Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
| 5 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹3.9 L
EMD Value
₹7,700
Closing Date
26 Jun 2020, 6:55 pmClosed
Executive Engineer Mech. Irrig. Div. Baramulla
Mech. Irrig. Div. Baramulla
Urgent Electrical works required for restoration of Lift Irrigation Scheme Zehanpora.
2020_IFC_98605_1
eNIT 24 of 2020-21
Open Tender
Repair and Maintenance Works
Item Rate
10 days
Zehenpora
Please refer Tender documents.
4 documents required · 4 mandatory
₹200
Yes
Mech. Irrig. Div. Baramulla
₹7,700
Yes
Mech. Irrig. Div. Baramulla
15 Jul 2020
20 Jun 2020
27 Jun 2020
20 Jun 2020
26 Jun 2020
20 Jun 2020
24 Jun 2020
Amount
Design, Supply, installation, testing and commissioning of 200 KVA manually operated 8/6 steps voltage Stabilizer for following broad band specifications: Type of voltage controller: Manually operated copper strip wound, 3 phase & neutral power supply. Type of Regulator: plate type with electrolytic copper contacts. Input Voltage: 150-330V. Output Voltage: 400V. Frequency: 50±3% c/s. Phase imbalance: Imbalanced voltage & frequency characteristics. Winding: Electrolytic grade copper strips of adequate section, vacuum impregnated and oven dried. Insulation: Fiber glass insulation to tested parameter. Efficiency: 98%. Cooling: Natural with convection fins, oil cooled. Mounting: Mounting on uni-directional wheels at four corner. Duty cycle: 100% continuous. Enclosure: M.S sheet 4mm thick in pressed CGR sheet, powder coated duly strengthened with stiffeners of M.S flat/angle. It shall also be provided with a filling nozzle at the top & a drain at the bottom dully plugged. Core laminates: High grade low eddy current loss grain oriented silicon steel laminations. Load: Three phase induction motor load with full load amperage (Max 200& Normal 190 Ampere). Load Ampere continuous: 200 Ampere (to be read on starter Ampere meter during operation). Display panel: The container shall be provided with a display on the top housing 2 no voltmeter (0-500V) digital type for incoming & outgoing feeder & 3 no phase indication lamps (RYB) of neon type. Cooling medium: The container shall be filled with relevant grade T-oil up to the required level. Connection Box: The stabilizer shall be provided with complete input/output connection box to ensure proper input/output power supply of voltage stabilizer. The equipment has to be provided/ installed at site and successfully tested commissioned on full load.
Providing, installation, successful testing of 37/.083 PVC insulated copper cable of polycab/ Finolex or equivalent reputed make.
M/S NEW BUHROO ELECTRICAL AND MECH ENGG WORKS
M/s INFO ENGINEERING WORKS
stage.html
html • 0.03 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .