Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.6 LAccepted-Finance 0 BETTER POWER SERVICES PVT LTD A K AZAD ROAD REHABARI KAMRUP ASSAM 781008 | KAMRUP METRO | ASSAM | 781008 | L1 | Accepted-Finance L1 | |
| 2 | L2₹11.0 L+₹2.3 L (27.1%)Rejected-Finance 685 SONARPUR STATION ROAD GREEN PARK KOLKATA 700103 | KOLKATA | 24 PARAGANAS SOUTH | WEST BENGAL | 700103 | L2 | Rejected-Finance L2 | |
| 3 | L3₹11.6 L+₹3.0 L (34.7%)Rejected-Finance 321 PATIL NAGAR BAWDHAN ROAD BAVDHAN BUDRUK PUNE MAHARASHTRA 411021 | PUNE | MAHARASHTRA | 411021 | L3 | Rejected-Finance L3 | |
| 4 | L4₹11.8 L+₹3.2 L (37.0%)Rejected-Finance 230 S N ROY ROAD SAHAPUR COLONY KOLKATA WEST BENGAL 700038 | KOLKATA | WEST BENGAL | 700038 | L4 | Rejected-Finance L4 | |
| 5 | L5₹12.6 L+₹4.0 L (45.8%)Rejected-Finance VILL DAKSHIN SHIBGANJ P O AND P S PATHARPRATIMA DIST SOUTH 24 PARGANAS | SOUTH 24 PARGANAS | WEST BENGAL | L5 | Rejected-Finance L5 |
Tender Value
Refer Docs
EMD Value
₹24,000
Closing Date
31 May 2025, 2:00 pmClosed
Superintending Engineer, CEC, PWD.
Office of the SUPERINTENDING ENGINEER, Central Electrical Circle 184, C.R.Das Road, Berhampore, Murshidabad, PIN-742101
Construction of 50 Bedded Critical Care Block CCB in the New General Campus of Murshidabad Medical College and Hospital, Berhampore, Murshidabad SITC of UPS
2025_WBPWD_840976_1
WBPWD/CEC/NIT/02/Q/25-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
Berhampore
Please refer Tender documents.
5 documents required · 5 mandatory
₹24,000
Central Electrical Circle, PWD.
2 Jul 2025
30 Apr 2025
2 Jun 2025
5 May 2025
31 May 2025
8 May 2025
7 May 2025
Amount
SITC of 15 KVA UPS including Battery Bank of(12480~15600) VAH or higher (SMF Battery 12 Volt, 42 AH~65AH ) 3ph Input / 3ph Output, static by pass arrangement, compitable with D.G. Set, DSP controlled IGBT based rectifire with minimum 90% efficiency on 100% Load. The UPS shall be provided with active input P.F. Correction system to obtain 0.9 lag at 100% resistive Load, Wave form - Pure sine wave Crest Factor 3:1 It Should be capable of operating in 50'c above ambient temperature, Built in Solid State float cum boost charger with automatic boost / trickel charge mode with current Limiting features. The charger should be designed for at least 15% of the total battery current. The UPS Should have current limiting protection, built in over load / Short circuit protection with snubber circuits for current limit. Soft start arrangement, Over voltage / under voltage protection, mains ON, Inverter ON/ OFF/ FAULTY/ TRIP (Reason), Charger ON/ FAULTY or TRIP, Battery Low, Static by-pass ON, Over temperature. Inbuilt Isolation Transformer of 1:1 ratio connected in Delta- Star Mode. Battery set Complete with self-standing cubicle or cabinet. The UPS should have external automatic load transfer switch for parallel operation.
Regulated Sealed Lead Acid Battery, Construction type: AGM or VRSLAB in ABS Flame Retardant Rating (12V,42 AH~65 AH SMF Battery -1 Lot) (Battery Make Amararaja Quntra/Exide Power Safe). Back up time 30 Min at full load. Warranty : One Year on UPS and One Year on SMF Battery on site against any manufacturing defects. Certificate: ISO 9001:2015, ISO 14001:2015, IOS 18001, OHSAS 18001. CE Certification: IEC/ EN 62040-1-1, IEC/EN50091- 1, IEC/EN 60950(Safety), IEC/ EN 5009 1-2, IEC/ EN 62040-2 (EMC Emmission), IEC/EN 62040-3 (Performance & Design), IEC/EN 61000-4(EMC Emmunity) & IEC/ EN 60146 (Design & Manufacture) (Make: APC-Schneider Electric / NUMERIC/ Power One/ VERTIV/ Switching AVO/ Powersafe/ Delta/ BETTER POWER/ PROSTARM)
SITC of 6 KVA UPS including Battery Bank of(4274~5376) VAH or higher (SMF Battery 12 Volt, 26 AH~28ah ) 1ph Input / 1ph Output, static by pass arrangement, compitable with D.G. Set, DSP controlled IGBT based rectifire with minimum 90% efficiency on 100% Load. The UPS shall be provided with active input P.F. Correction system to obtain 0.9 lag at 100% resistive Load, Wave form - Pure sine wave Crest Factor 3:1 It Should be capable of operating in 50'c above ambient temperature, Built in Solid State float cum boost charger with automatic boost / trickel charge mode with current Limiting features. The charger should be designed for at least 15% of the total battery current. The UPS Should have current limiting protection, built in over load / Short circuit protection with snubber circuits for current limit. Soft start arrangement, Over voltage / under voltage protection, mains ON, Inverter ON/ OFF/ FAULTY/ TRIP (Reason), Charger ON/ FAULTY or TRIP, Battery Low, Static by-pass ON, Over temperature. Inbuilt Isolation Transformer of 1:1 ratio connected in Delta- Star Mode. Battery set Complete with self-standing cubicle or cabinet. The UPS should have external automatic load transfer switch for parallel operation.
Regulated Sealed Lead Acid Battery, Construction type: AGM or VRSLAB in ABS Flame Retardant Rating (12V,26~28 AH SMF Battery -1 Lot) (Battery Make Amararaja Quntra/Exide Power Safe). Back up time 30 Min at full load. Warranty :One Year on UPS and One Year on SMF Battery on site against any manufacturing defects. Certificate: ISO 9001:2015, ISO 14001:2015, IOS 18001, OHSAS 18001. CE Certification: IEC/ EN 62040-1-1, IEC/EN50091- 1, IEC/EN 60950(Safety), IEC/ EN 5009 1-2, IEC/ EN 62040-2 (EMC Emmission), IEC/EN 62040-3 (Performance & Design), IEC/EN 61000-4(EMC Emmunity) & IEC/ EN 60146 (Design & Manufacture) (Make: APC-Schneider Electric / NUMERIC/ Power One/ VERTIV/ Switching AVO/ Powersafe/ Delta/ BETTER POWER/ PROSTARM)
WISE CHOICE (BID ID -6419020)
Prostarm Info Systems limited (BID ID -6472235)
switching avo Electro Power Ltd (BID ID -6412638)
B. ENGINEERING CO. (BID ID -6414135)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .