Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.6 LAccepted-AOC D NO 58 13 74 10 GF 111 VASAVI PARADISE GOWRI NAGAR WARD NO 42 NAD POST VISAKHAPATNAM 530009 AP | VISAKHAPATANAM | ANDHRA PRADESH | 530009 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹7.7 L+₹3,410 (0.45%)Rejected-AOC | L2 | Rejected-AOC Being not L1 | |
| 3 | L3₹9.0 L+₹1.3 L (17.6%)Rejected-AOC | L3 | Rejected-AOC Being not L1 |
Tender Value
₹9.3 L
EMD Value
₹18,600
Closing Date
16 Oct 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Shri Akash Agrawal,AGE (I) R and D NSTL
AGE (I) R and D, NSTL Complex, Visakhapatnam 530027
8348 RELAY CALIBRATIONS OF HT 33/11 KV VCBS, REPAIRS TO CT/ PT AND 33/ 11 KV STRUCTURES ALONG WITH CONNECTED ALLIED WORKS AT TECHNICAL AREA OF DRDO NSTL UNDER AGE (I) RnD NSTL, VISAKHAPATNAM.
2021_MES_475973_1
AGE I R AND D NSTL VIZAG 8348
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
Visakhapatnam
Class E Category b iii
7 documents required · 7 mandatory
₹500
AGE I R and D NSTL Visakhapatnam
₹18,600
Yes
25 Nov 2021
17 Sept 2021
18 Oct 2021
17 Sept 2021
16 Oct 2021
2 Oct 2021
60 days
Amount
Opening of the VCB , 11 KV 630/400 Amps of make kirloskar/Schnider/ABB by removing of the Breaker from the existing position after disconnecting all the connections from the system, servicing, Overhauling of the same, checking of the same for proper operation, spring charge, charged control cables are fastened tightly to the terminals, any abnormality, VCB, cleaning the surface of the insulators, fasten the bolts, checking and correcting interrupting units, mechanism, linkages etc, fasten the hardwares of control wiring, check that the split pins, Circlips, dowell pins etc. have not come out and are intact, lubricate the mechanism, moving parts by castrol, all purpose grease or equivalent, check that the vaccum pots/chambers is within limit including opening of the shutters properly, replacing of the trip catch, roller, holding catch, stopper, close push button, closing cum reassembling, control limit switches reconnecting of the breaker for smooth functioning complete all as directed.
Decarbonizing/cleaning complete HT 11KV, 3 phase independent bus bar, bus bar chamber of HT panel CT/PT current carrying parts and connections complete, HT VCB switch gear arrangement incoming and outgoing installed in sub-stations after removing the complete bus bar spout, circuit spout from the bus bar chamber, cleaning with CTC/ carbon removing solutions and ensure proper decarborizing, re-fixing the same after applying backtol (Red) solution to the spout, checking all the connections, tightening the nutsand bolts for incoming and outgoing system complete, replacement of damaged space heater along with thermostats, door/position limit switches, control fuses and servicing line CTs. PTs and replacement of damaged PT fuses complete all as specified and directed, Note: Rate quoted is inclusive of backtol red, CTC/ Carbon removing solution & cotton waste provided by contractor. Note for Srl Item nos. 1 & 2 : Spare parts for replacement are measured and paid separately as "Supply only"
Supply only closing coil assembly 110v DC for VCB all as specified & directed. Make: Areva/schneider
Supply only fix tripping coil 110V DC for VCB all as specified & directed. Make: Areva/schneider
Supply only closing buffer for 11KV VCB Make: Areva/schneider
Supply only motor cut-off switch(micro switch) 2NO+2NC. Make: Areva/schneider
Supply only Service/ test position limit switch(1NO+1NC). Make: Areva/schneider
Supply only 11 Kv PT HV Back up fuse cat no 12Kv ABCNA 3.15A 38/10 as per OEM Recommendation. Make: Schnider/Bussmann
Supply only 33 Kv PT HV Back up fuse,33 Kv SF6 CB PT HV Back upfuse 36KV 3.15A as per OEM Recommendation. Make Cat No 36KV ABQNA 3.15A 22/15 of ABB/ Bussman
Supply only 33 Kv PT HV Back up fuse, Un =36Ka,In 6A, I3 =35A, I1 =20Ka, R20 -1860mOhm for RMU as per OEM Recommendation. Make Cat No IXMB531006M0001/IXMB713613M of ABB / Schneider/ Bussman
Supply only Space/ strip heaters of 1 KW, 220Volts as per OEM
Supply only Thermostat for Heaters as per OEM.
Calibration & testing of all the electromagneitic/ thermal/ digital microprocessor based relays of 33KV and 11 KV and setting the relay tripping timings in advance to the feeding sub station to ensure pock wise re-installation of various relays in position with complete testing, commissioning and ensure proper functioning with following testing:- (i)CT Calibration through Primary injection test. (ii) Secondary injection for relay calibration. Notes :- (a). Primary & secondary injection kit shall be arranged by the contractor (b) DC Supply for relay testing shall arranged by the contractor (c) The contractor shall prepare the relay adjustment and tripping timing chart in the follow up fashion and submit to Engineer-in-Charge
Material and labour for servicing of SF 6 insulated outdoor type compact ring main unit HT 630 Amp, 33KV, 50 Hz one incomer and two outgoing with PT Chamber and line CT of 300/150/1-1A by removing both the sources of supply power cable switch modules, interlocking mechanism with earth Swith carefully. Checkly its cable ends, removing the body cover of RMU, opening its and servicing and greasing of moving / fixed parts.of its drive mechanism. fixing its body covers. refixing the RMU with both ends of cables necessary testing,closing and opening function shall be done and charging the RMU all as specified and directed. Note: Before testing of RMU the relay setting of RMU shall be set at minimum values for smooth functioning.
Opening of the SF-6 CBs, 33 KV 400 Amps of ABB make and removing of the Breaker from the existing position after disconnecting all the connections from the system, servicing, Overhauling of the same, checking of the same for proper operation, spring charge, charged control cables are fastened tightly to the terminals, any abnormality GCB, cleaning the surface of the insulators, fasten the bolts, checking and correcting interrupting units, mechanism, linkages etc, fasten the hardwares of control wiring, check that the split pins, Circlips, dowell pins, limit switches etc. have not come out and are intact, lubricate the mechanism, moving parts by castrol, all purpose grease or equivalent, check that the contact erosion is within limit including opening of the shutters properly, replacing of the trip catch, roller, holding catch, stopper, close push button, closing cum reassembling, reconnecting of the breaker for smooth functioning all as directed.
Decarbonizing/cleaning complete HT 33KV, 3 phase independent bus bar, bus bar chamber of HT panel electrification connection complete, HT SF-6 CB switch gear arrangement incoming and outgoing installed in sub-stations after removing the complete bus bar spout, circuit spout from the bus bar chamber, cleaning with CTC and ensure proper decarbonizing, servicing / cleaning to 11KV CT and 11 KV PT re-fixing the same after applying backtol (Red) solution to the spout, checking all the connections, tightening the nuts, bolts thimbles for incoming and outgoing system complete all as specified and directed. Note: Rate quoted is inclusive of bactol red, CTC & cotton waste provided by contractor.
Repairs to Auto tap changing control panel of 33/11 KV Transfoirmer by opening, cleaning, checking for faults, repalcement of minor spares required, checking properly, including replacement of temperature meters, indication lamps, Current sensing devices, rotary switches of suitable type/ model and complete servicing of panels and doors, painting with two coats of synthetic enamel paint complete all as specified and as directed.
Repairs to Spring Charging motors of capacity 230 V AC/DC Universal with gear box for VCB of 33/ 11KV of suitable size and capacity for existing VCB as recommended by OEM complete all as specified and as directed by Engineer-in-charge.
Supply and fix in replacement of Breaker control switch of capacity 25A, 3-position (Trip/ Neutral/ Close) Suttable for 11Kv/33kv VCB/SF6 brakears
Supply and fix Control wiring for space heater & thermostat panel near Entryside and at CT Chamber area using with 2x2.5 sqmm copper multistranded conductor cable laid in PVC conduit upto control circuit including testing after completion of work for smooth functioing complete all as specified and as directed.
Supply and fix LED Indication lamps for VCB of 11KV and 33 KV, of Universal voltage AC/DC 110/230 Volts of colour Red, Yellow, Blue, Green, Amber, White as required at site complete all as specified and as directed.
Supply and fix Multi functional meter for VCB complete all as specified and as directed.
Supply and replacement of Spring Charge/ Holding gear mechanism for 33 KV SF6 breaker complete all as speciied and as directed.
Supply, fixing, testing and commissioning of resin current transformer suitable for 11 KV, 100/50/1-1A of primary wound type with adjustable VA burden and accuracy in cleaning the CT wiring with primary and secondary injection kit incl identification to the base and connecting links to HT VCB to match with the existing system including taking down unserviceable transformer. Make : Kappa/CG/Alstom/Jyothi
Takingdown carefully 33 KV Outdoor type Oil cooled current Transformer from 33/ 11 KV Substation, Rated Voltage 36 KV, ratio: 150/75/1-1-1 A, 15VA Burdan, STC: 13.1KA/ 1Sec, Core1: 15VA/5P10, Core2: 15VA/Class1.0, Core 3: 15VA/5P10, transport to workshop for carrying out repairs, complete dismantling of CT, draining of old Transformer oil, replace with new one after completing repairs, replace the top cover gasket, oil O rings and bushings, bottom gasket, checking the condition of winding, replace with new copper winding wire of suitable size, Checking the Oil tank's inside and outside, cleaning and removing old paint and paint with new synthetic enamel paint od standard electri ccolour, Primary termination replace with new hard ware, secondary terminals replace and checking the secondary connections upto relay terminals for smooth functioning complete all as specified and as directed by Engr-in-Charge.
All as per Item No here-in-before but of 11KV Outdoor type Oil cooled Current Transformer, Rated Voltage: 12 KV, ratio: 150/75/1-1-1 A, 15VA Burdan, STC: 13.1KA/ 1Sec, Core1: 15VA/ 5P10, Core2: 15VA/Class1.0, Core 3: 15VA/5P10 Complete all as specified and as directed.
Takingdown carefully 33 KV Outdoor type Oil cooled Voltage (Potential) Transformer from 33/ 11 KV Substation, Rated Voltage: 36 KV, Primary voltage: 33 KV, Secondary Voltage 110 Vols, Connection Y/Y, 50VA Burden, transport to workshop for carrying out repairs, complete dismantling of CT, draining of old Transformer oil, replace with new one after completing repairs, replace the top cover gasket, oil O rings and bushings, bottom gasket, checking the condition of winding, replace with new copper winding wire of suitable size, Checking the Oil tank's inside and outside, cleaning and removing old paint and paint with new synthetic enamel paint od standard electri ccolour, Primary termination replace with new hard ware, secondary terminals replace and checking the secondary connections upto relay terminals for smooth functioning complete all as specified and as directed by Engineer-in-Charge.
All as per Item No here-in-before but of 11KV Outdoor type Oil cooled Voltage (Potential) Transformer, Rated Voltage: 12 KV, Primary voltage: 11 KV, Secondary Voltage 110 Vols, Connection Y/Y, 50VA Burden Complete all as specified and as directed.
Supply and fix 6 core 2.5 sqmm copper control cable armoured for connections from CTs to relay control panel of capacity 33KV and 11KV including all necessary connections required, testing of relay after completing for proper functioning complete all as specified and as directed.
Supply and fix 4 core 2.5 sqmm copper control cable armoured for connections from PTs to relay control panel of capacity 33KV and 11KV including all necessary connections required, testing of relay after completing for proper functioning complete all as specified and as directed.
Repair to HT 11 KV 2 pole structure of 11 meter height Steel/RCC poles including replacement of ACSR Conductor (Beaver) type, jumpering and binding with aluminium conductor to the post insulators/pin insulators and providning PVC sleeves to the down conductor with colour code R, Y&B, replacing all rusted nuts & bolts on the two pole structure including PG clamps and connectors complete all as directed.
M & L for taking down 11 KV grade unserviceable Pin/post insulators from the HT 2 pole/4 pole structure and S&F pin type composite insulation/silicon rubber material including one galvanishing MS spingle, nuts & washers of 150mm height, 150 mm dia for 11000 volt grade and fixing to the structure and binding of conductor all as directed. Make: GK Electricals /Jaipuria/ ABI
M & L for taking down HT 11 KV grade triple pole gange operated Air break switch from 4 pole/2 pole structure and S & F NEW gang operated Air break switch (GOD) HT 11 KV of 200 A capacity out door type suitable for vertical/horizantal mounting fixed type complete with 3 no. silicon rubber polymeric insulator per phase all as specified and directed. Make: GK Electricals/ Jaipuria/ ABI
M & L for taking down HT 11 KV drop out fuse from 4 pole/2 pole structure and S & F NEW single phase with silicon rubber polymeric insulator type drop out fuse complete all as specified and directed. Make: GK Electricals /ABB / Areva /BHEL/Jaipuria
M & L for taking down the damaged / un serviceable Lighting arresters expulsion type suitable for 11000 volts complete with all fittings, transmission class, discharge capacity 6.5 Kilo Amps Make: HTSG /JAIPURIA
M&L Earthing complete with galvanised steel earth plate electrode 600x600x6mm thick,40mm bore medium grade (steel pipe) buried directly in ground (earth pit not less than 2.25m deep below GL) with top edge of the plate not less than 1.5m below normal GI, connected to galvanised earth strip 32 x 6 mm by means of bolts nuts check nuts and washers of galvanised iron or steel all as shown in electrical plate No.5 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and as directed. Note : Rate shall be deemed to be inclusive of necessary excavation and earth work in any type of soil, removal of surplus soil to a distance not exc 50 M, RCC covers slab and PCC chamber etc.
M&L for isolating, cutting, removing the existing damaged end termination and S&F outdoor end termination Cold shrinkable outdoor type (Earthed) suitable for HT UG cable XLPE insulated 3 Core 120 to 185 Sqmm 11000V grade including preparation complete all as directed. (Make: REPL/3M/Raychem)
M&L for cutting, removing the existing damaged joint and S&F straight through joint Cold shrinkable type suitable for HT UG cable XLPE insulalted 3 core 185sqmm 11000V grade including preparation complete all as directed (Make:Raychem/ REPL/ Denson).
M&L for preparation of old painted surface, cleaning of oils, lubricants, grease etc complete of 2 pole structure as per IS above PCC coping with applying two coats of alluminium paint over one coat of red oxide, incl brackets clamps, channels and cross arms and writing MES no of poles (Number size shall be 25 mm and lettering shall be 40 mm) complete all as directed by Engineer - In - Charge (Note: The quoted rate inclusive of two coats of white wash on exposed concrete surfaces) (Make of Paint: Berger/ Jenson & Nicholson/ Shalimar/ Asian paint)
LAKSHMI SAI CONSTRUCTIONS
HARSHITHA INFRA
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .