RequiredCertificate (Requested in ATC)
RequiredOEM Authorization Certificate Bid to RA enabled Yes Diesel Generators- DG Sets ( 1 pieces ) Technical Specifications * As per GeM Category Specification Specification Specification Name Values Bid Requirement (Allowed Values) OUTPUT CAPACITY RATING/PHASE Nominal Rated Capacity (KVA) 5 5
Required7.5
Required10
Required15
Required20
Required25
Required30
Required40
Required62.5
Required82.5
Required100
Required125
Required160
Required180
Required200
Required250
Required320
Required380
Required400
Required500
Required600
Required750
Required50
Required140 Or higher No of Phase - Single phase ENGINE Make of Engine - * Model Number of - * 1/4 Engine Capacity of Engine (cc) - * Engine Power (kWm) - * ISI Marking to IS :10001 for engine Yes * BIS license No
Requiredif applicable - * Type of Engine cooling Liquid Cooled Liquid Cooled Type of governer Mechanical Mechanical
RequiredElectronic Or higher Class of governer A2 A0
RequiredA1
RequiredA2 Or higher Number of cylinders (nos) 1 * No of Strokes (nos) 4 * Rated RPM of Engine (RPM) - 1500 Overload capacity for one hour for every 11 hours continuous running at full load (%) 10 * Specific Fuel Consumption (gm/kWh) - * Starting voltage (volt) 12 * ALTERNATOR AC GENERATOR(ALTER NATOR) Make - * AC GENERATOR(ALTER NATOR) model Number - * Rating of AC Generator (KVA) 5 * Power Factor of AC generator 0.8 * Efficiency at rated Power factor at 75% of full Load 75.2 * Compliance of Alternator to IS:13364(part-1) Yes * Type of alternator Brushless * Voltage Regulation Grade VG 3 * Alternator IP Rating IP 23 * Class of Insulation H * CONTROL PANEL Control Panel AMF AMF 2/4 IP Rating of Control Panel IP 53 * ACOUSTIC ENCLOSURE Sheet Thickness 1.6 1.6
Required1.8
Required2 Or higher Thickness of Foam 25 * Density of Foam for sound insulation 28 * Noise level at 1 meter (dB) 74 * BATTERY Battery Type & Specification Low Maintenance free to IS: 14257 for high cranking performance * Battery capacity (Ah) - * No of batteries 1 * TEST REPORTS Availability of Type test report for Engine from Central govt/NABL/ILAC accredited laboratory Yes * Test Report number and date(Engine) - * Name and address of laboratory(Engine) - * Availability of Type test report for Alternator from Central government/NABL/ILAC accredited laboratory Yes * Test Report number and date(Alternator) - * Name and address of laboratory(Alternator) - * DG set meet requirements of Enviro nmental(Protection) Rules 1986
Requiredin respect of noise and emission norms
Requiredas described in STC Yes * WARRANTY INSTALLATION & COMMISSIONING Warranty 2 2.0 Installation & Commissioning Without Installation With Installation
RequiredWithout Installation Agreed to STC of the Product Yes * * Specifications highlighted in bold are the Golden Parameters. * Bidders may note that In respect of non-golden Parameters
Requiredthe specifications 'Values' chosen by Buyer will generally be preferred over 'Bid requirement ( allowed Values) by the Buyer. Additional Specification Documents 3/4