Executive Engineer EDII KPDCL Rajbagh
Office of the Executive Engineer EDII KPDCL Rajbagh
Supply Installation Testing and Commissioning of various electrical items required for Upgradation or Upkeement of Electrical Network at Civil Secretariat Srinagar CP and AO Srinagar under Capex 2026 to 2027 with Scheme Code PDDSS2627100283
2026_PDD_327399_1
EDII/eNIT20 of 26-27SITC of electrical items required Upgradation Electrical Network CivilScretarait
Open Tender
Electrical and Maintenance Works
Percentage
45 days
Karanagar
As Per SBD
8 documents required · 8 mandatory
₹500
Executive Engineer EDII KPDCL Rajbagh
₹18,820
28 Nov 2026
7 Oct 2026
1 Dec 2026
10 Oct 2026
28 Nov 2026
10 Oct 2026
10 Oct 2026 - 10 Oct 2026
180 days
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | COMPONENT (1) : New items | - | - | - | - |
| 2 | Loading ,Unloading , Carriage ,Supply,Fabrication Installation/Fixing/ laying Testing and Commissioning of following Items/ Equipments | - | - | - | - |
| 3 | Three-Phase LT Distribution Box, complete with RYBN Aluminium Bus Bars 60X10 mm (600 MM) with suitable insulation covers, suitable for 3-Phase, 440 V, 400 A operation, housed in a robust, properly fabricated and powder-coated sheet-metal enclosure with min 2.0 mm thick MS sheet, with properly reinforced double doors, heavy-duty hinges, suitable locking arrangement and mounting supports/legs complete in all respects with the following:
1. 400 A, 4-Pole, 36 kA MCCB – 1 No. for incomer, with adjustable thermal setting.
2. 400 A, 4-Pole, 36 kA MCCB – 1 No. for bus coupling, with adjustable thermal setting.
3. 250 A, 4-Pole, 25 kA MCCB – 6 Nos., with adjustable thermal setting,
4. Multi-Function Digital Meter – 1 No. for measurement/display of Voltage, Current, Frequency and Power.
5.RYB Phase Indicating Lamps, reputed make, complete with necessary accessories.
6.“DANGER – 440 VOLTS” warning plate of suitable size, prominently fixed on the enclosure.
The LT Distribution Box shall be supplied, installed, tested and commissioned complete in all respects, conforming to relevant IS/IEC standards and departmental specifications.including dismantelling of existing MCCBs of existing Pannels and installation of same where ever required | 1 | Job | 2,93,173.47 | ₹2,93,173.47 |
| 4 | Three-Phase LT Distribution Box, complete with RYBN Aluminium Bus Bars 60X10 mm (600 MM) with suitable insulation covers, suitable for 3-Phase, 440 V, 400 A operation, housed in a robust, properly fabricated and powder-coated sheet-metal enclosure with min 2.0 mm thick MS sheet, with properly reinforced double doors, heavy-duty hinges, suitable locking arrangement and mounting supports/legs complete in all respects with the following:
1. 400 A, 4-Pole, 36 kA MCCB – 1 No. for incomer, with adjustable thermal setting, of Legrand/L&T/Schneider/Havells or equivalent make.
2. 250 A, 4-Pole, 25 kA MCCB – 6 Nos., with adjustable thermal setting, of Legrand/L&T/Schneider/Havells or equivalent make.
3. Multi-Function Digital Meter – 1 No. for measurement/display of Voltage, Current, Frequency and Power, of Schneider/L&T/Siemens or equivalent make.
4.RYB Phase Indicating Lamps, reputed make, complete with necessary accessories.
5.“DANGER – 440 VOLTS” warning plate of suitable size, prominently fixed on the enclosure.
The LT Distribution Box shall be supplied, installed, tested and commissioned complete in all respects, conforming to relevant IS/IEC standards and departmental specifications.including dismantelling of existing MCCBs of existing Pannels and installation of same wher ever required | 1 | Job | 2,65,110.67 | ₹2,65,110.67 |
| 5 | Luminaire on existing poles/ structure/wall of 190 W LED outdoor flood/street with IP66/IP67, die-cast aluminium housing, toughened glass/PC lens, 230 V AC, 50 Hz, PF ≥0.95, THD ≤10%, efficacy ≥120 lm/W, CCT 5700–6500 K, surge protection ≥6 kV, suitable for outdoor installation, complete with LED driverHeavy-duty GI/MS mounting arm/bracket, suitable for luminaire, complete with clamps, U-bolts, nuts, washers and painting/galvanizing,25 mm² / 32 mm² weatherproof junction/terminal box ,IP 65/^^ with suitable cable glands and terminals set,1.5 sq.mm, 3-core copper flexible/FRLS cable, from junction box to luminaire, approx. 3 m
6 A/10 A, 2-pole MCB, 10 kA, suitable for lighting circuit
Outdoor weatherproof switch, 6/10 A, 1-way, IP55/IP65, complete with box
2.5 sq.mm, 3-core copper XLPE/FRLS cable, suitable for outdoor power connection, including termination
Brass/nickel-plated cable glands, lugs, ferrules, heat-shrink sleeves, PVC insulation tape, SS/GI hardware and miscellaneous accessories,
Earthing connection with 6 sq.mm copper/GI earth wire, lugs and accessories | 4 | No | 8,295.36 | ₹33,181.44 |
| 6 | Construction of 15 RM long , 500 mm wide X 1000 mm deep Cable Trench by laying Reinforced Cement Concrete (RCC) 1:2:4 (1 cement : 2 coarse sand : 4 graded granite/basalt stone aggregate of 20 mm nominal size), including excavation in existing earth, centering and shuttering, reinforcement with TMT bars and angle irons as per KPDCL Drawings, 15 mm thick cement plaster in 1:6 mortar, fabrication and fixing of required structural components, backfilling with excavated earth and disposal of surplus excavated soil as directed by the Engineer-in-Charge, and Supply including loading, carriage and unloading of all materials, complete in all respects as per approved drawings, KPDCL standards and directions of the Engineer-in-Charge. | 15 | Rm. | 11,700.79 | ₹1,75,511.85 |
| 7 | Cutting to required size, fabrication, drilling, fixing and placing of 6 mm thick Mild Steel Chequered Plates, conforming to IS 3502, including necessary supports, stiffeners, welding, bolts, nuts and other fixing accessories,for covering the cable trench including loading, carriage and unloading of materials to site, complete in all respects as per approved drawings and directions of the Engineer-in-Charge. | 300 | Kg | 91.2 | ₹27,360 |
| 8 | 400mm² Single Core Cable,1.1kV Grade, Armoured, XLPE Insulated Stranded Conductor FRLS type, as per approved drawings/standards | 30 | Mtr | 1,147.86 | ₹34,435.8 |
| 9 | Heat Shrinkable Straight Through Jointing Kit for LT 3.5 Core Cable, 185–240 Cable | 3 | set | 4,288.23 | ₹12,864.69 |
| 10 | Heat Shrinkable End termination Kit for 3½ C 185-300mm | 3 | set | 3,624.06 | ₹10,872.18 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.38 MB
Tendernotice_2.pdf
PDF • 1.06 MB
allspec_merged.pdf
Tender Documents • 33.92 MB
Drawing1updated.pdf
Tender Documents • 0.47 MB
Drawing2updated.pdf
Tender Documents • 0.56 MB
SBD20updated.pdf
Tender Documents • 1.04 MB
Vendorlist.pdf
Tender Documents • 3.28 MB
BOQ_1107710.xls
BOQ • 0.32 MB
ExtensioneNIt204th.pdf
PDF • 0.34 MB
ExtensioneNItthird.pdf
PDF • 0.34 MB
ExtensioneNItsecond.pdf
PDF • 0.34 MB
Extensionupdated.pdf
PDF • 0.34 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .