Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.0 LAccepted-AOC 448 MUZAFFAR AHMED STREET KOLKATA 700 016 | KOLKATA | KOLKATA | WEST BENGAL | 700016 | L1 | Accepted-AOC Successful bidder | |
| 2 | L2₹4.3 L+₹35,020 (8.84%)Rejected-Finance VILLAGE PANSILA P O DEULIA DIST PURBA MEDINIPUR PURBA MEDINIPUR 721154 | DEULIA | PURBA MEDINIPUR | WEST BENGAL | 721154 | L2 | Rejected-Finance Higher bid value | |
| 3 | L3₹4.4 L+₹47,040 (11.9%)Rejected-Finance | L3 | Rejected-Finance Higher bid value | |
| 4 | L4₹10.2 L+₹6.2 L (157.6%)Rejected-Finance | L4 | Rejected-Finance Highest bid value | |
| 5 | Rejected-Technical WEBEL IT PARK 1ST FLOOR ROOM 105 TARATALA INDUSTRIAL ESTATE P1 TARATALA ROAD OPP BRACE BRIDGE RLY STATION KOLKATA WEST BENGAL 700088 | KOLKATA | WEST BENGAL | 700088 | - | Rejected-Technical Submitted MSME doc which is not a valid doc for EMD exemption. |
| Sl No | Description | Qty | Unit | RASH ELECTRICAL WORKS L1 | STAR ELECTRICALS L2 | ROYCO ENGINEERING L4 | M/S. S C ELECTRIC CO L3 |
|---|---|---|---|---|---|---|---|
| 1.00RENOVATION OF ERC SWITCHGEARS | |||||||
| 1.01 | Supply, installation, testing & commissioning of cubical type panel , compartmentalized floor mounted , indoor type dust and vermin proof powder coated panel board, suitable for 415V 3phase, 4wire,50Hz, ac supply of suitable size made out of 2mm. thick M.S. sheet so as accommodate the following mounting complete with detachable gland plate, with suitable size M.S. channel frame(75mm width), at the bottom, Incl. suitable size G.I. net guard with key & locking arrangement with interconnection With necy.nuts, bolts, clamps, grouting bolts incl. providing and fixing the following accessories etc. complete as required.
Incoming:-
a) 415V, 320 Amp TPN MCCB (25KA) -- - - 2 no. b) 320A on load changeover switch---01 no
b)415V, 125 Amp TPN MCCB (25KA) -- - - 1 no. b) 125A on load changeover switch---01 no
c)415V, 400A, 4-bar Aluminium Bus-bar ----01 set
d)415V, 125A, 4-bar Aluminium Bus-bar ----01 set
Outgoing:-
a) 415V, 200 Amp TPN MCCB (25KA) -- - - 1 no.
b) 415V, 125 Amp TPN MCCB (25KA) -- - - 1 no.
c) 415V, 100 Amp TPN MCCB (25KA) -- - - 5 no
d) 0-500 Amp digital Ammeter with selector switch with CT ratio 500/5 Amp(3 nos)--3 set.
e) 0-500V digital Voltmeter - - - - - - 3set.
f) LED indication lamp with fuse base & HRC fuse - - 9 nos.
g) Danger notice board. | 1 | Number | 2,44,500 ₹2,44,500 | 2,90,000 ₹2,90,000 | 4,70,030 ₹4,70,030 | 2,13,300 ₹2,13,300 Lowest |
| 1.02 | Supply, installation, testing & commissioning of cubical type panel, compartmentalized Wall
mounted , indoor type dust and vermin proof powder coated panel board, suitable for 415V 3phase, 4wire,50Hz, ac supply of suitable size made out of 2mm. thick M.S. sheet so as
accommodate the following mounting complete with detachable gland plate, with suitable size M.S. channel frame(75mm width), at the bottom, Incl. suitable size G.I. net guard with key &
locking arrangement with interconnection With necy.nuts, bolts, clamps, grouting bolts incl. providing and fixing the following accessories etc. complete as required.
Incoming:-
a) 415V, 200 Amp TPN MCCB (25KA) -- - 2 no. b) 200A on load changeover switch---01 no
b) 415V,250A, 4-bar Aluminium Bus-bar ----01 set
Outgoing:-
a) 415V, 125 Amp TPN MCCB (25KA) -- - -1 no.
b) 415V, 63 Amp TPN MCCB (25KA) -- - -1 no.
c) 415V, 32 Amp TPN MCCB (25KA) -- - -1 no.
d)(0-500 Amp digital Ammeter with selector switch with CT ratio 500/5 Amp(3 nos)--1 set.
e) 0-500V digital Voltmeter - - - - - - 1set.
f) LED indication lamp with fuse base & HRC fuse - - 3 nos.
g) Danger notice board | 1 | Number | 1,04,500 ₹1,04,500 | 99,590 ₹99,590 Lowest | 1,72,417 ₹1,72,417 | 1,53,500 ₹1,53,500 |
| 1.03 | Supplying and fixing of double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall &
mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment.(Make - L&T / Legrand/ABB ) 8-Way VTPN Double Door DB-MCCB Incomer (Up to 160 A) | 1 | Number | 12,000 ₹12,000 | 7,190 ₹7,190 Lowest | 54,910 ₹54,910 | 13,000 ₹13,000 |
| 1.04 | Supplying and fixing of 415 V, 125 A FP MCCB (Breaking capacity-25KA/35KA) Four Pole MCCB in existing Vertical DBs including necessary connection as per GS. ( Make - L&T / Legrand/ABB) | 1 | Number | 5,500 ₹5,500 Lowest | 7,200 ₹7,200 | 27,455 ₹27,455 | 13,000 ₹13,000 |
| 1.05 | Supplying and fixing 240/415 V 6-32A SP MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connectionas per GS (Make- Legrand/L&T/ABB) | 6 | Number | 215 ₹1,290 | 120 ₹720 Lowest | 16,473 ₹98,838 | 300 ₹1,800 |
| 1.06 | Supplying and fixing of 415 V, 63 A TP MCB of Breaking capacity 10kA & C characteristics on
din rail of existing DBs and necessary connectionas per GS ( Make - L&T / Legrand/ABB ) | 6 | Number | 1,500 ₹9,000 | 1,020 ₹6,120 Lowest | 16,473 ₹98,838 | 1,330 ₹7,980 |
| 1.07 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: By TATA-Medium GI pipe | 2 | Number | 2,500 ₹5,000 | 1,200 ₹2,400 Lowest | 6,040 ₹12,080 | 3,000 ₹6,000 |
| 1.08 | Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe | 2 | Number | 450 ₹900 Lowest | 520 ₹1,040 | 7,687 ₹15,374 | 2,900 ₹5,800 |
| 1.09 | Extra for treatment of soil by using salt & charcoal or coke for plate electrode | 1 | Number | 150 ₹150 Lowest | 800 ₹800 | 4,393 ₹4,393 | 1,030 ₹1,030 |
Tender Value
₹4.4 L
EMD Value
₹8,728
Closing Date
2 Apr 2026, 2:00 pmClosed
General Manager (KTPS)
GM (Admin) building, KTPS, Mecheda, Purba Medinipur, 721137
Installation, Testing, Commissioning and Supply of LT Power Distribution Panel at Employees Recreation Club (ERC), KTPS.
2026_WBPDC_1023348_1
GM(K)/CC/EMOPH/3747/ E3850/25-26
Open Tender
Support/Maintenance Service
Item Rate
180 days
KTPS, Mecheda, Purba Medinipur, 721137
Please refer Tender documents.
4 documents required · 4 mandatory
₹0
₹8,728
Yes
2 Jul 2026
23 Mar 2026
4 Apr 2026
23 Mar 2026
2 Apr 2026
24 Mar 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1RENOVATION OF ERC SWITCHGEARS | |||||
| 1.01 | Supply, installation, testing & commissioning of cubical type panel , compartmentalized floor mounted , indoor type dust and vermin proof powder coated panel board, suitable for 415V 3phase, 4wire,50Hz, ac supply of suitable size made out of 2mm. thick M.S. sheet so as accommodate the following mounting complete with detachable gland plate, with suitable size M.S. channel frame(75mm width), at the bottom, Incl. suitable size G.I. net guard with key & locking arrangement with interconnection With necy.nuts, bolts, clamps, grouting bolts incl. providing and fixing the following accessories etc. complete as required.
Incoming:-
a) 415V, 320 Amp TPN MCCB (25KA) -- - - 2 no. b) 320A on load changeover switch---01 no
b)415V, 125 Amp TPN MCCB (25KA) -- - - 1 no. b) 125A on load changeover switch---01 no
c)415V, 400A, 4-bar Aluminium Bus-bar ----01 set
d)415V, 125A, 4-bar Aluminium Bus-bar ----01 set
Outgoing:-
a) 415V, 200 Amp TPN MCCB (25KA) -- - - 1 no.
b) 415V, 125 Amp TPN MCCB (25KA) -- - - 1 no.
c) 415V, 100 Amp TPN MCCB (25KA) -- - - 5 no
d) 0-500 Amp digital Ammeter with selector switch with CT ratio 500/5 Amp(3 nos)--3 set.
e) 0-500V digital Voltmeter - - - - - - 3set.
f) LED indication lamp with fuse base & HRC fuse - - 9 nos.
g) Danger notice board. | 1 | Number | - | - |
| 1.02 | Supply, installation, testing & commissioning of cubical type panel, compartmentalized Wall
mounted , indoor type dust and vermin proof powder coated panel board, suitable for 415V 3phase, 4wire,50Hz, ac supply of suitable size made out of 2mm. thick M.S. sheet so as
accommodate the following mounting complete with detachable gland plate, with suitable size M.S. channel frame(75mm width), at the bottom, Incl. suitable size G.I. net guard with key &
locking arrangement with interconnection With necy.nuts, bolts, clamps, grouting bolts incl. providing and fixing the following accessories etc. complete as required.
Incoming:-
a) 415V, 200 Amp TPN MCCB (25KA) -- - 2 no. b) 200A on load changeover switch---01 no
b) 415V,250A, 4-bar Aluminium Bus-bar ----01 set
Outgoing:-
a) 415V, 125 Amp TPN MCCB (25KA) -- - -1 no.
b) 415V, 63 Amp TPN MCCB (25KA) -- - -1 no.
c) 415V, 32 Amp TPN MCCB (25KA) -- - -1 no.
d)(0-500 Amp digital Ammeter with selector switch with CT ratio 500/5 Amp(3 nos)--1 set.
e) 0-500V digital Voltmeter - - - - - - 1set.
f) LED indication lamp with fuse base & HRC fuse - - 3 nos.
g) Danger notice board | 1 | Number | - | - |
| 1.03 | Supplying and fixing of double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall &
mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment.(Make - L&T / Legrand/ABB ) 8-Way VTPN Double Door DB-MCCB Incomer (Up to 160 A) | 1 | Number | - | - |
| 1.04 | Supplying and fixing of 415 V, 125 A FP MCCB (Breaking capacity-25KA/35KA) Four Pole MCCB in existing Vertical DBs including necessary connection as per GS. ( Make - L&T / Legrand/ABB) | 1 | Number | - | - |
| 1.05 | Supplying and fixing 240/415 V 6-32A SP MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connectionas per GS (Make- Legrand/L&T/ABB) | 6 | Number | - | - |
| 1.06 | Supplying and fixing of 415 V, 63 A TP MCB of Breaking capacity 10kA & C characteristics on
din rail of existing DBs and necessary connectionas per GS ( Make - L&T / Legrand/ABB ) | 6 | Number | - | - |
| 1.07 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: By TATA-Medium GI pipe | 2 | Number | - | - |
| 1.08 | Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe | 2 | Number | - | - |
| 1.09 | Extra for treatment of soil by using salt & charcoal or coke for plate electrode | 1 | Number | - | - |
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.71 MB
BOQ_2515220.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .