CWE AF Borjhar
HQ CWE AF Borjhar Military Engineer Services PO Airport Borjhar Guwahati Assam 781015 Tele 0361 2841626
REPAIR/ MAINTENANCE OC VCB, RMU AND HT CABLE RING MAIN SYSTEM OF EXTERNAL ELECTRIFICATION AND ALLIED WORKS UNDER GE (AF) TEZPUR
2026_MES_799250_1
9168
Open Tender
Electrical and Maintenance Works
Item Rate
334 days
Tezpur
As per tender documents.
8 documents required · 8 mandatory
₹500
GE (AF) Tezpur
₹96,000
Yes
18 Nov 2026
18 Nov 2026
11 Dec 2026
18 Nov 2026
9 Dec 2026
2 Dec 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Servicing, Repairing and Maintenance of existing HT 11 KV,400/630/800 Amps rating VCBs (Make : Crompton Greaves/ Areva ‘Alstom’/ Schneider/ Seimens/ ITE/Andrew Yule) by removing from housing, overhauling the mechanical parts and periodic maintenance servicing of 11KV indoor/ outdoor VCBs, checking of quality of vacuum interrupter, insulation resistances, static contact resistance, testing ( IR value, Ratio Test, Polarity) and connection checking of 11 KV Current Transformer ( Set of Three) by primary injection kit ,testing and calibration of relay ( Set of, Two Over Current and One Earth Fault Relays) by secondary injection kit including,all other functional tests of the VCB panels including for CTs, PTs, complete all as specified and directed.
Notes:- (i) (i) The work shall be carried out through Authorised & Qualified agencies as approved by the Engineer in Charge. (ii) Calibration and Testing(s) shall be done through State Electrical Licencing Board's valid electrical licence holder for the appropriate class/category of the work as approved by the Engineer in Charge. (iii) Contractor shall submit Tripping test & Relay calibration certificate against each VCB duly signed by all concerned. (iv) Spare Parts for replacement will be measured and paid seperately under respective items of this BOQ here in after. | 30 | Each Job | -10.75 | - |
| - | Servicing, Repairing and Maintenance of existing HT 33 KV,1250 Amps rating VCBs (Make : Areva ‘Alstom’) by removing from housing, overhauling the mechanical parts and periodic maintenance servicing of 33 KV indoor outdoor VCBs,checking of quality of vacuum interrupter, insulation resistances, static contact resistance, testing ( IR value, Ratio Test, Polarity) and connection checking of 11 KV Current Transformer ( Set of Three) by primary injection kit ,testing and calibration of relay ( Set of, Two Over Current and One Earth Fault Relays) by secondary injection kit including,all other functional tests of the VCB panels including for CTs, PTs,complete all as specified and directed.
Notes:- (i) The work shall be carried out through Authorised & Qualified agencies as approved by the Engineer in Charge. (ii) Calibration and Testing(s) shall be done through State Electrical Licencing Board's valid electrical licence holder for the appropriate class/category of the work as approved by the Engineer in Charge. (iii) Contractor shall submit Tripping test & Relay calibration certificate against each VCB duly signed by all concerned. (iv) Spare Parts for replacement will be measured and paid seperately under respective items of this BOQ here in after. | 3 | Each Job | -9.75 | - |
| - | Servicing, Repairing and Maintenance of existing HT 11 KV, 630 Amps rating Ring Main Unit, SF 6 insulated isolator (Make : Crompton Greaves) by removing from housing, overhauling the mechanical parts and periodic maintenance servicing of 11 KV indoor / outdoor RMUs, including cutting, fabrication and welding of gas chamber and checking of quality of interrupter, insulation resistances, static contact resistance, testing ( IR value, Ratio Test, Polarity) and connection checking of 11 KV Current Transformer ( Set of Three) by primary injection kit ,testing and calibration of relay ( Set of, Two Over Current and One Earth Fault Relays) by secondary injection kit including,all other functional tests of the VCB panels including for CTs, PTs,complete all as specified and directed.
Notes:- (i) The work shall be carried out through Authorised & Qualified agencies as approved by the Engineer in Charge. (ii) Calibration and Testing(s) shall be done through State Electrical Licencing Board's valid electrical licence holder for the appropriate class/category of the work as approved by the Engineer in Charge. (iii) Contractor shall submit Tripping test & Relay calibration certificate against each RMU duly signed by all concerned. (iv) Spare Parts for replacement will be measured and paid seperately under respective items of this BOQ here in after. | 5 | Each Job | -8.75 | - |
| - | Supply Only, panel indicating lamp fitting, LED type suitable for110 volt/ 230 volt AC with base complete all as specified
(Make: L&T / Siemens / STS/AE) | 30 | Each | -7.75 | - |
| - | Supply Only, Digital AC Ammeter with 3 ½ digit display and with built in selector switch, Type 3 PH, Range 5 Amp Direct and with CT secodary site selectable 1A/5A, flush mounting size 96 mm X 96 mm, Accuracy Class 1.0, all as per Model No WL131010OOOO of Make “L&T” or equivalent Model of Make MECO/AE / Secure / Conzerv, complete all as specified. | 10 | Each | -6.75 | - |
| - | Supply Only, Breaker Control Switches,TNC (Trip,Neutral and Close), rating 25 Amps with contact arrangement 1Trip + 1Close, barrel lock mounting type, suitable for 11 KV VCB panels, complete all as specified. (Cat No 73257SEB90PGBB of Make L&T or equivalent Model of Make: Switron / Recom /Kaycee / Areva) | 10 | Each | -5.75 | - |
| - | Supply Only, heater with heater switch & thermostat suitable for 11KV VCB panels, 80 watts, as per OEM's specifications,complete all as specified. (OEMs:-Crompton Greaves/ Areva ‘Alstom’/Schneider/ Seimens/ITE/ Andrew Yule) | 20 | Each | -4.75 | - |
| - | Supply Only, HT Current Transformers, single phase indoor solid state (Resin cast) 11 KV, ratio 150/5A, accuracy class 5P10, rated burden 15VA, STC 13.1 KA for 1second,suitable for VCB Panels as per OEM's specifications,complete all as specified. (OEMs:-Crompton Greaves/ Areva ‘Alstom’/Schneider/Seimens/ITE/ Andrew Yule) | 5 | Set of Three | -3.75 | - |
| - | Supply Only,microprossesor based feeder protection neumerical relay with overcurrent, earth-fault, phase-discontinuity, negative-phase sequence and thermal-overload protections, inrush current detection, reclosing and measurement,preconfigured functionality facilitates, configurable binary inputs/outputs using local HMI or communication interface,modbus and IEC 60870-5-103 protocols supports,universal power supply 24-265 V AC/DC,suitable for 11 KV VCB panels,complete all as specified. (Cat No REJ601 of Make ABB or equivalent Model of Make: Schneider/ Seimens) | 2 | Each | -2.75 | - |
| - | Supply Only,auxiliary relay with high-speed operation,rated voltage 24Volts DC,operating range - 30% to +10% of rated voltage,frequency 50 Hz +/-5%,pick-up voltage < 80%,Drop-off voltage > 20% ,Pick-up time 20-30ms,contacts 6N/O + 1N/C,suitable for 6.6 KV VCB panels,complete all as specified. (Type PQ8n of Make ABB or equivalent Model of Make: Schneider/ Seimens) | 5 | Each | -1.75 | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.54 MB
9168tender.pdf
Tender Documents • 0.96 MB
BOQ_896712.xls
BOQ • 0.42 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .