SHRI SAURABH, IDSE, CWE
HQ CWE Tenga PIN-900194 c/o 99 APO
PROVN OF DEDICATED 33 KV LINE FROM 33/11 KV RANGAPARA DSS TO 33/11 KV SUB STN AT MISSAMARI
2026_MES_781635_1
8653/E8
Open Tender
Civil Works
Item Rate
GE Missamari
Please refer Tender documents.
8 documents required · 8 mandatory
₹1,000
Yes
GE MISSAMARI
₹1.6 L
Yes
30 Jul 2026
30 Jul 2026
2 Sept 2026
30 Jul 2026
26 Aug 2026
19 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply & Erecting Steel Tubular Swaged Pole Type 410-SP-64 (12.0 Metre long) including Cast Iron Base Plate, Finial Taper Plug, Cap, Mild Steel Bolts, Nuts, Screws including applying two coats of Black Bituminous Paint Internally and Externally from bottom End of Pole upto PCC Coping and applying with two coats of Aluminium Painting over a coat of Aluminium Primer (Externally from Top of Coping) including writing MES Pole No. with synthetic Enamel Paint (First Grade/quality), complete all as specified and as directed. | 12 | Each | 100 | ₹1,200 |
| 2 | Supply, laying & testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 33000 volts grade, of size 3 core 300 sq mm complete all as specified and as directed. | 250 | RM | 100 | ₹25,000 |
| 3 | M&L for fabrication and installation of 33 KV Bracing support to mount electrical equipments of Sub Stn and grid structure /Tower for stringing of 33 KV Over Head Bus /ACSR Conductor to form a Bus Bar inside Sub Station with Hot dip galvanized lattice type steel structure , main structural members and bracing system supports , clamps & Backplates etc of any size any design fabricated from structural steel sections including GI nuts , bolts , washers , welding , bending , cold or hot drilling holes for bolts in any shape or size as indicated or directed, complete all as specified and as directed. (Note :- Civil work for foundation for Tower/Bracing Support is included under quoted rate) | 15 | Qtl | 100 | ₹1,500 |
| 4 | Supply ,fixing , testing & commissioning ,operating voltage 33 kV ,630A , 50Hz rated lighting withstand voltage 99 KV , rated power withstanding voltage 84KV for 1 min ,Peak Current 52.5kA ,rated short circuit time 21 kA for 3 sec , with 3 O/C and 1 E/F with dispaly and self power supply relay 26.3kA 3way RMU EC grade copper busbars , with main tank IP67 and other compartments IP 54 ,(2I/C+1O/G) 3CB, Outdoor type , operated Motorized as per IEC 62271-100,62271-102,62271-103,62271-200,60056, 60185,60186 complete all as specified and as directed . | 1 | Each | 100 | ₹100 |
| 5 | S&F Insulator Pin type Polymer, including one Galvanised Mild Steel Spindle, Two Galvanised Iron Washers and One Galvanised Iron Nut, for 33 KV grade, complete all as specified and as directed | 12 | Each | 100 | ₹1,200 |
| 6 | S&F Disc type insulator polymer suspension type , for tension with Tension Clamps for conductors working pressure 33 KV, complete all as specified and as directed. | 18 | Each | 100 | ₹1,800 |
| 7 | S&F ACSR with permissible Sags and providing Jumper, etc., fixing on Electric Poles and binding to Insulators with Aluminium Binding Wire as in OH Conductors including stringing, tightening, etc., complete all as specified and as directed.
NOTE : Cost of Binding Wire is deemed to be included in the quoted Unit Rate. | 2 | Qtl | 100 | ₹200 |
| 8 | Supply & Fix Lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp complete all as specified and as directed. | 1 | Set of 3 | 100 | ₹100 |
| 9 | Supply, installation, testing, and commissioning of 33 KV outdoor Current Transformer (CT) suitable for metering and protection purposes, complete with all accessories.Voltage class: 33 kV , Outdoor type , oil-filled Current ratio 200/ 5 A , Accuracy class 5P10 , Burden 10–15 VA ,Protection: 15–30 VA Frequency: 50 Hz System Hermetically sealed construction Primary terminals suitable for ACSR/AAAC conductor Secondary terminal box (weatherproof, IP-55 or better Oil level indicator (for oil-filled CT) ,Pressure relief device Earthing terminals (2 nos) Nameplate and rating plate complete all as specified and as directed. | 1 | Set of 3 | 100 | ₹100 |
| 10 | Supply, installation, testing, and commissioning of 33 KV outdoor Potential Transformer (PT/VT) suitable for metering and protection, complete with all accessories and fittings. Technical Specifications Voltage Class: 33 kV
Type: Outdoor, oil-filled / cast resin (as per requirement) Insulation Level:
Lightning impulse withstand: 170 kVp Power frequency withstand: 70 kV (1 min) Rated Primary Voltage: 33 kV Rated Secondary Voltage: 110 V or 110 V Number of Phases: Single phase (used in sets of 3) Accuracy Class: Metering Core: 0.2 Protection Core: 3P Burden: Metering: 50–100 VA Protection: 100–200 VA Frequency: 50 Hz Porcelain / polymeric insulated housing Hermetically sealed (for oil-filled type) Primary terminals suitable for outdoor connection Secondary terminal box (weatherproof, IP-55 or higher) Built-in HV fuse / protection (if applicable) Oil level indicator (for oil-filled PT) Complete PT unit (3 Nos. for 3-phase system) Mounting structure / support frame Terminal connectors and clamps Secondary terminal box with wiring facilities Earthing terminals (2 Nos.) Nameplate and rating details complete all as specified and as directed | 1 | Set of 3 | 100 | ₹100 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.65 MB
TENDERDOCUMENT8653.pdf
Tender Documents • 1.36 MB
BOQ_875634.xls
BOQ • 0.25 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].