REGISTRAR NIT ROURKELA
NATIONAL INSTITUTE OF TECHNOLOGY, ROURKELA, ODISHA - 769008
Design, fabrication, assembling, wiring and supply of MAIN DISTRIBUTION METER PANEL and POWER DISTRIBUTION PANEL and other ancillary jobs in E, F,G ,TF blocks and Institute Guest House South Block in NIT Rourkela
2024_NITRK_828372_1
NITR/EM/2024/L/0736/1281
Open Tender
Electrical Goods/Equipment
Supply
120 days
NIT Rourkela
As per tender document
4 documents required · 4 mandatory
₹4,000
DIRECTOR NIT ROURKELA
₹1 L
Yes
3 Jan 2025
28 Sept 2024
22 Oct 2024
28 Sept 2024
21 Oct 2024
28 Sept 2024
28 Sept 2024 - 14 Oct 2024
Amount
Design, fabrication, assembling, wiring & supply of following Panels, fabricated out of 14/16 Gauge CRCA sheet steel in cubicle compartmentised modular construction complete with supporting rigid structure, interconnections, aluminium bus bar strip with heat shrinkable colour coded current density of bus bar 0.8 A per sqmm Identification on all breakers & MCCB to indicate the area they serve. Degree of protection IP 65, earthing hinged doors with 2.5 sqmm tinned braded copper wire, suitable for pedestal floor mounted with removable Gland Plates on bottom of the panel, all mounting plates shall be GI sheets. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. Galvanised hardwares with zinc passivation shall be used in fabrication of panels 2 Nos. earthing terminals shall be provided for all distribution panels. Panels shall be suitable for 415 V, 3 Phase, 4 Wire, 50Hz supply system.
MAIN DISTRIBUTION METER PANEL (Type 1): INCOMER: MCCB, 160A, 4P, 50 KA, 415 VAC with adjustable O/L, S/C protection with suitable spreader link & Rotary Handle with aux. contact- 01 set Make: SIEMENS (VA/VL series), LEGRAND Whole current Single phase, two wire energy meter 230/240 V (P-N), 10-60A, 50 Hz, Accuracy class 1.0 Burden Voltage circuit: < 0.5W and 1 VA Current circuit: < 0.1 VA : 12 nos. Make: SECURE SARAL RED, YELLOW & BLUE INDICATION LAMP 230VAC, ON OFF Indication Lamp 230 VAC LED Lamp with necessary switch control for operation during night hours. Outgoing: MCB, 63A,DP, 10 KA - 12 sets Make: SIEMENS / Legrand Terminal Block 150 A for outgoing feeders connected wth 16 sqmm copper flexible wire -12 sets Fabrication: 2/1.6 mm CRCA Steel Sheet (OUTDOOR TYPE) Aluminium bus-bar of suitable size Paint: RAIL 7035 Protection: IP65 Panel drawing will be finalized by EE, NIT depending on the compatibility of installtion on the existing pedestrial with minor modification.
MAIN DISTRIBUTION METER PANEL (Type-2): INCOMER: MCCB, 160A, 4P, 50 KA, 415 VAC with adjustable O/L, S/C protection with suitable spreader link & Rotary Handle with aux. contact- 01 set Make: SIEMENS (VA/VL series), LEGRAND Whole current Single phase, two wire energy meter 230/240 V (P-N), 10-60A, 50 Hz, Accuracy class 1.0 Burden Voltage circuit: < 0.5W and 1 VA Current circuit: < 0.1 VA : 09 nos. Make: SECURE SARAL RED, YELLOW & BLUE INDICATION LAMP 230VAC, ON OFF Indication Lamp 230 VAC LED Lamp with necessary switch control for operation during night hours. Outgoing: MCB, 63A,DP, 10 KA - 09 sets Make: SIEMENS / Legrand Terminal Block 150 A for outgoing feeders connected wth 16 sqmm copper flexible wire -09 sets Fabrication: 2/1.6 mm CRCA Steel Sheet (OUTDOOR TYPE) Aluminium bus-bar of suitable size Paint: RAIL 7035 Protection: IP65 Panel drawing will be finalized by EE, NIT depending on the compatibility of installtion on the existing pedestrial with minor modification.
MAIN DISTRIBUTION METER PANEL (Type-3): INCOMER: MCCB, 160A, 4P, 50 KA, 415 VAC with adjustable O/L, S/C protection with suitable spreader link & Rotary Handle with aux. contact- 01 set Make: SIEMENS (VA/VL series), LEGRAND Whole current Single phase, two wire energy meter 230/240 V (P-N), 10-60A, 50 Hz, Accuracy class 1.0 Burden Voltage circuit: < 0.5W and 1 VA Current circuit: < 0.1 VA : 09 nos. Make: SECURE SARAL RED, YELLOW & BLUE INDICATION LAMP 230VAC, ON OFF Indication Lamp 230 VAC LED Lamp with necessary switch control for operation during night hours. Outgoing: MCB, 63A,DP, 10 KA - 09 sets Make: SIEMENS / Legrand Terminal Block 150 A for outgoing feeders connected wth 16 sqmm copper flexible wire -09 sets Fabrication: 2/1.6 mm CRCA Steel Sheet (INDOOR TYPE) Aluminium bus-bar of suitable size Paint: RAIL 7035 Protection: IP65 Panel drawing will be finalized by EE, NIT depending on the compatibility of installtion on the wall.
Hall Area Shopping Complex Meter Panel Incomer: 250A 4P 50KA MCCB with O/L & S/C Thermal Magnetic Release, Rotary Handle & necessary spreader link - 01 set (Make: SIEMENS VL/VA series or Legrand) Digital MFM meter (96X96 mm),CTR-250/5, Cl-1, Aux supply-230V AC with R-Y-B and ON-OFF indicating lamp along with required SP MCB control OUTGOING: 63A 3P 36KA MCCB (Make: SIEMENS VL/VA series or Legrand) with O/L & S/C Thermal Magnetic Release, Rotary Handle, 100 A 3 phase whole current meter (SECURE) with suitable wiring by copper wire upto the terminal blocks - 03 sets each 40A DP 10kA MCB with 60 A 1-phase KWH meter (SECURE) - 06 sets each
Design, fabrication, assembling, wiring & supply of Following outdoor Panels, fabricated out of 14/16 Gauge CRCA sheet steel in cubicle compartmentised modular construction complete with supporting rigid structure, interconnections, aluminium bus bar strip with heat shrinkable colour coded current density of bus bar 0.8 A per sqmm Identification on all breakers & MCCB to indicate the area they serve. Degree of protection IP 65, earthing hinged doors with 2.5 sqmm tinned braded copper wire, suitable for pedestal floor mounted with removable Gland Plates on bottom of the panel, all mounting plates shall be GI sheets. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. Galvanised hardwares with zinc passivation shall be used in fabrication of panels 2 Nos. earthing terminals shall be provided for all distribution panels. Panels shall be suitable for 415 V, 3 Phase, 4 Wire, 50Hz supply system.
PDB Panel at Guest House (NB) Incomer-1: 400A 4P 50KA MCCB with O/L & S/C Thermal Magnetic Release, MCCB AUX. CONTACTs, Rotary Handle & necessary spreader links/Aluminium BusBar - 01 set (Make: SIEMENS VL/VA series or Legrand) Digital MFM meter (96X96 mm),CTR- 400/5A, 5VA Class: 1.0, Metering Current Transformer, Aux supply-230V AC with R-Y-B and ON-OFF indicating lamp along with required SP MCB control Incomer-2: 250A 4P 50KA MCCB with O/L & S/C Thermal Magnetic Release, MCCB AUX. CONTACTs, Rotary Handle & necessary spreader links/Aluminium BusBar - 01 set (Make: SIEMENS VL/VA series or Legrand) Digital MFM meter (96X96 mm),CTR- 250/5A, 5VA Class: 1.0, Metering Current Transformer, Aux supply-230V AC with R-Y-B and ON-OFF indicating lamp along with required SP MCB control 400A ONLOAD CHANGEOVER: 400A ONLOAD CHANGROVER SWITCH - 01 set Make: ABB/SOCOMEC Digital MFM meter (96X96 mm),CTR- 400/5A, 5VA Class: 1.0, Metering Current Transformer, Aux supply-230V AC with R-Y-B indicating lamp along with required SP MCB control OUTGOING: 200A 4P 36KA MCCB (Make: SIEMENS VL/VA series or Legrand) with O/L & S/C Thermal Magnetic Release, Rotary Handle, MCCB Aux Contact, Digital MFM meter (96X96 mm), CTR- 200/5A, 5VA Class: 1.0, Metering Current Transformer, Aux supply-230V AC with R-Y-B indicating lamp, ON/OFF lamp along with required SP MCB control - 03 sets each 100A 4P 36KA MCCB (Make: SIEMENS VL/VA series or Legrand) with O/L & S/C Thermal Magnetic Release, Rotary Handle, Aux supply-230V AC with R-Y-B indicating lamp, ON/OFF lamp along with required SP MCB control, 100 A 3 phase whole current KWH meter (SECURE) with suitable wiring by copper wire upto the terminal blocks - 01 set 63A FP 10 kA MCB: 06 sets 40A DP 10kA MCB : 06 sets
AMF Panel Incomer-EB 250A 4P 50KA MCCB with O/L & S/C Thermal Magnetic Release and suitable contactors for auto opertion MCCB Door Interlock (Rotary Handle) MCCB Spreader Link MCCB AUX. CONTACT 250A 4P POWER CONTACTOR AUX. CONTACTOR 2N0+2NC-COIL-230VAC ONDELAY TIMER-230VAC Digital MFM meter (96X96 mm),CTR-250/5, Cl-1, Aux supply-230V AC 250/5A, 5VA Class: 1.0, Metering Current Transformer Red Indicating Lamp, 230V AC Yellow Indicating Lamp, 230V AC Blue Indicating Lamp, 230V AC Red Indicating Lamp, 230V AC-ON GREEN Indicating Lamp, 230V AC-OFF START PUSH BUTTOM WITH NO ELEMENT STOP PUSH BUTTOM WITH NO ELEMENT 6A 10KA C-CURVE SP MCB 10A 10KA C-CURVE DP MCB Incomer-2-63KVA DG 250A 4P 50KA MCCB with O/L & S/C Thermal Magnetic Release and suitable contactors for auto opertion MCCB Door Interlock (Rotary Handle) MCCB Spreader Link MCCB AUX. CONTACT 250A 4P POWER CONTACTOR AUX. CONTACTOR 2N0+2NC-COIL-230VAC AUX. CONTACTOR 2N0+2NC-COIL-24VDC AUX. RELAY 2N0+2NC-COIL-24VDC AUX. RELAY 2N0+2NC-COIL-230VAC ONDELAY TIMER-230VAC AMF RELAY 12V-10A BATTERY CHARGER AUTO/MANUAL SWITCH Digital MFM meter (96X96 mm),CTR-250/5, Cl-1, Aux supply-230V AC 250/5A, 5VA Class: 1.0, Metering Current Transformer Red Indicating Lamp, 230V AC Yellow Indicating Lamp, 230V AC Blue Indicating Lamp, 230V AC Red Indicating Lamp, 230V AC-ON GREEN Indicating Lamp, 230V AC-OFF START PUSH BUTTOM WITH NO ELEMENT STOP PUSH BUTTOM WITH NO ELEMENT 6A 10KA C-CURVE SP MCB 10A 10KA C-CURVE DP MCB 10A 10KA C-CURVE DP MCB OUTGOING 100A MCCB 100A FP 36KA MCCB with O/L & S/C Thermal Magnetic Release – 02 sets MCCB Door Interlock (Rotary Handle) MCCB Spreader Link MCCB AUX. CONTACT Digital MFM meter (96X96 mm),CTR-100/5, Cl-1, Aux supply-230V AC 100/5A, 5VA Class: 1.0, Metering Current Transformer Red Indicating Lamp, 230V AC-ON GREEN Indicating Lamp, 230V AC-OFF 6A 10KA C-CURVE SP MCB OUTGOING 40A DP MCB 63A FP 10KA MCB -06 sets 40A DP 10KA MCB -06 sets
For detailed specification, please refer the Annexure TS of main tender document.
AAA SWITCHGEAR PVT. LTD
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .