Superintending Engineer, K. H.E.C., P.W.D.
Superintending Engineer, K.H.E.C., P.W.D.
Construction of proposed 2nos of basement Gplus2 building with provision of Gplus9 storied foundation for TERTIARY CARE CANCER CENTRE TCCC at College of Medicine Sagore Dutta Hospital Kamarhati Kolkata SITC of 1010 KVA Silent DG Set
2020_WBPWD_308170_1
WBPWD/SEKHEC/KNHED/NIQ12/20-21
Open Tender
ELECTRICAL WORKS ORG
Item Rate
120 days
TERTIARY CARE CANCER CENTRE
Please refer Tender documents.
4 documents required · 4 mandatory
₹2 L
Superintending Engineer, K.H.E.C., P.W.D.
1 Mar 2021
8 Dec 2020
8 Jan 2021
9 Dec 2020
6 Jan 2021
18 Dec 2020
14 Dec 2020
Amount
Supply , delivery at site on foundation , commissioning of 1010 KVA, 415V, 50Hz, 3Ø silent new DG Set, comprising of Engine, alternator, separate AMF panel, Base frame, Fuel tank, Battery, CPCB-II approved Engine & Acoustic Enclosure having following specifications :-
Engine:-
Make : CUMMINS/Caterpillar /Parkins/MTU/Volvo Penta
Engine Type : 4 Stroke Diesel Engine
Rated Output : 1180 BHP or Higher
Duty : PRIME
Cooling : Water cooled with radiator
Cylinder : 12/16
Aspiration : Turbo Charged
Type of Governor : Electronic
Fuel Tank Capacity : Minimum capacity 990 Ltrs.
Fuel Consumption at 75% rated Load with Radiator or Fan : 165 Ltr./ Hr. or Less
Fuel Consumption at 100% rated Load with Radiator or Fan : 216 Ltr./ Hr. or Less
Overload Capacity : 10% overload for one hour for every 12 hours continuous running at full load or better
Engine instrument Panel : Consisting of starting switch with Key, Lube Oil Indicator, water temperature Indicator, RPM indicator and hour meter.
Safety Controls : Emergency Stop, Low Lube Oil Pressure warning/ Shutdown, High Engine Water Temp. warning/ Shutdown, Sensor failure Indicator, Engine over speed indicator, Battery charging and low battery indicator
Exhaust Silencer : Residential Type
Starting system : 12V./ 24 V. starting system complete with starter motor, charging alternator with rectifier and Cutout as per manufacturer standard.
Battery : Lead Acid, Low Maintenance or SMF and conforming to relevant IS Specification with Low/High Battery Voltage and Weak Battery warning
Alternator
Make : Stamford/ Leroy Somer
Rating : 415 V., 3Ph. 50 Hz., 1010 KVA, 1500 rpm
Type : Brushless, self excited and self regulated
Insulation : Class H
Protection : screen-protected drip proof with Min.IP-23 degree of protection
Voltage Regulation (max) : ±1%
Winding connection : Star with Neutral
Total Distortion factor : Less than 3%
Total Harmonic distortion in output waveform : < 5%
AMF Panel
Cubical type floor mounted AMF panel made from 14 SWG Sheet Steel, duly pretreated, powder coated painted and aesthetically finished, suitable for controlling of 1010 KVA DG set having following specification/features.
i) 415V, 1600 A , 65KA, EDO type ACB with O/L, S/C, E/F protection and microprocessor based protection release , U/V release etc. [make: Legrand DMX3/ Siemens ‘WL’ series / Schneider Electric (Master pact )NW/ L&T (‘U power’ Series) /ABB Emax] - 2Sets
ii) In Built By-Pass switch for rated capacity
iii) On -delay timer for load change over
iv) On-delay timer for engine shut off
v) Engine On-Off switch (Push button type)
vii) Minimum five number indicating lamps to indicate 'mains ON', 'load on mains', Set running', 'load on set' and 'battery charger on'.
viii) Audio visual alarm for 'Low lubricating oil pressure', 'High water temperature, Start failure', and DG over load'.
x) Microprocessor based relay with composite meter for digital display of following.
Generator voltage/AC Mains voltage.
Generator Current in all phases
Frequency
Power Factor
Energy
Indication for alternator supply
Running time indications number of hours of operation and service intervals, service due indications
The AMF panel must be designed to ensure trouble free performance and ensure switching over Electrical Load to DG within 15 (fifteen) second from the instant of mains failure.
Acoustic Enclosure
The DG set should have integrated acoustic enclosure at the manufacturing state itself. High quality acoustic enclosure must be certified as per CPCB-II norms.
Base Frame
Common iron channel fabricated base frame containing the engine and alternator, mounted on AVM pads and having provision for lifting Hook.
INSTALLATION WORK: S&F MS angle iron structure made of (80x80x6)mm / (50x50x6)mm MS angle 50mm X 8mm MS flat, nut bolt etc to support 350mm dia MS pipe, chair for AMF panel etc. Incl painting as per GS.
Supply and Installation of exhaust pipe line connection with MS black pipe 350mm (14”) dia ISI approved, necessary nuts, bolts, washer, gasket incl. electrical welding where necessary.
S&F 350mm dia MS heavy type long bend
S&F 350mm dia MS heavy type 'T'
S&F 350mm dia MS plug.
Supply and Installation of exhaust pipe line connection with MS black pipe 250mm (10”) dia ISI approved, necessary nuts, bolts, washer, gasket incl. electrical welding where necessary.
S&F 250mm dia MS heavy type long bend
S&F250mmX 250mm X350mm MS heavy type reducing ''T''/ ''Y''
Painting the 350 dia MS black pipe by Aluminum paint of two coat over the RO primer. Approved make.
Painting the 250 dia MS black pipe by Aluminum paint of two coat over the RO primer. Approved make.
Wrapping the Exhaust pipe line (350mm dia) with Al. sheet high quality with necessary wire mesh & 50mm thick glass wool.as per direction of EIC.
Wrapping the Exhaust pipe line (250mm) with Al. sheet high quality with necessary wire mesh & 50mm thick glass wool.as per direction of EIC.
S&F rain protection canopy for 350mm Exhaust pipe.
wrapping the residential type exhaust silencer.
Hire charges for scaffolding by bamboo required rope of square type arrangement for smooth working & carriage of MS black pipe by vertical run & dismantling at the end of work.
Excavation of soil for installation of Earth Electrode and filling & ramming. For Soft Soil
Earthing with 80 mm dia GI pipe (TATA-Medium)x 3.0 Mts. long and 1 No. 65 mm x 8 mm galvanized (Hot Dip) steel strip (4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S & F 80 mm dia GI pipe (ISI-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe
Extra for treatment of soil by using salt and charcoal for earth electrod .
Supplying & fixing of galvanized (Hot Dip) MS flat 65 mm x 8 mm in excess of 4mt for each earthing.
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 65 mm x 8 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required
S&F black colour heat shrinkable PVC sleve for 65mm x 8mm GI Flat.
Supply & Laying of 1.1 KV grade single core 400Sqmm Copper Aurmoured cable, [Make :-Havells/ Gloster / Polycab ] through existing PVC pipe. [ 4nos x3run x10mt]
Supply and Laying of PVC insulated single core 240 sqmm copper conductor (Polycab /RRcable/ Gloster / Havels )
Supply and Laying 150mm dia spiral nylon pipe inside the DG foundation.
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cable as below : a. Single core 400 sqmm copper conductor
Finishing the end of following sizes armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials a. Single core 400 sqmm copper conductor
b. Single core 240 sqmm copper conductor
Supply & Laying of 16core 2.5Sqmm Copper Aurmoured control cable, after cutting floor/pavement/wall/ and making holes incl., embedding the cable at an average depth as 100mm and mending good the damages to original finish incl. removing the rubbish
Supply & Laying of 2core 6 Sqmm Copper Aurmoured cable, after cutting floor/pavement/wall/ and making holes incl., embedding the cable at an average depth as 100mm and mending good the damages to original finish incl. removing the rubbish
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : a. 16core 2.5Sqmm Copper Aurmoured cable
b. 2core 6Sqmm Copper Aurmoured cable
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. a. 2.5Sqmm
b. 6Sqmm
Supply and delivery DIESEL for 1010 DG set . ( 990 ltr DG oil Tank + 1200 ltr Reserve )
Cerring cost for 2190 ltr Diesel from Pump Station to Site .
Supply and delivery 200 ltr capacity Oil Tank as per direction of EIC .
Supply and delivery Diesel Hand fuel transfer pump . ( manual operation ) as per direction of EIC .
S&F 2 Kg capacity ABC type Gas pressure (DCP) fire extinguisher on wall by suitable size of iron bracket (Make - Fire Shield)
S&F 9 ltr. Capacity round fire bucket with iron hook and duly filled up by sand.
For External Fuel Tank Installation charge of fuel tank Incl S&F Iron chair made by (80x80x6)mm / (50x50x6)mm MS angle 50mm X 8mm MS flat, nut bolt etc including painting.
S&F fuel line by 25mm dia heavy gauge MS pipe with fittings inc welding arangement & painting.
S&F 25mm dia gun metal ball socket valve
Guarding arrangement of Fuel tank by 20mm X 6mm MS flat grill incl painting & locking arrangement with S&F 6 lever Godrej lock.
Terms & Conditions (i) Rate should be quoted inclusive of all applicable taxes and Duty etc. (ii) All materials, equipments & accessories must conform to relevant IS specifications. The DG Set to be supplied must be from the authorized OEM of the respective Engine Manufacturer. (iii) Necessary manufacturer's test certificate for Diesel Engine, Alternator etc. Will have to submit in triplicate copy during delivery of the equipment. (iv) Copy of "Type Approval Certificate" and Certificate of "COP" must be produced at the time of delivery issued from competent Authority (As per CPCB-II). (v) Circuit Diagram for AMF Panel must be submitted from the Manufacturer/OEM. (vi) The entire set must be warranted at least 15 months from the date of Delivery/12 months/ 5000 Hrs from the date of Commissioning whichever is earlier. However Engine & Alternator should be warranted of 2 years/5000 Hrs, whichever is earlier.
Defect Libilities Period : 01 Years
(Rate should be quotated including all taxes and duties)
CHAKRABORTY ENTERPRISE
THE INDIAN OVERSEAS TRADING COMPANY
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .