| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.3 CrAccepted-AOC | ₹1.3 Cr | L1 | Accepted-AOC L1 |
| 2 | L2₹1.3 Cr+₹3.0 L (2.34%)Rejected-AOC | ₹1.3 Cr+₹3.0 L (2.34%) | L2 | Rejected-AOC L2 |
| 3 | L3₹1.4 Cr+₹12.0 L (9.44%)Rejected-AOC | ₹1.4 Cr+₹12.0 L (9.44%) | L3 | Rejected-AOC L3 |
| 4 | L4₹1.4 Cr+₹12.3 L (9.68%)Rejected-AOC | ₹1.4 Cr+₹12.3 L (9.68%) | L4 | Rejected-AOC L4 |
Tender Value
₹1.3 Cr
EMD Value
₹50,000
Closing Date
13 Oct 2021, 3:00 pmClosed
Deputy Vice President (HCD)
HLL Lifecare Limited, HCD Projects, HLL Bhavan, 6th Floor, Golden Jubilee Block, Poojapura, Thiruvananthapuram - 695012, Kerala, Ph 0471-2775651
Civil and Electrical Work for Strengthening of Maternity Wing as per LaQshya Standards at IMCH Kozhikode at Kerala as per Schedule of Work enclosed.
2021_HLL_443519_1
HLL/HCD/PS/CE/IMCH/LQ/KZD/2122
Open Tender
Civil Works - Buildings
Item Rate
270 days
IMCH Kozhikode
Please refer Tender documents.
10 documents required · 10 mandatory
₹2,800
₹50,000
Yes
28 Dec 2022
6 Oct 2021
14 Oct 2021
6 Oct 2021
13 Oct 2021
6 Oct 2021
Amount
Civil Work
Demolishing and Dismantling
Demolishing brick work manually / by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-Charge.In cement mortar
Demolishing R.C.C. work manually / by mechanical means including stacking of steel bars and disposal of unserviceable material with in 50 metres lead as per direction of Engineer -in-Charge.
Taking out doors, windows and clerestory window shutters (steel or wood ) including stacking within 50 metres lead:Of area 3 sq. metes and below
Dismantling aluminium / Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable surplus material and stacking of serviceable material with in 50 metres lead as directed by Engineer - in-Charge
Dismantling tile work in floors and roofs laid in cement mortar including stacking material within 50 metres lead.For thickness of tiles 10 mm to 25 mm
Dismantling of flushing cistern of all types (C.I. / PVC/ Vitrous China) including stacking of useful materials near the site and disposal of unserviceable materials within 50 metres lead
Taking out existing wooden door shutter, repair by cutting, painting etc. andrefixing of repaired door shutters to existing door frames, including replacementof hinges with screws, etc. as required, all complete as per the direction of theEngineer-in-charge.
MASONRY WORK
Solid block masonry using pre cast solid blocks (Factory made) of size 40x20x20cm or nearest available size confirming to IS 2185 part I of 1979 for super structure up to floor two level thickness 20cm and above in: CM 1:6 ( 1 cement: 6 coarse sand) etc complete.
Providing and laying autoclaved aerated cement blocks masonry with 100 mm thick AAC blocks in super structure above floor 2 level up to floorV level in cement mortar 1:4 (1 cement :4 coarse sand). The rate includes providing and placing in position 2 Nos 6 mm dia M.S. bars at every third course of masonry work.
Reinforced cement concrete work in beams, suspended floors, roofs, having slope up to 150 landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement, with1:1.5:3 (1 cement : 1.5 coarse sand (Zone III) : 3 graded stone aggregate 20 mm nominal size).
Centering and shuttering including strutting, etc. and removal of form for:Lintels, beams, plinth beams, girders bressumers and cantilevers
Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size)
PLASTERING
12 mm cement plaster finished with a floating coat of neat cement of mix:1:4 ( 1 cement : 4 fine sand)
TILE WORK
Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600 x 600 mm.
Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), including pointing the joints with white cement and matching pigment etc., complete.
Providing and fixing I st quality ceramic glazed wall tiles conforming to IS : 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer -in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3 kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
Providing and laying Vitrified tiles in walls with different sizes (thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS : 15622, of approved brand & manufacturer, in all colours and shade, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS : 15477, in average 10 mm thickness, including grouting of joints (Payment for grouting of joints to be made separately).<br>Size of Tiles 600x600 mm
PAINTING WORK
Removing white or colour wash by scrapping and sand papering and preparing the surface smooth including necessary repairs to scratches etc. complete.
Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete.
Finishing with Deluxe Multi surface paint system for interiors and exteriors using primer as per manufacturers specifications:Two or more coats applied on walls @ 1.25 ltr/10 sqm over and including one coat of special primer applied @ 0.75 ltr /10 sqm
Finishing with Deluxe Multi surface paint system for interiors and exteriors using primer as per manufacturers specifications:Painting wood work with Deluxe Multi Surface Paint of required shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.75 ltr/10 sqm of approved brand and manufacture
Finishing with Deluxe Multi surface paint system for interiors and exteriors using primer as per manufacturers specifications:Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.80 ltr/10 sqm of approved brand and manufacture
ALUMINIUM,CEILING AND FLUSH DOOR WORK
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS : 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminnium snap beading for glazing /paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge.(Glazing, paneling and dash fasteners to be paid for separately):For fixed portionPowder coated aluminium (minimum thickness of powder coating 50 micron)
For shutters of doors, windows & ventilators including providing and fixing hinges / pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber/ neoprene gasket required (Fittings shall be paid for separately)Powder coated aluminium (minimum thickness of powder coating 50 micron)
Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS : 12823 Grade I Type II, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of Engineer - in- Charge.Pre-laminated particle board with decorative lamination on one side and balancing lamination on other side
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 5.50 mm thickness
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 4.0 mm thickness
Providing and fixing frosted film in the fixed glass etc. Complete as per the direction of departmental officers
Providing and fixing GI Clip in Metal Ceiling System of 600x600 mm module which includes providing and fixing 'C' wall angle of size 20x30x20 mm made of 0.5 mm thick pre painted steel along the perimeter of the room with help of nylon sleeves and wooden screws at 300 mm center to centre, suspending the main C carrier of size 10x38x10 mm made of G.I steel 0.7 mm thick from the soffit with help of soffit cleat 37x27x25x1.6 mm, rawl plugs of sixe38x12 mm and C carrier suspension clip and main carrier bracket at 1000 mm c/c. Inverted triangle shaped Spring Tee having height of 24 mm and width of 34 mm made of GI steel 0.45 mm thick is then fixed to the main C carrier and in direction perpendicular to it at 600 mm centers with help of suspension brackets. Wherever the main C carrier and spring T have to join, C carrier and spring T connectors have to be used. All sections to be galvanized @ 120 gms/sqm (both side inclusive), fixing with clip in tiles into spring 'T' with :GI Metal Ceiling Clip in plain Beveled edge global white color tiles of size 600x600 and 0.5 mm thick with 25 mm height, made of G I sheet having galvanizing of 100 gms/sqm(both sides inclusive) and 20% perforation area with 1.8 mm dia holes and having NRC of 0.5, electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending and perforation.
Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/ sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37 mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50 mm long with 6 mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25 mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5x25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound, jointing tapes, finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with:12.5 mm thick tapered edge gypsum moisture resistant board
Providing and fixing panelling or panelling and glazing in panelled or panelled and glazed shutters for doors, windows and clerestory windows (Area of opening for panel inserts excluding portion inside grooves or rebates to be measured), Panelling for panelled or panelled and glazed shutters 25 mm to 40 mm thick:Decorative plywood one side decorative veneer and commercial veneer on other face (type 1) conforming to IS 1328 BWR Type
Providing laminated veneer lumber conforming to IS: 14616 and TAD - 15:2001 ( Part B) in factory made frames of doors, windows, clerestory windows and other frames, wrought framed and fixing in position with hold fast lugs or with dash fasteners of wrought framed and fixing in position with hold fast lugs or with dash fasteners of required dia & length (hold fast lugs or dash fastener shall be paid for separately)
Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of I st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters.35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws
Providing and fixing plywood 4 mm thick, one side decorative veneer conforming to IS : 1328 (type - 1) for plain lining / cladding with necessary screws, including priming coat on unexposed surface with:Decorative veneer facings of approved manufacture
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 8 mm thickness
Providing and fixing bright finished brass tower bolts (barrel type) with necessary screws etc. complete:250x10 mm
Providing and fixing bright finished 100 mm mortice lock with 6 levers without pair of handles of approved quality for aluminium door, with necessary screws etc complete as per direction of Engineer- in- charge.
Providing and fixing aluminium tubular handle bar 32 mm outer dia, 3.0mm thick & 2100 mm long with S.S. screws etc. complete as per direction of Engineer -in-Charge.Anodized (AC 15) aluminium tubular handle bar
Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of cross- section 90 mm x 45 mm having single rebate of 32 mm x 15 mm to receive shutter of 30 mm thickness. The laminated shall be moulded with fire resistant grade unsaturated polyester resin and chopped mat. Door frame laminate shall be 2 mm thick and shall be filled with suitable wooden block in all the three legs. The frame shall be covered with fiber glass from all sides. M.S. stay shall be provided at the bottom to steady the frame.
Providing and fixing to existing door frames.30 mm thick Fiberglass Reinforced Plastic (F.R.P) flush door shutter in different plain and wood finish made with fire retardant grade unsaturated polyester resin, moulded to 3 mm thick FRP laminate all around, with suitable wooden blocks inside at required places for fixing of fittings and polyurethane foam (PUF) / Polystyrene foam to be used all filler material throughout the hollow panel, casted monoolithically with testing parameters of F.R.P. laminate conforming to table - 3 of IS : 14856, complete as per direction of Engineer-in-charge.
PLUMBING AND SANITAR FITTINGS
Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreous china flushing cistern & C.P. flush bend with fittings & C.I. brackets, 40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required :W.C. pan with ISI marked white solid plastic seat and lid
Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:White Vitreous China Wash basin size 630x450 mm with a pair of 15 mm C.P. brass pillar taps
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall40 mm nominal outer dia pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.25 mm nominal outer dia pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & coldwater supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.32 mm nominal outer dia pipes
Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms 15mm Nominal Bore
Providing and fixing PTMT grating of approved quality and colour.Rectangular type with openable circular lid150 mm nominal size square 100 mm diameter of the inner hinged round grating
Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 50 mm dia 10 Kfg/cm - Internal work- Exposed on wall
Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc. 50 mm pipe 6 kgf/cm2
Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge. Concealed work including cutting chases and making good the wall etc. 63 mm pipe 6 Kgf/cm2
Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc. 75 mm pipe 6 Kgf/cm2
Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as pe direction of Engineer-in-Charge. Concealed work, including cutting chased and making good the wall etc. 110 mm pipe 6kgf/cm2
Providing and fixing PVC pipes includings jointing of pipes with one step PVC solvent cement, trenching, refilling & testing of Joints complete as per direction of engineer in charge.110 mm dia 6Kgf/cm2
Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 50 mm dia 10Kgf/cm2 - External work - Exposed on wall
Providing and fixing PVC pipes including fixing the pipe with clamps/ clip at 1.00 m spacing . This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 63 mm dia 6 Kgf/cm2 - External work - Exposed on wal
Providing and fixing PVC pipes including fixing the pipe with clamps/clips at 1.00 m spacing. This included jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 75 mm dia 6Kgf/cm2 - External work- Exposed on wall
Providing and fixing PVC pipes includings jointing of pipes with one step PVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. 75 mm dia 6 Kgf/ cm2
Providing and fixing PVC pipes including fixing the pipe with clamps/ clips/ at 1.00 m spacing . This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 110 mm dia 6 Kgf/cm2 - External work- Exposed on wall
Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 63 mm dia Elbow
Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement -63 dia 45 degree Elbow
Providing and fixing PVC moulded fittings /accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 63 mm dia Door Elbow
Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 63 mm dia Bend
Providing and fixing PVC moulded fittings/accessories for Rigid PVC pipes including jointing with PVC solvent cement - 63x63x63 mm dia Tee
Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement -63x63x63 mm dia Door Tee
Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 63 mm dia vent cowl
Providing and fixing PVC moulded fitting / accessories for Rigid PVC pipes, including jointing with PVC solvent cement-63 mm dia Socket /coupling
Providing and fixing PVC moulded fittings/accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 63x50 mm dia Reducer
Providing and fixing PVC moulded fittings/accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 75 mm dia Elbow
Providing and fixing PVC moulded fittings/accessories for Rigid PVC pipes, including jointing with PVC solvent cement -75 mm dia 45 degree Elbow
Providing and fixing PVC moulded fittings / accessories for Rigid PVC pipes, including jointing with PVC solvent cement -75 mm dia Door Elbow
Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 75 mm dia Bend
Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement -75x75x75 mm dia Tee
Providing and fixing PVC moulded fittings/accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 75x75x75 mm dia Door Tee
Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 75 mm dia Vent cow
Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 75 mm dia Socket /coupling
Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement -75x63 mm dia Reducer
Providing and fixing PVC moulded fittings / accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 110 mm dia 45 degree Elbow
Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement-110 mm dia Door Elbow
Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement- 110 mm dia Bend
PProviding and fixing PVC moulded fittings/ accessories for Rigid PVC pipes including jointing with PVC solvent cement 110x110x110 mm dia Tee
Providing and fixing PVC moulded fittings/accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 110x110x110 mm dia Door tee
Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 110x110x75 mm dia Door Tee
Providing and fixing PVC moulded fittings /accessories for Rigid PVC pipes, including jointing with PVC solvent cement -110 mm dia Vent cowl
Providing and fixing PVC moulded fittings/accessories for Rigid PVC pipes,including jointing with PVC solvent cement - 110 mm dia Socket/ coupling
Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 110x75 mm dia Reducer
Supplying and fixing CP Health Faucet superior quality ( Jagur or equvalent make ) including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge.
Providing and fixing Double station Elbow operated 304 Stainless Steel & seamless welded construction polished to a satin finish Scrub Sink with Curved Seamless Corner. Overall Size 1600mm Length, 622 mm Width, 718mm Height. Sink Size 1525 mm Length, 508mm Width, 356mm Height. 2 Nos of Elbow Operating Water Taps and 1 Nos Soap Dispenser Holder. TIG welded seamless Curved Drain.
Providing and fixing 15 mm C.P. brass pillar taps with elbow operated levers
STEEL WORK
Steel work in built up G I tubular ( round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting,fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete
Steel work for purlin/single section with G I pipes including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete
Providing at all heights, levels and locations 0.45 mm thick Galvalume sheet of Alloy 31500/31000/40800, conforming to IS 1254, IS 737, IS 2676. The sheet shall be fixed using self drilling/self tapping SS screws of size 5.5x65 mm with EPDM seal complete upto required pitch in horizontal, vertical or curved surfaces i/c cutting to size and shape where required as per the direction of Engineer-in-Charge. The rate shall be inclusive of all screws, seal, ridge, labour, scaffolding, machinery for fixing and approved sealant where required etc. but excluding the cost of purlins, rafters and trusses.
Providing and fixing precoated galvanised steel sheet roofing accessories 0.50 mm (+ 0.05%) total coated thickness, zinc coating 120 grams per sqm as per IS:mm(+0.05%) total coated thickness, Zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/self tapping screws complete:Ridges plain (500-600 mm)
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes.110 mm diameter
Supply of MS Tees, Angles, Joists, ISMB, ISMC confirming to IS2062GrA/B including cost of conveyance charges
Supply of MS checquered plates including cost of conveyance charges
Fabrication, erection and commissioning of Structural steel Embedded parts in IS2062 Grade and accessories as per approved specifications, drawings and directions of deptl officer at site including cost of labour , machinery , incidental and handling charges etc complete but excluding cost of material already supplied
Providing and fixing M.S. Grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete.Fixed to openings/ wooden frames with rawl plugs screws etc
Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.)
WATER PROOFING
22.22A Providing and applying fibre reinforced elastomeric liquid water proofing membranewith resilient acrylic polymers having Sun Reflectivity Index (SRI) of 105 on top ofconcrete roof in three coats @10.76 litre/ 10 sqm. One coat of self-priming ofelastomeric waterproofing liquid (dilution with water in the ratio of 3:1) and twocoats of undiluted elastomeric waterproofing liquid (dry film thickness of completeapplication/system not less than 500 microns). The operation shall be carried outafter scrapping and properly cleaning the surface to remove loose particles withwire brushes, complete in all respect as per the direction of Engineer-in-Charge.
CURTAIN WORK
Supplying and laying polyester, washable and stain free cloth(Bio-Active fabric washable germ freesuitable for sterile area) curtain system with maximum curtain cloth height 230 cm(top 30 cm white colour net and 200cm light blue color as per approval) stitching with stifiner tape, pleats, ironing and layingaround each bed using PVC runner with hooks & stopper for hanging/sliding etc. as per the direction of engineer in charge including conveyance to site, laying in line and level, sealing all cutting in false ceilingwith powder coated MS cup, all leads and lifts including all labour charges etc. complete. (unpleated length of the cloth measurement will be considered for payment also the bottom and top foldings will notbe considered in cloth measurement)/ supplying and fixing powder coated 20mm dia. GI round tube hanging support of required length(app. length 1.10m) one end fixing from slab by using 6mm dia expansion bolt at a distance not more than 2m, c/c down end fixed to powder coated aluminium channel frame 45 x 20mm x 1mm thick section by using SS screw as per the direction of engineer in charge including conveyance.
Providing and fixing, vertical blinds of polymerized vinyl chloride with vertical pattern, vertical open style, Water resistant, Foldable including all frames, hinges, etc all. Complete lead as per direction of Engineerin- charge.
NURSES STATION,RECEPTION AND CUPBOARD WORK
Providing and fixing panelling or panelling and glazing in panelled or panelled and glazed shutters for doors, windows and clerestory windows (Area of opening for panel inserts excluding portion inside grooves or rebates to be measured), Panelling for panelled or panelled and glazed shutters 25 mm to 40 mm thick:Decorative plywood one side decorative veneer and commercial veneer on other face (type 1) conforming to IS 1328 BWR Type
Providing and fixing Thomson Multi wood board or equivalent make, in shelves with screws and fittings wherever required, edges to be painted with polyurethane primer (fittings to be paid separately) as per the direction of site Engineer-in-charge.
Providing and fixing bright finished brass handles with screws etc. complete:100 mm
Providing and fixing concealed hinge of approved quality for 19-20mm thickdoor with stainless steel screws complete :
Providing and fixing special quality chromium plated brass cupboard locks with six levers of approved quality including necessary screws etc. complete.Size 40 mm
Providing and fixing magnetic catcher of approved quality in cupboard/ward robe shutters, including fixing with necessary screws etc. complete.Triple strip vertical type
Providing and fixing 1 Pair Cold Rolled Steel Ball Bearing Drawer Telescopic Channel Runner, Loading Capacity 45 Kg, 450 mm, 18 Inches, Zinc plated ( best make of approved quality ) including necessary cutting and making good etc. complete
ELECTRICAL WORKS
ELECTRICAL WORKS-LIGHT POINTING
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C
Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Call bell point with 6 A bell push at one end and 6 A, 3 plate ceiling rose at other end - Long point
Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Independent plug - Short point
ELECTRICAL WORKS - SUB/CIRCUIT MAINS
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm sq.mm + 1x1.5 sq.mm earth wire
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 2.5 sq. mm
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 4 sq. mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
Supplying and drawn of UTP 4 pair CAT 6 LAN cable in the existing surface/recessed steel/PVC conduit as required1 run of Cable
Supplying and drawn of UTP 4 pair CAT 6 LAN cable in the existing surface/recessed steel/PVC conduit as required3 run of Cable
ELECTRICAL WORK - PLUG POINTING
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp swit
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.12 Module (200mmX150mm)
ELECTRICAL WORKS- POWER CIRCUITRY
PANEL BOARD - [1+ (4+2)]<br>Supply, Installation, Testing & Commissioning of cubicle type, made out of 1.6mm thick CRCA sheet,totally enclosed , free standing, floor mounting, dust and vermin proof, indoor, compartmentalized, suitable for operation on 3 phase , 415 V, 50Hz AC system with busbars , including internal wiring with suitable size wires/cable, interconnection, duly powder coated with seven tank process etc., including following components as per drawing and technical specifications.The panel shall be with Top/bottom entry to receive incoming & outgoing cable-EB SIDE Incomer-250A, FP 35/36 KA microprocessor type MCCB Having isolation duty with 3O/C+1E/F Release SET AT 200A - 1No.Instruments (incomer)-2A MCB - 6 Nos.-RYB indication lamp, LED type - 2set-Digital Multi function meter with Acc Cl1 with RS485 communication -1no - 1set (3P+1N).Busbar 300A ,35kA TPN busbar chamber with Aluminium busbar- Outgoings - 4+2(spare) No.s 16-100A, 25 kA FP MCCB with adjustable thermal magnetic release with OL & SC protection, with RS 485 communication facility as required. Earth Leakage relay upto 100A with CBCT as required shall be connected to the system via suitable end termination as required.
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required8 way (8+24) - three phase double cover (IP 42/43)
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required8 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43)
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps)
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current breaker with overload (RCBO), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required<br>25A, 2P, 30mA<br>
Supplying and fixing following rating, four pole, (three phase and neutral), 415 V, residual current breaker with overload (RCBO), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc.<br>40A 4P,30MA<br>
TP MCB -40A SITC 40A TP C-Curve 10 kA MCB is a three pole highly durable MCB with finger touch proof terminals conforming to IP-20 degree of protection. It is used in Three Phase Supply to break the phase and the neutral is not the part of the MCB conforming to certification IEC 60947-2, mounting on symmetric rail EN/IEC 60715 or DIN 35 rail. made up of Halogen free plastic material, Large cable terminals of 35 Sq. mm capacity for better terminal.
SF -63A,30mA RCCB-FP<br>Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual <br> current circuit breaker (RCCB), having a sensitivity current up to 30 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.<br>63 amps
TP MCB -63A SITC 63A TP C-Curve 10 kA MCB is a three pole highly durable MCB with finger touch proof terminals conforming to IP-20 degree of protection. It is used in Three Phase Supply to break the phase and the neutral is not the part of the MCB conforming to certification IEC 60947-2, mounting on symmetric rail EN/IEC 60715 or DIN 35 rail. made up of Halogen free plastic material, Large cable terminals of 35 Sq. mm capacity for better terminal.
Supplying and fixing following rating, four pole, (three phase and neutral), 415 V,<br>residual current breaker with overload (RCBO), having a sensitivity current 100 mA in the existing MCB DB complete with connections, testing and commissioning etc. 63A 4P 100MA
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.100 amps
ELECTRICAL WORKS-FITTINGS
Supply, Installation, testing and commissioning of pre - wired, LED Light fitting (12W) of all types, complete with all accessories and tube etc. directly on ceiling/ wall, including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
Supply, Conveyance, installation, testing and commissioning of wall mounting fans of 400mm sweep of all types using mounting brackets supplied along with the fan.
2X2 SQUARE TYPE RECESS MOUNTED LED LIGHT<br>SITC OF 600mmX600mm square type Cool White, Warm White, Pure White LED light fixture with Integrated Driver & Backlight Technology with a minimum system efficacy of 95w/Lm, Standard CCT: 3000K*, 4000K & 6500K, high color rendering CRI >80, with high efficiency driver, minimum of 35000 hours working life, and Surge protection -4KV (light variant as decided by engineer in charge),including connection with existing point using suitable gauge copper conductor directly to the ceiling rose. Each module should be tested and QC approved by competent authority and the same to be furnished before electrical engineer HLL Lifecare limited before purchase or else any higher version approved by the Electrical Engineer HLL Lifecare Limited
1X1 ROUND/SQUARE-RECESS MOUNTED LED FITTINGS<br>Supply & installation of 1x18 watts recess mounted down light fixture, with aluminium reflector, CRCA sheet housing, complete with all accessories like ballast, 18W CFL lamp etc complete as required
ELECTRICAL WORKS- CABLING & END TERMINATION
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 150 sq mm
Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required.6 Sq m
Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required.16 sq mm
Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required.150 sq mm
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured copper power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 25 sq mm with factory made clamp
Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required.25 sq mm
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 70 sq mm
Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required.70 sq mm
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured copper power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3 core 6 sq mm with factory made clamp
Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG
Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.00 mm (8 SWG)
NETWORKING and COMMUNICATIONS
Supply Installation & Coomissioning of IP-PBX SIP SERVER - Having 20 Extensions with 8 Analog builtin FXS and 2 No's of PSTN Lines which can be expanded upto 4. Works with SIP/IAX2, PSTN lines, Provision to add GSM/3G/4G Built-in call recording capability Powerful Apps (add-ons) include Mobile applications, AutoProvision, LDAP, Conference Panel, VPN Server. Connect multiple sites and remote users instantly. Voice guidance - Interactive Voice Response Soft Phone in both PC & MOBILE is mandatory. Make: Cisco/ Matrix/Grandstream or equivalent without change in specification and rate and only as per the direction of engineer in charge.
Supply and fixing of MDF and IDF telephone distribution junction box along with krone module DP box including 20 pair Krone Connector Module along with all accessories comp
TELEPHONE<br>Supplying & Drawing unarmored PVC insulated and & PVC sheathed copper conductor Telephone Pair Cable conforming to ITD specification for indoor application through the existing conduit<br>10pair<br>
Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor,unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required.1 Pair
Supply and Installation of Push Button Telephone set
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.Telephone socket outlet
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
VRV SYSTEM-HVAC
DRAIN PIPING -VRV SYSTEM IDU<br>SITC of PVC drain piping, pressure rating 6 Kg complete with fittings, supports as per specifications and insulated with 9 mm Class 1 Nitrile rubber insulation as per specifications and drawings etc. complete as required. <br>32mm Thick
DRAIN PIPING -VRV SYSTEM IDU<br>SITC of PVC drain piping, pressure rating 6 Kg complete with fittings, supports as per specifications and insulated with 9 mm Class 1 Nitrile rubber insulation as per specifications and drawings etc. complete as required. <br>25mm Thick
VRV -ODU MS STAND<br>CONDENSING UNIT MS PLATFORM STAND FOR VRF ODUs Supply and Installation of Hot-dip galvanized MS platform stand of adequate weight-bearing capacity, should be safe for maintenance and installation work. It to be mounted on wall or Slab provided by Civil agency/existing slab. Double rubber pads & galvanized MS plates for each leg. Rates should be quoted per numbers not per Kg rates.
VRF PIPELINE WORKS<br>SITC of Interconnecting copper refrigerant pipe with19mm Nitrile rubber protection insulation between each set of Ductable /split indoor & outdoor units and 13mm insulation for VRF systems as per specifications, all piping inside the room shall be properly supported with MS hanger & clamps and all external piping with UV Coating as per specification etc. complete as required. All piping inside the room in ceiling shall be properly supported in cable tray/hangers. rates should quote inclusive of loading and unloading charges, The requirement of sizing of pipeline will be as per the location of ODU in the premises. -6.35mm
VRF PIPELINE WORKS<br>SITC of Interconnecting copper refrigerant pipe with19mm Nitrile rubber protection insulation between each set of Ductable /split indoor & outdoor units and 13mm insulation for VRF systems as per specifications, all piping inside the room shall be properly supported with MS hanger & clamps and all external piping with UV Coating as per specification etc. complete as required. All piping inside the room in ceiling shall be properly supported in cable tray/hangers. rates should quote inclusive of loading and unloading charges, The requirement of sizing of pipeline will be as per the location of ODU in the premises. -9.5mm
VRF PIPELINE WORKS<br>SITC of Interconnecting copper refrigerant pipe with19mm Nitrile rubber protection insulation between each set of Ductable /split indoor & outdoor units and 13mm insulation for VRF systems as per specifications, all piping inside the room shall be properly supported with MS hanger & clamps and all external piping with UV Coating as per specification etc. complete as required. All piping inside the room in ceiling shall be properly supported in cable tray/hangers. rates should quote inclusive of loading and unloading charges, The requirement of sizing of pipeline will be as per the location of ODU in the premises. -15.9mm
VRF PIPELINE WORKS<br>SITC of Interconnecting copper refrigerant pipe with19mm Nitrile rubber protection insulation between each set of Ductable /split indoor & outdoor units and 13mm insulation for VRF systems as per specifications, all piping inside the room shall be properly supported with MS hanger & clamps and all external piping with UV Coating as per specification etc. complete as required. All piping inside the room in ceiling shall be properly supported in cable tray/hangers. rates should quote inclusive of loading and unloading charges, The requirement of sizing of pipeline will be as per the location of ODU in the premises. -19.1mm
VRF PIPELINE WORKS<br>SITC of Interconnecting copper refrigerant pipe with19mm Nitrile rubber protection insulation between each set of Ductable /split indoor & outdoor units and 13mm insulation for VRF systems as per specifications, all piping inside the room shall be properly supported with MS hanger & clamps and all external piping with UV Coating as per specification etc. complete as required. All piping inside the room in ceiling shall be properly supported in cable tray/hangers. rates should quote inclusive of loading and unloading charges, The requirement of sizing of pipeline will be as per the location of ODU in the premises. -22.2mm
VRF PIPELINE WORKS<br>SITC of Interconnecting copper refrigerant pipe with19mm Nitrile rubber protection insulation between each set of Ductable /split indoor & outdoor units and 13mm insulation for VRF systems as per specifications, all piping inside the room shall be properly supported with MS hanger & clamps and all external piping with UV Coating as per specification etc. complete as required. All piping inside the room in ceiling shall be properly supported in cable tray/hangers. rates should quote inclusive of loading and unloading charges, The requirement of sizing of pipeline will be as per the location of ODU in the premises. -34.9mm
VRF PIPELINE WORKS<br>SITC of Interconnecting copper refrigerant pipe with19mm Nitrile rubber protection insulation between each set of Ductable /split indoor & outdoor units and 13mm insulation for VRF systems as per specifications, all piping inside the room shall be properly supported with MS hanger & clamps and all external piping with UV Coating as per specification etc. complete as required. All piping inside the room in ceiling shall be properly supported in cable tray/hangers. rates should quote inclusive of loading and unloading charges, The requirement of sizing of pipeline will be as per the location of ODU in the premises. -44.5mm
CENTRAL CONTROLLER W/o PC Monitoring Systems Supply installation, testing and commissioning of Central Remote Controller. System should have facilities for start, stop, temperature setting, fan speed control, mode control, Group control, emergency start & stop, BMS access and fault Diagnosis. etc complete as required
CONCEALED UNIT - 2 TR<br>Supply, Installation, Testing and Commissioning of air cooled IVRF System indoor units equipped with highly efficient normal air filters , low noise evaporator coil fan, vibration isolator along with suitable for connecting Data based system and cordless remote with group control system
Supply installation, testing and commissioning of VRF based indoor units complete with Cordless remote, Drain pump and all accessories, Vibration isolators & supports, Including all electrical control panel. (Bidder To offer nearest size of the Unit available) Ceiling Suspended "High-Static Type Ductable type" VRF Indoor Unit having following approximate capacities with Cordless remote Controls and Drain Pump. - 4.0 TR Four-way Cassette VRF Indoor Unit (with cordless remote, Decorative Panel and Inbuilt Drain pump)
Supply, Installation, testing and commissioning of 28 HP VRF/VRV Outdoor Units (condensing Units)- TOP DISCHARGE with Hot & Cold Technology, with minimum 2 Nos. of compressors for the better reliability of the system. Special pre-coated fins, panel, corrosion resistant coated condenser, condenser fan , electrical & microprocessor panel, isolating valves and all the necessary accessories for proper functioning of the units. having following approximate capacities. Power Supply will be made available at one point only near outdoor unit.
Supply, Installation, testing and commissioning of 16 HP VRF/VRV Outdoor Units (condensing Units)- TOP DISCHARGE with Hot & Cold Technology, with minimum 2 Nos. of compressors for the better reliability of the system. Special pre-coated fins, panel, corrosion resistant coated condenser, condenser fan , electrical & microprocessor panel, isolating valves and all the necessary accessories for proper functioning of the units. having following approximate capacities. Power Supply will be made available at one point only near outdoor unit.
Ancillary works - VRV/VRF - ODU<br>Supply installation , testing commissioning of FACTORY SUPPLIED INSULATED REF JOINTS / Y-JOINTS, CONTROL BOX, SPLITTERS, PIPE FITTINGS, ACCESSORIES ETC. for all the above VRF ODUs units.
Ancillary works - VRV/VRF - IDU<br>Supply installation , testing commissioning of FACTORY SUPPLIED INSULATED REF JOINTS / Y-JOINTS, CONTROL BOX, SPLITTERS, PIPE FITTINGS, aCCESSORIES ETC. for all the above VRF IDUs units
MEDICAL GAS PIPELINE WORKS
AREA VALVE SERVICE UNIT (AVSU) - 4 gas<br>SITC of 4 gas AVSU as required and as specified under the guidelines laid for Medical gas system, as approved by Engineer HLL
22mm OD X .9mm THIICK Cu PIPE<br>SITC of copper pipes manufactured from phosphorous deoxidised non-arsenical copper of grade CW024A (Cu-DHP), manufactured EN 13348:2008 to metric outside diameters and having mechanical properties, pipes shall be of R250 (half hard)temper. Pipes shall be degreased suitable for oxygen use and cleanliness is to be maintained by filling each pipe with dry, clean, oil and oxygen free nitrogen, fitting suitable end caps and protectively wrapping. Solid drawn, seamless, deoxidised, non- arsenical, half hard, tempered and degreased copper tubes manufactured to metric outside diameters and should have mechanical properties in accordance with HTM 02-01 and conforming to EN13348:2008.The pipes should also be accompanied with manufacturer’s test certificate for the physical and chemical composition. Copper Fittings should be as per HTM 02-01. All plastic saddles should have brass screws. as per the specifications and requirements, painting of the pipes installed as per color code for medical gas system is also under the scope of contractor<br>20 mm
15mm OD X .9mm THICK Cu PIPE<br>SITC of copper pipes manufactured from phosphorous deoxidised non-arsenical copper of grade CW024A (Cu-DHP), manufactured EN 13348:2008 to metric outside diameters and having mechanical properties, pipes shall be of R250 (half hard)temper. Pipes shall be degreased suitable for oxygen use and cleanliness is to be maintained by filling each pipe with dry, clean, oil and oxygen free nitrogen, fitting suitable end caps and protectively wrapping. Solid drawn, seamless, deoxidised, non- arsenical, half hard, tempered and degreased copper tubes manufactured to metric outside diameters and should have mechanical properties in accordance with HTM 02-01 and conforming to EN13348:2008.The pipes should also be accompanied with manufacturer’s test certificate for the physical and chemical composition. Copper Fittings should be as per HTM 02-01. All plastic saddles should have brass screws. as per the specifications and requirements, painting of the pipes installed as per color code for medical gas system is also under the scope of contractor<br>20 mm
deoxidised non-arsenical copper of grade CW024A (Cu-DHP), manufactured EN 13348:2008 to metric outside diameters and having mechanical properties, pipes shall be of R250 (half hard)temper. Pipes shall be degreased suitable for oxygen use and cleanliness is to be maintained by filling each pipe with ry, clean, oil and oxygen free nitrogen, fitting suitable end caps and protectively wrapping. Solid drawn, seamless, deoxidised, non- arsenical, half hard, tempered and degreased copper tubes manufactured to metric outside diameters and should have mechanical properties in accordance with HTM 02-01 and conforming to EN13348:2008.The pipes should also be accompanied with manufacturer’s test certificate for the physical and chemical composition. Copper Fittings should be as per HTM 02-01. All plastic saddles should have brass screws. as per the specifications and requirements, painting of the pipes installed as per color code for medical gas system is also under the scope of contractor<br>20 mm
22 mm BALL VALVE (MGPS)<br>SITC of Line Valves for use in plant rooms and to facilitate the isolation of areas or areas where area zone valve are unnecessary. These shall be of the ball valve type and shall be constructed of a nickel plated brass body, PTFE seats and brass chrome plated ball. The valve shall be operated by a manual operating lever by 90º turn. All medical gas line ball valves shall provide a full bore flow and shall be cleaned for oxygen service and fully tested. The valve assembly shall terminate in copper stub pipes to enable brazing directly into the distribution system using the flux less brazing technique. A locking device shall be provided to lock the valve in either the fully open or fully closed position. Line valves shall be located in readily accessible areas of ducts and shafts, however care should to ensure safety to prevent danger from leakage. Line valve installation should be carried out as per HTM 2022/HTM 02-01 standards.
12 mm BALL VALVE (MGPS)<br>SITC of Line Valves for use in plant rooms and to facilitate the isolation of areas or areas where area zone valve are unnecessary. These shall be of the ball valve type and shall be constructed of a nickel plated brass body, PTFE seats and brass chrome plated ball. The valve shall be operated by a manual operating lever by 90º turn. All medical gas line ball valves shall provide a full bore flow and shall be cleaned for oxygen service and fully tested. The valve assembly shall terminate in copper stub pipes to enable brazing directly into the distribution system using the flux less brazing technique. A locking device shall be provided to lock the valve in either the fully open or fully closed position. Line valves shall be located in readily accessible areas of ducts and shafts, however care should to ensure safety to prevent danger from leakage. Line valve installation should be carried out as per HTM 2022/HTM 02-01 standards.
15 mm BALL VALVE (MGPS)<br>SITC of Line Valves for use in plant rooms and to facilitate the isolation of areas or areas where area zone valve are unnecessary. These shall be of the ball valve type and shall be constructed of a nickel plated brass body, PTFE seats and brass chrome plated ball. The valve shall be operated by a manual operating lever by 90º turn. All medical gas line ball valves shall provide a full bore flow and shall be cleaned for oxygen service and fully tested. The valve assembly shall terminate in copper stub pipes to enable brazing directly into the distribution system using the flux less brazing technique. A locking device shall be provided to lock the valve in either the fully open or fully closed position. Line valves shall be located in readily accessible areas of ducts and shafts, however care should to ensure safety to prevent danger from leakage. Line valve installation should be carried out as per HTM 2022/HTM 02-01 standard
Oxygen Flow meter with Humidifier Bottle<br>SITC of Flow meter Back pressure Compensated. Flow meter would be accurate gas flow measurement and control within a range of 0-15 liters per minute. It would meet strict precision and durability standards. Flow meter body would be made of brass material. Flow tube and shroud components would be made of clear, impact resistant polycarbonate. The humidifier bottle would be unbreakable polycarbonate material and autoclavable at 134 degrees centigrade. The humidifier would have built in safety valve.
Vacuum regulator with suction bottle<br>SITC of Single piece wall mounted suction collection & regulation unit With jar capacity of 600 ml each shall be provided at each of the bed side. Jars would be made of autoclavable materials. The units shall be clamped neatly to the wall using suitable clamps
Gas / Vacuum Outlets<br>SITC of Gas/Vacuum Outlets with Front loading type terminal outlets designed to dispense medical gases or an inlet for medical vacuum to the secondary equipment flow meters, Surgical Tools, Suction regulators, etc. Terminal unit sealed by O ring. The outlets should Quick Connect Type and gas specificity is accomplished by Diametric indexing / Geometric indexing Should have Push to IN and press-to-OUT mechanism for probes. Allows plugging of probes from front. Parking Type probe / connector Self-sealing valve on disengaging the probe (Quick disconnect) Smooth quite action Non return valve for on line servicing/ repairing , Indexed to eliminate inter-changeability of gas services, Color-coded gas specific front plate Flow rate exceeds the requirements of ISO 9170 – 1. Totally leak proof, safe & easy to operate Configurations possible: surface, flush & Bead-head. The terminal outlets should comply with ISO and NFPA. Body shall be of one piece brass construction.
BED HEAD PANEL <br>Supply, Installation, testing and commissioning of Bed head panels(1.2m) with Terminal unit provisions as per tender drawing. Provision for Electrical and data points . Accessories<br>including suction holder and one monitor tra
Classic Builders
PAN PACIFIC ENGINEERING SERVICES PRIVATE LIMITED
RAJAN P
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .