Chief Mechanical Engineer, VPT
CMEs Dept.,2nd Floor,AOB,VPT,VSP 0891-287-3210 PA to CME 0891-287-3209 Dy. CME 0891-2873202 S.E (M) 0891-287-3213 Office
Up-gradation of Fire Fighting Facilities for OSTT Berth to accommodate Vessels of capacity 1,00,000 DWT and above (Cape size Vessels) as per OISD 156 guidelines (For detail work description refer NIT.)
2021_VPT_77629_1
48/ 2020-21/IMn EE/MOF/ MII/ OSTT/FFF,Dt.17.5.21
Open Tender
Miscellaneous Works
Item Rate
540 days
VPT
Please refer Tender documents.
9 documents required · 9 mandatory
₹1,770
Yes
AS PER NIT
Exempted
CMEs Dept.,2nd Floor,AOB,VPT,VSP
30 Jul 2021
18 May 2021
7 Jul 2021
18 May 2021
5 Jul 2021
29 May 2021
26 May 2021
Amount
PART - I Fire Hydrant, Jumbo curtain Nozzles and Water/ Foam Monitors.
Supply, Erection, Testing and Commissioning of Water Cum Foam Tower Monitors in SS316 construction. UL Listed Tower Mounted Long Range Water Cum foam Monitor with fixtures, clamps, SS Fasteners, supporting for riser pipe and monitor suitable to discharge 7570 LPM of water at horizontal range of 90-100 m and vertical range 30-40 m or 7570 LPM foam & water mixture with a horizontal throw range of 80-90 m and vertical range 30-40m with electrical /electro hydraulic equipment's for horizontal and vertical rotation, with base operation control. The operation of tower monitor shall be remote controlled, electrically operated from control tower and from Local flame proof Control panel . MOC of Nozzle, Body, Elbow, Bend, Flange, shall be SS316. The Monitor shall be suitable to install on structural platform at height of 20-22 mtr. All electrical component of shall be flameproof type suitable for gas group IIA/IIB A) . Make: HD Fire/ SBJ / New age/Fire Tech
Supply, Erection, Testing and Commissioning of Water Cum Foam Ground Monitors in SS316 construction. UL listed Water Cum foam monitors shall includes all fixtures, clamps, SS Fasteners and flanged connection as per ANSI B16.5 150# . Monitor suitable to discharge 2820 LPM of water at horizontal range of 60 m and vertical range 30 m or 2820 LPM foam & water mixture with a horizontal throw range of 55 m and vertical range 25 m with hadweel for horizontal and vertical rotation, with Manual operation control. MOC of Nozzle, Body, Elbow, Bend, Flange, shall be SS316. Make: HD Fire/ SBJ / New age/Fire Tech
Supply, Erection, Testing and Commissioning of Mayura type Jumbo water curtain spray nozzles in SS 316 construction. Mayura type Jumbo Water curtain spray nozzles in SS 316 construction, capacity 6000 lpm flanged connection as per ANSI B16.5 150# Complete with all required accessories as per OISD 156-2017 . JC nozzle are required on the central loading platform (CUB) in front of the loading/ unloading arms . JC Nozzle shall be capable of operating from the local control panel for each Oil Jetty and operational from Remote Control Panel The MOC of Body, flange shall be SS316. Coverage of nozzle shall be 40 Mtr horizontally and 20Mtrs vertical Make:SBJ / New age / HD Fire/ FIRE TECH
Supply, erection, testing and commissioning of Double Headed Standard Fire Hydrants (SS-316 size 63mm) Hydrant valve Confirming to IS : 5290 Type - A, ISI marked (S.S 316) with two separate landing valve including 80mm dia flanged inlet & 63mm dia female outlet complete with cap and other accessories. Make: SBJ / Sukan / Newage/ FIRE TECH
Double headed hydrant valves
Supply, erection, Testing and commissioning 80 mm dia SS 316 with 3mm thk Orifice plates for Hydrant Valve
Supply, erection, testing and commissioning of External FRP hose cabinet stand/wall mounted type. Fabricated out of FRP Body, 5mm thick & Door with 3mm thk. Front Glass, (3 mm thick glass with rubber beading) door and size of cabinet shall be 900 mm x 750mm x 250mm , quoted rate shall includes suitable stand for mounting, fasteners, Lock, Key, hammer etc. Hose Box shall be suitably marked on the outside with the letters "FIRE HOSE" including necessary locking arrangement. Make: SBJ / Sukan / Newage
Supply , Installation, testing and commissioning of 63 mm dia RRL Fire Hose of Type B (as per IS : 636) with SS316 coupling of 63 mm dia and length as described below including SS 316 male and female instantaneous type coupling, suitable for burst pressure of min 35.7 kg/sq.cm. Hose shall be permaline hose and coupling to I.S.903-1975 with ISI certification, riveted to hose pipe with copper rivets & 1.5 mm copper wire. Make: SBJ / Newage /Rapiddrop
Suppy, installation, testing and commissioning of standard size SS316 Branch pipe with Tripple purpose nozzle standard instantaneous type 63 mm dia coupling as per IS 2871. Make: SBJ / Sukan / Newage/ FIRE TECH
Supply, erection, testing and commissioning of SINGLE Headed Standard Fire Hydrants (SS-316 size 63mm) Make:SBJ / Make:Sukan / Newage/ FIRE TECH
Single headed hydrant valves
Supply , erection , Testing and commissioning 80 mm dia SS 316 with 3mm thk Orifice plates for Hydrant Valve
Supply, erection, testing and commissioning of External FRP hose cabinet stand/wall mounted type. Fabricated out of FRP Body, 5mm thick & Door with 3mm thk. Front Glass, (3 mm thick glass with rubber beading) door and size of cabinet shall be 900 mm x 750mm x 250mm , quoted rate shall includes suitable stand for mounting, fasteners, Lock, Key, hammer etc. Hose Box shall be suitably marked on the outside with the letters "FIRE HOSE" including necessary locking arrangement. Make:SBJ / Sukan / Newage
Suppy, installation, testing and commissioning of 63 mm dia RRL Fire Hose of Type B (as per IS : 636) with SS316 coupling of 63 mm dia and length as described below including SS 316 male and female instantaneous type coupling, suitable for burst pressure of min 35.7 kg/sq.cm. Hose shall be permaline hose and coupling to I.S.903-1975 with ISI certification, riveted to hose pipe with copper rivets & 1.5 mm copper wire. Make:SBJ / Newage /Rapiddrop
Suppy, installation, testing and commissioning of standard size SS316 Branch pipe with Tripple purpose nozzle standard instantaneous type 63 mm dia coupling as per IS 2871. Make: SBJ / Newage /Rapiddrop
Suppy, installation, testing and commissioning of M.S. Swing type of Hose Reel, Wall Mounting type with 19 mm bore with 36 M long Nylon braided high pressure rubber Hose as per IS 884, 6mm bronze shut off nozzle and valve confirming to IS 884. along the SS Isolation valve at tapping point. Make: SBJ / Newage /Rapiddrop
Supply, installation, testing and commissioning of SS 316 Air Release valve with isolation valve of 25 mm. dia. Make: Leader / Zoloto / Flowchem
Suppy, installation, testing and commissioning transportation, loading & unloading of Above ground M S ERW Heavy ( Class C ) Pipe as per IS:1239 Part-1 for 150mm die and below & IS:3589 Gr.Fe. 410 with .thk.6.35mm for 200 mm dia and above. Pipes for all sizes shall be provided with internal Poly-Glass coating of 1000 micron including cutting, screwing, welding etc. and providing all fittings (thickness of fitting+B50s shall be matched with parents pipes) like elbow, tee, reducer, companion flanges, All fittings shall be A234 WPB. All flanged valves shall be as per ASME B 16.20 and all gaskets shall be of metallic with SS316 spiral wounded CAF filler. All studs and nuts shall be SS 316 As per ASTM A 193 Gr.B7/194 Gr.2H . All ERW pipe with internal bead flushed fully with internal surface of pipe or maximum 0.2 mm projection or below throughout the length of pipe and flange fixing for Poly-Glass coating. Pipe to pipe joint shall be flanged type with Poly-Glass coating. External painting of pipe shall be as per Annexure-1 painting specification NOTE: THIS LINE ITEM INCLUDES RIENFORCEMENT PADS , CORROSION PADS WHERE EVER IS REQUIRED ALONG WITH ALL TYPES OF FITTINGS SUIT AT SITE , GASKETS , studs and nuts shall be SS 316 As per ASTM A 193 Gr.B7/194 Gr.2H INTERNAL AND EXTERNAL PAINTING AS PER TENDER SPECIFICATION) Suppy, installation, testing and commissioning, transportation, loading & unloading of Above ground M S ERW Heavy ( Class C ) Pipe as per IS:1239 Part-1 for 150mm die and below & IS:3589 Gr.Fe. 410 with .thk.6.35mm for 200 mm dia and above. Pipes for all sizes shall be provided with internal Poly-Glass coating of 1000 micron including cutting, screwing, welding etc. and providing all fittings (thickness of fittings shall be matched with parents pipes) like elbow, tee, reducer, companion flanges, All fittings shall be A234 WPB. All flanged valves shall be as per ASME B 16.20 and all gaskets shall be of metallic with SS316 spiral wounded CAF filler. All studs and nuts shall be SS 316 As per ASTM A 193 Gr.B7/194 Gr.2H . All ERW pipe with internal bead flushed fully with internal surface of pipe or maximum 0.2 mm projection or below throughout the length of pipe and flange fixing for Poly-Glass coating. Pipe to pipe joint shall be flanged type with Poly-Glass coating. External painting of pipe shall be as per Annexure-1 painting specification. The quantity of pipes are indicative and may vary depending upon thesite conditios. Accordingly, the bidder shall acess and supply the quntities as required. NOTE: THIS LINE ITEM INCLUDES RIENFORCEMENT PADS , CORROSION PADS WHERE EVER IS REQUIRED ALONG WITH ALL TYPES OF FITTINGS SUIT AT SITE , GASKETS , studs and nuts shall be SS 316 As per ASTM A 193 Gr.B7/194 Gr.2H INTERNAL AND EXTERNAL PAINTING AS PER TENDER SPECIFICATION) Pipes: Jindal / Surya Roshni / TATA / Fittings: Fittech/ Pipefit/ Montex
Suppy, installation, testing and commissioning of Above ground Seamless SS316L pipe as per ASTM-A-312, TP-316L, Schedule-20 including cutting, screwing, welding etc. and providing all fittings like elbow, tee, reducer, companion flanges, SS316 nut-bolt, SS washer EPDM gasket etc as per ASTM-A-403, WP-316L, Schedule-20 / ASTM-A-182, F-316, Class 3000# and including structure supports like clamps, ISMC, ISA, Base plate, hanger, U-Bolt etc. and including cutting holes and chases in brick/RCC wall / slabs complete with External painting with SS pipes painting as per tender specification. The unit rate of pipe shall include the cost of fitting and painting . Make: Jindal/ TATA/ Surya Roshni/MSL
Supply, installation, testing and commissioning of M.S Raised Face flange as per IS 2062 Gr. B , Flange dimensional standard as per ANSI B 16.5 Class 150 and above . All flange shall be provided with internally Poly galss coating 1000 micron . The quantity of flanges are indicative and may vary depending upon the length of each pipe supplied by the bidder. Accordingly, the bidder shall acess and supply the quntities as required. Make: Fittech/Amforge/ Pipefit/ Montex/ Tube bend
Supply, installation, testing and commissioning of SS Super Dublex Gate Valve With Rising Spindle ,as per API 603 with falnge end connection as per ANSI B 16.5 150 # and SS 316 Nut and Bolt as per ASTM A 193 Gr.B8M . The valve shall be tested as per API598. MOC of valve Body, cover & bonnet shall be as per A890GR.F5A, Trim, Body seat, disc shall be UNS J93404. Make: L&T(Audco), Flowchem, Advance valves, saki, venus, KBL
Supply, Erection, Testing and Commissioning of Motorised SS Super Dublex Gate Valve with Actuator.(For Jumbo Curtain & Tower monitor )SS Super Dublex Gate Valve with Rising Spindle ,as per API 603 with falnge end connection as per ANSI B 16.5 150 # and Nut and Bolt as per ASTM A 193 Gr.B8M .The valve shall be tested as per AP I598. MOC of valve Body, cover & bonnet shall be as per A890GR.F5A, Trim, Body seat, disc shall be UNS J93404 with open/close limit switches for Position sensing. Torque limit switches for instant torque relesing and control. a)MOV With Operting Voltage of 415 V AC 50 HZ and flameproof Enclosure with zone IIA/ II B application and 3-phase squirrel cage motor TEFC class F insulated (temperature rise limited to class B) both for motor and its terminal box, for outdoor duty, the motor shall be provided with anti-condensation heater. b)Actuator shall be provided with motor over-riding feature like hand wheel for emergency manual operation and a limit switch shall be provided whose contacts shall be used in the motor control circuit to forbid the motorized operation during manual operation by hand wheel. Internal wiring shall be tropical grade PVC insulated, stranded copper conductor cable of 10A rating for control circuits and required rating for motor. Make: L&T(Audco), Flowchem, Advance valves, saki, venus, KBL
200 NB Dia
150 NB Dia
International Shore Fire Connection (IFSC) through which water could be supplied to a tanker fire main if required for shipboard fire fighting. 1) Outside Dia : 178 mm,2) Bolt Circle Dia. : 132 mm, 3)Inside dia : 64 mm dia,4)Pipe connection 150NB dia, 5) Slots in flange : 4 Holes 19 mm in dia spaced equidistantly on a bolt circle of above dia, 6) slotted to flange periphery flange thickness 14.5 mm minimum. 7) Bolts and Nuts : 4 Nos. each of 16 mm diameter, 50 mm in length. Make: SBJ / Sukan / Newage
Supply, Installation, Testing and Commissioning of Pressure gauges with siphon tube and cock, Glycerine filled, 150mm dial, range - 0 to 16 kg/cm2 as per ,with isolation valve/cock including required all fixing accessories. MOC - SS316 for inlet of Tower Monitor , Water monitor and Water Curtain Nozzle. Make: H Guru /General Instruments / Wika
Supply , Installtion , Testing and commissioning of 25NB Gunmatal (Globe Valve ) Valve for above pressure gaguges. Make: L&T(Audco), Flowchem, Advance valves,Saki, Venus, KBL
Supply, Installation, Testing & Commissioning of Modular type ceiling mounted Clean agent type fire extinguisher, ISI Marked IS 15683:2006, having sprinkler with glass bulb rated at 68 deg.C, suitable for Class A,B and C type of fires, Capacity - 15 Kg. (required for Control room). Make: Supremex/FireFite/Safex
Fire Water Pump room
Supply , Installation, Testing & Commissioning of FM/UL of Flame Proof Electric motor driven Vertical Turbine pump suitable for rating mentioned below capable of starting automatically and also manually. Suppy, installation, testing and commissioning of Electrical driven Vertical turbine type pump set (for Hydrant / Water Monitor / Water curtain / Tower Monitor) ,Capacity : 900 cu.mtrs/hr @140 MWC at discharge flange complete with suitable HT Motor , base frame, coupling, coupling guard and all other accessories as required. Pump shall be able to deliver 150% of discharge with minimum 65% rated head with shut off not exceeding 140%. The pump , Motor and accessories manfacturing and installation shall comply to OISD codes. The pump set and its water contact parts shall be suitable for sea water application (1) MOC of Pump - (a) Casing diffuser: Super Duplex SS, (b) Suction bell mouth: Super Duplex SS, (c) Impeller and allied wear rings: Super Duplex SS, (d) Shaft & Shaft Sleeve: Super Duplex (e) Bearing bush: Thordon (f) Rising (Column) Pipe: Super duplex, (g) Discharge bend: Super Duplex (h) Muff Coupling with collar etc: Super duplex, (i) Suction strainer: Super duplex, (j) Stuffing box: Super duplex, (k) Sleeve, gland: Super Duplex, (l)Fasteners: SS316L, (m) Sole plate, Motor stool: M.S with epoxy coating, (n) Foundation bolts: SS316L, (o) Auto release valve: SS316L, 1)Motor Shall be Flameproof having Suitable KW Rating @ 1500 Rpm 2)Type : 3-phase squirrel cage motor TEFC class F insulated, IE 2 3) Motor Protection : IP 55 4) min 460HP / 344KW ( bidder shall validate the same during the contruction stage ) 5) Operting Voltage : 3.3 KV HT Supply 6) Column Length - 16.3 Meter . Note : Power for Main Electric pump shall be drawn directly from electrical substation. Necessary separate feeder with ACB for both pumps shall be made available by VPT in substation. Make: Pump : KBL/Flow more/Pentair /Grundfos/ Wilo (M&P) Motor: ABB/CGL/Siemens/WEG
Supply, Installation, Testing & Commissioning of Flame Proof FM/UL approved Electric driven Vertical Turbine Jockey pump suitable for rating mentioned below capable of starting automatically and also manually. Suppy, installation, testing and commissioning of Electrical driven Vertical turbine Jockey pump set Capacity : 900 LPM (54 m3/hr)@150 MWC at discharge flange complete with suitable LT Motor , base frame, coupling, coupling guard and all other accessories as required. The pump , Motor and accessories manfacturing and installation shall comply to OISD codes. The pump set and its water contact parts shall be suitable for sea water application (1) MOC of Pump - (a) Casing diffuser: Super Duplex SS, (b) Suction bell mouth: Super Duplex SS, (c) Impeller and allied wear rings: Super Duplex SS, (d) Shaft & Shaft Sleeve: Super Duplex (e) Bearing bush: Thordon (f) Rising (Column) Pipe: Super duplex, (g) Discharge bend: Super Duplex (h) Muff Coupling with collar etc: Super duplex, (i) Suction strainer: Super duplex, (j) Stuffing box: Super duplex, (k) Sleeve, gland: Super Duplex, (l)Fasteners: SS316L, (m) Sole plate, Motor stool: M.S with epoxy coating, (n) Foundation bolts: SS316L, (o) Auto release valve: SS316L, 1)Motor Shall be Non Flameproof having Suitable KW Rating @ 1500 Rpm 2)Type : 3-phase squirrel cage motor TEFC class F insulated and IE2 3) Motor Protection : IP 55 4) min 18HP / 13.2KW ( bidder shall validate the same during the contruction stage) 4) Operting Voltage : 415 V AC Supply @ 50 Hz 5) Column Length - 16.3 Meter Make: Pump : KBL/Flow more/Pentair /Grundfos/wilo(M&P) Motor : ABB/CGL/Seimens/WEG
Suppy, installation, testing and commissioning of Cassion pipe cover for vertical turbine pump shaft, MOC, SS316L with all required fixing accessories including painting as per Tender specification. (Length shall be as per postiive suction requirement). The unit rate of pipe shall include cost of fittings and painting. Fabricated
A) 800 mm dia - 8 mm Thickness
B) 400 mm dia - 8 mm thickness
Supply, erection, testing & commissioning of the following ERW steel pipe as per IS 1239 /3589. Suppy, installation, testing and commissioning of Above ground M S ERW Heavy ( Class C ) Pipe as per IS:1239 Part-1 for 150mm dia and below & IS:3589 Gr.Fe. 410 with .thk.6.35mm for 200 mm dia and above. Pipes for all sizes shall be provided with internal Poly-Glass coating of 1000 micron including cutting, screwing, welding etc. and providing all fittings (thickenss of fittings shall be matched wth parents pipes) like elbow, tee, reducer, companion flanges, All fittings shall be A234 WPB-W.All flanged valves shall be as per ASME B 16.20 and all gaskets shall be of metallic with SS316 spiral wounded CAF filler. All studs and nuts shall be SS 316 As per ASTM A 193. All ERW pipe with internal bead flushed fully with internal surface of pipe or maximum 0.2 mm projection or below throughout the length of pipe and flange fixing for Poly-Glass coating. Pipe to pipe joint shall be flanged type with Poly-Glass coating. External painting of pipe shall be as per Tender (Annexure-1 ) painting specification The quantity of pipes are indicative and may vary depending upon thesite conditios. Accordingly, the bidder shall acess and supply the quntities as required. NOTE: THIS LINE ITEM INCLUDES RIENFORCEMENT PADS , CORROSION PADS WHERE EVER IS REQUIRED ALONG WITH ALL TYPES OF FITTINGS SUIT AT SITE , GASKETS , studs and nuts shall be SS 316 As per ASTM A 193 Gr.B7/194 Gr.2H INTERNAL AND EXTERNAL PAINTING AS PER TENDER SPECIFICATION). Pipes: Jindal / Surya Roshni / TATA / Fittings: Fittech/ Pipefit/ Montex
MCC Panel- Supply , installation, testing & commissioning of Flameproof Modular compartmentalized Motor Control Centre fabricated main body from 14 SWG CRCA sheet. The panel shall be dust and vermin proof, 415V 3Ph, 50 Hz as per IP 42 construction. The panel shall be powder coated with FIRE RED with 7 tank process for clearing and phosphating before powder coating.The panel should be with Suitable incomer & outgoing to meet the above mentioned pumps puls with required starter and MCCBs CT, Voltmeter, Phase indicators, indication lamps, Aluminium bus bars with colour coded heat shrinkable insulating sleeves, All MCCB shall be suitable for motor duty application. Main components shall be of Siemens/Merlin Gerin / L&T / Schneider/ ABB. Cost including for required fabricated angle support, earthing & required also. ( as per site conditions it should be placed inside the pump room-indoor) - Vendor shall submit the GA/SLD drawing for review. The panel shall include the starters for jockey pumps. Outgoing Feeder a) 415 V Soft Starer for 37 KW motor rating for Jockey Pump - 2 Nos b) Out going feeders to diesel pumps-3 No's Incoming Feeder-250A MCCB, 25KA with required RYB Al. Bus bars. Make: SGPL/ Pyrotech/ Positronics/ Sunlight/ APJ
Suppy, installation, testing and commissioning of Diesel engine Flameproof Control panel with 2 set of battery charger , on/off push buttons , Hooter for all Diesel engine Fire Pumps with required control cables. Make: SGPL/ Pyrotech/ Positronics/ Sunlight/ APJ
Suppy, installation, testing and commissioning of Annunciation cum Remote Control panel (at Control Room) with on/off push buttons for all Fire Pumps with required control cables from Main panels.
Supply , Installation, Testing and Commissioning of SS Super duplex valve as per A890GR.F5A with double flanged connection as per ANSI B 16.5 Class 150 , Swing type Non-return valve including SS 316 nuts, bolts,as per ASTM A 193 Gr.88 M & 15mm thick compressed asbestos gasket including matching flanges complete as per requirement. Make: L&T(Audco), Flowchem, Advance valves,Venus, Saki, KBL
400 mm nominal dia
300 mm nominal dia
100 mm nominal dia
Supply , installation, testing and commissioning of SS Super Duplex Gate Valve With Rising Spindle ,as per API 603 with falnge end connection as per ANSI B 16.5 150 # and SS 316 Nut and Bolt as per ASTM A 193 Gr.B8M . The valve shall be tested as per API598. MOC of valve Body, cover & bonnet shall be as per A890GR.F5A, Trim, Body seat, disc shall be UNS J93404. Make: L&T(Audco), Flowchem, Advance valves,Venus, Saki, KBL
400 mm nominal dia
300 mm nominal dia
100 mm nominal dia
Supply , Installtion , Testing and commissioning of Gunmatal Globe Valve Make: L&T(Audco), Flowchem, Advance valves,Venus, Saki, KBL
Supply , Installation, Testing and Commissioning of pressure gauges with siphon tube and cock, Glycerine filled, 150mm dial, range - 0 to 16 kg/cm2 as per ,with isolation valve/cock including required all fixing accessories. MOC - SS316. Make: H Guru /General Instruments / Wika
Supply , Installation, Testing and Commissioning of pressure switches with tubing, isolation valves. complete as per requirement steel plated with IP 33 protection.(Inside the Pump room) MOC - SS 316 , DPST Contacts Make: Indfos / Switzer / Wika / Emerson
Supply , Fixing, commissioning of Electromagnetic Type Flow Meter complete with all accessories Flowmeter of size 300 NB having flow handling capacity of 150% of single pump discharge for test line Body - WCB , Flange 300# - with required accessories matching fianges, nuts, bolts gaskets etc. Make: E&H/ Emerson/ Yokogawa/ ABB/ Krohne Marshal
Providing & Fixing of 300NB Pressure Releif Valve . Flange end connection as per ASTM A 16.5 150#. with matching flanges, nuts, bolts, gaskets etc. which ever required as per site conditions. Make: Darling muesco / Rapidrop / Viking/Tyco
Supply , Installation, testing and commissioning of Precharged air vessel (size 250 mm dia & 1200 mm height) complete with adequate pressure gauge (as per design / requirement) with valves to operate as per operating sequences including 25 mm dia drain valve, air release valve with stop cock on the top, required inlet with isolating valve duly painted from inside and outside complete as required. (The vessel should be suitable of working pressure of 16 Kg/Sqcm including synthetic enamel paint over a coat of primer). Fabricated
LT CABLES Supply, laying, testing and commissioning of 1100 Volt grade XLPE insulated PVC type aluminium conductor FRLS armoured cables with required accessories. For Jockey Pump FRLS-H Standard Make: Polycab/Technoflex/Avocab/Alankar
3 C x35 Sq.mm FRLS Al Arm cable
12 C x 2.5 sqmm Cu Conductor, FRLS armoured as Control Cabling for diesel engine complete with all accessoires like double compression cable glands
24C x 1.5 sqmm Cu Control, FRLS Armoured Cable for FWPH to Control Room complete with all accessoires like double compression cable glands
4C x 1.5 Sq.mm Cu.conductor FRLS armoured cable for Flow meter complete with all accessoires like double compression cable glands
2 C x 1.5 sqmm Cu. Conductor, FRLS armoured cable for Instrumentation complete with all accessoires like double compression cable glands
G.I. Earthing strips of suitable size shall be run on floor / ceiling / walls, from the equipment to the nearest earth pit ( Existing- location to be identified at site ) with necessary accessories as required. ISI Approved
CABLE TRAY FRP Ladder / Perforated type cable tray with necessary bands, tees and clamps for fixing. All material shall be FRP. Cable Trays shall be considered with Double Coupler Plates. All Bolts shall be SS 316 L .Thickness of the cable tray material shall be 6 mm for 300 mm & above & 4 mm for below 300 mm size. Make: EPP/ Sumip/ Ercon
Providing & Fixing of Structural steel like Angle, Channels with fabrication, welding, Erection , base plate SS nut bolts fasteners for pipe supports with grounting with jetty surface and Gang ways structure as per VPT requirement etc. complete with corrosion protection of all structural items are to be ZINC COATED ABOUT 200 MICRONS (UNIT RATE INCLUDE ALL ABOVE ACTIVITIES ) Make: SAIL /TATA/Essar/Jindal
Suppy, installation, testing and commissioning of Double girder Electric Operated Under Slung Trolley Crane (EOT) (5- Ton Capacity) with 3Phase Motor and starter panel including with remote control necessary cabling etc..erection and commisioning and testing of crane by TPI. Make: Reva Industries /Safex Electromech / Brady & Morris /Eddy Crane
Suppy, installation, testing and commissioning of Double girder Electric Operated Under Slung Trolley Crane (EOT) (20- Ton Capacity) with 3Phase Motor and starter panel remote control necessary cabling etc..Erection and commisioning testing of crane by TPI. Make: Reva Industries /Safex Electromech / Brady & Morris /Eddy Crane/Mukand
FOAM SYSTEM
Design, supply, erection and testing of SS-316L Inline Balance Pressure Foam Proportionating System consisting of proportioner, spool valves, foam concentrate valve, drain cock valves, duplex gauge, pressure gauge, check valves at foam concentrate inlet, water & foam sensing line, automatic concentrate control valve with flush connection complete in all respect and suitable for out door installation.(Capable for Flow Max - 8000 LPM with 0.5 max. bar pressure drop) Make: Fire Tech /HD Fire
Suppy, installation, testing and commissioning of Foam barrel for 3% AFFF foam storage of solution (Each Cap 200 litre) - with foam concentrate for Ground water Monitor. Make: Integrated / KV fire / Firetech
Suppy, installation, testing and commissioning of Foam barrel for 3% AFFF foam storage of solution (Each Cap 200 litre) - with foam concentrate for testing Purpose. Make: Integrated / KV fire / Firetech
Structural supports including ISA, ISMC, M.S Plates, stiffener plate, u bolts, clamps etc. for piping and cable tray inside pump house complete with corrosion protection as per tender Specifications.(Annuxure-1) Make: SAIL /TATA/Essar/Jindal
Suppy, installation, testing and commissioning of Trolley mounted Foam concentrate tank (for Monitor capacity 2580lpm) of CS Construction (corrosion allowance for plate shall be considered minimum 2mm) with internal 4mm thick FRP lining of effective capacity:500 litre including drain valve etc. with Foam concentrate. Make: Fire Tech / HD Fire / New Age
MVWS FOR LOADING /UNLOADING MANIFOLD Scope: Design, Supply, Installtion, Testing & Commissioning of Water Spray system for loading arms. Make: L&T(Audco), Flowcehm, Advance valves/ KBL/Venus/Saki
SS Super Dublex Gate Valve SS with Rising Spindle ,as per API 603 with falnge end connection as per ANSI B 16.5 150 # and Nut and Bolt as per ASTM A 193 Gr.B8M .The valve shall be tested as per AP I598. MOC of valve Body, cover & bonnet shall be as per A890GR.F5A, Trim, Body seat, disc shall be UNS J93404 a)MOV With Operting Voltage of 415 V AC 50 HZ and flameproof Enclosure with zone IIA/ II B application and 3-phase squirrel cage motor TEFC class F insulated (temperature rise limited to class B) both for motor and its terminal box, for outdoor duty, the motor shall be provided with anti-condensation heater. b)Actuator shall be provided with motor over-riding feature like hand wheel for emergency manual operation and a limit switch shall be provided whose contacts shall be used in the motor control circuit to forbid the motorized operation during manual operation by hand wheel. Internal wiring shall be tropical grade PVC insulated, stranded copper conductor cable of 10A rating for control circuits and required rating for motor. 100 NB
Supply , Installation, testing and commissioning of SS Super Duplex Gate Valve With Rising Spindle ,as per API 603 with falnge end connection as per ANSI B 16.5 150 # and SS 316 Nut and Bolt as per ASTM A 193 Gr.B8M . The valve shall be tested as per API598. MOC of valve Body, cover & bonnet shall be as per A890GR.F5A, Trim, Body seat, disc shall be UNS J93404. 100 NB Make: L&T(Audco), Flowcehm, Advance valves/ KBL/Venus/Saki
Suppy, installation, testing and commissioning of Pressure Gauge, Bourdon type, Case- Die cast aluminium with polyethylene paint, movement - Ph bronze, wetted parts - brass, 150mm dial,Range 0 - 25 Kg/cm2, accuracy - +/- 1%. The instrument shall be suitable for zone IIA / IIB area classification. Make: H Guru /General Instruments / Wika
Providing and fixing a set of UL Listed SS316 MOC Medium Velocity spray nozzle (housing as per A351-CF8M) as per technical specification of Size 1/2" NPT, SS with required Spray angle. Each Nozzle body permanently marked with model number, batch number, spray angle, K-factor & UL mark . Make: HD fire /Tyco/ Viking
Suppy, installation, testing and commissioning of Above ground Seamless SS316L pipe as per ASTM-A-312, TP-316L, Schedule-20 including cutting, screwing, welding etc. and providing all fittings like elbow, tee, reducer, campanion flanges, sockolets and weldolets , SS316 nut-bolt, SSwasher, EPDM gasket etc as per ASTM-A-403, WP-316L, Schedule-20 / ASTM-A-182, F-316, Class 3000# and including structure supports like clamps, ISMC, ISA, Base plate, hanger, U-Bolt etc. and including cutting holes and chases in brick/RCC wall / slabs complete with External painting for SS pipes Enamle color code painting as per tender specification. The unit rate of pipe shall include the cost of all above items mentioned above )NOTE: THIS LINE ITEM INCLUDES ALONG WITH ALL TYPES OF FITTINGS SUIT AT SITE , GASKETS , EXTERNAL PAINTING AS PER TENDER SPECIFICATION) Make: Jindal/ TATA/ Surya Roshni /MSL
Flame Proof Local control panel
Flame Proof Local control panel of Die-Cast Aluminium construction with Push button and indication lamp for two valve Operation. Make: FEPL/ Baliga /Flexpro / CEAG /FCG / Sudheer
Explosen proof Junction box of Die-cast Aluminium construction complete with all required fixing accessories as per E&I Specification. (JB shall be suitable for installation in zone IIA / IIB classified area.) Make: FEPL/ Flamepack / Baliga / Flexpro / Neptune / Airlight/ Triflp
Supply, laying, testing and commissioning of 1100 Volt grade XLPE insulated PVC type aluminium conductor FRLS armoured cables with required accessories. 2C x 1.5 mm2 Copper Armoured FRLS Cable for pressure swtch connection. Make: Universal / Havells / RR Cables / Gloster Polycab/KEI
Structural supports including ISA, ISMC, M.S Plates, stiffener plate, u bolts, clamps etc. for piping and cable tray inside pump house complete with corrosion protection like Zinc coat about 200 microns. Make: SAIL /TATA/Essar/Jindal
CONTROL SYSTEM FOR TOWER MONITOR Supply, erection and testing of Flameproof Electrical System for remote Operation of tower monitor Make: Honeywell/ Siemens / Rockwell/ ABB/ Yokogawa a) Common Modular PLC Based remote control panel With Redundant CPU and Dual redundant Power supply Module for Powering field devices for opertion of Tower monitor , Mayura Jumbo Water Curtain Spray System. Control panel shall be CRCA Construction with tender painting scheme including Control Desk with required joy-sticks, Push-buttons, emergency stop switch, indicator lamps including inside wiring, earthing etc. up to terminals, System mimic diagram for displaying and overall view of configuration of tower monitors at Jetty (Status of tower monitors function to be indicated by LED indicators) including all required accessories. .PLC should have sufficient I/O with Several sensor/actuator Bus networks with Ethernet TCP/IP, Multi-task application software, Extended application-specific functions :Counting/position control, Analog/PID, Math functions, Fuzzy logic, etc, Compact pocket-size modules, Open network-Profibus-DP, DeviceNet, Fast Ethernet. compliant to IEC 61131. b) PLC panel have provision of connecting Redundant FO cable to connect Local Control Panel . C) Remote panel have provision of fire Pumps and foam pumps and jockey pumps operation and status signal D) Control Wiring shall be - 0.75 sq.mm Copper Flexible wires & all wiring enclosed in PVC channels . E) Seprate Grounding bus will be Provided at bottom of the Panel . F) All PLC function shall be tested at Factory before dispatched to site g)Third party interface over MODBUS TCP/IP h)Gas detection i)Communication j) Mayura /Jumbo Water Curtain Spray System k) Provision for Emergency shutting down of loading arms during the emrgency condition- for 5 no's to be provided on PLC (Control cable to be connected by HPCL) NOTE: PLC design to be rewiewed by VPT before placing order
Flame Proof Local control panel of Die-Cast Aluminium construction with suficient I/O Modue , Interface module for Control & Operation of ROM & MOV for ROM & Water Curtain system , ( For Tower Monitors Control panel should consist ,FORWARD, REVERSE, LEFT, Right, Jet & Fog Push Buttons exclusively ) SS316 , Explosen proof with double compression flameproof glands, suitable for installation in zone IIA/IIB classified area. wire with 25 % spare TB inside. Local control panel connected to PLC panel through Redundant FO cable Local control panel inclusive of: a) Input/Output Cards b) Analogue Input cards for interfacing of gas detector/flame detectors c) Push Buttons d) Indicating Lamps e) MCB's Make: Honeywell/ Siemens / Rockwell/ ABB/ Yokogawa
Explosen proof Junction box of Die-cast Aluminium construction complete with all required fixing accessories as per E&I Specification. (JB shall be suitable for installation in zone IIA / IIB classified area.) Make: FEPL/ Flamepack / Baliga /Flexpro / Neptune / Airlight/ Triflp
Supply , Installtion , Testing and commissioning of 6C single mode Fibre optic FRLS armoured Cable, PVC jacket,Armoured for Interconnection. Make: Molex/ Lapp/ Finolex/ Reliance
SSupplying, laying, testing and commissioning of 1100 Volt grade armoured Fire Survival cables with required accessories. Make: Polycab/Technoflex/KEI
24C x 1.5sq.mm, Cu. Armoured Cable - Control Cable - (RCP to MCC)
4C x 4sq.mm, Cu. Armoured Cable - Power Cable - (MCC to LCP)
12C x 2.5sq.mm Cu. Armoured Cable - Power Cable - (LCP to JB)
6P x 1.5sq.mm Cu. Armouted Cable - Control Cable - (LCP to JB)
4C x 2.5sq.mm Cu. Armoured Cable - Power Cable - (LCP to MOV)
5P x 1.5sq.mm Cu. Armouted Cable - Control Cable - (LCP to MOV)
CABLE TRAY FRP Ladder / Perforated type cable tray with necessary bands, tees and clamps for fixing. All material shall be FRP. Cable Trays shall be considered with Double Coupler Plates. All Bolts shall be SS 316 .Thickness of the cable tray material shall be 6 mm for 300 mm & above & 4 mm for below 300 mm size. Make: EPP/ Sumip/ Ercon
Structural supports including ISA, ISMC, M.S Plates, stiffener plate, u bolts, clamps etc. for piping and cable tray complete with corrosion protection lioke Zinc coated about 200 microns. Make: SAIL /TATA/Essar/Jindal
VHF- Radio System MOTOROLA
Supply, Installation, Testing & configuration of Hand heel units with 1850 mAh li ion, 16 programmable Channels 12.5 kHz / 25 kHz Channel Spacing, 1-5 Watts Power Output, User manual, 2.5" rugged belt clip, Heliflex Antenna, Rapid Charger etc..
Supply, Installation, Testing & configuration of VHF Synthesized Transceiver – REPEATER STATION Frequency range 136Mhz to 174Mhz,12.5/25 KHz Channel Spacing,50 Watts Power Output , Compact Microphone & cable Installation Kit (Trunnion), Power Cable, Front facing internal 4WSpeaker, Meets MIL STD 810. RG 213 U CO-AXIAL CABLE WITH CONNECTORS With GP Antenna 0db.
Supply, Installation, Testing & configuration of VHF Base station with required accociated accessories to full fill the requirement.
Portable Fire Extinguishers Make: Kanex / Safex / ANSUL / SBJ/ Zenith Fire Supply, erection, testing & commissioning of Portable fire extinguisher.
9 kg Capacity DCP (Dry chemical powder) Extinguishers , MS seamless body, as per IS:15683
75 kg capacity wheel mounted dry chemical powder fire extinguisher , as per IS : 10658/1999
50Lit capacity wheel mounted AFFF foam fire extinguishers as per IS: 13386
4.5 Kg CO2 fire extinguishers
Dismantling of Existing above ground pipes, Fire water Pumps and associated accessories, Valves (Hydrant Valves, Gate Valves, Butterfly Valves, etc). Dismantling includes : Dismantling of old MS works in joists, angles, plates, bracings, pipes of different sizes etc. including cutting rusty bolts and nuts etc. from damaged / corroded structures of jetty and stacking the materials at shore within 150 mtr. lead. Include for loading the dismantled steel materials into truck at Oil Jetty area, carriage of the materials over pucca road lead upto 2-4 Kms. and unload at the VPT Store Division after weighment, stack properly in stack yard etc. as directed including carriage by head load upto a lead of about 30 m of each of the two points. This includes , Dismantling of Electric Pumps , Diesel pumps and jockey Motor and its associated accessories 1)Replacing of Suction, Delivery, Priming Lines, By Pass Lines Pertaining to proposed New Fire Fighting Pumpsets at New Pump House as per drawings enclosed. 2)Existing old Tower monitor - Structral Steel , height of 20 meter along with two tower monitors and connecting piping , 4 no's jumbo curtain pipline, 11 no's of old fire Hydrant pipelines 3)Existing valves Size from 450 NB to 100 NB inside pumproom 4)Existing Hydrant monitors Valves and Water monitor with Accessories 5)Cutting of Pipes and dismattling of Valves inside pumphouse 6)Handing over the pipes and Valves to VPT designated location.
Cutting of existing hydrant standpost, & Jumbo curtain lines and installing Boiler Makers on flange with SS bolts and gaskets Cost included Blinds and Flanges where ever required for 11 hydrants and 4 jumbo curtians lines (THIS LINE ITEM INCLUDES SS BOLTS, Blinds and Gaskets )
Replacement of existing tower monitor Construction of SteelTower for Monitor with platform on top of the tower and necessary safety guards, ladder, & mid landing, etc. The tower shall design a taper lattice type steel structure of height 20 m and operating plateform shall be 2.5 m x 2.5 m & the base shall be as per the suitable wind, sway & siesmic load calculation. The calculation shall be performed on approved licensed software. The lattice structure/round pipe structure made from Structural supports including ISA/ISMC/M.S Pipe/M.S Plates/stiffener plate /u bolts/clamps etc. Drawing should be approved by any NIT/IIT/IACS members The entire steel structure shall be applied with fireproof paint of thickness corresponding to 2 hours fire rating as per respective UL design as instructed by Engineer-in-charge.
Foam Tank relocation inside tower structure attending any repair required and hydrotested tested for any leaks and provide new inlet, outlet connections, drain, venting, ladder, staging, manhole, level indicator, low and high level alarms, with transparent graduated scale & supports / saddles etc.,( Valves & Piping are of SS). Suitable dyke wall to be constructed to house the tank. The cost shall include the temporary storing arrangement for storage of Foam during relocation of foam tank. and shall attend any repairs required
FIRE DETECTION AND ALARM SYSTEM Control & Automation
Supply , Installation , Testing and Commissioning of Fire alarm and Control Panel having the Following features: a) Redundant Central Processing Unit ( CPU) b)16 lines 40 character backlit alphanumeric liquid crystal display (LCD) c) Loop ( signaling line circuit) Control Module with loop capacity of max. 250 devices. ( No. of loops : 2 nos.) d) Redundant Power Supply Unit e) Mudbugs gateway ( Redundant) f) Network Communication Interface for repeater panel. g) 24 hours backup battery and battery charger h) Stand alone enclosure i) Autodialed ( 5nos. dialing) j) Loop expandable to 4 loops Approvals : UL listed / FM / VDS approved. Make: Honeywell / Edwards / Siemens / Tyco / Bosch / SCHRACK
Supply , Installation , Testing and Commissioning of Repeater panel having the same display size and keypads as the Main Fire alarm Panel with required network communication interface unit. Make:Honeywell / Edwards / Siemens / Tyco / Bosch / SCHRACK
FIELD DEVICES
Supply , Installation, Testing and Commissioning of Addressable Multi-criteria Detector (Smoke & Heat).The intelligent multi criteria detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena. The detector shall have twin bi-color LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches. Device shall be with standard base. UL Listed. Make: Honeywell / Edwards / Siemens / Tyco / Bosch / SCHRACK
Supply,Installation,Testing & Commissioning of Flame proof Conventional Manual Call Point for outdoor marine application with Stainless Steel(SS-304) hardware, Material, 2Wire : Aluminum Lm6, IP 65, Anti corrosive epoxy powder coated Finish, Cable Entry : 2 x M25, Neoprene Gasket, 24V DC operating Voltage. The line item should include 1 meter length MS channel painted with Fire red color to mount the MCP along with canopy and Flame proof double compression cable glands & Flame proof MS platted stoppers to shield against rainy conditions and FLP JB with foundation works and related flexible hard conduits till the Hooter. Make: Flame pack / Baliga /Flexpro / Neptune / Air light/ FEPL/ EX-Protect
Addressable Monitor Module for monitoring of FLP Manual call point Make: Honeywell / Edwards / Siemens / Tyco / Bosch / SCHRACK
Supply,Installation,Testing & Commissioning of Flame proof Conventional Hooters For outdoor marine application Hooter, FLP, Type: Conventional Area classification: ZONE 1- Gr. IIA/IIB MOC : Aluminum die cast (LM6) IP rating -IP66 - Input Supply :24V DC; Sound level:106dB at 1 meter distance; Tone type: Single tone; Cable Entries: 2Nos 0.75ET; Finish: Epoxy Light grey shade 631/IS-5. With FLP double compression glants and Plugs. Make: Flame pack / Baliga /Flexpro / Neptune / Airlight/ FEPL/EX-Protecta
Supply,Installation,Testing & Commissioning of Addressable Safe Area Manual Call point. Make: Honeywell / Edwards / Siemens / Tyco / Bosch / SCHRACK
Addressable Control Relay Module for driving of FLP hooters . Make: Honeywell / Edwards / Siemens / Tyco / Bosch / SCHRACK
Addressable Relay Module for AHU tripping & closing of Fire Dampers Make: Honeywell / Edwards / Siemens / Tyco / Bosch / SCHRACK
Supply , Installation, Testing and Commissioning of Isolator Module for Isolating short / dewired / loose circuits with automatic resetting arrangement. Isolator Base can also be proposed, however in that case needs to be considered with each detector & module. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary decimal switches. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. FLP JB shall be considered. ( if required by system) Make: Honeywell / Edwards / Siemens / Tyco / Bosch / SCHRACK
Supply installation,Testing & Commissioning of Flame Proof Electrical Siren with Horizontal Single Mounting single Phase 220/250V, 2800 RPM 50Hz, AC RPM 50 C/s 1 km range, 1/2 HP, with required accessories like Flame proof double compression cable glands & Flame proof MS platted stoppers to shield against rainy conditions with required junction box. with required starter control panel to start / stop manually from control room or specified locations. Make: Kheraj / Perfect
FLAME AND GAS LEAK DETECTION SYSTEM HYDROCARBON GAS DETECTORS ( ZONE -1 - EEx'd) Type : Infrared Point type Accessories to be supplied : Calibration cup, Splash guard/dust guard ( SS material), rain guard , flashback arrestor , collecting cone Detector output: 4-20ma Range : 0-100% LEL With display unit Poison resistant Response time : T90</+ 10 seconds Repeatability : +/- 2% FSD IP rating : IP-65 Detector Housing material : SS 316 Zero drift : 2% FSD per year maximum Certification : FM approved/ UL listed Hazardous certification Approval : PESO/CMIFR Ambient Temperature : 0-50degree C ( Detector will be connected to nearest LCP) Make: Drager / Oldham / Crowcon / Gas sensor/ Det- Tronics
FLAME DETECTOR Type: UV/IR Spectral Response: UV: 0.185-0.260 µm; IR: 2.5-3 µm Detection Range: For Methane 16 Feet Response Time: 5 seconds; High Speed 150 msec response to saturated signal Adjustable time delay up to 30 seconds Sensitivity Range: up to 15 meters Field of view: Horizontal: 100 degrees, Vertical: 95 degrees Should have Automatic and Manual in-built test to ensure continued reliable operation Detector output: 4-20ma Should have Heated window for operation in harsh weather conditions Operating temperature: -40 OC to +70 OC Power supply: 18 to 30 V DC Cable Entry: 2 entries Should be EMI/ RFI protected as per EN61326-3 and EN61000-6-3 Outputs: i) Relays for alarm ii) fault indication iii) 4-20 mA iv) HART protocol v) RS-485 output Should have a special logic circuit to help prevent false alarms caused by solar radiation. Enclosure: Explosion proof Ingress Protection: IP 66 Certification : FM approved/ UL listed Hazardous certification Approval : PESO/CMIFR ( Detector will be connected to nearest LCP) Make: Tyco / Agni Controls/ Spectrex/ Rezontech / Gas sensor
SCADA Software - Server Package Make: Yokogawa/ Honeywell / Allen Bradley / Schneider
PUBLIC ADDRESS SYSTEM Supply, Installation, Testing & Commissioning of Flame Proof-Exf T6 IP 65 Speaker with 30W rated and 15W/20W/25W line matching transformer with Cast Aluminium LM 6, ZoneI & II, Gas groups Class-I & IIA, IIB, IIC, Neoprene Gasket, SS, 100V / 70V Line transformer, Sound output 115db, earthing terminals, input terminal blocks, Pilfer proof, FLP JBs with Mounting MS stand corrosion resistance for Hooter and JB with foundation works and related flexible hard conduits till the Hooters. Approval CCE & BIS, IS 2148. Make: Baliga / Bosch/Bose/EV
Supply, Installation, Testing & Commissioning of 6W wall Mount Speaker with line matching transformer and mounting accessories for indoor application.(For office area etc). Make: Honeywell / Bosch/Bose/EV
Supply, Installation, Testing & Commissioning of 6 Zone PA controller built in amplifier . And shall have pre-recorder massage facilty to evacuate in case of emergency conditions, and as per technical specification. Make:Honeywell / Bosch/Bose/EV. Make: Honeywell / Bosch/Bose/EV
Supply, Installation, Testing & Commissioning of 240 / 480W Power Amplifier. Make: Honeywell / Bosch/Bose/EV
Supply, Installation, Testing & Commissioning of 6 Zone Call Station with Goose neck Mic.with interconnecting cable. Make: Honeywell / Bosch/Bose/EV
Supply & Fixing of PA Rack .( Height as per site conditions) with interconnecting cable and cable power manager. Make: Honeywell / Bosch/Bose/EV
Supply, Installation, Testing & Commissioning of 10KVA UPS with interconnecting cable. Make: Honeywell / Bosch/Bose/EV
Network Video Recorder ( NVR) The storage solution shall be NVR based with Hot swappable of hard drive and hot spare redundancy (N+1). The actual estimated storage requirement shall be worked out as per the number of cameras at 15 fps, 4CIF resolution for 45 days storage. The contractor shall propose the best cost effective solution for storage with reference to the parameters mentioned in the technical specification. The contractor shall furnish the backup calculation sheet for storage while quoting. Make:Axis/ Bosch/Interlogix/ Pelco
Video Management Software: The Video Management System shall be a software based solution running on SMS server and communicating over Ethernet network using the TCP/IP network protocol. The proposed solution shall be based on the latest compatible Windows Server Operating System. The NVMS shall sustain full operation using CIF, 2CIF, VGA, 4CIF, 800 x 600 (0.5 m pixel) and Megapixel video resolutions (upto 5 MP ). It shall support all types of cameras and latest compression technology and Onvif compliant. The contractor shall propose his best solution to meet the requirement. The cost shall include the required licenses to meet the requirement.
IP Based Joystick Controller for PTZ Cameras. The same should be FCC & UL listed. Make: Axis/ Bosch/Interlogix/ Pelco
MS poles for outdoor cameras, made out of 5mm thick, 80mm dia pipe with zinc chromite primer & powder coating of suitable shade along with Outdoor IP 65 rated Flameproof Junction box for termination,Power supply & module fixing. Total Pole height including pedestal = 5Mts. Make: Local
NETWORKING ACCESSORIES
Supply, Installation , Testing and Commissioning of 24 ports , 10/100/1000Base-T ports + 4 SFP ports Metro Ethernet Switch and shall be rack mountable with SMPS power supply & other termination. The switch shall have 1 Gigabit port to communicate with other switches. Make: Moxa / Dlink/ Net gear / Cisco/ Hearschmann
Supply, Installation , Testing and Commissioning of 8 ports , 10/100/1000Base-T ports + 2 SFP ports Metro Ethernet Switch and shall be rack mountable with SMPS power supply & other termination. The switch shall have 1 Gigabit port to communicate with other switches. Make: Moxa / Dlink/ Net gear / Cisco/ Hearschmann
Supply, Installation , Testing and Commissioning of Wall Mount enclosure (9U x 550 W x 500 D) , Front Glass Door (tinted,Toughened) with Lock & Key, 2 pairs of 19" Mounting Rails with U-Marking Welded Side Walls Standard Accessories: 1U Cable Manager (1), Hardware Packet (1 Pkt) 6 Socket 5 Amp. Power Distribution Unit (1 No) Roof Mounted Fan Unit / 90 CFM /230V AC (1 No). Make: Moxa / Dlink/ Net gear / Cisco/ Hearschmann
Supply, Installation , Testing and Commissioning of LIU 24 PORT Rack Mount - Loaded (SC) SM. Make: LOCAL
Supply, Installation , Testing and Commissioning of Work station: 70 inch Monitor OS comprising Intel Xeon Processor, Quad Core 3.2 GHz. 8 GB ddR3 Ram, 500GB SATA Hdd, USB Ports, Keyboard & Mouse etc.. Make: HP/ DELL
CABLES AND ACCESSORIES Supply, Installation , Testing and Commissioning of the following size of Armoured Cables and type FRLS-H Standards
1P X 1.5 Sq.mm Fire Survival cable for Manual call point Loop connections Make: Polycab/Technoflex/KEI
2C X 2.5 Sq.mm FS cable for Hooter Loop connections Make: Polycab/Technoflex/KEI
1P X 1.5 Sq.mm Fire Survival cable for FLP Speakers connections Make: Polycab/Technoflex/KEI
Cat - E Ar. cable for Camera integration Make: Dlink / Belden / Radiant
3C X 2.5 Sq.mm FS Power cable for Network Swtches Make: Polycab / Bonton /Deepanja/ Polycab / Radiant
Supply, Installation, Testing, and commissioning of GI Conduit applicable for marine applications with required foundation works and fittings. ISI mrked
Supply, Instalaltion, Testing, and commissioning of HDPE sleeves as per site requirement. ISI mrked
CIVIL WORK
RCC foundation for Fire Water pumps.
RCC/PCC Foundation for Water monitor Operating Plat form and Hose Box foundation
Painting of existing 450 dia fire water lines specification provided in tender for pipline ( grit blasting and painting) as per IS 05 AND annexure attached for external painting
Painting of existing Tower (OLD TOWER) monitor with grit blasting and painting spec provided in tender for structural material . The entire steel structure shall be applied with fireproof painting of thickness corresponding to 2 hours fire rating as per respective UL design fireproofing system as instructed by Engineer-in-charge.
Pump Room stability to be certifed by ( IIT/NIT /IACS Member ) and their recommendation to be implemented by Bidder , which includes of all civil works with in the pump room including-All pumps foundation RCC works, RCC Tie beams , Slab Opening/Dismantling to suite the site requirements for installation of Pumps . The cost including all the labour and materials to excute the above said work. Any other related works as instructed by Engineer-in-charge shall be carriedout at site.
1)Construction of RCC buliding with shutters with proper anticorrosive paint a) Suitable for Exisiting Diesel Generator and Relocation of Same Diesel generator from Old pump house to new RCC building constructed on MD, b) Suitable for panel room of approx size ( 3mx5mx 3.5m height) 2) Dismantling of 3 no's Civil Cross over bridge and disposing the debris which included tranportation to shore by VPT suggested place Note : This line item cost including all the labour and materials to excute the above said work. .
Survey, Design, Supply, Installation, Testing and commissioning of Main Power control panel for Diesel Generator 200KV for OSST. The panel should have sufficent feeder for all power ( Jockey Fire pumps, foam pumps ), Berth lighting and communication services. Bidder to examine the present site conditions and accordingly has to be dervied suitable Power control panel. The panel must be Flame proof, Civil foundation works, Industrial MCCB,s or VCBs, Bus bars, earthing arrangement etc . Control panel to be design and wire daigram to be Approved by IACS body / BV / any statutory body.
Repair of existing control room , scope including plasting, new flooring with tiles , provide wash basin, required electrical works as modular fans , lighting ,wiring as suggested by vpt , new window with glass and new Door , False Cieling , painting of room ( suitable for marine environment ) as per VPT requirements etc as per site conditions.
Hiring of floating crane for installation and for transportation of materials/ equipment from shore to jetty and for taking back the dismantled materials/ equipment to shore shall be Vendor scope including boat arrangment for transporting material should be done by bidder. Bidder has to consider required costing for trasportation.
Eelctrical Audit of the entire berth by a competent person under Petroleoum rule 114. and OISD AND PESO guidelines related to Electrical Installations.
PART II
ANNUAL MAINTENANCE CONTRACT (AMC) FOR A PERIOD OF 10 YEARS FOR OPERATION AND MAINTENANCE (O&M) OF UPGRADED FIRE FIGHTING FACILITIES OF OSTT/VPT AFTER COMMISSIONING INCLUDING SPARES. SEE DETAILS AT ANNEXURE FOR PAYMENT TERMS AND CONDITIONS AND GENERAL INSTRUCTIONS.
Thermosystems Private Ltd
RKEC PROJECTS LIMITED
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .