Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.7 CrAdmitted-Finance | ₹2.7 Cr | L1 | Admitted-Finance |
| 2 | L2₹2.7 Cr+₹1.3 L (0.47%)Admitted-Finance | ₹2.7 Cr+₹1.3 L (0.47%) | L2 | Admitted-Finance |
| 3 | L3₹2.8 Cr+₹3.1 L (1.14%)Admitted-Finance | ₹2.8 Cr+₹3.1 L (1.14%) | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | IBRAHIMKUTTY K K L2 | SAAJCONSTRUCTIONS L1 | AMJATH M A L3 |
|---|---|---|---|---|---|---|
| 1.00STEEL WORK | ||||||
| 1.01 | 10.16.3 : Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete.Electric resistance or induction butt welded tubes | 25,000 | kg | 182 ₹45,50,000 | 175 ₹43,75,000 Lowest | 180 ₹45,00,000 |
| 1.02 | od171968/2021_2022 : Providing and fixing S.S fan clamp of 16mm dia in RCC slabs, beams including cost and conveyance of all materials,labour charges etc complete as directed by the Engineer-in-Charge at all levels.<br> | 30 | no | 155 ₹4,650 | 160 ₹4,800 | 150 ₹4,500 Lowest |
| 1.03 | 10.28 : Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.) | 1,166.33 | kg | 800 ₹9,33,064.8 | 780 ₹9,09,738.18 | 700 ₹8,16,431.7 Lowest |
| 1.04 | 13.50.4 : Applying priming coat:With ready mixed red oxide zinc chromate primer of approved brand and manufacture on steel work (second coat) | 138 | sqm | 30 ₹4,140 Lowest | 35 ₹4,830 | 35 ₹4,830 |
| 1.05 | 13.61.1 : Painting with synthetic enamel paint of approved brand and manufacture to give an even shade:Two or more coats on new work | 718.1 | sqm | 120 ₹86,172.36 | 100 ₹71,810.3 Lowest | 110 ₹78,991.33 |
| 1.06FLOORING WORK | ||||||
| 1.07 | 11.41.2 : Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600 x 600 mm. | 1,500 | sqm | 1,450 ₹21,75,000 Lowest | 1,600 ₹24,00,000 | 1,700 ₹25,50,000 |
| 1.08 | 11.46.2 : Providing and laying Vitrified tiles indifferent sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete.Size of Tile 600x600 mm | 56.97 | sqm | 1,450 ₹82,606.5 Lowest | 1,600 ₹91,152 | 1,650 ₹94,000.5 |
| 1.09 | 11.37 : Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), including pointing the joints with white cement and matching pigment etc., complete. | 55 | sqm | 1,100 ₹60,500 | 1,100 ₹60,500 | 1,050 ₹57,750 Lowest |
Tender Value
Refer Docs
EMD Value
₹1 L
Closing Date
20 Dec 2021, 12:00 pmClosed
Manager Subcontract
KEL Kochi
CONSTRUCTION OF NEW BUILDING OF WORKING WOMENS HOSTEL AT KAKKANAD - PHASE II
2021_KEL_460050_1
KRO/ BDC/969/ 2021
Open Tender
Civil Works - Others
Item Rate
240 days
KEL Kochi
As per NIT
6 documents required · 6 mandatory
₹8,850
₹1 L
Yes
22 Dec 2021
13 Dec 2021
21 Dec 2021
13 Dec 2021
20 Dec 2021
13 Dec 2021
13 Dec 2021 - 17 Dec 2021
Amount
STEEL WORK
10.16.3 : Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete.Electric resistance or induction butt welded tubes
od171968/2021_2022 : Providing and fixing S.S fan clamp of 16mm dia in RCC slabs, beams including cost and conveyance of all materials,labour charges etc complete as directed by the Engineer-in-Charge at all levels.<br>
10.28 : Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.)
13.50.4 : Applying priming coat:With ready mixed red oxide zinc chromate primer of approved brand and manufacture on steel work (second coat)
13.61.1 : Painting with synthetic enamel paint of approved brand and manufacture to give an even shade:Two or more coats on new work
FLOORING WORK
11.41.2 : Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600 x 600 mm.
11.46.2 : Providing and laying Vitrified tiles indifferent sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete.Size of Tile 600x600 mm
11.37 : Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), including pointing the joints with white cement and matching pigment etc., complete.
8.31 : Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineerin-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
22.5 : Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/sqm. This layer will be allowed to air cure for 4 hours. b) Second layer of slurry of cement @ 0.242 kg /sqm mixed with water proofing cement compound @ 0.126 kg/ sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry.
11.55.1 : Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge :Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
8.2.2.2 : Providing and fixing 18 mm thick gang saw cut, mirror, polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations, of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 ( 1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.Area of slab over 0.50 sqm
8.5 : Extra for providing opening or required size & shape for wash basin/kitchen sink in kitchen platform, vanity counter and similar location in marble/granite/ stone work, including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete.
16.92 : Providing and fixing 10x10x7.50 cm Granite stone block hand cut and chisel dressed on top, for paving in floors, drains etc. laid over 20mm thick base mortar 1:4 (1 cement : 4 coarse sand) with joints 10 mm wide filled with same mortar including ruled pointing etc. complete as per direction of engineer-in-charge
FINISHING WORK
13.16.1 : 6 mm cement plaster of mix:1:3 ( 1 cement : 3 fine sand)
13.1.1 : 12 mm cement plaster of mix:1:4 ( 1 cement : 4 fine sand)
13.2.1 : 15 mm cement plaster on the rough side of single or half brick wall of mix:1:4 (1 cement :4 fine sand)
13.10 : 15 mm cement plaster 1:3 ( 1 cement :3 coarse sand) finished with a floating coat of neat cement on the rough side of single or half brick wall.
13.43.1 : Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface:Water thinnable cement primer
13.47.1 : Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade:New work (Two or more coats applied @ 1.43 ltr/ 10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm)
13.60.1 : Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade:Two or more coats on new work
22.6 : Providing and laying water proofing treatment on roofs of slabs by applying cement slurry mixed with water proofing cement compound consisting of applying : a) after surface preparation, first layer of slurry of cement @ 0.488 kg/ sqm mixed with water proofing cement compound @ 0.253 kg/ sqm. laying second layer of fibre glass cloth when the first layer is still green. Overlaps of joints of fibre cloth should not be less than 10 cm. c) third layer of 1.5 mm thickness consisting of slurry of cement @ 1.289 kg/ sqm mixed with water proofing cement compound @ 0.670 kg/sqm and coarse sand @ 1.289 kg/sqm. This will be allowed to air cure for 4 hours followed by water curing for 48 hours. The entire treatment will be taken upto 30 cm on parapet wall and tucked into groove in parapet all around. d) fourth and final layer of brick tilling with cement mortar (which will be paid for separately. For the purpose of measurement the entire treated surface will be measured)
13.67.2 : Varnishing with varnish of approved brand and manufacture :Two or more coats glue sizing with spar varnish or an under coat of flatting varnish
MISCELLANEOUS BUILDING WORK
2.34.1 : Supplying chemical emulsion in sealed containers including delivery as specified.Chlorpyriphos / Lindane emulsifiable concentrate of 20%
2.35.3.1 : Diluting and injecting chemical emulsion for POST -CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion):Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1:2 (1 cement : 2 coarse sand) to match the existing floor:With Chlorpyriphos/Lindane E.C. 20% with 1% concentration
19.6.2 : Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 ( 1 cement : 2 fine sand) including testing of joints etc. complete:150 mm dia R.C.C. pipe
19.6.4 : Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 ( 1 cement : 2 fine sand) including testing of joints etc. complete:300 mm dia R.C.C. pipe
od171969/2021_2022 : Supplying and fixing of following sizes of medium duty PVC conduits conforming to IS 9537/1983 part III along with accessories in surface /recess including cutting the wall and making good the same in case of recessed conduit as required-32 mm dia
od171970/2021_2022 : Supplying and fixing of following sizes of medium duty PVC conduits conforming to IS 9537/1983 part III along with accessories in surface /recess including cutting the wall and making good the same in case of recessed conduit as required-25 mm dia
od171971/2021_2022 : Supplying and fixing of following sizes of medium duty PVC conduits conforming to IS 9537/1983 part III along with accessories in surface /recess including cutting the wall and making good the same in case of recessed conduit as required-20 mm dia
12.4.1 : Providing ridges or hips width 60 cm overall width plain G.S. sheet fixed with polymer coated J or L hooks, bolts and nuts 8 mm dia G.I. limpet and bitumen washers complete.0.80 mm thick with zinc coating not less than 275 gm/m2
od171973/2021_2022 : Providing and laying profiled sheeting 970mm to 1000mm cover width, 26/28mm crest height at 195-200mm centers, made out of '0.5mm TCT, Cold Rolled steel of 550 Mpa yield strength conforming to ASTM A 368 or AS 1595 with hot dip metalic coating 'of minimum 150gm/Sqm zinc-aluminium alloy coating mass (55% Aluminium, 43.5% zinc and 1.5% Silicon ) total of both size as 'per ASTM A 792 or AS1397. The colour have shall have a total coating thickness iof 35microns of polyster paint system as per 'AS/NZS - 2728:1997 ( category 3 ) of approved colour, comprising of 20 microns exterior coat on top surface and 5 microns reverse 'coat on back surface over 5 microns primer coat on both surfaces. Roofing sheet shall be factory cut and required length of '(up to 12mtr ) to suite site conditions and design drawings. Roofing sheet shall be crest fixed to purlines with hot dip 'galvanized self drilling fastners with integral EPDM washers (one fastner on each crest) also, fastners to be provided on side laps. 'Minimum sheet overlap at end laps shall be 150mm. Penetration and end laps in sheet shall be sealed by using proper sealant. 'Profiled HDPE fillers shall be provided wherever required to close voids between capings and troughs of the sheet to provide a 'weather tight exterior. Rate shall include cost and conveyence of all materials, lead, lift, scaffolding, all labour charges, making the roof water tight with required sealent etc complete at all level and as directed by Engineer-in-Charge.<br>
od171975/2021_2022 : Supplying and fixing in position PVC plain ended rain water gutter 150 mm or nearest size (semi circular section) of approved quality and design with all accessories like stop ends, 32x5mm MS flat supports at 1m interval, scaffolding etc. complete for all heights including cost and conveyance of all materials, labour charges, scaffolding, sundries etc complete as directed by the Engineer- in-charge at all levels.<br>
16.69 : Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature jointed with cement mortar 1:3 ( 1 cement : 3 coarse sand) , including making joints with or without grooves ( thickness of joints except at sharp curve shall not to more than 5 mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge ( length of finished kerb edging shall be measured for payment ). ( Precast C.C. kerb stone shall be approved by Engineer-in-Charge)
PLUMBING AND SANITARY FITTINGS
18.8.2 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.20 mm nominal outer dia pipes
50.18.7.2.2 : Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge 20 mm dia 10 Kgf/cm2- Internal work - Exposed on wall
50.18.7.6.1 : Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 50 mm dia 10 Kfg/cm - Internal work- Exposed on wall
50.18.9.9.1 : Providing and fixing PVC pipes includings jointing of pipes with one step PVC solvent cement, trenching, refilling & testing of Joints complete as per direction of engineer in charge.110 mm dia 6Kgf/cm2
50.18.9.10.1 : Providing and fixing PVC pipes includings jointing of pipes with one step pvc solvent cement, trenching , refilling & testing of joints complete as per direction of Engineer in Charge. 150 mm dia 6 Kgf/cm2
50.18.9.22.3 : Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement-110 mm dia Door Elbow
50.18.9.22.1 : Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 110 mm dia Elbow
50.18.9.22.2 : Providing and fixing PVC moulded fittings / accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 110 mm dia 45 degree Elbow
50.17.1.5 : Supplying and fixing CP Health Faucet superior quality ( Jagur or equvalent make ) including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge.
17.3.1 : Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreous china flushing cistern & C.P. flush bend with fittings & C.I. brackets, 40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required :W.C. pan with ISI marked white solid plastic seat and lid
17.7.2 : Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:White Vitreous China Wash basin size 630 x 450 mm with a single 15 mm C.P. brass pillar tap
18.51.1 : Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms.15 mm nominal bore
18.52.1 : Providing and fixing C.P brass stop cock ( concealed) of standard design and of approved make conforming to IS: 893115 mm nominal bore
17.32.2 : Providing and fixing mirror of superior glass ( of approved quality) and of required shape and size with plastic moulded frame of approved make and shade with 6 mm thick hard board backing :Rectangular shape 453x357 mm
18.65 : Providing and fixing PTMT Soap Dish Holder having length of 138 mm, breadth 102 mm, height of 75 mm with concealed fittings arrangements, weighing not less than 106 gms.
17.73.2 : Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fitting arrangement of approved quality and colour600 mm long towel rail with total length of 645 mm, width 78 mm and effective height of 88 mm, weighting not less than 190 gms
od180611/2021_2022 : Providing and fixing 110mm PVC pipe fittings: PVC Y' Tee
od180612/2021_2022 : Providing and fixing 110mm PVC pipe fittings: PVC door tee
od180613/2021_2022 : Providing and fixing 150mm PVC pipe fittings: 45⁰
od180614/2021_2022 : Providing and fixing 150mm PVC pipe fittings: Coupling
od180615/2021_2022 : Providing and fixing 150mm PVC pipe fittings: PVC elbow
od180628/2021_2022 : Providing and fixing PTMT towel ring complete with CP brass screws with the concealed fitting arrangement of approved quality
18.64 : Providing and fixing PTMT swivelling shower, 15 mm nominal bore, weighing not less than 40 gms.
17.60.1.1 : Providing and fixing trap of self cleansing design with screwed down or hinged grating without vent arm complete, including cost of cutting and making good the walls and floors:100 mm inlet and 100 mm outletSand cast iron S & S as per IS : 3989
od180629/2021_2022 : Providing and fixing PVC ball valve of an approved quality conforming to IS: 893: 25 mm nominal bore
od185854/2021_2022 : Providing and fixing PVC ball valve of an approved quality conforming to IS: 893: 40 mm nominal bore
od185855/2021_2022 : Providing and fixing PVC ball valve of an approved quality conforming to IS: 893: 50 mm nominal bore
od185853/2021_2022 : Providing and fixing shower cock, 15 mm nominal bore, weighing not less than 40 gms.
ADDITIONAL REQUIREMENTS
9.147A.1 : Providing and fixing factory made uPVC white colour casement/casement cum fixed glazed windows comprising of uPVC multi-chambered frame, sash and mullion (where ever required) extruded profiles duly reinforced with 1.60 +/- 0.2mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), uPVC extruded glazing beads of appropriate dimension, EPDM gasket, stainless steel (SS 304 grade) friction hinges, zinc alloy (white powder coated) casement handles, G.I fasteners 100 x 8 mm size for fixing frame to finished wall, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, mullion (if required) shall be also fusion welded including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealant shall be paid separately)<br> Note: For uPVC frame, sash and mullion extruded profiles minus 5% tolerance in dimension i.e. in depth & width of profile shall be acceptable.Casement window single panel with S.S. friction hinges (300 x 19 x 1.9 mm), made of (small series) frame 47 x 50 mm & sash 47 x 68 mm both having wall thickness of 1.9 +/- 0.2 mm and single glass pane glazing bead of appropriate dimension. (Area of window upto 0.75 sqm.)
9.147A.3 : Providing and fixing factory made uPVC white colour casement/casement cum fixed glazed windows comprising of uPVC multi-chambered frame, sash and mullion (where ever required) extruded profiles duly reinforced with 1.60 +/- 0.2mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), uPVC extruded glazing beads of appropriate dimension, EPDM gasket, stainless steel (SS 304 grade) friction hinges, zinc alloy (white powder coated) casement handles, G.I fasteners 100 x 8mm size for fixing frame to finished wall, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, mullion (if required) shall be also fusion welded including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealant shall be paid separately)<br> Note: For uPVC frame, sash and mullion extruded profiles minus 5% tolerance in dimension i.e. in depth & width of profile shall be acceptable.Casement window double panels with top fixed with S.S. friction hinges (350 x 19 x 1.9 mm) made of (small series) frame 47 x 50 mm, sash 47 x 68 mm & mullion 47 x 68 mm all having wall thickness of 1.9 ± 0.2 mm and single glazing bead of appropriate dimension. ( Area of window upto 2.50 sqm).
25.7 : Designing, fabricating, testing, installing and fixing in position Curtain Wall with Aluminium Composite Panel Cladding, with open grooves for linear as well as curvilinear portions of the building , for all heights and all levels etc. including: a) Structural analysis & design and preparation of shop drawings for pressure equalisation or rain screen principle as required, proper drainage of water to make it watertight including checking of all the structural and functional design. b) Providing, fabricating and supplying and fixing panels of aluminium composite panel cladding in pan shape in metalic colour of approved shades made out of 4mm thick aluminium composite panel material consisting of 3mm thick FR grade mineral core sandwiched between two Alumini um sheets (each0.5mm thick). The aluminium composite panel cladding sheet shall be coil coated, with Kynar 500based PVDF / Lumiflon based fluoropolymer resin coating of approved colour and shade on face # 1 and polymer (Service) coating on face # 2 as specified using stainless steel screws, nuts, bolts, washers, cleats, weather silicone sealant, backer rods etc. c) The fastening brackets of Aluminium alloy 6005 T5 / MS with Hot Dip Galvanised with serrations and serrated washers to arrest the wind load movement, fasteners, SS 316 Pins and anchor bolts of approved make in SS 316, Nylon separators to prevent bi-metallic contacts all complete required to perform as per specification and drawing The item includes cost of all material & labour component, the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working curtain wall with aluminium composite panel cladding, cleaning and protection of the curtain wall with aluminium composite panel cladding till the handing over of the building for occupation. Base frame work for ACP cladding is payable under the relevant aluminium item.s The Contractor shall provide curtain wall with aluminium composite panel cladding, having all the performance characteristics all complete , as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer-in-Charge. However, for the purpose of payment, only the actual area on the external face of the curtain wall with Aluminum Composite Panel Cladding (including width of groove) shall be measured in sqm. up to two decimal places.
od185823/2021_2022 : Supplying and fixing powder-coated aluminium louvers by using 50mm x 25mm aluminium sections fixing with 20mm spacing to the backside with GP tube vertical support etc, complete…
od177529/2021_2022 : Providing and fixing SS coin mesh with 20mm dia openings and ISA 20X20X4mm frame for bird proofing including applying two coats of zinc chromate primer and two coats of synthetic enamel paint etc complete as directed by the engineer in charge<br>
10.3 : Providing and fixing in position collapsible steel shutters with vertical channels 20x10x2 mm and braced with flat iron diagonals 20x5 mm size, with top and bottom rail of T-iron 40x40x6 mm, with 40 mm dia steel pulleys, complete with bolts, nuts,locking arrangement, stoppers, handles, including applying a priming coat of approved steel primer .
od185824/2021_2022 : Supply and erecting 1.5HP bore well pump set submersible type 100mm dia CRI make including all fittings and connections etc. complete.
od185825/2021_2022 : Providing and fixing shelf door (two shutters)by using aluminium electroplated sections for outer frame with showcase frame and vertical members by using 11/2x1x1 mm thick box section,20mm lip section for shutter frame,3mm APP, and 4mm mirror fixing into the shutter frame and tighten with EPDM rubbers. 3’’ SS hinges, handle, lock with key, etc. The top of the shelf is covered with two track sliding shutter by using an ordinary sliding section with lock and handle etc.. complete…
22.6 : Providing and laying water proofing treatment on roofs of slabs by applying cement slurry mixed with water proofing cement compound consisting of applying : a) after surface preparation, first layer of slurry of cement @ 0.488 kg/ sqm mixed with water proofing cement compound @ 0.253 kg/ sqm. laying second layer of fibre glass cloth when the first layer is still green. Overlaps of joints of fibre cloth should not be less than 10 cm. c) third layer of 1.5 mm thickness consisting of slurry of cement @ 1.289 kg/ sqm mixed with water proofing cement compound @ 0.670 kg/sqm and coarse sand @ 1.289 kg/sqm. This will be allowed to air cure for 4 hours followed by water curing for 48 hours. The entire treatment will be taken upto 30 cm on parapet wall and tucked into groove in parapet all around. d) fourth and final layer of brick tilling with cement mortar (which will be paid for separately. For the purpose of measurement the entire treated surface will be measured)
18.48 : Providing and placing on terrace (at all floor levels) polyethylene water storage tank :ISI 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank.
18.36.1 : Constructing masonry chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for fire hydrants, with C.I surface box 350x350 mm top and 165 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 grades stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand: 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design:With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
21.2.1 : Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS : 12823 Grade I Type II, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of Engineer - in- Charge.Pre-laminated particle board with decorative lamination on one side and balancing lamination on other side
13.85.1 : Applying priming coats with primer of approved brand and manufacture, having low VOC ( Volatile Organic Compound) content.With ready mixed pink or grey primer on wood work (hard and soft wood ) having VOC content less than 50 grams/ litre
13.48.2 : Finishing with Deluxe Multi surface paint system for interiors and exteriors using primer as per manufacturers specifications:Painting wood work with Deluxe Multi Surface Paint of required shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.75 ltr/10 sqm of approved brand and manufacture
9.48.1 : Providing and fixing M.S. Grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete.Fixed to steel windows by welding
11.20.1 Chequerred precast cement concrete tiles 22 mm thick in footpath & courtyard, jointed with neat cement slurry mixed with pigment to match the shade of tiles, including rubbing and cleaning etc. complete on 20 mm thick bed of cement mortar 1:4 ( 1 cement : 4 coarse sand).Light shade pigment using white cement
9.141 Providing and fixing PVC Door Frame of size 50x47 mm with a wall thickness of 5 mm (±0.2mm), made out of single piece extruded PVC profile, with mitred cut joints and with 2 nos of PVC bracket of size 190 mm x 100 mm long arms of cross section size 35 x 15 mm & self driven self taping screws, the vertical door profiles to be reinforced with 40x20 mm M.S. rectangular tube of 0.8 mm, including providing EPDM rubber gasket weather seal throughout the frame, including jointing 5 mm PVC frame strip with PVC solvent cement on the back of the profile. The door frame to be fixed to the wall using 8x100 mm long anchor fasteners complete, all as per manufacturer's specification and direction of Engineer-in--charge.
9.142.2 35 mm thick factory made Solid panel PVC Door shutter, made out of single piece extruded solid PVC ( ±0.2 mm) thick, having styles & rails (except lock rail ) of size 95 mmx 35 mm x 5 mm, out of which 75 mm shall be flat and 20 mm shall be tapered (on both side), having one side thickness of 15 mm integrally extruded on the hinges side of the profile for better screw holding power, including reinforcing with MS tube of size 40 mm x 20 mm x 1 mm, joints of styles & rails to be mitered cut & joint with the help of PVC solvent cement, self driven self tapping screws & M.S. rectangular pipes bracket of size 190 mm x 100 mm of cross section size 35 mm x 17 mm s 1 mm at each corner. Single piece extruded 5 mm thick solid PVC Lock rail of size 115 mm x 35 mm x 35 mm, out of which 95 mm to be flat and 20 mm to be tapered at both ends, having 15 mm solid core in middle of rail section integrally extruded, fixing the styles & rails with the help of solvent and self driven self tapping screws of 125 mm x 11 mm, including providing 5 mm Single piece solid PVC extruded sheet inserted in the door as panel, all complete as per manufacturer's specification and direction of Engineer-in-charge.Decorative finish (wood grained finish)
50.9.15.2 Supplying and fixing 300 mm Aluminium aldrop
od246715/2021_2022 Supplying and fixing C.I cover 600x600 mm with frame (standard pattern) the weight of cover to be not less than 9 Kg.
Rain water harvesting and its connecting works etc. complete.
ELECTRIFICATION
HT METERING PANEL WITH LBS
Supply, installation, testing and commissioning of 11KV Outdoor
Metering Panel with Load Break Switch fabriacted in CRCA
sheet steel of 2mm thickness with IP - 54 Protection comprising
of 3 Nos of 11KV */5A 10VA Class 0.2S CT and 1 Nos
11KV/110V, 20VA, Class 0.2 PT having separate chamber for
CT, PT and TOD Meter with provision for fixing TOD Meter
including Test Terminal Block, Control Fuses, KSEB sealing
provision and 1 Nos of 11 KV, 630A, 26.3 kA/1 sec Air break
manual front operated LBS with tripping coil rated for 230V AC,
mechanical trip push button, electrical trip push button, ON/OFF
indicator, earth switch, interlock between SFU and earth switch,
3 Nos of HRC fuses with suitable rating, space heater and
thermostat etc. complete with wiring and connections as
required. The panel shall conform to Electrical Inspectorate and
KSEB standards. This scope also includes the testing of CT,PT
and obtaining test certificate from KSEB / TMR. (*CT ratio will
be furnished later and all Statutory fees shall be remitted by the
Client /Consumer or it shall be reimbursed on the submission of
supporting documents).
HT ENERGY METER
Supply, installation, testing and commissioning of CT, PT
connected TOD Meter of approved brand and conforming to
relevant IS and KSEB, Electrical Inspectorate regulations, IP 51
with unbreakable transparent cover, provision for sealing,
anti-tamper features, real time and calibrated quartz clock tested
by KSEB.This scope also includes the testing of TOD Meter and
obtaining test certificate from KSEB / TMR. (*All Statutory fees
shall be remitted by the Client / Consumer or it shall be
reimbursed on the submission of supporting documents).
TRANSFORMER
Installation, testing and commissioning of 11KV/433V Three
Phase Oil Type 160KVA Outdoor Transformer with OLTC
conforming to Electrical Inspectorate and KSEB Standards. The
supply of transformer shall come within the scope of KEL.
NEUTRAL CT WITH ENCLOSURE
Supply and installation of 50/5 Resin cast class 5P10 10VA
Neutral CT with bar primary 25x6mm copper in a suitable
powder enclosure box with necessary wiring and earthing of the
box etc. complete as required.This scope also includes the testing
of CT and obtaining test certificate from Electrical Inspectorate.
(*All Statutory fees shall be remitted by the Client / Consumer or
it shall be reimbursed on the submission of supporting
documents).
EMERGENCY PUSH BUTTON
Supply, installation, testing and commission of Emergency
Stop Push Button with enclosure for the Transformer
DG SET
Installation, Testing and Commissioning of 125 KVA, Three
Phase, 415V, 0.8 power factor, comprising of diesel engine, fuel
tank, alternator, base plate radiator, control panel with MCCB,
EFR with CT, starting equipment exciter, home silencer and all
necessary accessories etc. complete as required. (Including
Acoustic Enclosure). This scope also includes the testing of
Energy Meter, CTs, Relays etc and obtaining test certificate
from KSEB / Electrical Inspectorate. (*All Statutory Fees shall
be remitted by the Client / Consumer or it shall be reimbursed
on the submission of supporting documents). The supply of
DG SET shall come within the scope of KEL.
LT METERING PANEL
Supply, installation, testing and commissioning of cubicle
type Outdoor KSEB Metering Panel Board with Double Door
and Canopy fabricated in compartmentalised design from
CRCA sheet steel of 2mm thick for frame work, covers and
gland plates, cleaning and finishing complete with 7 tank
process for powder coating in approved shade having
250A capacity Aluminium alloy bars of high conductivity,
DMC/FRP bus bar supports, 2 Nos of common earth bar of
25 x 6 Copper Strip etc. complete as required. For MCCBs Ics
shall be 100% Icu. The Panel shall conform to the Electrical
Inspectorate and KSEB standards and it should only be
manufactured after getting approval from Electrical Inspectorate
and the Consultant.
Specification & Components
4 Nos - Bus bar Provision for fixing CTs
1 Nos - Provision for Fixing Three Phase Energy Meter
3 Nos - Open Type / Bakelite Fuse with suitable rating
1 Nos - 250A Neutral Link
1 Nos - 250A, 36kA 4 Pole Microprocessor based MCCB with
ROM and spreader
MAIN SWITCH BOARD
Supply, installation, testing & commissioning of CPRI approved
cubical type Main Switch Board Panel suitable for 415V, Three
Phase, 4 Wire 50 Hz AC supply system having sufficient front
surface area fabricated in compartmentalised design from CRCA
sheet steel of 2 mm thick for frame work and covers, 3 mm
thick for gland, plates, cleaning and finishing complete with 7
tank process for powder coating in approved shade, having
320 Amps capacity extensible type TPN Aluminum alloy bus
bars of high conductivity, DMC / SMC / FRP bus bar supports,
with short circuit withstand capacity of 31 MVA for 1 Sec.,
bottom base channel of MS section not less than 100 mm x
50 mm x 5 mm thick, fabrication shall be done in transportable
sections, entire panel shall have a common copper earth bar
of size 25 mm x 6 mm at the rear with 2 Nos. earth stud, solid
connections from main bus bar to switch gears with required
size of AL. bus bars and control wiring with 1.5 Sq.mm PVC
insulated LSZH (Low Smoke Zero Halogen) copper conductor
cables, cable alleys etc. For all MCCBs Ics shall be 100% Icu.
The panel shall conform to the Electrical Inspectorate standards
and it shall only be manufactured after getting approval from the
Electrical Inspectorate and the consultant.
Busbar
1 Runs of 40 x 10mm AL.Busbar for each Phase
1 Runs of 32 x 10mm AL.Busbar for Neutral
EB Side
1 Nos - 250A, 36kA 4P Microprocessor based MCCB set
at 213A with 3 O/C and 1 E/F releases as Incomer
1 Set - RYB Indication lamps with Control MCBs
3 Nos - 250/5A CL:1, 10VA CT
1 Nos - Digital Multifunction Meter measuring V, A, F, KW,
KVA, PF with Control MCBs
1 Nos - 250A 4P Power Contactor (AC3)
1 Nos - Stand by Earth Fault Relay (In case of HT Connection)
or ELR with CBCT (In case of HT/LT or LT Connection)
DG Side
1 Nos - 200A 4P Isolator
1 Set - RYB Indication lamps with Control MCBs
3 Nos - 200/5A CL:1, 10VA CT
1 Nos - Digital Multifunction Meter measuring V ,A, F, KW,
KVA, PF with Control MCBs
1 Nos - 200A 4P Power Contactor (AC3)
1 Set - Contactor with Mechanical and Electrical Inter-lock
AMF control suitable for control of 125 KVA DG set complete
with AMF Relay with Control MCBs, Timer and all other
necessary accessories.
Surge Protection Device
2 Nos - 8 Module DIN Rail Mounting Type 1 + Type 2 +
Type 3 / Class 1 + class II 100kA SPD on incomer of EB supply
and DG Supply with all accessories etc. complete as required. The
connections to RYB Phases, Neutral and Earth shall be done
using 16 Sq.mm Single Core Flexible Copper conductor cables
with less than 0.45m in length.
Outgoings
1 Nos - 160A 36kA 4P Thermal Magnetic MCCB having 70 to
100% setting provision with ROM and spreader
3 Nos - 125A 36kA 4P Thermal Magnetic MCCB having 70 to
100% setting provision with ROM and spreader
2 Nos - 100A 36kA 4P Thermal Magnetic MCCB having 70 to
100% setting provision with ROM and spreader
2 Nos - 80A 36kA 4P Thermal Magnetic MCCB having 70 to
100% setting provision with ROM and spreader
APFC PANEL (45 KVAR)
Supply, installation, testing & commissioning of CPRI approved
cubical type Automatic Power Factor Correction Panel suitable
for 415 V, Three Phase, 4 Wire 50 Hz AC supply system having
sufficient front surface area fabricated in compartmentalized
design from CRCA sheet steel of 2 mm thick for frame work
and covers, 3 mm thick for gland, plates, cleaning and finishing
complete with 7 tank process for powder coating in approved
shade, having 200 Amps capacity type TPN Aluminum alloy bus
bars of high conductivity, DMC / SMC / FRP bus bar supports,
with short circuit withstand capacity of 31 MVA for 1 Sec.,
bottom base channel of MS section not less than 100 mm x
50 mm x 5 mm thick, fabrication shall be done in transportable
sections, entire panel shall have a common copper earth bar of
size 25 mm x 6 mm at the rear with 2 Nos. earth stud, solid
connections from main bus bar to switch gears with required
size of Al. bus bars and control wiring with 1.5 Sq. mm. PVC
insulated LSZH (Low Smoke Zero Halogen ) copper conductor
cables, cable alleys etc. For all MCCBs Ics shall be 100% Icu.
The panel shall conform to the Electrical Inspectorate standards
and it shall only be manufactured after getting approval from the
the Electrical Inspectorate and the consultant.
Busbar
1 Runs of 25 x 10mm AL.Busbar for each Phase
1 Runs of 25 x 6mm AL.Busbar for Neutral
Incomer
1 Nos - 160A 4P Isolator
1 Set - RYB Indication lamps with Control MCBs
3 Nos - 150/5A CL:1, 10VA CT
1 Nos - Digital Multifunction Meter measuring V, A, F, KW,
KVA, PF with Control MCBs
1 Nos - 8 Stage Microprocessor based APFC Relay
1 Nos - 250/5A CL:1, 10VA CT in EB Side of MSB
Surge Protection Device
1 Nos - 4 Module DIN Rail Mounting Type 1 + Type 2 100kA
SPD on Incomer side with all accessories etc. complete
as required. The connections to RYB Phases, Neutral and Earth
shall be done using 16 Sq.mm Single Core Flexible Copper
cables with less than 0.45m in length.
Outgoings
1 Nos - 40A TP MCB with Capacitor Duty Contactor and
15 KVAr Heavy Duty Cylindrical Type Capacitor
1 Nos - 40A TP MCB with Capacitor Duty Contactor having
provision for fixing 15 KVAr Heavy Duty Cylindrical Type
Capacitor in future
1 Nos - 32A TP MCB with Capacitor Duty Contactor and
10 KVAr Heavy Duty Cylindrical Type Capacitor
1 Nos - 32A TP MCB with Capacitor Duty Contactor having
provision for fixing 10 KVAr Heavy Duty Cylindrical Type
Capacitor in future
1 Nos - 16A TP MCB with 5 KVAr Heavy Duty Cylindrical Type
Capacitor
1 Nos - 16A TP MCB with Capacitor Duty Contactor and
5 KVAr Heavy Duty Cylindrical Type Capacitor
1 Nos - 16A TP MCB with Capacitor Duty Contactor having
provision for fixing 5 KVAr Heavy Duty Cylindrical Type
Capacitor in future
8 Nos - Green ON Push Buttons with Indicators
8 Nos - Red OFF Push Buttons with Indicators
2 Nos - Cooling Fan ( 6 Inches)
DISTRIBUTION BOARD
Supply and fixing of following ways surface / recess mounting,
vertical type, 415 V, TPN MCCB distribution board of sheet
steel, dust protected, duly powder coated, inclusive of 200A
tinned copper bus bar, common neutral link, earth bar, din bar
for mounting MCBs (But without MCCB/MCBs) as required.
6 Way , Double Door
Supply and fixing of following ways surface / recess mounting,
vertical type, 415 V, TPN MCB distribution board of sheet steel,
dust protected, duly powder coated, inclusive of 200A tinned
copper bus bar, common neutral link, earth bar, din bar for
mounting MCBs (But without MCCB/MCBs) as required.
8 Way , Double Door
6 Way , Double Door
Supply and fixing of following way, horizontal type three pole
and neutral, sheet steel, MCB distribution board, 415V, on
surface/recess, complete with tinned copper bus bar, neutral bus
bar, earth bar, din bar, interconnections, powder coated
including earthing as required. (But without MCB/RCCB/Isolator)
6 Way , Double Door
4 Way , Double Door
Supply and fixing following rating and breaking capacity and pole
MCCB with thermal magnetic release having 70 to 100% setting
provision with terminal spreaders in the existing MCCB DB
complete with connections, testing and commissioning etc. as
required.
63A to 100A 25kA 4 Pole MCCB
Supply and fixing following rating, four pole, (three phase and
neutral), 415V, Residual Current Circuit Breaker (RCCB), having
a sensitivity current 30 mA in the existing MCB DB complete
with connections, testing and commissioning etc. as required.
Supply and fixing following rating, four pole, (three phase and
neutral), 415V, Residual Current Circuit Breaker (RCCB), having
a sensitivity current 100 mA in the existing MCB DB complete
with connections, testing and commissioning etc. as required.
Supply and fixing 5A to 32A rating, 240/415V, 10kA, C Curve,
miniature circuit breaker suitable for inductive load of the
following poles in the existing MCB DB complete with
connections, testing and commissioning etc as required.
Single Pole
Double Pole
Three Pole
40A to 63A Three Pole
MCB DUMMY
Supply and fixing single pole blanking plate in the existing MCB
DB complete etc. as required.
ISOLATOR
Supply and fixing following rating, four pole, 415V, isolator in
the existing MCB DB complete with connections, testing and
commissioning etc. as required.
63A 4P Isolator
40A 4P Isolator
Supply and fixing following rating, double pole, 240V, isolator in
the existing MCB DB complete with connections, testing and
commissioning etc. as required.
63A 2P Isolator
40A 2P Isolator
METAL ENCLOSURE
Supply and fixing Sheet Steel enclosure on surface / recess
having provision to fix MCB/Isolator complete with connections,
testing and commmissioning etc. as required.
HT CABLE
Supply, laying, testing and commissioning of 11 KV grade XLPE
insulated armoured cables of the following size and laying in
earth excavated trenches, clamping in built up trenches, trays
using heavy duty Aluminium or GI Flat or by using heavy duty
GI spacer saddles and on 11 KV pole structure using necessary
heavy duty GI supports and clamps of which spacing of clamps
not exceeding 40cm and pulling through pipes etc. including all
minor civil works.
3C x 300 Sq.mm
3C x 240 Sq.mm
3C x 185 Sq.mm
3C x 150 Sq.mm
LT CABLES
Supply, laying, testing and commissioning of PVC 1.1 KV grade
XLPE insulated armoured Aluminium / Copper cables of the
following sizes and laying in earth excavated trenches, clamping
in built up trenches, trays, racks, risers, trusses, walls etc. using
using heavy duty Aluminium Flat or heavy duty GI spacer
saddles of which spacing of clamps not exceeding 50cm and
pulling through pipes including all minor civil works.
3.5C x 185 Sq.mm Al. cable
3.5C x 150 Sq.mm Al. cable
3.5C x 120 Sq.mm Al. cable
3.5C x 95 Sq.mm Al. cable
3.5C x 70 Sq.mm Al. cable
3.5C x 50 Sq.mm Al. cable
3.5C x 35 Sq.mm Al. cable
4C x 25 Sq.mm Al. cable
4C x 16 Sq.mm Al. cable
4C x 10 Sq.mm Al. cable
4C x 6 Sq.mm Al. cable
4C x 4 Sq.mm Al. cable
4C x 2.5sq.mm. Copper Armoured cable
2C x 2.5sq.mm. Copper Armoured cable
4C x 1.5sq.mm. Copper Armoured cable
2C x 1.5sq.mm. Copper Armoured cable
HT END TERMINATION
Supply and making outdoor cable end termination with heat
shrinkable jointing kit complete with all accessories including
lugs, additional sleeves etc suitable for following size of 3 core,
XLPE Aluminium conductor cable of 11KV grade as required.
Supply and making indoor cable end termination with heat
shrinkable jointing kit complete with all accessories including
lugs, additional sleeves etc suitable for following size of 3 core,
XLPE Aluminium conductor cable of 11KV grade as required.
GLANDING AND TERMINATION
Supply and making end termination with brass compression
gland and alluminium lugs for following size of PVC insulated
and PVC sheathed/ XLPE Aluminium conductor cable of 1.1KV
grade as required.
3.5C x 185 Sq.mm Al. cable
3.5C x 150 Sq.mm Al. cable
3.5C x 120 Sq.mm Al. cable
3.5C x 95 Sq.mm Al. cable
3.5C x 70 Sq.mm Al. cable
3.5C x 50 Sq.mm Al. cable
3.5C x 35 Sq.mm Al. cable
4C x 25 Sq.mm Al. cable
4C x 16 Sq.mm Al. cable
4C x 10 Sq.mm Al. cable
4C x 6 Sq.mm Al. cable
4C x 4 Sq.mm Al. cable
4C x 2.5sq.mm. Copper Armoured cable
2C x 2.5sq.mm. Copper Armoured cable
4C x 1.5sq.mm. Copper Armoured cable
2C x 1.5sq.mm. Copper Armoured cable
GLAND EARTHING
Supply and providing gland earthing using Aluminium or copper
strip / shim / wire using copper sockets etc. complete as
required conforming to Electrical Inspectorate Standards.
3.5C x 185 Sq.mm Al. cable
3.5C x 150 Sq.mm Al. cable
3.5C x 120 Sq.mm Al. cable
3.5C x 95 Sq.mm Al. cable
3.5C x 70 Sq.mm Al. cable
3.5C x 50 Sq.mm Al. cable
3.5C x 35 Sq.mm Al. cable
4C x 25 Sq.mm Al. cable
4C x 16 Sq.mm Al. cable
4C x 10 Sq.mm Al. cable
4C x 6 Sq.mm Al. cable
4C x 4 Sq.mm Al. cable
4C x 2.5sq.mm. Copper Armoured cable
2C x 2.5sq.mm. Copper Armoured cable
4C x 1.5sq.mm. Copper Armoured cable
2C x 1.5sq.mm. Copper Armoured cable
PLATE EARTHING
Supply and providing earthing with CI earth plate 1200mm x
1200mm x 12.6mm thick electrode including accessories, and
providing masonary enclosure with cover plate having locking
arrangement and watering pipe of 2.7 meter long etc. with
charcoal/coke and salt as required conforming to relevant IS,
Electrical Inspectorate standards etc.
Supply and providing earthing with CI earth plate 600mm x
600mm x 6mm thick electrode including accessories, and
providing masonary enclosure with cover plate having locking
arrangement and watering pipe of 2.7 meter long etc. with
charcoal/coke and salt as required conforming to relevant IS,
Electrical Inspectorate standards etc.
EARTHING CONDUCTORS
Supply and providing the earth conductors of the following sizes
and laying in earth excavated trenches, clamping in built up
trenches , walls, trays, racks, risers, trusses, etc. using heavy
duty Aluminium Flat or heavy duty GI spacer saddles of which
spacing of clamps not exceeding 90cm without making holes in
the earthing conductor and pulling through pipes including all
minor civil works. All the joints shall be properly tinned and
all connections shall only be done using SS Nut and Bolts with
double washers etc. complete as required.
25 x 6 mm Copper Strip
25 x 3 mm Copper Strip
8 SWG Copper Wire
10 SWG Copper Wire
MS STRUCTURALS
Supply, fabrication and installation of cable tray and supports
using M.S angles and plates of adequate size painted with one
coat of epoxy primer and two coats of epoxy grey paint.
Supply, fabrication and installation of Transformer, Panel Board
mounting supports using C Channels of adequate size painted
with one coat of epoxy primer and two coats of epoxy grey
paint.
Supply, fabrication and installation of checkered plates of 6mm
thickness to use above the cable trenches duly supported with
channels and duly painted with one coat of epoxy primer and
two coats of epoxy grey paint.
DG EXHAUST PIPING
Supply and laying of 100mm dia exhaust line with flexible
including bends, flanges, nut, bolt, packing, necessary supports
etc. and painting the same using Heat resistant Aluminium paints.
Supply and laying of 150mm dia exhaust line with flexible
including bends, flanges, nut, bolt, packing, necessary supports
etc. and painting the same using Heat resistant Aluminium paints.
Providing thermal insulation of exhaust line glass wool with AL.
Sheet, chicken mesh, necessary supports and screws.
CABLE ROUTE MARKER
Supply and fixing cable route marker with 10 cm x 10 cm x
5 mm thick G.I. plate with inscription there on, bolted / welded
to 35 mm X 35 mm X 6 mm angle iron, 60 cm long with
painting and fixing the same in ground at 5 meter intervel with
cement concrete in M.15 Grade (1:2:4) etc. complete as required.
PIPES FOR CABLE PROTECTION
Supply and laying of the following size medium class GI pipe in
ground or clamping in wall/ceiling with heavy duty GI or
Aluminium clamps etc complete as required.
150mm dia
100mm dia
80mm dia
50mm dia
25mm dia
Supply and laying of the following size DWC HDPE pipe ISI
marked along with all accessories like socket, bend, couplers etc.
conforming to IS 14930, Part II complete with fitting and
cutting, jointing etc. in the existing trench, complete as required.
200mm dia
160mm dia
120mm dia
90mm dia
63mm dia
POINT WIRING
Wiring for light point/ fan point/ exhaust fan point/ call bell point
with 1.5 sq.mm FRLS PVC insulated copper conductor single
core cable in surface / recessed medium class PVC conduit, with
with modular switch, modular plate, suitable GI box / PVC
surface box and earthing the point with 1.5 sq.mm FRLS PVC
insulated copper conductor single core cable etc. as required.
Group C
Wiring for twin control light point with 1.5 sq.mm FRLS PVC
insulated copper conductor single core cable in surface/recessed
medium class PVC conduit, 2 way modular switch, modular
plate, suitable GI box / PVC surface box and earthing point with
1.5 sq.mm FRLS PVC insulated copper conductor single core
cable etc. as required.
Wiring for group controlled (looped) light point / fan point /
exhaust fan point / call bell point (without independent switch
etc.) with 1.5 sq.mm FRLS PVC insulated copper conductor
single core cable in surface / recessed medium PVC conduit, and
earthing the point with 1.5 sq.mm FRLS PVC insulated copper
conductor single core cable etc. as required.
Group C
Supply and fixing two module stepped type electronic fan
regulator on the existing modular plate switch box including
connections but excluding modular plate etc. as required.
Supply and fixing suitable size GI box /PVC surface box with
modular plate and cover in front on surface or in recess including
recess including providing and fixing 6 pin 16/20 A modular
socket outlet and 20 A DP modular switch, connections etc.
as required.
Supply and fixing suitable size GI box /PVC surface box with
modular plate and cover in front on surface or in recess including
recess including providing and fixing 3 pin 5/6 A modular socket
outlet and 5/6 A modular switch, connections etc. as required.
Supply and fixing suitable size GI box /PVC surface box with
modular plate and cover in front on surface or in recess including
providing and fixing 2 Nos. 3 pin 5/6 A modular socket outlet and
2 Nos of 5/6 A modular switch, connections etc. as required.
(For light plugs to be used in non residential buildings).
Supply and fixing suitable size GI box / PVC surface box with
modular plate and cover in front on surface or in recess including
providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet
and 15/16 A modular switch, connections etc. as required
Supply and fixing following size/ modules, GI box / PVC surface
box along with modular base and cover plate for modular
switches in surface or in recess etc. as required.
1 or 2 Module
3 Module
4 Module
6 Module
8 Module
12 Module
Supply and fixing following modular switch/socket on the
existing modular plate and switch box including connections etc.
as required.
5/6A switch
3 pin 5/6A socket outlet.
6 pin 15/16A socket outet
Telephone socket outlet
TV antenna socket outlet
Data socket outlet
Supply and fixing 3 pin, 5A ceiling rose on the existing junction
box/wooden block including connections etc. as required.
Supply and fixing modular blanking plate on the existing modular
plate & switch box excluding modular plate as required.
CIRCUIT WIRING
Wiring for circuit / submain wiring along with earth wire with the
following sizes of FRLS PVC insulated copper conductor, single
core cable in surface / recessed medium class PVC conduit as
required.
2 x 1.5 sqmm + 1 x 1.5 sq.mm earth wire
2 x 2.5 sqmm + 1 x 2.5 sq.mm earth wire
2 x 4.0 sqmm + 1 x 4.0 sq.mm earth wire
2 x 6.0 sqmm + 1 x 6.0 sq.mm earth wire
TELEPHONE, TV, DATA WIRING & CCTV WIRING
Supply and drawing following pair 0.5mm dia FRLS PVC
insulated annealed copper conductor, unarmoured telephone cable
cable in the existing surface/recessed PVC conduit as required.
Supply and drawing co-axial TV cable RG-6 grade, 0.7mm solid
copper conductor PE insulated, shielded with fine tinned copper
braid and protected with PVC sheath in the existing surface/
recessed PVC conduit as required.
Supply and drawing of UTP 4 pair CAT 6 LAN Cable in the
existing surafce/recessed PVC conduit as required.
1 run of cable
Supply and drawing of 3+1 CCTV Camera Cable in the surface/
recessed PVC conduit as required.
SUPPLY AND LAYING OF CONDUITS
Supply and fixing of following sizes of medium class PVC
conduit along with accessories in surface/recess including cutting
the wall and making good the same in case of recessed conduit
as required.
SUPPLY OF LIGHT AND OTHER ITEMS
Supply and providing the following fittings and items at site
Battern/Angle Holder
LED Bulb (up to 12W)
3W LED Deep Junction Box Light
LED Tube Set of 1 x 20W with Tube
12W LED Bulk Head
50W LED Flood Light
100W LED Flood Light
26W BLDC Ceiling Fan of Sweep 1200mm
High Speed Shutter Type Exhaust Fan of Sweep 150mm
Heavy Duty Metal Type Exhaust Fan of Sweep 450mm
INSTALLATION OF LIGHT AND OTHER FIXTURES
Installation, testing and commissioning of PVC battern / angle
holder fitting complete with all accessories directly on ceiling/wall
including giving connections etc. as required.
Installation, testing and commissioning of 3W LED Light in Deep
Junction Box complete with all accessories directly on ceiling
including giving connections etc. as required.
Installation, testing and commissioning of pre-wired, flourescent
fitting/compact flourescent fitting of all types complete with all
accessories and tube/lamp etc. directly on ceiling/wall, including
connections with 1.5 sq.mm FRLS PVC insulated, copper
conductor, single core cable and earthing etc. as required.
Installation, testing and commissioning of 50W LED Flood light
fittings complete with all accessories directly on wall/pillar/ceiling
including giving connections etc. as required.
Installation, testing and commissioning of 100W LED Flood light
fittings complete with all accessories directly on wall/pillar/ceiling
including giving connections etc. as required.
Installation, testing and commissioning of ceiling fan, including
wiring the down rods of standard length (up to 30cm) with 1.5
sq.mm FRLS PVC insulated, copper conductor , single core
cable etc. as required
Installation of exhaust fan in the existing opening, including
making good the damage, connection, testing, commissioning etc.
as required.
up to 450mm sweep
AIR CONDITIONER
Supply, installation, testing and commissioning of 1 TR inverter
5 star rated split AC with fully copper condensing unit, with
copper piping up to 5 meters.
Supply, installation, testing and commissioning of 4KVA wide
range, single phase, 50Hz, 170V-270V AC voltage stabilizer.
Supply of outdoor support stand for condensing unit of the 1 TR
split AC unit.
WATER PUMP
Supply, installation, testing and commissioning of 5HP/3.7KW
openwell submersible pump with head from 28 to 40M, with
8.0 to 3.8 LPS discharge, suction size 65mm and delivery size
50mm etc. complete as required. This scope does not include
SS ropes for hanging the pump and/or any piping works etc.
Supply, installation, testing and commissioning of 3HP/2.2KW
openwell submersible pump starter complete with connections
as required.
SAFETY EQUIPMENTS
Supply and fixing HT danger notice plate of 250 mm x 200mm,
made of mild steel at least 2mm thick and vitreous enameled
white on both sides and with inscriptions in signal red colour on
front side as required.
Supply and fixing MV danger notice plate of 200 mm x 150mm,
made of mild stee,l at least 2mm thick and vitreous enameled
white on both sides and with inscriptions in signal red colour on
front side as required.
Supply and fixing 2Kg Dry Chemical Powder (DCP) type fire
extinguisher complete with Gun Metal cap, hose with squeeze
grip nozzle, wall fixing brackets conforming to BIS: 2171 and
with ISI mark
Supply and fixing safety instruction chart in word duly framed in
good frame work as required.
Supply and providing a set of 2 Nos. 9.5 Litre capacity GI bucket
painted in post office red colour with prior coat of red oxide paint
and written with white paint "FIRE" and mounted on MS angle
iron frame with bracket of appropriate size and capacity including
filling sand etc.
Supply and providing First Aid Box as approved by St.John
Ambulance Brigade / Indian Red Cross conforming to IS 2217 : 1963
Supply and fixing laminated shock treatment chart duly mounted
on a good frame work
Supply and providing electrical grade rubber mat of size 2m x 1m
having 12mm thickness in front of panels and DBs conforming to
IS 15652 : 2006 standard.
Supply and providing electrical grade rubber mat of size 2m x 1m
having 6mm thickness in front of panels and DBs conforming to
IS 15652 : 2006 standard.
Supply and providing tested industrial safety helmet conforming
EARTH EXCAVATION AND BACK FILLING
Excavation of all types of soils for the laying of XLPE insulated
power cable, GI / HDPE / RCC Pipes, Earthing Copper
conductors to the required width and depth up to1.2m and back
filling after providing sand cushioning and protective covering by
laying bricks breadth wise above the cable. The supply of sand
and bricks will come within this scope. The trench dimensions
and specifications shall be as per the Electrical Inspectorate,
KSEB & CPWD standards.
Excavation and Back Filling
Supply and laying of Bricks
Supply and filling of sand
NAMING FOR IDENTIFICATION
Painting letters or figures of 2.5cm/4.5cm sizes with enamel paint
as identification mark to Panel boards, DBs etc as required.
DOCUMENTATION
Taking soil resistivity at site and obtaining test certificate from
Electrical Inspectorate (*All Statutory fees shall be remitted by
the Client / Consumer or it shall be reimbursed on the
submission of supporting documents).
Preparation of drawings and getting approval from Electrical
Inspectorate. (*All Statutory fees shall be remitted by the Client/
Consumer or it shall be reimbursed on the submission of
supporting documents).
Submission of completion report, arranging Inpsection and
obtaining Sanction Order from Electrical Inspectorate .(All
Statutory fees shall be remitted by the Client / Consumer or it
or it shall be reimbursed on the submission of supporting
documents.
Co-ordination with KSEB getting power allocation by the
submission of 7 sets of HT agreement and executing the
agreement etc or prepration of necessarry application,
drawings and submission to KSEB for getting HT/LT or
LT Connection. (All Statutory fees shall be remitted by the Client/
Consumer or it shall be reimbursed on the submission of
supporting documents.
Make of Electrical equipments/materials
All electrical materials/equipments shall be of best branded items with ISI, strictly as per schedule specification
Panel Boards: CPRI certified reputed manufacturers make
MCB/ELCB/DB - L&T/LEGRAND/SCHNEIRDER or equivalent
Cables & wires - Finolex/KEI/POLYCAB/RPG/V-GUARD
Switches/Sockets/Regulators - SCHEIDER/ABB/HAVELS/LEGRAND or equivalent
Rigid PVCPipes/Casing & Capping - A-ONE/REPUTED MAKE with ISI , Precession, Balco, GEO
Cable Glands & Sockets - REPUTED MAKE , Cosmos
Indicating Lamps - TEKINIC/RISHUB/STC, L&T, Schneider or equivalent
Ceiling/Exhaust fan: Havells, Orient, Usha, Crompton Greaves, Bajaj
Push Button- L&T, Schneider, Rishabh
Note :1 All materials, Items, Equipment shall be best branded items with IS and approved by client/KEL
2:Rate should be inclusive of Transportation, delivery and installation cost for all items
3.Rate should be Exclusive of GST.
4.Work should be executed as per DSR/PWD specification and direction of Engineer at site.
IBRAHIMKUTTY K K
AMJATH M A
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .