Nature of work : Supply, Installation, Testing and Commissioning of "Submerged Centrifugal " Type Pumpset with accessories and allied equipements at Bhagapura Reservior sump, Bhagapura Ind. Estate.
Sr. Item No. Description Qty. Unit Rate/Unit in Total Amount
Sr. Item No. Description Qty. Unit Rate/Unit in Total Amount
No. Rs without GST
1 1 Supply, installation, testing & commissioning of Providing submerged centrifugal pump sets with all required accessoires (water immersed, dry air filled, class "F"
insulated TEWC motor integrally mounted on volute casing pump sets for water duty, 3-phase, 50 ± 3% Hz, 415 ± 10% V along with suitable foundation / installation
device with cable length from pumps to panels & of following Material of Construction: Impeller: CF8M, Casing: C.I. FG 260, Wearing Ring: SS, TC mechanical seal,
CS/SS bearing, SS shaft with sleeve, SS strainer & MS motor body. For 22 Kw
For Supply Only 44.00 per Kw 11750.34
For ItC Only 2.00 Job 21157.48
2 2 Expansion Bellows : Supply, testing & commissioning of flange ends 250 mm Dia., PN-1.6, Expanssin Bellows as per EJMA standards of overall length of minimum 2.00 No. 8273.92
300 mm, designed for 15 mm axial compression and 5 mm axial extension with tie rods, etc. of following MOC & pressure ratings. The Flanges should be machined
faced and the dimensions, i.e. OD, ID, PCD, Thickness, Hole dia. & nos. of holes, etc., of Flanges should be as per ISO:7005-1: 1992 (E) for Steel Flange, : MOC:
Bellows: SA 240 Gr. 304; Internal Sleeve: SA 240 Gr. 304; Weldends: IS 2062 Gr. B; Flanges: IS 2062 Gr. B & Limit Rods & Nuts: CS - IS 1367 - (on Delivery Side)
3 3 DUAL PLATE CHECK VALVE (DPCV) : Supply, Installation, Testing and Commissioning of 250 mm Dia., PN-1.6, Double Flange Dual Plate Check (DPCV) Valve 2.00 No. 29063.76
confirming to manufacturing and testing as per API -594/ 598, having body of Cast Iron : IS-210, FG 260, Disc - Cast Steel - ASTM A216, Gr WCB, Hinge Pin - SS
The Flanges should be machined faced and dimensions, i.e. OD, ID, PCD, Thickness, Hole dia. & nos. of holes, etc. of flanges should be as per ISO:7005-2: 1988 (E)
for Cast Iron Flanges with required accessoreis, erection hardware, necessary mounting supports, etc. Valve seat tested to 16 Kg/cm2 and Body tested at 24 Kg/cm2 .
Hydraulic test certificate and certificate of material of construction of parts shall be submitted before despatch of valves. (on Delivery Side)
4 4 SLUICE VALVE : Supply, Installation, Testing and Commissioing of 250 mm Dia., PN-1.6, Double Flanged Manually Hand Wheel Operated Non Rising Spindle Sluice 2.00 No. 17521.48
Valve (PD Type Short Body) confirming to manufcaturing and testing standard of IS-14846, having body, Dome of Cast Iron - IS:210, FG 260 and Wedge seat ring of
SS 304 and Valve seal tested to 16 Kg/cm2 and Body tested at 24 Kg/cm2. The Flanges should be machined faced and dimensions, i.e. OD, ID, PCD, Thickness, Hole
dia. & nos. of holes, etc. of flanges should be as per ISO:7005-2: 1988 (E) for Cast Iron Flanges. Hydraulic test certificate and certificate of material of construction
of parts shall be submitted before despatch of valves (for Bypass arrangement on each pump delivery)
5 5 Providing and supplying & erecting & commissioning of ISI mark CI D/F Temper proof Air Valvewith SS 304float gun metal nozzle ofapproved make & quality 2.00 No. 28895.09
offollowing class and diameter including all taxes,insurance,transportation,freight charges,octroi,inspection charges,loading,unloadingwithout isolating sluice
valvePN 1.6 for 200 mm dia
6 6 Supply,Installation,Testing and Commissioning of 250mm dia Electric Resistance Welded (Up to 400mm)/ Submerged Arc welded (Above 400 mm) M.S. pipe having 100.00 R.Mt. 3132.01
thickness 5.0 mm beveled ends plate or coil conforming to IS-3589-20001 or its latest revision/ammendment for following thickness outside diameter at store or site
anywhere in Gujarat state including all taxes, insurance, transportation, freight charges, octroi, inspection charges, loading, unloading conveyance to departmental
stores, stacking etc. all complete.
7 7 SITC of MS Specials Flanged Ends : like (i) D/F Tapper/ Reducer/ Enlarger (ii) 90 Deg. D/F Bend (iii) D/F Distance Piece (iv) Single flanged M. S. Pipes piece for Air 200.00 kg 98.98
Valves (v) 90 Deg. Bend for By pass arrangement (vi) Blind Flange/ Blank plate (vii) Std. Drilled Flange for pumpset delivery (viii) Std. Drilled Flange for Header line
(ix) D/F required size Enlarger/ Reducer & specials required to complete installation, if any, etc. including bolts, nuts, washers, rubber packing, etc, suitable for
above pumpsets and common header. The Flanges should be machined faced and dimensions, i.e. OD, ID, PCD, Thickness, Hole dia. & nos. of holes, etc. of flanges
should be as per ISO:7005-1: 1992 (E) for Steel Flanges. M.S pipe of 168.3 mm OD & above should be conforming to IS-3589/ 2001 and for below 168.3 mm OD
conforming to IS-1239 Part-1/ 2004 shall be applicable. All specials & pipes should be painted by epoxy paint.
8 8 Pressure Gauges with Accessories : Design, Supply, Installation, Testing, Commissioning of 150 mm Dia. - 0 to 20 kg/cm2, Bourdon type Pressure Gauge, ±1% 2.00 No 1426.12
accuracy, Direct bottom, 1/2" NPT (M) process connection, IP 67, Glycerine filled, SS304 Case with Bayonet Type Bezel, SS316 L Bourdon Tube, SS 316 Movement
material, Aluminium dial with black graduation on white background, Micro Zero adjustable pointer, neoprene gasket, Blow out disc, shatter proof glass, SS tag
plate etc as per IS 3624 complete with syphon tube with isolating cock.
9 9 SITC of 250 mm Dia. x PN 1.6 (PN16) Full Bore Electromagnetic Flow Meter- Regular Power operated : Design, Supply, Installation, Testing, Commissioning of 2.00 No. 130210.32
Full Bore Electromagnetic flow meter with factory calibrated, Regular Power Operated, flanged connection, Flow sensor, Indicator, transmitter and totaliser with all
accessories viz. surge arrestor, associated cables, cabinets, hardwares, etc complete as per following specifications: (I) Flow Meter/ Sensor: DC pulsed type, IP
Protection, Flanged process connection as per ISO : 7005-1 : 1992 (E) or latest, SS304/ Metallic Alloy Flow Tube : SS316/ SS 316 L/ Hastelloy, Sensor : SS316/
Hastelloy Grounding Ring/ Inbuilt Grounding Electrode, lining : Neoprene/ Polyurethane/ Hard Rubber/ Rilsan lining, Coil Housing with Junction Box : SS304/
Die Cast Aluminium/ Carbon steel with Anticorrosive Paint, CS (Carbon Steel) flanges (II) Flow Transmitter/ Converter (Remote Field Mounted): Microprocessor
based, Modular design, 2 line LCD for indication of actual flow rate, forward, reverse, sum totaliser display, ±0.5% accuracy at 0.3 to 4 m/sec velocity, 4 to 20 mA
with HART/Modbus output, one scalable pulse, one status output, IP 67 protection, Die cast aluminium/ polycarbonate/ SS316 with Anticorrosive Paint/ PU finish
with glass window enclosure, Inbuilt EEPROM and Data Logger, 20 meters cable length for sensor to transmitter communication, etc., alongwith wall mounted/ stand
mounted cabinet. The Flanges should be machined faced and dimensions, i.e. OD, ID, PCD, Thickness, Hole dia. & nos. of holes, etc. of flanges should be as per
ISO:7005-1: 1992 (E) for Steel Flanges. (2 No. - For Flow meter on Common Header)
10 10 Providing , erecting , fabricating the M.S Structure as per requirement on site incorporating proper size of M.S. angles, flats, bars, channels, I-sections, complete 100.00 Kg 85.13
with cutting, welding, grinding & finishing duly painted with one coat of red oxide with erection on site as per direction of engineer in charge with necessary
grouting, cementing, plastering & finishing complete
11 11 Lifting/Lowering of submersible motor-pump set complete with required No.& size of casing pipes by means of proper chain pulley block and pipe. wrenches. Job 2.00 Job 1711.95
includes stacking of pipes chronologically after due checking of threads. For Open well Horizontal submersible pumpset for sump well (iii)Above 15 HP
12 12 Providing and erecting XLPE (IS:7098) (I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. To be laidon wall with necessary clamps or in existing 100.00 Mtr. 183.82
trench /pipe of following size of cables (A)3 1/2 core 25 Sq.mm (16Sq.mm1/2core)
13 13 Solderless crimping type Aluminium lugs conforming to IS suitable for cable of following size evenly crimped with high pressure tool & connected to switchgear 10.00 Each 15.15
terminals with brass/cadmium plated nut bolts in an approved manner. C) 16/25 Sq.mm.
14 14 Providing and,fixing heavy duty flange type brass double compression type cable gland with rubber ring for PVC insulated armoured cable complete without going 4.00 Each 66.66
tails,insulating tape etc for following size of cables. (A) 3 & 1/2 / 4 core 25 Sq. mm
15 15 Supplying & erecting XLPE (IS:7098) (I)-88 ISI unarmoured copper cable 1.1 KV grade to be erected as directed of following size. H) 3 core 10 Sq. mm. 60.00 Mtr. 443.39
16 16 Solderless crimping type Copper lugs conforming to IS suitable for cable of following size evenly crimped with high pressure tool & connected to switchgear 20.00 Each 10.10
terminals with brass/cadmium plated nut bolts in an approved manner.(B) 10 Sq.mm.
17 17 Providing and, fixing heavy duty flange type brass cable gland with rubber ring for PVC insulated armoured cable complete without going tails, insulating tape etc 4.00 Each 38.38
for following size of cables. C) 2 to 4 core 10 Sq. mm
18 18 Providing & erecting weather proof,dust &vermin proof,floor mounted front operated indoor type cubical panel board necessary IP-42 and above protection as per 4.00 Sq.Mtr. 19387.96
approval from engineer incharge made from 14 SWG thick CRCM.S. sheet for outer body & doors,16SWG thick CRCM.S. sheet for internal partition swith necessary
accesories, supporting angles/flats channel including cutting, bending, drilling, welding, riveting with internal partitions & cable alley as per requirements &
instruction of engineer-in-charge with erection of supplied switchgears, BUSBARS, suitable size of inter connecting PVC copper wire/copper-aluminiums trips, rubber
grommets, rib, bakelite control fuses/MCB for measuring instruments, earthbus& earth bolts, foundation flange-bolts-base Plates, sufficient nos.of hinged doors,
handle swith locking arrangement and rubber gasket, heavy duty end terminal connection, danger notice board,necessary ventilation, earthing strip complete.The
Panel shall be painted with epoxy powder coating. The standard companies switch gear shall be used and only manufacturers at CPRI approved factory ii) with
19 19 Providing and erecting busbar chamber confirming to IS-375 fabricated from 16G. M.S. sheet, dust & vermin proof having hinged door with rubber gasket and 2.00 Rn.Mtr. 4421.78
necessary busbar supports with COPPER busbar having current density not more than 1.6 Amp. / sq.mm (Rated current/ cross section area) duly wrapped with colour
insulation tape for phase sequence, three phase & neutral each suitable for following current capacity with necessary painting mounted on wall or pedestal frame of
required size with necessary connections.(A) Suitable for 63/100 Amp. capacity
20 20 Supplying and erecting triple pole & neutral 440V /500V panel mounting Copper Busbars with four equal Nos. of electrolyte bus having current density not more than 2.00 Rn.Mtr. 1961.42
1.6 Amp./sq.mm (Rated current/cross section area)duly wrapped with colour insulating tape for phase sequence off following current carrying capacity, erected
with necessary busbar supports/ insulators, main cable socket to each bar,erected inexisting cubical panel with necessary connections. (A) Suitable for 100 Amp.
21 21 Providing and erecting Approved make Four pole moulded case circuit breaker having breaking capacity ICU of 25KA. at 415V, having normal current rating up to 3.00 Each 6173.12
100A. with Fixed thermal & magnetic release suitable to work on A.C. supply 50 c/s.with all internal connections, spreader tinned copper & complete erected in
existing 16 G.M.S.housing. ICS=100% of ICU only Cat III
22 22 Suppl, installation, testing & commissioning of 415 V Fully automatic microprocessor based Variable Frequency drive for pump control 2.00 No. 62140.25
application as per general specification as under: The VFD unit shall have modular construction, 6 Pulse Bridge rectifier, speed control by means of sensorless vector
control (open loop), high torque at low frequencies, locking at high and low frequency settings, In-built PID control, frequency accuracy of ± 0.1 % (min), frequency
resolution of ± 0.1 Hz (min), protections against; a) overload (motor and drive), b) short circuit, c) ground fault, d) input /output phase loss (open circuit), e)
stalling, f) input / output undervoltage (momentary power loss restart), g) input / output overvoltage, h) over-frequency, i) Input surge, j) over temperature of
heatsink, k) loss of remote speed signal etc. The VFD shall also have userfriendly programming software & it shall be capable of at least two level parameter setting
with password lock for critical parameters, programming for I/Os, speed search function, copy parameters (upload / download) to other identical unit, tuning to
energy saving mode (maximum efficiency), event / fault recording (last 5 faults in non-volatile memory) & RS 485 communication port (MODBUS RTU protocol) with
required software. For 22 KW
23 23 Supplying and erecting approved make panel mounting type Digital Voltmeter having 3 digits LED display, 0to750 AC Volts range erected on existing panel board with 1.00 Each 1275.63
all connection, wiring etc.with manufacturers calibration certificate.
24 24 Supplying and erecting approved make panel mounting type Digital Ammeter having 3 digits LED display, external CT operated, calibrated for 0to1000 Amps suitable 1.00 Each 1558.43
to operate on 500 Volt AC,erected on existing panel board with all connection, wiring etc.with manufacturers calibration certificate.
25 25 Supplying and erecting Ammeter/ Voltmeter selector switch for 3phase AC Supply 500V on existing panel board with necessary connections. 2.00 Each 317.14
26 26 Providing & erecting L.T. Current Transformer with bar primary 50/5 to 1000/5 ratio 15VA burden erected in existing CRCA box duly secured with insulating 3.00 Each 274.72
materials connected tothe meter
27 27 Supplying & erecting approved make Power Factor Meter 150 mm dia flush/projection type/balanced & unbalanced load to work with appropriately provided 1.00 Each 5102.52
CT’s100/5A to 400/5A ratio & other accessories complete erected in M.S. box & connected to the circuit by means of PVC copper Core leads.
28 28 R, Y & B Phase Indicating Lamps (63.5 / 110 / 230 V AC) for Incoming module(s) 3.00 No 593.88
29 29 Supplying and erecting approved make suitable panel indicator LED type lamp, lenscover,complete erected with necessary connections. 5.00 Each 43.43
30 30 Providing and erecting AC-3 duty 3 Pole power contactor thermal overload relay (L&TBCH/Siemens, / C & S / Alstom make) [E] For 48 to 70 Amp. 1.00 Each 3554.19
31 31 Providing and erecting AC-3 duty 3 pole power contactor with 2NO & 2NC aux contacts complete with 415V/220V operating coil suitable for 1.00 Each 8141.61
(L&T,BCH,T.C.,Siemens,C&Smake). (C) for 60 / 70 A rating
32 32 providing and erecting Miniature circuit breaker single pole 6A to 25A suitable to operate on 240V A.C. system and having breaking capacity 10KA to be erected in 5.00 Each 112.11
existing box. confirming to IS 8828/1996 with ISI Mark Cat III.
33 33 Providing & erecting 415 V MCB Four Pole for Motor &Inductive Load (C-Curve) having 10KA breaking capacity & confirms to IS:8828 in existing box having following 2.00 Each 668.62
capacity (b)40 Amp.
34 34 Supplying and erecting approved make 415V bakelite fuse fittings for front connection/busbar type,to accommodate HRC fuselink, withspin-riveted brass contact, 4.00 Each 167.66
having thermoplastic inflammable material & single piece extruded brass box contact to lock with adequate cable hole to accommodate aluminium conductors
suitable for(withoutHRC fuse) C) 63 Amp.
35 35 TNC Switch for ACB controlled Incommer/ Bus Coupler / Outgoing modules, as required. 2.00 No 1695.79
36 36 Local / Remote Selector Switch for ACB controlled Incommer / Bus Coupler / Outgoings modules, as required. 2.00 No 578.73
37 37 EARTHING : Supplying & erecting earth pit of minimum bore dia.150mm size approved make Earthing Electrode consisting Pipe-in-Pipe Technology as per IS 3043- 2.00 No. 8636.51
1987 made of corrosion free G.I.Pipes having Outer pipe dia of 50mm having 80-200 Micron galvanising, Inner pipe dia of 25 mm having 200-250 Micron galvanising,
connection terminal dia of 12mm with constant ohmic value surrounded by highly conductive compound with high charge dissipation suitable for following type of
38 38 EARTHING : Supplying & erecting funnel type earthing having earth plate of following size burred in specifically prepared earth pit 3 mtr. below ground with 40 2.00 No. 7874.97
kg. charcoal and salt with alternate layers of charcoal & salt, 20mm.dia. G.I. PIPE with Funnel with a wire mesh for watering & bricks masonry block, C.I. Cover
complete as per para 7.3 of IS 3043 with necessary length of double Galvanised Iron / copper earth wire No 6 SWG bolted with lug to the plate and covered in
mm dia. G.I. pipe 2.5 mtr long complete connected to the nearest switch gear with end socket as per direction & duly tested by earth tester confirming to IS (As
per drawing) with following specification - with 60 x 60x 0.315 cms. Copper Earth Plate
39 39 Supply & erection of 30 mm x 6 mm thk. HOT deep Galvanised iron strip for earthing of H.T. , OCB/ ACB/ Transformer LT PANEL board, Motors, etc. using proper 70.00 kg 77.77
clamp for earthing
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Submerged Pump Bhagapura Schedule-B.pdf
Corrigendum-01 Submerged Pump Bhagapura.pdf
Submerged Pump Bhagapura Schedule-B.pdf
Corrigendum-01 Submerged Pump Bhagapura.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .