundred
welded with 4 hooks & duly painted with one coat of red lead & two coats of approved enammeled Seventy
silver paint.-Min.2 Nos. Eight &
(g) Supplying & erecting 4.5 kg capacity carbon dioxide (CO2) fire extinguisher with necessary Paise
clamps made from 50 x 6 mm M.S. Flat with nut & bolts grouted in wall complete.-Min.16 Nos. Twenty
(h) Supply & Erection metallic vertified danger notice board for medium voltage installation to be One only
erected as per IS-Min.4 Nos.
(i) Safety Shoes-lot
(j) Safety Helmet-lot
(k)Supply of 66kV rated discharge rod (earth discharge rod) complete with insulated telescopic
fiberglass body, brass hook, flexible copper earthing cable, and clamp, suitable for safe discharge of
residual voltage from 66kV equipment. The rod shall be rated for 72.5kV system voltage, with
minimum 100kV AC withstand capacity for 1 minute. It shall be provided with a weatherproof carrying
case and comply with IS:5561 / IS:2071 / IEC:60855-1. Cable size shall not be less than 16 sq.mm
copper, and total length of rod (fully extended) shall not be less than 3 meters.
Design, Supply, Installation, Testing, Commissioning of Bourdon Type Glycerin Filled 0-20 kg / cm2 - Rupees
150 mm dia., Pressure Gauge as , ±1% accuracy, Direct bottom 1/2"NPT (M) process connection, IP Two
67, Glycerin filled, SS304 Case with Bayonet Type Bezel, SS316 L Bourdon Tube, SS316 Movement Thousand
60 material, Aluminum dial with black graduation on white background, Micro Zero adjustable pointer, 10 Nos. 2,624.00 Six
neoprene gasket, Blow out disc, shatter proof glass, SS tag plate etc as per IS 3624 and as per the Hundred
direction of engineer incharge . Twenty
(on each pump delivery pipe - 8Nos. & on header pipe line-1Nos., For Dredging Pump -1Nos.) Four only
Range 0-16 kg/cm2
GWIL Page 60 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
Gauge cock for pressure gauge:
3way gauge cock, 1/2"NPT (F) X1/2" NPT(M) process conection complete to match pressure gauge
Pulsation Dampner/ Snubber for pressure gauge
Suitable to with stand upto 300kg/cm2,Viton gasket ,1/2"NPT (F) X1/2" NPT(M) process conection
complete to match pressure gauge
Insertion Type Ultrasonic Flow Meter:
Design, Supply, Installation, Testing, Commissioning of Two Path Insertion Ultrasonic flow meter
working on transit time principle,with factory calibrated and site verification, Regular Power Operated,
Flow sensor, Indicator, transmitter and totaliser with all accessories viz. surge arrestor, associated
cables, cabinets, hardwares, etc complete as per following specifications:
Flow meter / Sensor: 4 nos insertion ultrasonic type sensor (2pair) with ball valve for online removal
of sensors/ any other intersection/ retraction assembly, PN 16 pressure rating, SS
sensor MOC, IP 68 Protection.
Flow Transmitter/ Converter (Remote Field Mounted):
Microprocessor based, Modular design, 2 line LCD for indication of actual flow rate, forward, reverse,
sum totaliser display, ±1 %accuracy at 0.3 to 4 m/sec velocity, 4 to 20 mA with HART/Modbus Rupees
output, one scalable pulse output, IP 65/67 protection, Die cast aluminium/ polycarbonate/ SS316 Eight Lac
with Anticorrosive Paint/ PU finish with glass window enclosure, Inbuilt EEPROM and Data Logger, Eighty Six
61 20 meters cable length or as per site requirement forsensor to transmitter communication etc along 1 Nos. 8,86,500.00 Thousand
with wall mounted/stand mounted cabinet. Five
Worldwide transmission of measured data (Every Fifteen Minutes) and events via e‐mail and SMS by Hundred
integrated GSM/GPRS modem, reliable data storage facility through integrated SD card etc. The only
Flowmeter must conatin two no of Analog Input signal for transmission of signals. One signal will be
sent to GSM transmitter and one signal will be sent to PLC of NC-28
GSM/GPRS based trans receiver unit to be provided to send signals to centralized monitoring
system. Flow meter shall send signals to transmitter unit through digital output only.
The contractor shall ensure full bore of the flow meter on site for accurate reading & make required
arrangement for the same without any extra cost..
The RTU panel must contain Terminal blocks for terminations of ineranl and external cables , Power
supply SMPS for 24V Dc cobersion, HART to Modubus convertor, RTU modem with Sim card facility
Two path (4 Nos Insertion sensor)
SITC of Non Contact Type Ultrasonic Level Transmitter:
Ultrasonic Type Level Transmitter with Remote Display :
Design, Supply, Installation, Testing and Commissioning of Non Contact Ultrasonic Type Level
Transmitter with Remote Display.
Sensor: The sensor should be non contact type, field mounting type, housing shall have minimum
62 2 Nos. 59,723.00 Seven
IP65 protection, PP/ PVC Sensor MOC, with sensor to transmitter cable.
Remote Indicator cum Transmitter: Microprocessor based indicator with LED / LCD digital
display,panel/ wall mounting type, power supply shall be 110-240 Vac or 15 to 36 Vdc, 50 Hz ± 10 %.
Accesories: Mounting bracket, nut, bolts etc as per system requirement and Hook up diagram of the
GWIL Page 61 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
Level Transmitter shall be suitable for following Range. 0 to 10 Meter
One no for NC-28 Old Sump and One No for New Sump of NC-28
Float & Board Type Level Indicator Rupees
Design, Supply, Installation, Testing and Commissioning of Float & Board Type Level Indicator, Seventeen
guided construction, Full Range Travel, FRP/ SS316 MOC of Float and Guide Wire Rope, minimum Thousand
63 6” wide x aluminum powder coating with black graduations and numerical on calibrated gauge board, 2 Nos. 17,718.00 Seven
Red color pointer, protection conduit, Elbow pulley, Tensioner, Anchor, Rope Fastner, Gauge Hundred
Brackets, Counter Weight for rope type probe, spacer between the probes, etc complete with Eighteen
calibration of following sizes. Size: 0 to 10 Meter only
SITC of Float/Displacer Type Level Switch:
Design, Supply, Installation, Testing and Commissioning of Top mounted Displacer Type level Rupees
switches with 2 nos SPDTcontacts of Micro switch rated 5 A, potential free power supply, Material of Twelve
wetted parts shall be SS 316 and the material of accessories shall be SS. IP 65 or equivalent degree Thousand
of protection for enclosure, suitable for sump, ESR, tank, vessels and underground reservoirs. The Eight
top mounted level switches shall be supplied with still tubes to suit the requirement. Accessories like Hundred
name plate, mating flange, gaskets, fasteners, bolts & nuts, etc. shall be supplied with the Level Two only
Switch of following Range. 0 to 10 Meter
SITC of Pressure Transmitters:
Design, Supply, Installation, Testing and Commissioning of Sealed Diaphragm Type Pressure
Transmitter. Piezo-resistive sensor technolgy based pressure transmitter with Micro-processor based
integral LED/ LCD display, with accuracy of ± 0.3% of span, external zero and span adjustment, self
diagnostics, temperature sensor for compensation. 15 to 36 V DC power supply, output signal of 4-
20 mA DC with HART. Minimum IP 65 degree of protection. Aluminium housing with epoxy coating,
Accessories like snubbers for pump discharge applications, three way manifold, mounting brackets,
name plate etc. Material for accessories shall be SS. Protection Box/Canopy shall be provided for
outside installed transmitters. Pressure Transmitter shall be suitable for following Range.
SITC of Temperature Scanner (1 no for each pump motor) Twenty
Microprocessor based, 16 channel , input power supply 230 V AC, accuracy +/-0.1% of full scale, Four
66 resolution 0.1°C, backlit LED/LCD four digit display, non volatile memory, key board for alarm & 8 Nos. 24,750.00 Thousand
password setting etc., non corrosive MOC, IP 54, communication port RS 232/485, relay outputs, Seven
metal plate tag and all other hardware. Hundred
Programmable Logic Controller (PLC) with HMI & PC Based SCADA system :Design,
Manufacture, Supply, Installation, Testing and Commissioning of Indoor type PLC Panel of size Rupees
approx. 1000 mm X 600 mm X 2000mm (LBH) , abricated out of minimum 2 mm thick CRCA sheet Fifty Two
67 steel. wall/ floor mounted Panel having cable entry / exit through removeable gland plate preferably 1 set 52,05,000.00 Lac Five
at the bottom, IP-54 degree of rotection for enclosure, Separate terminal blocks (screwed type) shall Thousand
be used for analog and digital signal and also for signals with different voltages. Panel shall have only
single lockable door with gasket.PLC panel shall have 100% Redundunt Programmable Logic
GWIL Page 62 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
Controller (PLC) with following specifications PLC system (with Analog Input/Output cards, Digital
Input/Output cards, communication cards, RS 485 communication Ports, ethernet communication
ports, MOD Bus compatibility, Aux supply 24 V DC, Real Time Clock, operating temperature range
to 55° C, Detachable EPROM/SD CARD for Programme backup, support various protocol standards
such as Modbus, IEC 60870/ DNP3, Redundant SMPS of 230V AC Input-24VDC out put, distribution
boards, set of control relay, MCB of suitable rating, suitable no. of LED indicator Lamps, Selector
Switches, push Buttons / illuminited Push Buttons, 0.5 sqmm multistanderd Internal wiring with
ferruling complete as per technical specifications and approved system architecture, necessary
programming software for PLC & SCADA and comprising of all accessories not limited to the
following:- Programmable Logic Controller (PLC) with Dual Hot Redundant CPU, Power supply,
Communication Module, Hot Swappable Input,Output Modules & Processor rack (Standard DC),
Back up Interface/Expansion Module, Rack (Backplane) 10 slots for IO and Processor. SCADA
software shall have facility VPN, OPC, Smart Client, Web Enabled, Automation Report Generation,
Archiving, Treands, Data Logging, a) The PLC System peripherals shall consist of the
followingMCB,SMPS 240VAC/ 24 VDC, Control Relays, Annunciator with 24 Windows NO to NC
Type Microprocessor Based, Window Size 75*42mm, 110VAC, with Electronic Hooter, Panel Cooling
Fan & Filter,Panel Light with Door Switch, Control Indication Lamp for 24VDC, 220VAC,Push Button,
Power Wiring, Control Wiring, Control TB/ Fuse 2A,TB etc., Panel Hardware, lugs, terminations,
ferruls, name plate etc.UTILITY SOCKET, HMI Display 15 Inch, Colour, Isolators Dual Output,
24VDC, Ethernet Switch ( Managed)b)One No. Operator Station including, Core i5 processor, 8 GB
RAM, 1TB SSD, DVD RW Drive, RS-232/485/RJ45 Port, 1 Parallel Port, 4 nos. USB Port, 2x
Ethernet Cards, Keyboard, Optical mouse, 32'' LED monitor, Latest windows professional, Anti Virus,
etc. c) One No. Engineering Station including, Core i7 processor, 8 GB RAM, 1TB SSD, DVD RW
Drive, RS-232/485/RJ45 Port, 1 Parallel Port, 4 nos. USB Port, 2x Ethernet Cards, Keyboard, Optical
mouse, 32'' LED monitor, Latest windows professional, Anti Virus, etc. d) Licensed version software:
PLC software and HMI software development & Run Time & Development Programming and
Troubleshooting software for PLC, HMI, SCADA, VPN, Web Client - OWSe) A4 size black & white
printer, minimum 250 paper input capacity, 1 port USB compatible with USB 2.0 specification with
Ethernet 10/100 base, Separate power ON/OFF switch with required all accessories for complete the
system. f) Industrial UPS 3 KVA with one hour backup (SMF Ni-Cd batteries), 230 V AC O/P, and
any other items required to complete the system and as per detailed tender specification. which will
be installed in NC-28 PPLC SCAD room g) SITC of Process Indicator (for Pressure, Flow, Level
Transmitter, Temperature,Transformer OTI and WTI All data from PPMS as per tender
specifications) Web Based Pump PerformanceMonitoring System Required Following Parameters
Shall be Measured Pump Efficiency - % Flow Rate – m3/hr Discharge Pressure – Kg/cm2 Inlet
Pressure – Kg/cm2 Sump Level – m Overall Eff - %Cumulative Flow – m3/hr Drive Power – kW
Phase Voltage – V Phase Currents – Amp Power Factor Frequency – Hzh)Microprocessor based
Digital Indicator, Input Supply 230 VAC, Input Signal 4 to 20 mA, Digital Display of Flow, Level and
Pressure, Relay Contact output, RS485 port / computer interface port and as per detailed tender
specificationi)SITC of Surge Protection Device(for Pressure, Flow, Level Transmitter, Temperature,
All data from PPMS as per tender specifications)j) Microprocessor based Digital Indicator, Input
Supply 230 VAC, Input Signal 4 to 20 mA, Digital Display of Flow, Level and Pressure, Relay Contact
GWIL Page 63 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
output, RS485 port / computer interface port and as per detailed tender specification.h)License
version windows 10 pro (64bit), 11th Generation Intel i7 or higher version processor, NVIDIA Video
Card GeForce GT 1030 2GB GDDR5 or latestThe item descriptions provided in the BOQ indicate the
minimum requirement only. The specifications and details mentioned in the tender datasheet and
technical specifications shall also be strictly followed to complete the work in all respect.
Supply, Installation, Testing and Comissioning of Inverter type Air Cooled Hi Wall split type Air Rupees
conditioners with latest star rating system as per BEE amended upto date complete with Indoor Fifty Five
unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed Thousand
cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto Three
68 3.5 Mtr (IDU to ODU), R-32/R-410 Green Refrigerant, wireless Remote control, suitable for working 2 Nos. 55,359.32 Hundred
between 230V +/- 10% with low & high voltage cutoff and 50 hz , single phase AC supply capable of Fifty Nine
performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary & Paise
compressor. All as per pre approved by Engineer in-charge. For additional technical parameters of Thirty Two
products/ work .2.0 TR only
Junction Box: (MOV to PLC)(Minimum 60 Terminal Block)
Gasket: Neoprene Rubber
Machine Screw with washer: SS304
69 Earthing Stud with washer &Nut 6 Nos. 19,000.00
Inscription plate
Terminal Block(Clip on Type)
Removable Gland Plate
Instrumentation Power/ Control/ Signal/ Networking & Communication Cables including Cable Twenty
Glands and Lugs: Three Lac
Designing, Supplying, Installing, commissioning & testing with Terminating & Interfacing of Five
1.1Kvgrade, Non Compact circular copper conductor, XLPE insulated cores laid up , with PVC inner Thousand
sheated, Armoured, FR-LSH PVC Outer sheath cables.24CX1.5 Sq mm(Non Shielded Armoured Eight
FRLS) For Digital Input Signal from Electrical Feeders Hundred
Designing, Supplying, Installing, commissioning & testing with Terminating & Interfacing of Lac Ninety
1.1Kvgrade, Non Compact circular copper conductor, XLPE insulated cores laid up , with PVC inner Six
sheated, Armoured, FR-LSH PVC Outer sheath cables.16CX1.5 Sq mm(Non Shielded Armoured Thousand
FRLS) For MOV Signals from field Eight
Designing, Supplying, Installing, commissioning & testing with Terminating & Interfacing of Rupees
1.1Kvgrade, Non Compact circular copper conductor, XLPE insulated cores laid up , with PVC inner Five Lac
GWIL Page 64 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
sheated, Armoured, FR-LSH PVC Outer sheath cables.8CX1.5 Sq mm(Non Shielded Armoured Forty
FRLS) FOR Digital Output Signal from Electrical feeders Seven
Designing, Supplying, Installing, commissioning & testing with Terminating & Interfacing of
1.1Kvgrade, Non Compact circular copper conductor, XLPE insulated cores laid up , with PVC inner
70.3 1 Lot 8,13,500.00 Thousand
sheated, Armoured, FR-LSH PVC Outer sheath cables.30CX1.5 Sq mm(Non Shielded Armoured
FRLS) For connecting MOV from Junction box
Signal cables 500V Standard Annealed Bare copper conductor , Extruded XLPEinsulated , two core
twisted to form a pair, Pair laid up, Individual pair shielded and overall shielded with almunium malyar
tape along with allelead tin copper drain 2PX1.5sqmm(twisted pair Shielded ,Armour FRLS) For
500V Standard Annealed Bare copper conductor , Extruded XLPEinsulated , two core twisted to form Thirty
a pair, Pair laid up, Individual pair shielded and overall shielded with almunium malyar tape along Three Lac
with allelead tin copper drain 24 PX1.5sqmm(twisted pair Shielded ,Armour FRLS) For Temp Fifty Three
Scanner cables Thousand
500V Standard Annealed Bare copper conductor , Extruded XLPEinsulated , two core twisted to form Ninety
a pair, Pair laid up, Individual pair shielded and overall shielded with almunium malyar tape along Three
with allelead tin copper drain 6PX1.5sqmm(twisted pair Shielded ,Armour FRLS) For VFD Analog Thousand
72 Cable for Comminication for soft communication: RS485 2CX1.5 Sq mm(Shielded) 1 Lot 1,80,730.00 Thousand
CCTV Survellience system for safety and monitoring of pumping station with all required Rupees
accessories, fittings, cables. The item includes camera(minimum 15 nos), PeE switch, Network Three Lac
GWIL Page 65 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
Switch with minimum 2 TB harddisk , Rack, HDD Surveillance, Cables (UTP Cat 6 Cable with PVC Seven
conduit & Power Cable with PVC pipe & accessories), Power Plug Points etc. complete which will Thousand
include PC with 27" monitor with viewing display. Total no of Camera with different types to be Seven
decided during detailed engg. CCTV system must cover all the area which will include all the pump Hundred
house and the screen will will be installed in NC-28 PLC room . The Accesories required while Ninety
installing the CCTV will be under bidder scope which will include( Ethernet Switch with FO Two only
compactibility, RJ45 Connector, PVC junctions boxes,Fibre Optic cable, LIU, Fibre Patch cord, Rack
for installtion of PoE Switch, Pole for installtion of Camera). Bidder to note that STQC certficate
will be compulsory for the supplied Camera. Kinldy note without STQC certificate the camera
shall not be accepted. The item descriptions provided in the BOQ indicate the minimum
requirement only. The specifications and details mentioned in the tender datasheet and technical
specifications shall also be strictly followed to complete the work in all respect
SITC of UL 10th edition / EN54 / VDS certified Microprocessor based inteligent, Analogue Two Lac
addressable,modular, expandable networkable loop Fire Alarm Control Panel with each loop Ninety
capacity of min 125 detectors per loop with total of 125 detectors & devices with Loop length up to 1 Eight
KM as per NFPA 72 approval. The Panel shall be able to give pin point location of addressable units Thousand
via the address code for each unit. The Panel shall also be able to automatically switch off all control Nine
switches when-ever any Alarm is 1 - Loop Panel Add Extra for Graphics User Inteface (GUI) Hundred
Software for programming the fire detection and voice alarm system through FACP / PC.The item Twenty
descriptions provided in the BOQ indicate the minimum requirement only. The specifications and Five &
details mentioned in the tender datasheet and technical specifications shall also be strictly followed Paise
to complete the work in all respect Forty Two
SITC of EN / LPCB/ UL listed / approved conventional automatic fire Alarm Optical/Photoelectric One
type smoke detectors of photo-optic sensing chamber, 12 / 24 volt D.C., visual alarm indicator Thousand
(LED's) "Blink - green" in stand by and "Steady - red" in alarm complete in all respects with base as Two
required.including the cost of all accessories Etc. as required. All as per pre approved by Engineer Hundred
in-charge. For additional technical parameters of products/ work catalog to be provided during detiled Eighty
engg The item descriptions provided in the BOQ indicate the minimum requirement only. The Eight &
specifications and details mentioned in the tender datasheet and technical specifications shall also Paise
be strictly followed to complete the work in all respect. Ninety
SITC of EN / LPCB/ UL listed / approved conventional type Manual call point resettable complete Five
with Glass, hammer and chain etc.including the cost of all accessories Etc. as required. All as per pre Hundred
approved by Engineer in-charge. For additional technical parameters of products/ work catalog to be Twenty
provided during detiled engg. The item descriptions provided in the BOQ indicate the minimum Six &
requirement only. The specifications and details mentioned in the tender datasheet and technical Paise
specifications shall also be strictly followed to complete the work in all respect Twenty
GWIL Page 66 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-5 Electrical & Instrumentation Works [For NC-28 Works]
Description Qty. Unit [In
No. [In Figures] [In INR]
SITC of EN / LPCB/ UL listed / approved conventional type Hooter cum strobe including the cost of Five
all accessories,Etc. as required. All as per pre approved by Engineer in-charge. For additional Hundred
technical parameters of products/ work catalog to be provided during detiled engg.The item Eighty
descriptions provided in the BOQ indicate the minimum requirement only. The specifications and Four &
details mentioned in the tender datasheet and technical specifications shall also be strictly followed Paise
to complete the work in all respect Seventy
Supplying and drawing Fire Resistant flexible / stranded bare copper conductor, PVC / XLPE
insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial
Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existing surface
or recessed PVC/ MS conduit/casing capping / Cable tray / Open Duct making connections, testing
etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables.
78 1.00 Lot 27,457.63 Hundred
All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work
, 2 x 1.5 Sq.mm Armoured With Outer Sheath in Red Color The item descriptions provided in the
BOQ indicate the minimum requirement only. The specifications and details mentioned in the tender
datasheet and technical specifications shall also be strictly followed to complete the work in all
Supply, installation, Testing and Commissioning of Pump performance monitoring with required
accessories for each pump at pumping station and deploy a web based pump performance
monitoring and mobile application along with providing access to department officials through login
credential for monitoring of each pump and the entire pumping station alike Required
79 8 Nos. 3,00,000.00 Three Lac
Following Parameters Shall be Measured Pump Efficiency - % Flow Rate – m3/hr Discharge
Pressure – Kg/cm2 Inlet Pressure – Kg/cm2 Sump Level – m Overall Eff - % Cumulative Flow –
Drive Power – kW Phase Voltage – V Phase Currents – Amp Power Factor Frequency – Hz
Total (Electrical and Instrumentation Works)
GWIL Page 67 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-6 Electrical & Instrumentation Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
1 HT Switchgear Panel (HV Panel for SPP-3A Pumping Station)
HT Switchgear Panel
Design, engineering, procurement, installation, testing and commissioning both side extensible,
type tested, Indoor type HV Switchgear panel confirming to IS-3427, IS-2516 (Part- I & II.sec.1 )
& IEC-60056 & IEC-62271-100/200 for use on 3phase, 50 Hz, unearthed AC supply system and
having breaking/ ruptuing capacity as mentioned below complete with spring charged
mechanism, ON-OFF mechanical push button, operation counters, Breaker TNC switch, Breaker
L/R switch, necessary auxiliary switches, closing coil, shunt trip, protection relays & Indicators,
Push Buttons, Emergancy Push Button, Hooter, Annunciators, and accessories mentioned in
tender Datasheet and Technical Specifications etc. to complete the work in all respect. The
panel shall comprise of air insulated busbars provided with heat shrinkable PVC sleeves. The
VCB trolley shall comprise of three vacuum interrupters with epoxy support insulators and self
aligning finger type isolating contacts and necessary mechanical interlocks, safety shutters,
isolating plugs. Enclosure shall be openable from front as well as rear end. The breaker shall be
Manual cum motorised mechanism with following accessories and accessories mentioned in as
per tender datasheet and Specifications.
a) 96 x 96 mm square flush mounting type Ammeter & Volt meter with selector switches for all
b) Multi function meter for all feeders
c) Three Core cast resin type current transformer having ratio, burden and accuracy as per
requirement or as per tender specification and Datasheet (One core for metering, Second core 1 No. 40,02,017
for protection and third core for differential protection applicable for incomer feeder), Double
core, cast resin type current transofrmers having ratio as per requirement, one core for metering
& second core for protection having required class of accuracy for outgoing feeders
d) Instantaneous under voltage relay & Temperature rise tripping Relay and relays as mentioned
in tender datasheet and specifications,
e) Feeder Protection Numerical IDMT Relay with IEC-61850 & RJ-45 port Protection, Tranformer
fault relay as mentioned in tender datasheet and specifications,
f) Comprehensive Motor Protection Relay as mentioned in tender datasheet and specifications (if
g) Electrical closing. coil & shunt trip coil operating on 110 V DC.
h) Auxiliary relay for anti pumping device.
h) Three limb, dual core, drawout type, feeder connected, cast resin insulated, Potential
transformers at line side and common bus having ratio, burden & accuracy mentioned in tender
datasheet and specifications.
i) Annunciator Windows, Hooter / Alarm bell operating on 230 AC/ 110 V DC for each feeders.
j) Cable boxes suitable to terminate 3 core XLPE cable of required size (As per design).
k) 230V AC to 110 V DC power pack for closing & tripping circuit common.
l) Breaker ON-OFF, Auto trip and spring charged indicators.
m) Phase indicating & panel illumination lamps with plug socket.
n) Space Heater with Thermostat. The item descriptions provided in the BOQ indicate the
GWIL Page 68 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-6 Electrical & Instrumentation Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
minimum requirement only. The specifications and details mentioned in the tender datasheet and
technical specifications shall also be strictly followed6.6 kV HV Switchgear Panel- Comprising
of 1250 A Vacuum circuit breaker for 2nos. Incomer, 1no. Bus coupler, 2 Nos. Bus PT,
Nos. 1250A O/G feeders Vacuum circuit breakers (9 nos. O/G feeders for Motor Outgoing
2 6.6/6.6kV (Unearthed) Grade Cable- Aluminium Conductor
Supply, laying, testing & commissioning 6.6 / 6.6 kV (UE) grade, XLPE insulated, stranded
Aluminium conductor, galvanised steel flat strip / round wire armoured, extruded PVC type ST2
sheathed, heavy duty, FRLS cable (to be laid on wall surface with necessary clamps / in existing
1 Lot 11,58,696.00 Thousand
cable trench / cable trays / conduit / pipe sleeves at road crossing or floor as per site
requirement) conforming to IS: 7098 (Part- 2) & IEC: 60502 (Part-2) of following sizes:
3 Core X 240 Sqmm (From 6.6 kV VCB Panel to 6.6KV HT Soft Starter Panel, 6.6KV HT Soft
Starter Panel to HT Motor, HT Panel to HT Capacitor Bank)
Cable Terminations / Jointing Kits for 6.6 kV (UE) XLPE Cable Two Lac
Providing & fitting heat shrink cable termination/ jointing kits for 6.6 kV (UE) grade XLPE Eighty
insulated cable including necessary earth connectivity connection, material & consummables Seven
making the termination / joint complete ensuring the joint resistance is within the permissble limit Thousand
as per IS, of following types & sizes: Eight
3C x 240 Sqmm ( Indoor Terminations Kit suitable for 6.6KV Panel) Hundred
4 Flux Compensated Magnetic Amplifier (FCMA) Soft Starter for 900 KW (Line Side)
Supply, installation, testing & commissioning Line Side FCMA (Flux compensated magnetic
amplifier) HV soft starter panel suitable for 3 phase squirrel cage induction motor & provided with Rupees
built in bypass terminal with bypass device as a Vacuum Circuit breaker having Rating Seven Lac
6.6KV, 1250A, 3Pole, 26.3KA for 3Sec for pump control application by torque control method Thirty
as per tender specification. Thousand
Soft Starter shall be operated on 3 phase, 50 Hz, fault Level 25 kA for 1 second with Copper bus Seven
bar & enclosure fabricated from 2 mm CRCA sheet steel, solidly earthed neutral system earthing Hundred
complete with following associated necessary equipment & accessories as per tender technical Fifty Five
specification and Datasheet.The item descriptions provided in the BOQ indicate the minimum only
requirement only. The specifications and details mentioned in the tender datasheet and technical
specifications shall also be strictly followed.
5 HT Fix Capacitor Panel min. 400 kVAR or Suitable Rating as per Details Engineering
whichever is Higher Rupees
Supply, installation, testing & commissioning of minimum 400kVAR or Suitable Rating as per Five Lac
Details Engineering whichever is better/Higher , 6.6 kV, 3 Ph. 31.5KA for 1 Sec., MV Capacitor Fifty Five
Bank. Along with associated equipment’s like 6.6KV, 630A, Vacuum Contactor (Class C2) of 9 Nos. 5,55,500.00 Thousand
Requied Capacity, On Delay Timers, Remote/Local Selector Switch, Indication Lamps, Push Five
Buttons, Protection Relays, Ammeter, Current Transformers, HT capacitor,0.2% Series Reactor Hundred
RVT, NDR, etc., to be assembled in a Power coated Sheet metal enclosure of IP-42 as below only
3Ph., 50Hz. comprising of APP star connected Type Capacitor unit along with discharge resister,
GWIL Page 69 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-6 Electrical & Instrumentation Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
Indoor Type, 0.2% Inrush Current Limiting , 6.6KV, 3-Ph., 150% rated current, Super Heavy Duty
Long Life Low Losses Dry Type Air core Cu Wound Series Reactor suitable, 7.2kV, 3Ph.,Off
Load Isolator 630A, STC 31.5kA/1Sec, 7.2kV HT HRC Fuse Link of suitable current rating,
Residual Voltage Transformer 6.6kV/110-190V Resin Cast, Neutral Displacement Relay
(Microprocessor Based Electrostatic Relay), Indicating Lamps (On/Off)., Limit Switches, Set of
interconnecting high conductivity electrolytic grade Cu bus bars & insulated by using Colour
coded heat shrinkable PVC Sleeves, Indoor Type Standalone / Free standing, Fully Enclosed,
dust & vermin proof, Powder coated CRCA Enclosure of IP-42 with Bottom entry for Busbar duly
wired with each Items as per tender technical specification and Datasheet. The item descriptions
provided in the BOQ indicate the minimum requirement only. The specifications and details
mentioned in the tender datasheet and technical specifications shall also be strictly followed.
6 SITC of 110 V DC, Min. 200 AH or Suitable Rating as per Details Engineering whichever is
Higher, Float and Float cum Boost type Battery Charger with Battery and Integral 63A DC Rupees Six
distribution board. The item descriptions provided in the BOQ indicate the minimum requirement Lac Twenty
only. The specifications and details mentioned in the tender datasheet and technical 1 Set. 6,26,000.00 Six
specifications shall also be strictly followed. (For NC-28 Pump House). 2Nos. Incomer , 1Nos. Thousand
Buscoupler 63A MCCB Feeder, 12Nos. Outgoing 16A MCB Feeders, Interconnecting work of only
Battery charger of Common HT Panel Room, NC-28, SPP-3B
Supply, laying, testing & commissioning 1.1 kV grade, XLPE insulated, stranded Aluminium /
Copper Conductor, galvanised steel flat strip / round wire armoured, extruded PVC type ST2
sheathed, FRLS heavy duty cable (to be laid on wall surface with necessary clamps / in existing
1 Lot 2,00,340.00 Three
cable trench / cable trays / conduit / pipe sleeves at road crossing or floor inclusive lugs & heavy
duty double compression brass glands with washers as per site requirement) conforming to
IS:7098 (Part-1) & IEC:60502 (Part-1) of following sizes:
3.5 C x 300 Sq. mm Aluminium Coductor (From NC-28 LVDB Panel to SPP-3A LVDB Panel)
---------do as above --------for 3.5 C x 95 Sq. mm Aluminium Conductor (From LVDB Panel to Thirty Six
60HP Dredging Pump) Thousand
---------do as above --------for 3.5 C x 35 Sq. mm Aluminium Conductor (From LVDB Panel to
1 Lot 34,650.00 Thousand
30HP Dredging Pump)
---------do as above --------for 3.5 C x 25 Sq. mm Aluminium Conductor (From LVDB Panel to
MOVDB, Battery Charger of SPP-3A, Battery Charger of SPP-3A to Battery Charger of NC-28, 1 Lot 98,490.00
ACDB of MCC Room, 2Nos. 30HT Dredging Pump)
7.04 ---------do as above --------for 4C x 16 Sq. mm Aluminium Conductor (From LVDB Panel to 1 Lot 1,13,400.00 Rupees
GWIL Page 70 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-6 Electrical & Instrumentation Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
Dewatering Pumps, Exhaust Fan DB, Welding Receptacles.) One Lac
---------do as above --------for 4C x 4 Sq.mm Copper Conductor (From LVDB TO LDB of MCC
1 Lot 2,36,880.00 Thousand
ROOM, PUMP HOUSE, OUTDOOR LIGHTING, LVDB TO UPS, PLC ROOM AC)
---------do as above --------for 4C x 2.5 Sq.mm Copper Conductor (From HT Panel to LPBS, HT
1 Lot 1,14,817.50 Eight
Panel to HT Capacitor Panel, , HT Panel to Soft Starter Panel etc.)
---------do as above --------for 3C x 2.5 Sq.mm Copper Conductor (For Actuators, Exhaust Fan,
1 Lot 2,61,870.00 Thousand
Instrument Power Supply & Small Misc. Loads etc.)
---------do as above --------for 2C x 2.5 Sq. mm Copper Conductor Power cables (For single Fifty Seven
phase power feeders - Space Heaters, HT Panels, NGR, NIFPS, FCMA Panels & DC Cables - 1 Lot 1,57,500.00 Thousand
DCDB to HT Panels, Isolator, Soft Starter etc.) Five
---------do as above --------for 8C x 2.5 Sq.mm Copper Conductor (Control cables for relay, Five Lac
AVR, VCB Interlock, Process Interlock, Local Push Button Station, Control cables HT Panel to Sixty
HT VFD and Soft Starter Panel, Control cables for relay, AVR, VCB Interlock, Process Interlock, Thousand
Local Push Button Station etc.) Five
GWIL Page 71 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-6 Electrical & Instrumentation Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
---------do as above --------for 12C x 2.5 Sq. mm Copper Conductor (Control cables Transformer Two
marshelling Box) Hundred
R. C. C. PIPE (Horizontal Cast)
Providing and supplying ISI Standard R.C.C. pipes(of Sulphate Resisting Cement) in standard
lengths of following class and diameter suitable for either collar joints or rubber ring joints
15 Meter 1,485.00 Four
including all taxes, insurance, transportation, freight charges, octroi, inspection charges, loading,
unloading, conveyance to departmental stores, stacking etc. (500mm Dia. - 5Nos. Pipe)
Class NP3 Test Pressure 0.7 Kg/sq.cm
Lowering, laying and jointing R. C. C. pipes in C. M. 1:1 1/2 of following diameters in proper One
position, grade and alignment at all level as directed by Engineer-in-charge including 15 Meter 189.00 Hundred
conveyance from stores to site of work, labour, giving hydraulic testing as per ISI code. Eighty Nine
10 Cable Gland/ Terminations:Providing & fitting heavy duty brass cable glands (nickel-plated)
with washers & rubber ring conforming to IS, suitable for 3, 3½ & 4 core cables of following type
& sizes: Double Compression Brass Cable Glands3.5 C x 300Sqmm"95 Sq. mm35 Sq. mm70
Sq. mm25 Sq. mm16 Sq. mm4 Sq. mm2.5 Sq. mm5C, 8C, 12C, 14 and 19C x 1.5 or as per 1 Lot 67,711.00
actual size of cable, The item descriptions provided in the BOQ indicate the minimum
requirement only. The specifications and details mentioned in the tender datasheet and technical
specifications shall also be strictly followed to complete the work in all respect.
11 Cable Terminals (Lugs)
Providing & fitting crimping type Cable Terminals (Lugs) conforming to IS of following types and Rupees
300Sqmm Aluminium Thousand
150Sqmm Aluminium 1 Lot 7,742.00 Seven
70Sqmm Aluminium Hundred
35Sqmm Aluminium Forty Two
25Sqmm Aluminium only
16Sqmm Aluminium
GWIL Page 72 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-6 Electrical & Instrumentation Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
1.5 and 2.5 Sq. mm or as per actual size of cable, The item descriptions provided in the BOQ
indicate the minimum requirement only. The specifications and details mentioned in the tender
datasheet and technical specifications shall also be strictly followed to complete the work in all
Supply, installation, testing and commissioning LV Distribution Board (LVDB) totally enclosed,
dust & vermin proof, indoor type, fabricated from CRCA sheet steel with minimum thickness of
mm for base frame / channel / gland plates, 2.0 mm for load bearing members / doors & 1.6 mm
for internal partitions, minimum degree of protection - IP 52 as per IS: 2147, suitable for
operation on 3-Phase, 4 Wire, 415 V, 50 Hz, Neutral effectively grounded, with strumentation
compartments accomodating meters, aux / protective relays, LED type indicating lamps & control
MCBs as per IS: 13947, current & voltage transformers as per IS: 2705, air insulated electrolitic
grade Copper bus bar for three phase & neutral system, GI earth bus for entire length, power /
control wiring using 1100 V grade, FRLS insulated copper conductor wires conforming to IS:
& 8130, equipment fittings, horizontally running busbar compartment height of minimum 300 mm,
incoming & ougoing cable connections for 1100 V grade, Aluminium / Copper conductor XLPE /
PVC insulated & PVC sheathed armoured cable. LVDB shall have required incomming / bus
coupler / outgoing modules of following type & ratings. Aluminium earth bus bar for entire length
as per SLD, detail specifications & data sheet including required testing @ factroy as per
applicable IS/ IEC standards. LVDB/ PCC Panel shall be comprising of ; Rupees
(a) 2Nos. 400A Incomer and 1Nos. Buscoupler, 4 Pole, Air Break Fixed MCCB conforms to IS/ Nine Lac
IEC 60947-2 with trip free mechanism, current limiting type with Microprocessor release (O / C, S Seventy Six
/ C & E / F) with adjustable settings & having minimum 2NO+2NC potential free auxiliary Thousand
contacts with all necessary Electro-Mechanical protections & interlocks etc. Four
(b) 5 Nos. 80 A, 3 Pole, Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free Hundred
mechanism, current limiting type with Thermal Magnetic (O / C, S / C & E / F) with adjustable Five & Paise
settings & having minimum 2NO+2NC potential free auxiliary contacts with all necessary Electro- Eighty only
Mechanical protections & interlocks etc.
(c) 3 Nos. 160A, 3 Pole, Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free
mechanism, current limiting type with Thermal Magnetic with adjustable settings & having
minimum 2NO+2NC potential free auxiliary contacts with all necessary Electro-Mechanical
protections & interlocks etc. MCCB module for Dredging Pumps -60HP-2Nos. , Spare-1Nos. etc.
(d) 10 Nos. 32A, 4 Pole , Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free
mechanism, current limiting type with Thermal Magnetic with adjustable settings & having
minimum 2NO+2NC potential free auxiliary contacts with all necessary Electro-Mechanical
protections & interlocks etc. MCCB module-4 Nos for ACDB, Welding Receptacles etc.
(e) 8 Nos. 63A, 3 Pole, Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free
mechanism, current limiting type with Thermal Magnetic with adjustable settings & having
minimum 2NO+2NC potential free auxiliary contacts with all necessary Electro-Mechanical
protections & interlocks etc. MCCB module-4 Nos for ACDB, Welding Receptacles, Battery
Charger, Spare etc.
(f) 10 Nos.32A 3 Pole, Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free
GWIL Page 73 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-6 Electrical & Instrumentation Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
mechanism, current limiting type with Thermal Magnetic with adjustable settings & having
minimum 2NO+2NC potential free auxiliary contacts with all necessary Electro-Mechanical
protections & interlocks etc. MCCB module- LDBs for Electrical control room, Pump House,
Monrail Hoist and EOT, Pipeline Valve Junction Box etc.
(g) 40 Nos Outgoing each with 32A DP MCB for 230V aux loads having breaking capacity 10 KA
& confirming to IS/IEC 60898-2:2003 for Exhaust Fans, etc.
The item descriptions provided in the BOQ indicate the minimum requirement only. The
specifications and details mentioned in the tender datasheet and technical specifications shall
also be strictly followed to complete the work in all respect.
13 Control Panel Board Rupees
Auto transformer starter suitable for local & remote pump control application consisting of Auto Twenty Four
Transformer (vacuum impregnated, air cooled having three (3) tappings at 50%, 65% and 80%), Thousand
incomer MCCB / MPCB, overload relay and contactors as per Type II coordination including 1.00 No. 24,276.00 Two
digital MFM with RS 485 communication port, analogue type ammeter with selector switch, run Hundred
hour meter, required protective relays & control accessories. Seventy Six
30 HP (New Proposed Collection Chamber) only
---------do as above --------for A. T. S. 60 HP for 60HP Dredging Pump (For SPP-3A sump) 1.00 Nos. 46,238.00 Two
15 AC POWER DISTRIBUTION BOARD:
Supply, installation, testing and commissioning LV Distribution Board (LVDB) totally enclosed,
dust & vermin proof, indoor type, fabricated from CRCA sheet steel with minimum thickness of
mm for base frame / channel / gland plates, 2.0 mm for load bearing members / doors & 1.6 mm
for internal partitions, minimum degree of protection - IP 52 as per IS: 2147, suitable for
operation on 3- Phase, 4 Wire, 415 V, 50 Hz, Neutral effectively grounded, with instrumentation
compartments accomodating meters, aux / protective relays, LED type indicating lamps & control
MCBs as per IS: 13947, current & voltage transformers as per IS: 2705, air insulated electrolitic
grade Aluminum / Copper bus bar for three phase & neutral system, GI earth bus for entire
length, power / control wiring using 1100 V grade, FRLS insulated copper conductor wires
1 Nos. 25,640.90 Six Hundred
conforming to IS: 694 & 8130, equipment fittings, horizontally running busbar compartment
height of minimum 300 mm, incoming & ougoing cable connections for 1100 V grade, Aluminium
/ Copper conductor XLPE / PVC insulated & PVC sheathed armoured cable. LVDB shall have
required incomming / bus coupler / outgoing modules of following type & ratings.
(a) 1Nos. 415VAC, 63A, 3Pole, Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free
mechanism, current limiting type with Thermal Magnetic (O / C, S / C & E / F) with adjustable
settings & having minimum 2NO+2NC potential free auxiliary contacts with all necessary Electro-
Mechanical protections & interlocks etcPole, MCCB with Breaking Capacity of Icu=50 KA at
415V (Ics =100% of Icu)
(b) 20 Nos Outgoing each with 16A DP MCB for 230V aux loads having breaking capacity 10 KA
GWIL Page 74 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-6 Electrical & Instrumentation Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
& confirming to IS/IEC 60898-2:2003.
1Nos. For MCC Room (For Power Supply of Space Heater of HT VFD, Soft Starter Panel,
Capacitor Panel and Exhaust Fan of MCC Room)
The item descriptions provided in the BOQ indicate the minimum requirement only. The
specifications and details mentioned in the tender datasheet and technical specifications shall
also be strictly followed to complete the work in all respect.
16 AC POWER DISTRIBUTION BOARD:
Supply, installation, testing and commissioning LV Distribution Board (LVDB) totally enclosed,
dust & vermin proof, indoor type, fabricated from CRCA sheet steel with minimum thickness of
mm for base frame / channel / gland plates, 2.0 mm for load bearing members / doors & 1.6 mm
for internal partitions, minimum degree of protection - IP 52 as per IS: 2147, suitable for
operation on 3- Phase, 4 Wire, 415 V, 50 Hz, Neutral effectively grounded, with instrumentation
compartments accomodating meters, aux / protective relays, LED type indicating lamps & control
MCBs as per IS: 13947, current & voltage transformers as per IS: 2705, air insulated electrolitic
grade Aluminum / Copper bus bar for three phase & neutral system, GI earth bus for entire
length, power / control wiring using 1100 V grade, FRLS insulated copper conductor wires Rupees
conforming to IS: 694 & 8130, equipment fittings, horizontally running busbar compartment Twenty
height of minimum 300 mm, incoming & ougoing cable connections for 1100 V grade, Aluminium Eight
/ Copper conductor XLPE / PVC insulated & PVC sheathed armoured cable. LVDB shall have 1 Nos. 28,005.31 Thousand
required incomming / bus coupler / outgoing modules of following type & ratings. Five & Paise
(a) 1Nos. 415VAC, 80A, 3Pole, Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free Thirty One
mechanism, current limiting type with Thermal Magnetic (O / C, S / C & E / F) with adjustable only
settings & having minimum 2NO+2NC potential free auxiliary contacts with all necessary Electro-
Mechanical protections & interlocks etcPole, MCCB with Breaking Capacity of Icu=50 KA at
415V (Ics =100% of Icu)
(b) 15 Nos Outgoing each with 16A TP MCB for 415V aux loads having breaking capacity 10 KA
& confirming to IS/IEC 60898-2:2003.
1Nos. For Motorised Valve Distribution Board
The item descriptions provided in the BOQ indicate the minimum requirement only. The
specifications and details mentioned in the tender datasheet and technical specifications shall
also be strictly followed to complete the work in all respect.
17 LIGHTING DISTRIBUTION BOARD (For MCC Room, Pump House):
Providing and erecting a 415V MCB Four-Pole Switch for lighting load (B curve), having a
breaking capacity of 10 kA and conforming to IS:8828, in the existing box, with the following Rupees Ten
capacity. Thousand
(a) 1 No. incomer with 63A FP EL+MCCB (O/L+S/C+E/F) for lighting & inductive load having Two
25kA breaking capacity & conforming to IS/IEC 60898-2:2003. 2 Nos. 10,208.47 Hundred
(b) 16 Nos Outgoing each with 32A DP MCB for 230V aux loads having breaking capacity 10 KA Eight &
& confirming to IS/IEC 60898-2:2003. Paise Forty
The item descriptions provided in the BOQ indicate the minimum requirement only. The Seven only
specifications and details mentioned in the tender datasheet and technical specifications shall
also be strictly followed to complete the work in all respect.
18 Supply , Installation, Testing and Comissioning of wall mounted remote ON/OFF Push Button 9 Set 5,569.49 Rupees
GWIL Page 75 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-6 Electrical & Instrumentation Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
station for Soft Starter Operated HT Motor and Potentiometer for HT VFD Panel made out from Five
powder quoted CRCA sheet of 16 SWG , illuminated ON/OFF push button including making Thousand
connections etc as required complete in all respect. All as per pre approved by Engineer in- Five
19 Supplying and erecting LED indoor fittings with LEDs of wattage 0.2Watt to 0.5Watt assembled
on single MCPCB,with housing used as a heatsink shall bemade of thick sheet Steel conforming
to IS:513/ CRCA/ aluminium diecast powder coated and high U.V.& corrosion resistance with
diffuser with company mark/name 160V to 270V,Power Factor more than 0.95, THD < 15%,CCT
3000 K to 6500K, Luminaire efficacy > 85 lumens/watt ,LED driver efficiency > 85 % (fitting Rupees
required LM-79 & LM-80 Certificates) (NOTE: Below description have shown ranges of Wattage Twenty Six
capacity of LED fittings.The Engineering charge may selec tany wattage capacity between the Thousand
ranges shown.) 1.00 Lot 26,949.00 Nine
- For control room, Common HT Panel room & other building as per the requirement of GWIL Hundred
and instructions of engineer-in-charge Forty Nine
(A) Tube Light with integral driver only
36-40Watts,Surge-2KV,IP-20,conventional 4 feet
(for ECR,Battery Room)
Min. 60Nos. or as per Lux level calculation whichever is higher and instructions of engineer-in-
20 Supplying and Erecting Of L.E.D. type High bay fixture having Power Consumption of following
watts with, Input Voltage 110 - 290 V.AC with full efficiency, Power Factor > 0.9 with 50/60 HZ, Rupees
CCVC LED Driver used for maximum power saving, Best Quality Aluminium alloy housing and Sixty Eight
aluminium Dome for better heat dissipation, CCT Cool white (6000K), CRI 80, Beam angle > 120 Thousand
degrees, working temperature -20 deg c to +55 deg c, Body IP 65, Nine
200 Watts Hundred
- For pump house area as per the requirement of GWIL and instructions of engineer-in- Forty Nine &
Min. 8 Nos. or as per Lux level calculation and instructions of engineer-in-charge whichever is Twelve only
21 Supplying and erecting Square/ Circular shaped Surface/ Recessed Mount Downlight with Rupees
provision for spring loaded mounting clips complete. IP20 Three
22-24 watts, Surge-2 KV, Cat.-III Thousand
for SCADA Room, Office Room Eight
Min. 6Nos. or as per Lux level calculation whichever is higher and instructions of engineer-in- Hundred
charge Sixteen only
22 Point wiring for Light/ Bell with 2 sq. mm & earthwire of 1.5 sq.mm (Green) both are of ISI Rupees
marked 1.1kV grade FRLS PVC insulated multistrand copper wires, in following type of pipe to Twenty
be erected concealed in/ on surface on wall/ ceiling complete with 6A Modular type switch/ bell Seven
push & accessories and earth continuity of following type, erected on PVC/ Metallic box, single Thousand
GWIL Page 76 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-6 Electrical & Instrumentation Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
mounting base frame covered with textured/ metallic front plate modules erected on/in wall/ Nine
ceiling as per pipe erected, with necessary Lamp holder/ceiling rose/ H.D.Connector as directed. Hundred Six
Contractor has to submit lighting layout and get it approved from competent authority before & Paise
execution of this work. Eighty Eight
- (a) with medium class Rigid PVC pipe and accessories erected flushed on wall/ceiling only
complete-Cat. III
- For pump house, Electrical control room, instrumentation room, Battery Room as per the
requirement of GWIL and instructions of engineer-in-charge.
Min. 74 Nos. or as per Detail Engineering whichever is higher
23 Providing and erecting Mains with 1.1KV grade FRLS PVC insulated ISI marked stranded Rupees
Copper conductor wire in following type of pipe to be erected concealed in / flushed on wall / Sixty Nine
ceiling with 1.5sq.mm copper conductor FRLS PVC insulated stranded wire of green colour for Thousand
earth continuity of following size Four
(A) With medium class Rigid PVC pipe and accessories Hundred
c) 3 wire 1.5 sq. mm Ninety only
24 Point wiring for Individual Plug with earthwire of 1.5 sq.mm (Green) both are of ISI marked
1.1kV grade FRLS PVC insulated multistrand copper wires, in following type of to be erected
concealed in/ on surface of wall/ ceiling complete with Modular type switch & 5 pin Plug erected
on PVC/ Metallic box covered with appropriate front plate modules erected on/ in wall/ ceiling as
per pipe erected with following type of accessories. Contractor has to submit lighting layout and 1 Lot 3,193.20
get it approved from competent authority before execution of this work- Modular Type Cat-III,[III]
For 6A Plug and 6 amp switch with 2-1.5 sq.mm Cu. Wire with 1.5 sq.mm (green) earthing wire
from MCB DB board. CAT-III(a) with medium class Rigid PVC pipe and accessories erected
flushed on wall/ceiling completeMin. 8 Nos. or as per Detail Engineering whichever is higher
25 Point wiring for Individual Plug with earthwire of 1.5 sq.mm (Green) both are of ISI marked
1.1kV grade FRLS PVC insulated multistrand copper wires, in following type of to be erected
concealed in/ on surface of wall/ ceiling complete with Modular type switch & 5 pin Plug erected
on PVC/ Metallic box covered with appropriate front plate modules erected on/ in wall/ ceiling as
per pipe erected with following type of accessories. Contractor has to submit lighting layout and
get it approved from competent authority before execution of this work
1 Lot 5,620.32 Six Hundred
- Modular Type Cat-III, With [III] For 16A Plug and 16 amp switch with 2-4 sq.mm Cu. Wire with
2.5 sq.mm (green) earthing wire from MCB DB board.
(a) with medium class Rigid PVC pipe and accessories erected flushed on wall/ceiling complete
- For pump house, Electrical control room, instrumentation room as per the requirement of GWIL
and instructions of engineer-in-charge.
Min. 8 Nos. or as per Detail Engineering whichever is higher
Supplying & erecting single phase approved make industrial exhaust fan suitable for medium Three
duty ring mounted low noise operation suitable for medium duty having following dia size and Thousand
maximum speed in RPM (10 Nos. for Electrical Control Room), (10 Nos. for Pump House), Three
(2Nos. Battery Room) and Exhaust Air Fan respectively 450 mm dia 1400 RPM Cat.II Hundred
GWIL Page 77 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-6 Electrical & Instrumentation Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
P & F of Wall cowl with Bird Screen Suitable for Outside Wall of Exhaust Fan Opening of
following size and made out from 24 SWG GI sheet as per instructions of Engineer in-charge
including fixing with suitable fasteners etc. as required. All as per pre approved by Engineer in- 25.00 No 1,766.10
charge. For additional technical parameters of products/ work. Suitable for 450 mm sweep
28 Providing & Fixing of IK08 IP-66 protected high power LED flood light system with single piece
Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to
achieve various beam angles, of high power LED of 3 to 5 watt each . Integrated potted driver as
a unique BIS R number having efficiency more than 85 % and in compliance to BIS certified and
Trade mark certificate. The System level Luminaire efficacy >=125 lm/ wt. LED driver Input
Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety
.Power Factor >0.95 , THD(I) <10% , driver current <=750mA. driver should be Phase to phase
protection of 440 V for 4 Hrs. Electrical Connector , Surge Protection Min >=4KV internal and
10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of
1.00 Lot 75,444.08 Four
Initial Lumens maintained, CRI>70 and CCT 5700K ±355K. Manufactures Word Mark/Name
Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity.
Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all
testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of
product/accessories from OEM shall be submitted. All as per pre approved by Engineer in-
High Power LED Flood Light Minimum lumen output 18650 lm (150W) (Min. 8 for Outdoor
side of Pump House wall Mounted as per Lux level calculation and instruction of Engineer - in -
29 Maintenance free Chemical Earthing :
Supply of UL Listed Maintenance Free Earthing System made of copper bonded rod of 10 feet (3 Rupees
mtr approx.) length, 17.2 mm dia. (Minimum copper bonding shall be 0.25mm, suitable for 25 kA Five
fault current) along with Rod-to-Conductor connectors, 95% pure Carbon-Based Earth Thousand
enhancement material of 30kg, Pit Cover as required and as per specification. (For HV panels, Three
MCC Panel, PLC Panel, UPS Panel, Motors, APFC Panel,LDB,PDB etc.). Contractor has to Hundred
submit earthing layout and get it approved from competent authority before execution of this Fifty Six only
30 Supplying & erecting funnel type earthing having earth plate of following size burred in Rupees
specifically prepared earth pit 3 mtr. below ground with 40 kg. charcoal and salt with alternate Nine
layers of charcoal & salt, 20mm.dia. G.I. pipe with Funnel with a wire mesh for watering & bricks 6.00 No 9,200.00 Thousand
masonry block, C.I. Cover complete as per para 7.3 of IS 3043 with necessary length of double Two
Galvanised Iron / copper earth wire No 6 SWG bolted with lug to the plate and covered in 12 mm Hundred
GWIL Page 78 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-6 Electrical & Instrumentation Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
dia. G.I. pipe 2.5 mtr long complete connected to the nearest switch gear with end socket as per only
direction & duly tested by earth tester
confirming to IS (As per drawing) with following specification complete with 60 x 60 x 0.315 cm
Copper earth plate (For Transformer neutrals & Lightning protection). Contractor has to
submit earthing layout and get it approved from competent authority before execution of this
31 Supply and erection of required size HOT Deep Galvanised Iron Strip for earthing of 66KV Rupees
Swithcyard, HT, VCB Panel, HT Soft Starter, HT Capacitor Panel, Battery Charger, PLC Panel, Sixty Five
LT Panel, Transformer, LT APFC Panel, HT Motors, etc., using proper clamp. Contractor has to Thousand
submit earthing layout and get it approved from competent authority before execution of this Two
Min. 1000kg or as per detailed engineering whichever is higher Fifty only
Supply & erection required size Copper strip for earthing of Auxiliary Transformers, Electronics Thirty Three
Earthing of PLC Panel etc. using copper clamp. Contractor has to submit earthing layout and get Thousand
it approved from competent authority before execution of this work Four
Min. 500kg or as per detailed engineering whichever is higher Hundred
SITC of Vertical Air Termination Solid aluminium with Base – 10 mm dia and 1000 mm long.
Air Termination Base tested for conditioning, Ageing Test & Lightning impulse current withstand
4.00 Nos. 7,900.85 Nine
test: 100 kA of 10/350µs waveform in an accredited Third party laboratory as per 6.3 & 6.4 of
IEC 62561-1 2017 protocol with MAST 34mm dia 3000 mm long – Cold Galvanized
34 SITC of 8 mm dia solid Aluminium Conductor for roof top mesh grid and tested as per IEC Rupees
62561-2 conducted in the Govt. accredited third party laboratory to meet the requirement of Thirty Six
IS/IEC 62305 with Required Accessories – Aluminium Holding clamp at every 1 mtr distance, Thousand
Aluminium/SS cross splicer at every crossing of Alu. conductor, Expansion piece with connectors Four
at every 20 mtr distance, Aluminium straight Splicer to connect conductors. All Accessories 1 Lot 36,495.76 Hundred
should be tested as per IEC 62561-1:2018 Cl. 6.3 for conditioning & Ageing Test & 6.4 for Ninety Five
Lightning impulse current withstand test: 100 kA of 10/350µs waveform (Ageing & Electrical test) & Paise
conducted in a sequence manner & tested in the Govt. accredited Third party laboratory to meet Seventy Six
the requirements of IS/IEC 6230. only
35 SITC of 10 mm Hot dipped Galvanised Round Solid Conductor having smooth surface should Rupees
be tested and used exclusively for lightning protection (Vertical Riser/Down Conductor which Eighteen
shall be concealed in column or flushed on) to meet the requirement of IS/IEC 62305. Thousand
Accessories: Three
Earthing stud of dimension SS–75mm OD plate with 10mm dia tail connector used in structural Hundred
steel ring earthing system to meet the requirements of IS/IEC 62305. Thirty &
GWIL Page 79 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-6 Electrical & Instrumentation Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
For interconnecting the column and the terrace AL conductor / strip / flat. Paise Fifty
SS Cross Connector to connect earth fixing point to vertical raiser/down conductor. One only
SS Straight Splicer at every 4 mtr to connect MS conductor in column.
Bonding/Rebar Clamp at every 3 mtr suitable for interconnecting round conductor with
reinforcement inside the concrete for structural earthing system.
SS Connector – To connect external conductor 8–10 mm with earth fixing point.
Testing Requirements:
All accessories should be tested as per IEC 62561-1:2018, Clause 6.3 for Conditioning & Ageing
Test and Clause 6.4 for Lightning Impulse Current Withstand Test: 100 kA of 10/350µs waveform
(Ageing & Electrical Test) conducted in a sequence manner and tested in the Govt. accredited
Third Party Laboratory to meet the requirements of IS/IEC
SITC of Galvanized Steel Flat 25×6 mm thickness from earth electrode directly in ground as Thousand
required. Zinc coating: 500 g/m² (Approx. 70 micron coating) tested and used exclusively for 1 Lot 3,500.85 Five
lightning protection earthing system and ring equipotential bonding. Hundred &
SITC of 14.2 mm dia, 3 mtr long Earth electrode of high tensile steel electrode with 250 micron Five
copper bonding and 1 bag of carbon fill-based environment-friendly backfill tested as per IEC Thousand
62561-7 in NABL accredited laboratory and suitable stainless steel double-sided clamp. Eco- 3 Nos. 5,027.97 Twenty
friendly, rust-proof, heavy-duty, weather-proof polyethylene Earth Pit Chamber with the following Seven &
dimensions: 254 mm dia (top), 330 mm dia (bottom) & 260 mm (height). Paise Ninety
Providing & erecting Hot dip Galvanisied strip/ iron wire 8 to16 SWG/25x6mm GI Strip for
ACDB, DCDB, LDB, Actuator Valves, Junction Box, Outdoor Lighting Poles & LPBS etc.
Contractor has to submit lighting layout and get it approved from competent authority before 1.00 Lot 32,625.00
execution of this work
Min. 500kg or as per detailed engineering whichever is higher
39 Cable Trays & Accessories:
Supply & laying GI ladder type cable trays with side channels having rungs of size spaced at
mm apart, fabricated from 2 mm thick sheet steel in standard length of 2.5 meter, duly hot dipped
galvanized after fabrication as per IS 2629-1989/ IS 4759-1984 including accessories such as
1.00 Lot 33,600.00 Thousand
coupler plates/ fish plates, bends, tees, reducers, elbows, covers and electro-galvanized
hardware etc, erected on existing support as per specification and instruction of Engineer-in-
150(W) x 75(H) x 2.0 mm Thick
---------do as above --------for 300(W) x 75(H) x 2.0 mm Thick 1.00 Lot 97,000.00 Ninety
GWIL Page 80 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-6 Electrical & Instrumentation Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
---------do as above --------for 450(W) x 75(H) x 2.0 mm Thick 1.00 Lot 43,900.00
---------do as above --------for 600(W) x 75(H) x 2.0 mm Thick 1.00 Lot 1,48,500.00 Thousand
40 Supply & laying GI perforated type cable trays with returned edge / flange, fabricated from
mm thk sheet steel in the standard length of 2.5 mtrs, duly hot dipped galvanized after fabrication
as per IS 2629-1989 / IS 4759-1984 including accessories such as coupler plates/ fish plates,
1.00 Lot 1,14,000.00 Fourteen
bends, tees, reducers, elbows, covers and electro-galvanized hardware etc, erected on existing
support as per specification and instruction of Engineer-in-charge.
100(W) x 35(H) x 2.0 mm Thick
---------do as above --------for 300(W) x 35(H) x 2.0 mm Thick 1.00 Lot 2,48,500.00 Thousand
41 Providing, erecting, and fabricating the M.S. structure for mounting of Cable Trays of
Electrical room, Pumphouse, etc.as per site requirements, incorporating proper sizes of M.S.
angles, squares, rounds, flats, bars, channels,Square Pipes and sections. The work shall include
cutting, welding, grinding, and finishing, duly painted with one coat of red oxide primer. Erection
on site shall be carried out as per the directions of the Engineer-in-Charge, along with necessary
1.00 Lot 3,26,250.00 Thousand
grouting, cementing, plastering, and finishing, all complete. Min. 5 ton or as per detailed
engineering whichever is higher
The item descriptions provided in the BOQ indicate the minimum requirement only. The
specifications and details mentioned in the tender datasheet and technical specifications shall
also be strictly followed to complete the work in all respect.
42 Power/ Welding Receptacle: (Two for Transformer Area, Two for Pump Room) Rupees
P & F of Industrial plug and socket conforming to IEC 60309-1/2 made out of self extinguishing Three
engineering polymer / polyamide, nickel plated brass sleeve and pins, socket with shutter Thousand
including making connection etc as reqd. IP -67 Surface/Wall mounted socket 63 A 5 Nine
GWIL Page 81 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-6 Electrical & Instrumentation Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
pin(3P+N+E) Hundred
43 Fire & Safety Equipments:Design, supply, erection, testing and commissioning of safety
accessories for all electrical equipment/ system as per tender specifications.(a) Providing printed
instruction chart both in English and Gujarati duly framed with front glasses for treatment of
person suffering from electric shock.- Min.2 Nos.(b) Providing of pair of rubber hand gloves for
working on 12 kV supply.- Min.10 Pair(c) Supplying and erecting dielectric flooring meeting
requirement of class B as per IS 15652:2006 for all HV & LV switchgear in Common HT Panel
Room, Electrical Control Room, SCADA Control Room(d) Supplying stand First Aid Box with
antiseptic cream, medicine for use on wounds due burn, crepe bandage ,gauge bandage
,medicated ready to use bandage adhesuve tape for medicinal user , Scissors, anti-septic
solution tec-( All above contents shall be of the standard makes ).-Min.5 Nos.(e) Supplying &
erecting FIRE bucket round bottom of 9 lit. capacity made out of 24 gauge GI sheet with extra
handle at bottom duly painted white inside & red out side with fire mark filled with dry sand &
kept on exsisting stand provided or hund on wall hook.-Min.8 Nos.(f) Suppying & erecting floor
1.00 Lot 4,89,478.21 Hundred
mounting stand for keeping 4 nos of fire buckets comprising 1500 mm in length & 900 mm height
made out of 30mmX30mmX4mm angle iron with cross supports for lags welded with 4 hooks &
duly painted with one coat of red lead & two coats of approved enammeled silver paint.-Min.2
Nos.(g) Supplying & erecting 4.5 kg capacity carbon dioxide (CO2) fire extinguisher with
necessary clamps made from 50 x 6 mm M.S. Flat with nut & bolts grouted in wall complete.-
Min.16 Nos.(h) Supply & Erection metallic vertified danger notice board for medium voltage
installation to be erected as per IS-Min.4 Nos.(i) Safety Shoes-lot(j) Safety Helmet-lot(k)Supply
of 66kV rated discharge rod (earth discharge rod) complete with insulated telescopic fiberglass
body, brass hook, flexible copper earthing cable, and clamp, suitable for safe discharge of
residual voltage from 66kV equipment. The rod shall be rated for 72.5kV system voltage, with
minimum 100kV AC withstand capacity for 1 minute. It shall be provided with a weatherproof
carrying case and comply with IS:5561 / IS:2071 / IEC:60855-1. Cable size shall not be less than
16 sq.mm copper, and total length of rod (fully extended) shall not be less than 3 meters.
45 Pressure Gauge
Design, Supply, Installation, Testing, Commissioning of Bourdon Type Glycerin Filled 0-20 kg /
cm2 - 150 mm dia., Pressure Gauge as , ±1% accuracy, Direct bottom 1/2"NPT (M) process
connection, IP 67, Glycerin filled, SS304 Case with Bayonet Type Bezel, SS316 L Bourdon
Tube, SS316 Movement material, Aluminum dial with black graduation on white background,
Micro Zero adjustable pointer, neoprene gasket, Blow out disc, shatter proof glass, SS tag plate 10 Nos. 2,624.00
etc as per IS 3624 and as per the direction of engineer incharge .
(on each pump delivery pipe - 8Nos. & on header pipe line-1Nos., For Dredging Pump -1Nos.)
Range 0-20 kg/cm2
Gauge cock for pressure gauge:
3way gauge cock, 1/2"NPT (F) X1/2" NPT(M) process conection complete to match pressure
GWIL Page 82 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-6 Electrical & Instrumentation Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
Pulsation Dampner/ Snubber for pressure gauge
Suitable to with stand upto 300kg/cm2,Viton gasket ,1/2"NPT (F) X1/2" NPT(M) process
conection complete to match pressure gauge
46 Insertion Type Ultrasonic Flow Meter:
Design, Supply, Installation, Testing, Commissioning of Two Path Insertion Ultrasonic flow meter
working on transit time principle,with factory calibrated and site verification, Regular Power
Operated, Flow sensor, Indicator, transmitter and totaliser with all accessories viz. surge
arrestor, associated cables, cabinets, hardwares, etc complete as per following specifications:
Flow meter / Sensor: 4 nos insertion ultrasonic type sensor (2pair) with ball valve for online
removal of sensors/ any other intersection/ retraction assembly, PN 16 pressure rating, SS
sensor MOC, IP 68 Protection.
Flow Transmitter/ Converter (Remote Field Mounted):
Microprocessor based, Modular design, 2 line LCD for indication of actual flow rate, forward,
reverse, sum totaliser display, ±1 %accuracy at 0.3 to 4 m/sec velocity, 4 to 20 mA with Rupees
HART/Modbus output, one scalable pulse output, IP 65/67 protection, Die cast aluminium/ Eight Lac
polycarbonate/ SS316 with Anticorrosive Paint/ PU finish with glass window enclosure, Inbuilt Eighty Six
EEPROM and Data Logger, 20 meters cable length or as per site requirement forsensor to 1 Nos. 8,86,500.00 Thousand
transmitter communication etc along with wall mounted/stand mounted cabinet. Five
Worldwide transmission of measured data (Every Fifteen Minutes) and events via e‐mail and Hundred
SMS by integrated GSM/GPRS modem, reliable data storage facility through integrated SD card only
etc. The Flowmeter must conatin two no of Analog Input signal for transmission of signals. One
signal will be sent to GSM transmitter and one signal will be sent to PLC of NC-28
GSM/GPRS based trans receiver unit to be provided to send signals to centralized monitoring
system. Flow meter shall send signals to transmitter unit through digital output only.
The contractor shall ensure full bore of the flow meter on site for accurate reading & make
required arrangement for the same without any extra cost..
The RTU panel must contain Terminal blocks for terminations of ineranl and external cables
Power supply SMPS for 24V Dc cobersion, HART to Modubus convertor, RTU modem with Sim
card facility with Antenna.
Two path (4 Nos Insertion sensor)
47 SITC of Non Contact Type Ultrasonic Level Transmitter:
Ultrasonic Type Level Transmitter with Remote Display :
Design, Supply, Installation, Testing and Commissioning of Non Contact Ultrasonic Type Level
Transmitter with Remote Display.
Sensor: The sensor should be non contact type, field mounting type, housing shall have
minimum IP65 protection, PP/ PVC Sensor MOC, with sensor to transmitter cable.
2 Nos. 59,723.00 Seven
Remote Indicator cum Transmitter: Microprocessor based indicator with LED / LCD digital
display,panel/ wall mounting type, power supply shall be 110-240 Vac or 15 to 36 Vdc, 50 Hz ±
Accesories: Mounting bracket, nut, bolts etc as per system requirement and Hook up diagram of
the Instruments.
Level Transmitter shall be suitable for following Range. 0 to 10 Meter
GWIL Page 83 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-6 Electrical & Instrumentation Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
One no for Old Sump of SSP-3A and One for New Sump of SSP-3A
48 Float & Board Type Level Indicator Rupees
Design, Supply, Installation, Testing and Commissioning of Float & Board Type Level Indicator, Seventeen
guided construction, Full Range Travel, FRP/ SS316 MOC of Float and Guide Wire Rope, Thousand
minimum 6” wide x aluminum powder coating with black graduations and numerical on calibrated 2 Nos. 17,718.00 Seven
gauge board, Red color pointer, protection conduit, Elbow pulley, Tensioner, Anchor, Rope Hundred
Fastner, Gauge Brackets, Counter Weight for rope type probe, spacer between the probes, etc Eighteen
complete with calibration of following sizes. Size: 0 to 10 Meter only
49 SITC of Float/Displacer Type Level Switch:
Design, Supply, Installation, Testing and Commissioning of Top mounted Displacer Type level Rupees
switches with 2 nos SPDTcontacts of Micro switch rated 5 A, potential free power supply, Twelve
Material of wetted parts shall be SS 316 and the material of accessories shall be SS. IP 65 or Thousand
equivalent degree of protection for enclosure, suitable for sump, ESR, tank, vessels and Eight
underground reservoirs. The top mounted level switches shall be supplied with still tubes to suit Hundred
the requirement. Accessories like name plate, mating flange, gaskets, fasteners, bolts & nuts, Two only
etc. shall be supplied with the Level Switch of following Range. 0 to 10 Meter
50 SITC of Pressure Transmitters:
Design, Supply, Installation, Testing and Commissioning of Sealed Diaphragm Type Pressure
Transmitter. Piezo-resistive sensor technolgy based pressure transmitter with Micro-processor Rupees
based integral LED/ LCD display, with accuracy of ± 0.3% of span, external zero and span Twenty Nine
adjustment, self diagnostics, temperature sensor for compensation. 15 to 36 V DC power supply, Thousand
output signal of 4-20 mA DC with HART. Minimum IP 65 degree of protection. Aluminium 10 Nos. 29,147.00 One
housing with epoxy coating, Accessories like snubbers for pump discharge applications, three Hundred
way manifold, mounting brackets, name plate etc. Material for accessories shall be SS. Forty Seven
Protection Box/Canopy shall be provided for outside installed transmitters. Pressure Transmitter only
shall be suitable for following Range.
SITC of Temperature Scanner (1 no for each pump motor)
Microprocessor based, 16 channel , input power supply 230 V AC, accuracy +/-0.1% of full scale,
resolution 0.1°C, backlit LED/LCD four digit display, non volatile memory, key board for alarm & 9 Nos. 24,750.00
password setting etc., non corrosive MOC, IP 54, communication port RS 232/485, relay outputs,
metal plate tag and all other hardware.
52 Programmable Logic Controller (PLC) with HMI & PC Based SCADA system :
Design, Manufacture, Supply, Installation, Testing and Commissioning of Indoor type PLC Panel
of size approx. 1000 mm X 600 mm X 2000mm (LBH) , abricated out of minimum 2 mm thick Rupees
CRCA sheet steel. wall/ floor mounted Panel having cable entry / exit through removeable gland Fifty Two
plate preferably at the bottom, IP-54 degree of rotection for enclosure, Separate terminal blocks 1 set 52,05,000.00 Lac Five
(screwed type) shall be used for analog and digital signal and also for signals with different Thousand
voltages. Panel shall have single lockable door with gasket.PLC panel shall have 100% only
Redundunt Programmable Logic Controller (PLC) with following specifications PLC system (with
Analog Input/Output cards, Digital Input/Output cards, communication cards, RS
GWIL Page 84 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-6 Electrical & Instrumentation Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
communication Ports, ethernet communication ports, MOD Bus compatibility, Aux supply 24 V
DC, Real Time Clock, operating temperature range 0 to 55° C, Detachable EPROM/SD CARD
for Programme backup, support various protocol standards such as Modbus, IEC 60870/ DNP3,
Redundant SMPS of 230V AC Input-24VDC out put, distribution boards, set of control relay,
MCB of suitable rating, suitable no. of LED indicator Lamps, Selector Switches, push Buttons /
illuminited Push Buttons, 0.5 sqmm multistanderd Internal wiring with ferruling complete as per
technical specifications and approved system architecture, necessary programming software for
PLC & SCADA and comprising of all accessories not limited to the following:- Programmable
Logic Controller (PLC) with Dual Hot Redundant CPU, Power supply, Communication Module,
Hot Swappable Input,Output Modules & Processor rack (Standard DC), Back up
Interface/Expansion Module, Rack (Backplane) 10 slots for IO and Processor. SCADA software
shall have facility VPN, OPC, Smart Client, Web Enabled, Automation Report Generation,
Archiving, Treands, Data Logging,
a) The PLC System peripherals shall consist of the following
MCB,SMPS 240VAC/ 24 VDC, Control Relays, Annunciator with 24 Windows NO to NC Type
Microprocessor Based, Window Size 75*42mm, 110VAC, with Electronic Hooter, Panel Cooling
Fan & Filter,Panel Light with Door Switch, Control Indication Lamp for 24VDC, 220VAC,Push
Button, Power Wiring, Control Wiring, Control TB/ Fuse 2A,TB etc., Panel Hardware, lugs,
terminations, ferruls, name plate etc.UTILITY SOCKET, HMI Display 15 Inch, Colour, Isolators
Dual Output, 24VDC, Ethernet Switch ( Managed)
b)One No. Operator Station including, Core i5 processor, 8 GB RAM, 1TB SSD, DVD RW Drive,
RS-232/485/RJ45 Port, 1 Parallel Port, 4 nos. USB Port, 2x Ethernet Cards, Keyboard, Optical
mouse, 32'' LED monitor, Latest windows professional, Anti Virus, etc.
c) One No. Engineering Station including, Core i7 processor, 8 GB RAM, 1TB SSD, DVD RW
Drive, RS-232/485/RJ45 Port, 1 Parallel Port, 4 nos. USB Port, 2x Ethernet Cards, Keyboard,
Optical mouse, 32'' LED monitor, Latest windows professional, Anti Virus, etc. d) Licensed
version software: PLC software and HMI software development & Run Time & Development
Programming and Troubleshooting software for PLC, HMI, SCADA, VPN, Web Client - OWS
e) A4 size black & white printer, minimum 250 paper input capacity, 1 port USB compatible with
USB 2.0 specification with Ethernet 10/100 base, Separate power ON/OFF switch with required
all accessories for complete the system.
f) Industrial UPS 3 KVA with one hour backup (SMF Ni-Cd batteries), 230 V AC O/P, and any
other items required to complete the system and as per detailed tender specification. g) SITC of
Process Indicator (for Pressure, Flow, Level Transmitter, Temperature,Transformer OTI and WTI
All data from PPMS as per tender specifications) Web Based Pump Performance Monitoring
System Required Following Parameters Shall be Measured Pump Efficiency - % Flow Rate –
m3/hr Discharge Pressure – Kg/cm2 Inlet Pressure – Kg/cm2 Sump Level – m Overall Eff - %
Cumulative Flow – m3/hr Drive Power – kW Phase Voltage – V Phase Currents – Amp Power
Factor Frequency – Hz
h)Microprocessor based Digital Indicator, Input Supply 230 VAC, Input Signal 4 to 20 mA, Digital
Display of Flow, Level and Pressure, Relay Contact output, RS485 port / computer interface port
and as per detailed tender specification
i)SITC of Surge Protection Device(for Pressure, Flow, Level Transmitter, Temperature, All data
GWIL Page 85 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-6 Electrical & Instrumentation Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
from PPMS as per tender specifications)
j) Microprocessor based Digital Indicator, Input Supply 230 VAC, Input Signal 4 to 20 mA, Digital
Display of Flow, Level and Pressure, Relay Contact output, RS485 port / computer interface port
and as per detailed tender specification.
The item descriptions provided in the BOQ indicate the minimum requirement only. The
specifications and details mentioned in the tender datasheet and technical specifications shall
also be strictly followed to complete the work in all respect.
53 Supply, Installation, Testing and Comissioning of Inverter type Air Cooled Hi Wall split type
Air conditioners with latest star rating system as per BEE amended upto date complete with
Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with
insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU),
copper power cable upto 3.5 Mtr (IDU to ODU), R-32/R-410 Green Refrigerant, wireless Remote
control, suitable for working between 230V +/- 10% with low & high voltage cutoff and 50 hz , 2 Nos. 55,359.32
single phase AC supply capable of performing cooling, dehumidification, air circulation of
following capacity with Scroll / rotary compressor. All as per pre approved by Engineer in-charge.
For additional technical parameters of products/ work , refer Annexure "A" attached with this
54 Junction Box: (MOV to PLC)(Minimum 60 Terminal Block)
Gasket: Neoprene Rubber Rupees
Machine Screw with washer: SS304 Nineteen
Earthing Stud with washer &Nut Thousand
Inscription plate only
Terminal Block(Clip on Type)
Shield bus bas, Removable Gland Plate
Instrumentation Power/ Control/ Signal/ Networking & Communication Cables including Twenty
Cable Glands and Lugs: Three Lac
Designing, Supplying, Installing, commissioning & testing with Terminating & Interfacing of Five
1.1Kvgrade, Non Compact circular copper conductor, XLPE insulated cores laid up , with PVC Thousand
inner sheated, Armoured, FR-LSH PVC Outer sheath cables.24CX1.5 Sq mm(Non Shielded Eight
Armoured FRLS) For Digital Input Signal from Electrical Feeders Hundred
Designing, Supplying, Installing, commissioning & testing with Terminating & Interfacing of
1.1Kvgrade, Non Compact circular copper conductor, XLPE insulated cores laid up , with PVC
55.1 1 Lot 13,96,800.00 Thousand
inner sheated, Armoured, FR-LSH PVC Outer sheath cables.16CX1.5 Sq mm(Non Shielded
55.2 1 Lot 5,47,200.00 Rupees
GWIL Page 86 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-6 Electrical & Instrumentation Works [For SPP-3A Works]
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
Designing, Supplying, Installing, commissioning & testing with Terminating & Interfacing of Five Lac
1.1Kvgrade, Non Compact circular copper conductor, XLPE insulated cores laid up , with PVC Forty Seven
inner sheated, Armoured, FR-LSH PVC Outer sheath cables.8CX1.5 Sq mm(Non Shielded Thousand
Armoured FRLS) FOR Digital Output Signal from Electrical feeders Two
Designing, Supplying, Installing, commissioning & testing with Terminating & Interfacing of Thirteen
55.3 1.1Kvgrade, Non Compact circular copper conductor, XLPE insulated cores laid up , with PVC 1 Lot 8,13,500.00 Thousand
inner sheated, Armoured, FR-LSH PVC Outer sheath cables.30C X1.5 Sq mm(Non Shielded Five
Armoured FRLS) Hundred
Signal cables 500V Standard Annealed Bare copper conductor , Extruded XLPEinsulated , two
core twisted to form a pair, Pair laid up, Individual pair shielded and overall shielded with
almunium malyar tape along with allelead tin copper drain 2PX1.5sqmm(twisted pair Shielded
500V Standard Annealed Bare copper conductor , Extruded XLPEinsulated , two core twisted to
form a pair, Pair laid up, Individual pair shielded and overall shielded with almunium malyar tape 1 Lot 35,53,000.00
along with allelead tin copper drain 24 PX1.5sqmm(twisted pair Shielded ,Armour FRLS)
Cable for Comminication for soft communication: RS485 2CX1.5 Sq mm(Shielded) 1 Lot 27,500.00 Thousand
58 Supply, installation, Testing and Commissioning of Pump performance monitoring with
required accessories for each pump at pumping station and deploy a web based pump
performance monitoring and mobile application along with providing access to department
officials through login credential for monitoring of each pump and the entire pumping station alike Rupees
Required 9 Nos. 3,00,000.00 Three Lac
Following Parameters Shall be Measured Pump Efficiency - % Flow Rate – m3/hr Discharge only
Pressure – Kg/cm2 Inlet Pressure – Kg/cm2 Sump Level – m Overall Eff - % Cumulative Flow –
m3/hr Drive Power – kW Phase Voltage – V Phase Currents – Amp Power Factor Frequency –
Total (Electrical and Instrumentation Works)
GWIL Page 87 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-7: SITC of New valves, Modification Work of existing valves & valve chambers at Navda PS
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
Demolition including stacking of serviceable materilas and disposal of unserviceable materials Rupees One
with all lead and lift. Thousand
1 (i) R.C.C. work Wall 99.65 Cum 1,082.35 Eighty Two &
(ii) R.C.C. work bottom slab Rupees One
2 24.08 Cum 1,082.35 Eighty Two &
Brick masonry work for raised height of Valve chamber Rupees Four
Brick work using common burnt clay building bricks having crushing strength not less than 35 Thousand
kg./Sq.Cm. in foundation and plinth in Cement Mortar 1:5. (1- Cement : 5 -fine sand)(B) Two Hundred
Conventional Forty Five &
Plaster for Valve Chamber Rupees Two
4 Cement plaster 20 mm thick in C.M. 1:2 using water proofing compound of approved quality 275.86 Sqm 202.00 Hundred Two
including finishing etc. complete. only
Painting for Valve Chamber Rupees One
Wall painting (Two coats) with plastic emulsion paint of approved brand and manufacture on Hundred
5 undercoated wll surface to give an even shade including throughly brushing the surface free from 137.94 sqm 120.26 Twenty &
mortar droppings and other foreign matter and sand papered smooth. Paise Twenty
Providing and cast in situ C.C. in grade M-25 proportions of ingredients as per mix design by
weigh batching using granite, quartzite trap metal of size 12 mm to 20 mm and or 6 mm to 12 mm
6 including scaffolding centering formwork, needle vibrated consolidation, curing and hydraulic 3.15 cum 8,077.00
testing etc. complete (excluding cost of reinforcement) with centering and shuttering/deshuttering
etc. comp. up to 6 meter height /depth Av. G.L.for all water retaining structures
Supplying cutting, bending, binding and placing in position steel as per plan and design and as Rupees
per ISS 2502 including cost of steel and binding wire for reservoirs/structures only including lift up Seventy Eight
to 6 meter height or depth below G.L. for all diameters Do-CRS steel all diameter Fe 500grade & Paise Fifty
confirming to relevant I.S. Eight only
Construction of RCC valve chambers of different sizes for different valve. The rates shall include Rupees
construction of RCC valve chamber in M 25 concrete. Excavation, Dewatering, foundation Seven Lac
concrete(PCC) in CC M-10 (approx. corresp. to prop. 1:3:6), pedestal and vertical wall in CC M25, Forty Three
CRS steel all diameter FE 500 grade confirming to relevant IS, top cover of minimum 7 mm thick Thousand
M.S. Chequered plate including necessary supporting arrangement with nuts, bolts, locking One Hundred
arrangement. Including form work, painting, C.I Step etc. Complete as per datasheet, & Fifty Seven &
specification and instruction of Engineer-In-Charge/Consultant Paise Ninety
GWIL Page 88 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-7: SITC of New valves, Modification Work of existing valves & valve chambers at Navda PS
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
Dismentaling of exising valves & SITC of PN 1.6 Double Flanged Modulating Type Electrically
Operated Butterfly valves with electric actuator having integral starter generally conforming to
IS:13095 having body & disc in graded Cast Steel of ASTM A216 Gr. WCB, shaft & thurst pad of
stainless steel AISI 410, body seat ring, clamping ring, disc pin, internal hardware of SS AISI
and disc seal ring of EPDM. Valve seat tested to 16 kg/ cm2 and body to 24 kg/ cm2, Flanges
machined faced and having Dimensions- PCD, OD, Thickness, Holes as per ISO-7005-1.
Hydraulic tests certificate & certificate of material of construction of parts shall be submitted before
despatch of valves as per design with companion flages, all accessories, hardware, bolts, nuts,
9 1.00 Job 6,83,479.00 Thousand
washers, rubber gasket, necessary mounting supports etc. For the erection of a new valve and
dismantling of the existing valve, the necessary isolation activities shall be carried out by providing
blinds, along with all required materials, tools and tackles, labour, etc., as per the instructions of
the Engineer-in-Charge. The job shall be executed as per the defined specifications.
The motorized actuator shall be mounted on top of the chamber, incorporating the extended SS
shaft and precision-aligned mounting bracket supported on a suitable rigid MS structural section
including all required material etc complete as per detailed specifications.
(A) ----Size: 900 NB, PN-1.6, Location: VBC-1 To SPP-4 CC
(B) ----do as above----Size: 1200 NB, PN-1.6, Location: SPP-2 to SPP-3 Rupees Ten
(C) ----do as above----Size: 1200 NB, PN-1.6, Location: SPP-2 to SPP-4 Rupees Ten
(D)----do as above----Size: 1500 NB, PN-1.6, Location: NC-26-27 Inlet at CC Rupees
(E)----do as above---Size: 1500 NB, PN-1.6, Location: VBC-1 Rupees
GWIL Page 89 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-7: SITC of New valves, Modification Work of existing valves & valve chambers at Navda PS
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
(F)----do as above---Size: 1800 NB, PN-1.6, Location: NC-28 Sump Inlet Rupees
(G)----do as above---Size: 1800 NB, PN-1.6, Location: SPP-3A Sump Inlet Rupees
Supply, installation, testing & commissioning of PN 1.6 flange ends Expansion Bellow as
per EJMA standards of overall length of minimum 300 mm, with companion flanges, accessories
erection hardware, necessary mounting supports etc. designed for 15 mm axial compression and
5 mm axial extension with tie rods etc. of following MOC & pressure ratings.MOC: Bellows: SA
10 1.00 No. 57,216.00 Thousand
240 Gr. 304; Internal Sleeve: SA 240 Gr. 304; Weldends: IS 2062 Gr. B; Flanges: IS 2062 Gr. B,
Flanges machined faced and having Dimensions- PCD, OD, Thickness, Holes as per ISO-7005-1
& Limit Rods & Nuts: CS - IS 1367. 900 mm dia. PN 1.6, Overall length of minimum 300 mm,
Location: VBC-1 To SPP-4 CC
Supply, installation, testing & commissioning of PN 1.6 flange ends Expansion Bellow as
per EJMA standards of overall length of minimum 350 mm, with companion flanges, accessories Rupees One
erection hardware, necessary mounting supports etc. designed for 15 mm axial compression and Lac Eighteen
5 mm axial extension with tie rods etc. of following MOC & pressure ratings.MOC: Bellows: SA Thousand
240 Gr. 304; Internal Sleeve: SA 240 Gr. 304; Weldends: IS 2062 Gr. B; Flanges: IS 2062 Gr. B, One Hundred
Flanges machined faced and having Dimensions- PCD, OD, Thickness, Holes as per ISO-7005-1 Seventy Six
& Limit Rods & Nuts: CS - IS 1367. only
1200 mm dia. PN 1.6, Overall length of minimum 350 mm, Location: SPP-2 to SPP-3
Supply, installation, testing & commissioning of PN 1.6 flange ends Expansion Bellow as
per EJMA standards of overall length of minimum 350 mm, with companion flanges, accessories Rupees One
erection hardware, necessary mounting supports etc. designed for 15 mm axial compression and Lac Eighteen
5 mm axial extension with tie rods etc. of following MOC & pressure ratings.MOC: Bellows: SA Thousand
240 Gr. 304; Internal Sleeve: SA 240 Gr. 304; Weldends: IS 2062 Gr. B; Flanges: IS 2062 Gr. B, One Hundred
Flanges machined faced and having Dimensions- PCD, OD, Thickness, Holes as per ISO-7005-1 Seventy Six
& Limit Rods & Nuts: CS - IS 1367. only
1200 mm dia. PN 1.6, Overall length of minimum 350 mm, Location: SPP-2 to SPP-4
GWIL Page 90 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-7: SITC of New valves, Modification Work of existing valves & valve chambers at Navda PS
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
Supply, installation, testing & commissioning of PN 1.6 flange ends Expansion Bellow as
per EJMA standards of overall length of minimum 350 mm, with companion flanges, accessories Rupees One
erection hardware, necessary mounting supports etc. designed for 15 mm axial compression and Lac Forty
5 mm axial extension with tie rods etc. of following MOC & pressure ratings.MOC: Bellows: SA Three
240 Gr. 304; Internal Sleeve: SA 240 Gr. 304; Weldends: IS 2062 Gr. B; Flanges: IS 2062 Gr. B, Thousand
Flanges machined faced and having Dimensions- PCD, OD, Thickness, Holes as per ISO-7005-1 Two Hundred
& Limit Rods & Nuts: CS - IS 1367. Fifty Six only
1500 mm dia. PN 1.6, Overall length of minimum 350 mm, Location: NC-26-27 Inlet at CC
Supply, installation, testing & commissioning of PN 1.6 flange ends Expansion Bellow as
per EJMA standards of overall length of minimum 350 mm, with companion flanges, accessories
erection hardware, necessary mounting supports etc. designed for 15 mm axial compression and
5 mm axial extension with tie rods etc. of following MOC & pressure ratings.MOC: Bellows: SA
14 240 Gr. 304; Internal Sleeve: SA 240 Gr. 304; Weldends: IS 2062 Gr. B; Flanges: IS 2062 Gr. B, 1.00 No. 1,43,256.00
Flanges machined faced and having Dimensions- PCD, OD, Thickness, Holes as per ISO-7005-1
& Limit Rods & Nuts: CS - IS
1500 mm dia. PN 1.6, Overall length of minimum 350 mm, Location: Location: VBC-1
Supply, installation, testing & commissioning of PN 1.6 flange ends Expansion Bellow as
per EJMA standards of overall length of minimum 350 mm, with companion flanges, accessories
erection hardware, necessary mounting supports etc. designed for 15 mm axial compression and Rupees One
5 mm axial extension with tie rods etc. of following MOC & pressure ratings.MOC: Bellows: SA Lac Sixty Five
240 Gr. 304; Internal Sleeve: SA 240 Gr. 304; Weldends: IS 2062 Gr. B; Flanges: IS 2062 Gr. B, Thousand Six
Flanges machined faced and having Dimensions- PCD, OD, Thickness, Holes as per ISO-7005-1 Hundred
& Limit Rods & Nuts: CS - IS 1367. Thirty Two
1800 mm dia. PN 1.6, Overall length of minimum 350 mm, Location: Location: NC-28 Sump
Supply, installation, testing & commissioning of PN 1.6 flange ends Expansion Bellow as
per EJMA standards of overall length of minimum 350 mm, with companion flanges, accessories
erection hardware, necessary mounting supports etc. designed for 15 mm axial compression and Rupees One
5 mm axial extension with tie rods etc. of following MOC & pressure ratings.MOC: Bellows: SA Lac Sixty Five
240 Gr. 304; Internal Sleeve: SA 240 Gr. 304; Weldends: IS 2062 Gr. B; Flanges: IS 2062 Gr. B, Thousand Six
Flanges machined faced and having Dimensions- PCD, OD, Thickness, Holes as per ISO-7005-1 Hundred
& Limit Rods & Nuts: CS - IS 1367. Thirty Two
1800 mm dia. PN 1.6, Overall length of minimum 350 mm, Location: Location: SPP-3A
SITC of following type of Flanged Type Fabricated MS Specials flanges, blank flange,
dismentling joint, bolts, nuts, washers, rubber packing, suction strainer etc, for suction, delivery, Rupees
17 header, bypass pipelines and suitable for above pumpsets. 11500.00 Kg. 98.00 Ninety Eight
Flanges machined faced and having Dimensions - PCD, OD, Thickness, Holes as per ISO 7005-1 only
(PN 20). All specials & pipes should be painted by epoxy paint. The item also includes job
GWIL Page 91 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-7: SITC of New valves, Modification Work of existing valves & valve chambers at Navda PS
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
connection work for connection of MS header pipeline to MS rising main pipeline.
1) Up to 300 mm dia.
2) Above 300 mm dia.
Supply, installation, testing, and commissioning of required components for the modification of
existing manually operated butterfly and sluice valves to convert them into motorized actuated
valves. The scope includes inspection and overhauling of existing valves, removal of manual
operating components, replacement or modification of gearboxes, and supply and installation of
electric actuators with integral starter & motors of adequate torque and IP-rated protection, along
with fitment of coupling arrangements, extended SS shafts, and precision-aligned mounting
brackets, suitable rigid MS structural section for mounting of actuator on the top of the chamber
with top cover of minimum 7 mm thick M.S. Chequered plate including necessary supporting
arrangement (For rigidly mounting of chequered plate on four side of chamber) with nuts, bolts,
locking arrangement. Including form work, painting etc. It also covers fabrication and installation of
necessary structural supports, supply of all required accessories, hardware, and fasteners,
execution of electrical works including cabling, termination, and integration with the control panel
for remote & local operation through LPBS with protective covers, and complete testing, Rupees Two
commissioning, and functional demonstration of the motorized valve system. All works shall be Lac Fifty Two
18 carried out in accordance with approved technical specifications, actual site conditions, and 1.00 Job 2,52,500.00 Thousand
relevant standards, including provision of all materials, labor, tools, and incidental works to deliver Five Hundred
a fully operational system. Execute the job as per the defined specification. only
(A) --- Valve Type: Butterfly Valve, 1100 NB, PN-1.6, Location: SPP-3 Voltas to SPP-3
(B) --- do as above----Valve Type: Butterfly Valve, 1200 NB, PN-1.6, Location: SPP-4 Header Rupees Two
18.01 1.00 Job 2,52,500.00 Thousand
(C) --- do as above--- Valve Type: Butterfly Valve, 1200 NB, PN-2.5, Location: SPP-3 Header Rupees Two
18.02 1.00 Job 2,52,500.00 Thousand
GWIL Page 92 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-7: SITC of New valves, Modification Work of existing valves & valve chambers at Navda PS
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
(D) --- do as above--- Valve Type: Butterfly Valve, 1200 NB, PN-2.5, Location: SPP-3 Voltas Rupees Two
Header Lac Fifty Two
18.03 1.00 Job 2,52,500.00 Thousand
(F) --- do as above---Valve Type: Butterfly Valve, 1500 NB, PN-1.6, Location: NC-27 to SPP-2 Rupees
(G) --- do as above---Valve Type: Butterfly Valve, 1500 NB, PN-1.6, Location: NC-27 to SPP-2 Rupees
& NC-39 Three Lac
(H) --- do as above---Valve Type: Butterfly Valve, 1500 NB, PN-1.6, Location: VBC-2 Rupees
(I) --- do as above--- Valve Type: Butterfly Valve, 1500 NB, PN-1.6, Location: SPP-3 Voltas to Rupees
SPP-3 Three Lac
(M) --- do as above---Valve Type: Sluice Valve, 1600 NB, PN-1.6, Location: SPP-3 Main Rupees
Header Three Lac
(N) --- do as above--- Valve Type: Sluice Valve, 1600 NB, PN-1.6, Location: SPP-4 Main Rupees
Header Three Lac
18.10 (J) --- do as above---Valve Type: Butterfly Valve, 1800 NB, PN-1.6, Location: CC to SPP-2 1.00 Job 3,51,500.00 Rupees
GWIL Page 93 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-7: SITC of New valves, Modification Work of existing valves & valve chambers at Navda PS
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
(L) --- do as above---Valve Type:Sluice Valve, 1800 NB, PN-1.6, Location: SPP-3B Sump Rupees Four
Inlet Lac Twelve
(K) --- do as above--- Valve Type: Butterfly Valve, 1900 NB, PN-2.0, Location: NC-39 Inlet Rupees Four
from NC-27 Lac Eighteen
(M) --- do as above--- Valve Type: Butterfly Valve, 1900 NB, PN-1.6, Location: SPP-2 Inlet at
Note: With valve installation (Lowering & Laying)
(O) --- do as above--- Valve Type: Butterfly Valve, 2400 NB, PN-1.6, Location: NC-43 to Rupees Four
Collection Chamber Lac Ninety
18.14 1.00 Job 4,92,184.00 Thousand
(P) --- do as above--- Valve Type: Butterfly Valve, 2400 NB, PN-1.6, Location: NC-43 to NC- Rupees Four
18.15 1.00 Job 4,92,184.00 Thousand
Supply, Installation, Testing and Commissioning of weather proof, dust & vermin proof, floor
mounted front operated outdoor type double door cubical panel board necessary IP-54 with
Canopy and above protection as per approval from engineer incharge made from 14 SWG thick
CRC M.S. sheet for outer body & doors, 16 SWG thick CRC M.S. sheet for internal partitions with
19 1.00 No 27,970.76 Nine Hundred
necessary accessories - supporting angles/flats channel including cutting, bending, drilling,
welding, riveting with internal partitions & cable alley as per requirements & instruction of
engineer-in-charge with erection of Supplied switch gears, BUSBARS, suitable size of inter
connecting PVC copper wire / copper-aluminium strips, rubber grommets, rib, bakelite control
GWIL Page 94 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-7: SITC of New valves, Modification Work of existing valves & valve chambers at Navda PS
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
fuses/MCB for measuring instruments, earth bus & earth bolts, foundation flange - bolts-base
Plates, sufficient nos. of hinged doors, handles with locking arrangement and rubber gasket,
heavy duty end terminal connection, danger board, necessary ventilation, earthing strip complete.
The Panel shall be painted with epoxy powder coating. (The rates excludes the cost of
switchgears, bus bars, inter connecting mains & Copper Aluminium strips, meters, Fuses etc. The
dimension shall be measured excluding base (legs) The panel shall be supplied with following
approved manufacturers with following size. (B) The Standard companies switchgear shall be
used and only manufacturers at CPRI approved factory (i) with 350mm depth., Providing and
Erecting 415VAC MCB three Pole for motor & inductive load (C curve) having 10KA breaking
capacity & confirms to IS: 8828 in exising box having following capacity 63Amp. Cat.III for
Incoming-1Nos. 32Amp for outgoing -6Nos., Supplying, wiring and interconnecting 3R, 1C,
2.5Sqmm copper conductor, flexible, PVC Insulated, FRLS industrial cables in exising junction
box from Incoming MCB to outgoing MCB with colour code as per respective phases (R, Y, B),
Supplying, wiring and interconnecting 4R, 1C, 4.0Sqmm copper conductor, flexible, PVC
Insulated, FRLS industrial cables in exising junction box from Incoming MCB to outgoing MCB
with colour code as per respective phases (R, Y, B), Cable Terminals (Lugs), Providing & fitting
crimping type Cable Terminals (Lugs) conforming to IS of following types and sizes 2.5Sqmm,
Providing and Fitting of Power Terminal connector block as per required current ratings., P & F in
position frame made out of M.S. angle (riveted or welded) finished with two coats of red oxide and
two coats enamel paint including cutting, welding, holes etc.of following sizes as required. 50mm x
(Junction Box -1 for Valve Actuator of
VBC -1 to SPP-4CC(900mm Dia. BFV ),
VBC-1, SPP-3 Voltas Header(1800mm Dia BFV),
SPP-2 Inlet at Navda(1900 mm Dia BFV)
NC-26,27 inlet at CC(1500 mm Dia BFV)
Supply, Installation, Testing and Commissioning of weather proof, dust & vermin proof, floor
mounted front operated outdoor type double door cubical panel board necessary IP-54 with
Canopy and above protection as per approval from engineer incharge made from 14 SWG thick
CRC M.S. sheet for outer body & doors, 16 SWG thick CRC M.S. sheet for internal partitions with
necessary accessories - supporting angles/flats channel including cutting, bending, drilling,
welding, riveting with internal partitions & cable alley as per requirements & instruction of Rupees
engineer-in-charge with erection of Supplied switch gears, BUSBARS, suitable size of inter Twenty Seven
connecting PVC copper wire / copper-aluminium strips, rubber grommets, rib, bakelite control Thousand
20 fuses/MCB for measuring instruments, earth bus & earth bolts, foundation flange - bolts-base 1.00 No 27,970.76 Nine Hundred
Plates, sufficient nos. of hinged doors, handles with locking arrangement and rubber gasket, Seventy &
heavy duty end terminal connection, danger board, necessary ventilation, earthing strip complete. Paise Seventy
The Panel shall be painted with epoxy powder coating. (The rates excludes the cost of Six only
switchgears, bus bars, inter connecting mains & Copper Aluminium strips, meters, Fuses etc. The
dimension shall be measured excluding base (legs) The panel shall be supplied with following
approved manufacturers with following size. (B) The Standard companies switchgear shall be
used and only manufacturers at CPRI approved factory (i) with 350mm depth., Providing and
Erecting 415VAC MCB three Pole for motor & inductive load (C curve) having 10KA breaking
GWIL Page 95 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-7: SITC of New valves, Modification Work of existing valves & valve chambers at Navda PS
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
capacity & confirms to IS: 8828 in exising box having following capacity 63Amp. Cat.III for
Incoming-1Nos. 32Amp for outgoing -4Nos., Supplying, wiring and interconnecting 3R, 1C,
2.5Sqmm copper conductor, flexible, PVC Insulated, FRLS industrial cables in exising junction
box from Incoming MCB to outgoing MCB with colour code as per respective phases (R, Y, B),
Supplying, wiring and interconnecting 4R, 1C, 4.0Sqmm copper conductor, flexible, PVC
Insulated, FRLS industrial cables in exising junction box from Incoming MCB to outgoing MCB
with colour code as per respective phases (R, Y, B), Cable Terminals (Lugs), Providing & fitting
crimping type Cable Terminals (Lugs) conforming to IS of following types and sizes 2.5Sqmm,
Providing and Fitting of Power Terminal connector block as per required current ratings., P & F in
position frame made out of M.S. angle (riveted or welded) finished with two coats of red oxide and
two coats enamel paint including cutting, welding, holes etc.of following sizes as required. 50mm x
Junction Box -2 for Valve Actuator of
SPP-2 to SPP-3 (1200mm Dia. BFV)
SPP-2 to SPP-4 (1200mm Dia. BFV),
SPP-3 Voltas to SPP-3 (1100mm Dia. BFV),
SPP-3 Voltas to SPP-3(1500mm Dia. BFV)
Supply, Installation, Testing and Commissioning of weather proof, dust & vermin proof, floor
mounted front operated outdoor type double door cubical panel board necessary IP-54 with
Canopy and above protection as per approval from engineer incharge made from 14 SWG thick
CRC M.S. sheet for outer body & doors, 16 SWG thick CRC M.S. sheet for internal partitions with
necessary accessories - supporting angles/flats channel including cutting, bending, drilling,
welding, riveting with internal partitions & cable alley as per requirements & instruction of
engineer-in-charge with erection of Supplied switch gears, BUSBARS, suitable size of inter
connecting PVC copper wire / copper-aluminium strips, rubber grommets, rib, bakelite control
fuses/MCB for measuring instruments, earth bus & earth bolts, foundation flange - bolts-base
Plates, sufficient nos. of hinged doors, handles with locking arrangement and rubber gasket,
heavy duty end terminal connection, danger board, necessary ventilation, earthing strip complete.
The Panel shall be painted with epoxy powder coating. (The rates excludes the cost of
switchgears, bus bars, inter connecting mains & Copper Aluminium strips, meters, Fuses etc. The
21 1 Each 21,560.32 Five Hundred
dimension shall be measured excluding base (legs) The panel shall be supplied with following
approved manufacturers with following size. (B) The Standard companies switchgear shall be
used and only manufacturers at CPRI approved factory (i) with 350mm depth., Providing and
Erecting 415VAC MCB three Pole for motor & inductive load (C curve) having 10KA breaking
capacity & confirms to IS: 8828 in exising box having following capacity 63Amp. Cat.III for
Incoming-1Nos. 32Amp for outgoing -4Nos., Supplying, wiring and interconnecting 3R, 1C,
2.5Sqmm copper conductor, flexible, PVC Insulated, FRLS industrial cables in exising junction
box from Incoming MCB to outgoing MCB with colour code as per respective phases (R, Y, B),
Supplying, wiring and interconnecting 4R, 1C, 4.0Sqmm copper conductor, flexible, PVC
Insulated, FRLS industrial cables in exising junction box from Incoming MCB to outgoing MCB
with colour code as per respective phases (R, Y, B), Cable Terminals (Lugs), Providing & fitting
crimping type Cable Terminals (Lugs) conforming to IS of following types and sizes 2.5Sqmm,
Providing and Fitting of Power Terminal connector block as per required current ratings., P & F in
GWIL Page 96 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-7: SITC of New valves, Modification Work of existing valves & valve chambers at Navda PS
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
position frame made out of M.S. angle (riveted or welded) finished with two coats of red oxide and
two coats enamel paint including cutting, welding, holes etc.of following sizes as required. 50mm x
50mm x 6mm Junction Box -3 for Valve Actuator of VBC-2 (1500mm Dia. BFV) , VBC-1
(1800mm Dia. BFV), Collecting Chamber to SPP-2 (1800mm Dia. BFV)
Supply, Installation, Testing and Commissioning of weather proof, dust & vermin proof, floor
mounted front operated outdoor type double door cubical panel board necessary IP-54 with
Canopy and above protection as per approval from engineer incharge made from 14 SWG thick
CRC M.S. sheet for outer body & doors, 16 SWG thick CRC M.S. sheet for internal partitions with
necessary accessories - supporting angles/flats channel including cutting, bending, drilling,
welding, riveting with internal partitions & cable alley as per requirements & instruction of
engineer-in-charge with erection of Supplied switch gears, BUSBARS, suitable size of inter
connecting PVC copper wire / copper-aluminium strips, rubber grommets, rib, bakelite control
fuses/MCB for measuring instruments, earth bus & earth bolts, foundation flange - bolts-base
Plates, sufficient nos. of hinged doors, handles with locking arrangement and rubber gasket,
heavy duty end terminal connection, danger board, necessary ventilation, earthing strip complete.
The Panel shall be painted with epoxy powder coating. (The rates excludes the cost of
switchgears, bus bars, inter connecting mains & Copper Aluminium strips, meters, Fuses etc. The
dimension shall be measured excluding base (legs) The panel shall be supplied with following Rupees
approved manufacturers with following size. (B) The Standard companies switchgear shall be Twenty One
used and only manufacturers at CPRI approved factory (i) with 350mm depth., Providing and Thousand
22 Erecting 415VAC MCB three Pole for motor & inductive load (C curve) having 10KA breaking 1 Each 21,560.32 Five Hundred
capacity & confirms to IS: 8828 in exising box having following capacity 63Amp. Cat.III for Sixty & Paise
Incoming-1Nos. 32Amp for outgoing -4Nos., Supplying, wiring and interconnecting 3R, 1C, Thirty Two
2.5Sqmm copper conductor, flexible, PVC Insulated, FRLS industrial cables in exising junction only
box from Incoming MCB to outgoing MCB with colour code as per respective phases (R, Y, B),
Supplying, wiring and interconnecting 4R, 1C, 4.0Sqmm copper conductor, flexible, PVC
Insulated, FRLS industrial cables in exising junction box from Incoming MCB to outgoing MCB
with colour code as per respective phases (R, Y, B), Cable Terminals (Lugs), Providing & fitting
crimping type Cable Terminals (Lugs) conforming to IS of following types and sizes 2.5Sqmm,
Providing and Fitting of Power Terminal connector block as per required current ratings., P & F in
position frame made out of M.S. angle (riveted or welded) finished with two coats of red oxide and
two coats enamel paint including cutting, welding, holes etc.of following sizes as required. 50mm x
Junction Box -4 for Valve Actuator of
SPP-3A Sump Inlet (1800mm Dia. BFV)
NC-28 Header (1400mm Dia. BFV),
SPP-3B Sump Inlet (1800mm Dia. BFV)
Supply, Installation, Testing and Commissioning of weather proof, dust & vermin proof, floor Rupees
mounted front operated outdoor type double door cubical panel board necessary IP-54 with Twenty Two
Canopy and above protection as per approval from engineer incharge made from 14 SWG thick Thousand
CRC M.S. sheet for outer body & doors, 16 SWG thick CRC M.S. sheet for internal partitions with Fifty Three &
necessary accessories - supporting angles/flats channel including cutting, bending, drilling, Paise Fifty
welding, riveting with internal partitions & cable alley as per requirements & instruction of Four only
GWIL Page 97 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-7: SITC of New valves, Modification Work of existing valves & valve chambers at Navda PS
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
engineer-in-charge with erection of Supplied switch gears, BUSBARS, suitable size of inter
connecting PVC copper wire / copper-aluminium strips, rubber grommets, rib, bakelite control
fuses/MCB for measuring instruments, earth bus & earth bolts, foundation flange - bolts-base
Plates, sufficient nos. of hinged doors, handles with locking arrangement and rubber gasket,
heavy duty end terminal connection, danger board, necessary ventilation, earthing strip complete.
The Panel shall be painted with epoxy powder coating. (The rates excludes the cost of
switchgears, bus bars, inter connecting mains & Copper Aluminium strips, meters, Fuses etc. The
dimension shall be measured excluding base (legs) The panel shall be supplied with following
approved manufacturers with following size. (B) The Standard companies switchgear shall be
used and only manufacturers at CPRI approved factory (i) with 350mm depth., Providing and
Erecting 415VAC MCB three Pole for motor & inductive load (C curve) having 10KA breaking
capacity & confirms to IS: 8828 in exising box having following capacity 63Amp. Cat.III for
Incoming-1Nos. 32Amp for outgoing -4Nos., Supplying, wiring and interconnecting 3R, 1C,
2.5Sqmm copper conductor, flexible, PVC Insulated, FRLS industrial cables in exising junction
box from Incoming MCB to outgoing MCB with colour code as per respective phases (R, Y, B),
Supplying, wiring and interconnecting 4R, 1C, 4.0Sqmm copper conductor, flexible, PVC
Insulated, FRLS industrial cables in exising junction box from Incoming MCB to outgoing MCB
with colour code as per respective phases (R, Y, B), Cable Terminals (Lugs), Providing & fitting
crimping type Cable Terminals (Lugs) conforming to IS of following types and sizes 2.5Sqmm,
Providing and Fitting of Power Terminal connector block as per required current ratings., P & F in
position frame made out of M.S. angle (riveted or welded) finished with two coats of red oxide and
two coats enamel paint including cutting, welding, holes etc.of following sizes as required. 50mm x
Junction Box -5 for Valve Actuator of Collecting Chamber to SPP-2 (1800mm Dia. BFV)
Supply, Installation, Testing and Commissioning of weather proof, dust & vermin proof, floor
mounted front operated outdoor type double door cubical panel board necessary IP-54 with
Canopy and above protection as per approval from engineer incharge made from 14 SWG thick
CRC M.S. sheet for outer body & doors, 16 SWG thick CRC M.S. sheet for internal partitions with
necessary accessories - supporting angles/flats channel including cutting, bending, drilling,
welding, riveting with internal partitions & cable alley as per requirements & instruction of
engineer-in-charge with erection of Supplied switch gears, BUSBARS, suitable size of inter Rupees
connecting PVC copper wire / copper-aluminium strips, rubber grommets, rib, bakelite control Twenty One
fuses/MCB for measuring instruments, earth bus & earth bolts, foundation flange - bolts-base Thousand
24 Plates, sufficient nos. of hinged doors, handles with locking arrangement and rubber gasket, 1 Each 21,560.32 Five Hundred
heavy duty end terminal connection, danger board, necessary ventilation, earthing strip complete. Sixty & Paise
The Panel shall be painted with epoxy powder coating. (The rates excludes the cost of Thirty Two
switchgears, bus bars, inter connecting mains & Copper Aluminium strips, meters, Fuses etc. The only
dimension shall be measured excluding base (legs) The panel shall be supplied with following
approved manufacturers with following size. (B) The Standard companies switchgear shall be
used and only manufacturers at CPRI approved factory (i) with 350mm depth., Providing and
Erecting 415VAC MCB three Pole for motor & inductive load (C curve) having 10KA breaking
capacity & confirms to IS: 8828 in exising box having following capacity 63Amp. Cat.III for
Incoming-1Nos. 32Amp for outgoing -4Nos., Supplying, wiring and interconnecting 3R, 1C,
GWIL Page 98 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-7: SITC of New valves, Modification Work of existing valves & valve chambers at Navda PS
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
2.5Sqmm copper conductor, flexible, PVC Insulated, FRLS industrial cables in exising junction
box from Incoming MCB to outgoing MCB with colour code as per respective phases (R, Y, B),
Supplying, wiring and interconnecting 4R, 1C, 4.0Sqmm copper conductor, flexible, PVC
Insulated, FRLS industrial cables in exising junction box from Incoming MCB to outgoing MCB
with colour code as per respective phases (R, Y, B), Cable Terminals (Lugs), Providing & fitting
crimping type Cable Terminals (Lugs) conforming to IS of following types and sizes 2.5Sqmm,
Providing and Fitting of Power Terminal connector block as per required current ratings., P & F in
position frame made out of M.S. angle (riveted or welded) finished with two coats of red oxide and
two coats enamel paint including cutting, welding, holes etc.of following sizes as required. 50mm x
50mm x 6mm Junction Box -6 for Valve Actuator of near Switchyard location (1500mm Dia.
Supply, Installation, Testing and Commissioning of weather proof, dust & vermin proof, floor
mounted front operated outdoor type double door cubical panel board necessary IP-54 with
Canopy and above protection as per approval from engineer incharge made from 14 SWG thick
CRC M.S. sheet for outer body & doors, 16 SWG thick CRC M.S. sheet for internal partitions with
necessary accessories - supporting angles/flats channel including cutting, bending, drilling,
welding, riveting with internal partitions & cable alley as per requirements & instruction of
engineer-in-charge with erection of Supplied switch gears, BUSBARS, suitable size of inter
connecting PVC copper wire / copper-aluminium strips, rubber grommets, rib, bakelite control
fuses/MCB for measuring instruments, earth bus & earth bolts, foundation flange - bolts-base
Plates, sufficient nos. of hinged doors, handles with locking arrangement and rubber gasket,
heavy duty end terminal connection, danger board, necessary ventilation, earthing strip complete.
The Panel shall be painted with epoxy powder coating. (The rates excludes the cost of
switchgears, bus bars, inter connecting mains & Copper Aluminium strips, meters, Fuses etc. The Rupees
dimension shall be measured excluding base (legs) The panel shall be supplied with following Twenty One
approved manufacturers with following size. (B) The Standard companies switchgear shall be Thousand
25 used and only manufacturers at CPRI approved factory (i) with 350mm depth., Providing and 1 Each 21,560.32 Five Hundred
Erecting 415VAC MCB three Pole for motor & inductive load (C curve) having 10KA breaking Sixty & Paise
capacity & confirms to IS: 8828 in exising box having following capacity 63Amp. Cat.III for Thirty Two
Incoming-1Nos. 32Amp for outgoing -4Nos., Supplying, wiring and interconnecting 3R, 1C, only
2.5Sqmm copper conductor, flexible, PVC Insulated, FRLS industrial cables in exising junction
box from Incoming MCB to outgoing MCB with colour code as per respective phases (R, Y, B),
Supplying, wiring and interconnecting 4R, 1C, 4.0Sqmm copper conductor, flexible, PVC
Insulated, FRLS industrial cables in exising junction box from Incoming MCB to outgoing MCB
with colour code as per respective phases (R, Y, B), Cable Terminals (Lugs), Providing & fitting
crimping type Cable Terminals (Lugs) conforming to IS of following types and sizes 2.5Sqmm,
Providing and Fitting of Power Terminal connector block as per required current ratings., P & F in
position frame made out of M.S. angle (riveted or welded) finished with two coats of red oxide and
two coats enamel paint including cutting, welding, holes etc.of following sizes as required. 50mm x
Junction Box -7 for Valve Actuator of near SPP-3 &
Transformer -1 &2 (1800mm and 1900mm Dia. BFV)
26 Supply, laying, testing & commissioning 1.1 kV grade, XLPE insulated, stranded Copper 500 meter 90.30 Rupees
GWIL Page 99 of
Volume-III - PRICE BID NC-28 & SPP-3A [Navda] Pumping Station - GWIL
SCHEDULE B-7: SITC of New valves, Modification Work of existing valves & valve chambers at Navda PS
Item Rate [In INR] Amount
Description Qty. Unit
No. [In Figures] [In Words] [In INR]
conductor, galvanised steel flat strip / round wire armoured, extruded PVC type ST2 sheathed, Ninety &
heavy duty cable (to be laid on wall surface with necessary clamps / in existing cable trench / Paise Thirty
cable trays / conduit / pipe sleeves at road crossing or floor as per site requirement) conforming to only
IS: 7098 (Part-1) & IEC: 60502 (Part-1) of following sizes:
3 Core x 2.5 Sqmm (From junction box to Motorised Valve Actuator(Branch Power Cable)
Supply, laying, testing & commissioning 1.1 kV grade, XLPE insulated, stranded Copper
conductor, galvanised steel flat strip / round wire armoured, extruded PVC type ST2 sheathed, Rupees Two
heavy duty cable (to be laid on wall surface with necessary clamps / in existing cable trench / Hundred Fifty
27 cable trays / conduit / pipe sleeves at road crossing or floor as per site requirement) conforming to 500 meter 256.27 Six & Paise
IS: 7098 (Part-1) & IEC: 60502 (Part-1) of following sizes: Twenty Seven
8 core x 1.5 Sq.mm (From Junction Box to Motorized valve Actuator(Branch Feedback only
Supply, laying, testing & commissioning 1.1 kV grade, XLPE insulated, stranded Copper
conductor, galvanised steel flat strip / round wire armoured, extruded PVC type ST2 sheathed,
heavy duty cable (to be laid on wall surface with necessary clamps / in existing cable trench /
28 1400 meter 113.00 Hundred
cable trays / conduit / pipe sleeves at road crossing or floor as per site requirement) conforming to
IS: 7098 (Part-1) & IEC: 60502 (Part-1) of following sizes:
3 Core x 4.0 Sqmm(For Power Main cable from MCC to Junction Box)
Supply, laying, testing & commissioning 1.1 kV grade, XLPE insulated, stranded Copper
conductor, galvanised steel flat strip / round wire armoured, extruded PVC type ST2 sheathed,
heavy duty cable (to be laid on wall surface with necessary clamps / in existing cable trench /
29 1800 meter 1,330.00 Three
cable trays / conduit / pipe sleeves at road crossing or floor as per site requirement) conforming to
IS: 7098 (Part-1) & IEC: 60502 (Part-1) of following sizes:
24 Core x 2.5 Sqmm( Form PLC panel to Junction Box for Feedback of Actuator )
Providing & fitting heavy duty brass cable glands (nickel-plated) with washers & rubber ring Rupees
30 conforming to IS, suitable for 3, 3½ & 4 core cables of following type & sizes: 2.5Sqmm 120 Each 73.00 Seventy
Providing & fitting heavy duty brass cable glands (nickel-plated) with washers & rubber ring Rupees One
31 conforming to IS, suitable for 3, 3½ & 4 core cables of following type & sizes: 4Sqmm 30 Each 107.00 Hundred
Cable Terminals (Lugs)
Providing & fitting crimping type Cable Terminals (Lugs) conforming to IS of following types and Rupees Five
Cable Terminals (Lugs)
Providing & fitting crimping type Cable Terminals (Lugs) conforming to IS of following types and Rupees
sizes Seven only
Cable Terminals (Lugs)
Providing & fitting crimping type Cable Terminals (Lugs) conforming to IS of following types and Rupees Five
GWIL Page 100 of
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
01 Volume IA Technical Bid - NC-28-SPP-3A-GWIL-03.03.2026.pdf
02 Volume IB-GCC-Part-01 - NC-28-SPP-3A-GWIL-03.03.2026.pdf
02 Volume IB-GCC-Part-02 - NC-28-SPP-3A-GWIL-03.03.2026.pdf
03 Volume IIA Extent of Work - NC-28-SPP-3A-GWIL-03.03.2026.pdf
04 Volume IIB Tech Spec Civil - NC-28-SPP-3A-GWIL-03.03.2026.pdf
05 Volume IIC Tech Spec M-EI - NC-28-SPP-3A-03.03.2026.pdf
06 Volume IID Technical Data Sheets - NC-28-SPP-3A-GWIL-03.03.2026.pdf
07 Volume III Price bid - NC-28-SPP-3A-GWIL-03.03.2026 (1).pdf
08 Volume IV Drawing - NC-28-SPP-3A-GWIL-03.03.2026-Merged.pdf
09 Volume V ONM - NC-28-SPP-3A-GWIL-03.03.2026.pdf
GR of Finance Dept-GOG-01-05-2025.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .