Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.3 LAccepted-AOC | ₹6.3 L Quoted ₹6.6 L | L1 | Accepted-AOC Lowest |
| 2 | L2₹6.9 L+₹33,770 (5.12%)Rejected-Finance | ₹6.9 L+₹33,770 (5.12%) | L2 | Rejected-Finance Second lowest |
Tender Value
₹6.1 L
EMD Value
₹9,200
Closing Date
17 Feb 2023, 6:00 pmClosed
The Executive Engineer Electrical HEED Harbour Eng
O/o The chief Engineer, Harbour Engineering Electrical Division, Kamaleswaram, TVPM
Supply and Installation of Two numbers of Ice Conveyor with Crusher at Ponnani Harbour Electrification
2023_HED_555369_1
49/HEED/2022-23/S
Open Tender
Electrical Works
Item Rate
45 days
PONNANI
Please refer Tender documents.
6 documents required · 6 mandatory
₹1,400
₹9,200
7 Jul 2023
3 Feb 2023
20 Feb 2023
3 Feb 2023
17 Feb 2023
3 Feb 2023
Amount
Supply and installation of wall mounting cubicle type dust and vermin proof size 4 , 600x300x214 mm, Mi2410 thermoplastic box including supply and fixing 63A, 25kA,4pole MCCB with BUC rotory drive kit , 230V ac shunt release ,ELR with CBCT including giving connection using 10.0 sq.mm pvc insulated copper wire
Supply and installation of wall mounting cubicle type dust and vermin proof size 4 , 600x300x214 mm, Mi2410 thermoplastic meterbox with provision for fixing KSEB meter.Supply and providing 3 Nos of 63A HRC porcelain fuse units with 40A HRC fuse link and 1No 63A 2way porcelain neutral link in the meter portion. Necessary holes are to be provided in the box for entry and exit of wire The inter connection should be done using 10.0 sq.mm copper wire.
Supply and fixing MPR 302 BE 040 L&T make motor protection Relay suitable for 7.5H.P motor starter
Supply and fixing MPR 302 BE 040 L&T make motor protection Relay suitable for 2.5H.P motor starter
Supply and fixing auxiliary contactors in the existing enclosure as required
Supply and fixing Emergency stop button -1 No and 25 A,415V,50Hz Push button unit ON and OFF switch -2 sets in the existing enclosure
Supply and fixing 3 phase,415V, 1 KVAR, ISI marked Heavy Duty Power factor improvement Capacitor with test certificate in the existing enclosure
Supply and fixing 3 phase,415V, 3 KVAR, ISI marked Heavy Duty Power factor improvement Capacitor with a test certificate in the existing enclosure
Supply and fixingTP MPCB Suitable for 7.5H.P star delta starter with thermal release range 10 to 15A
Supply and fixing TP MPCB Suitable for 2.5H.P DOL with thermal release range 3.5 to 6.3A
Supply and fixing 415V, 7A, 3 pole contactor AC-3 duty with 1NO+1NC contactor for 2.5 HP motor
Supply and fixing 415V ,12A, 3 pole contactor AC-3 duty with 1NO+1NC contactor for 7.5 HP motor
Supply and installation of wall mounting cubicle type dust and vermin proof CAPE make BRES -86, 800x600x300mm IP66,IK 10 Glass fiber reinforced polyester enclosure having hinged door and 3 points locking with provision for fixing terminal blocks, MCBs, Contactors, ELCBs including wiring using 2.5 sq.mm wire for control wiring and 4.0 sq,mm for power wiring.
Supply and fixing Cable Junction Boxes IP 66 for outdoor application( with metric knockouts for cable entry - Black Colour)) suitable for cable sizes upto 16/25 sq.mm,200 X 160 X 98 mm Hensel model No KF 5255 or equivalent and Terminal Set 2.5 sq.mm / 4 sq.mm including giving necessary connections, making good the damages etc. as required.
Supplying and fixing of surface/ recess mounting, vertical type, 415 volts,Dust and waterproof ,IP66 Hensel make or equivalent FPVN 0402 Transparent door (8 + 12 way) VTPN poly carbonate distribution board , with provision for MCCB as incomer, interconnection between incomer Isolator and bus bars of inclusive of 125 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's painted, inclusive of , tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required.
Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required 40 A, 25 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL & SC
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
Providing and fixing 10.00 SWG copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KVgrade of following size on wall surface as required.Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) as required.
Providing and laying earth connection from earth electrode with 4.00 mm dia copper wire in 15mm dia G.I. pipe from earth electrode including connection with copper thimble excavation and re-filling as required.
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing asrequired.
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm)
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 25 sq mm with factory made clamp
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 6 sq. mm
Supply & laying of one number PVC insulated and PVC sheathed armoured copper power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 4 sq mm
Supply of 63/50mm (OD/ID) Double Walled Corrugated (DWC) pipes made out of HDPE for mechanical protection to underground power/communication/ OFC / Signal cable conforming to IS 14930 Part - II
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group A
Supply and fixing Electronic IBT on delay timer for 7.5H.P motor starter.
KSEB Documentation Charge
Supply and fixing cast aluminium stove enameled elliptical shaped bulk head fittings with porcelain holder and mesh guard suitable for 3-14W LED lamps including connection etc as required.
Supply and fixing 7/9 W LED, BC, lamp OSRAM or equivalent
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
Supply and providing 25x6 mm brass bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required
Supplying and making end termination nickel plated single compression brass cable gland for 4 core 4 sq mm PVC insulated and PVC sheathed armoured copper conductor cable 1.1 KV grade, including providing earth clip and superior quality copper cable socket.
Painting letters or figures of the sizes 2.50 cm, 4 cm or 5 cm height with enamel paint as identification mark to SB, DB, panel board etc as required
Supply of superior quality copper earth socket for the 3.15mm (10 SWG) earth conductor including crimping etc. as required.
Supply, fabrication, conveyance and fixing of 40 mm dia Medium class GI pipe with clamps made from 20 x 3 mm MS flat bent to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of epoxy paint over a coat of epoxy primer, making good the damages, colour washing etc as required (for the installation of outdoor light fittings).
Providing and fixing 12 SWG insulated GI wire for service wire binding along with service line complete with all accesaries complete as required.
Best Power Controls
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_816227.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .