Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Infra Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹68.8 LAccepted-AOC VP 10 323 CHITHRALAYAM NALANKALLU VILAVOORKAL MALAYINKEEZHU THIRUVANANTHAPURAM 695571 | THIRUVANANTHAPURAM | KERALA | 695571 | L1 | Accepted-AOC L1 | |
| 2 | L2₹69.1 L+₹31,235.55 (0.45%)Rejected-AOC ULRA 75 MANOMANI HOUSE JAGATHY THYCADU P O THIRUVANANTHAPURAM 695014 | THIRUVANANTHAPURAM | KERALA | 695014 | L2 | Rejected-AOC L2 | |
| 3 | Rejected-Technical | - | Rejected-Technical Disqualified |
Tender Value
₹69.8 L
EMD Value
₹50,000
Closing Date
25 Mar 2024, 3:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Associate Vice President
HLL Lifecare Limited, HLL Bhavan, No26/4, Tambaram-Velachery Main Road, Pallikaranai, Chennai 600 100, Tamilnadu
Setting up of Integrated Public Health Lab(IPHL) at Kollam District , Kerala
2024_HCDPS_670514_1
HLL/HCD/IPHL/KLM/23-24
Open Tender
Civil Works - Buildings
Item Rate
330 days
IPHL Kollam District
Please refer Tender documents.
15 documents required · 15 mandatory
₹2,950
Yes
₹50,000
Yes
20 Mar 2025
15 Mar 2024
26 Mar 2024
15 Mar 2024
25 Mar 2024
15 Mar 2024
Amount
CIVIL WORKS
DISMANTLING AND DEMOLISHING
Demolishing brick work manually / by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-Charge.In cement mortar
Demolishing R.C.C. work manually / by mechanical means including stacking of steel bars and disposal of unserviceable material with in 50 metres lead as per direction of Engineer -in-Charge.
Dismantling doors, windows and clerestory windows (steel or wood ) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead:Of area 3 sq. metres and below
Dismantling steel work in built up sections in angles, tees, flats and channels including all gusset plates,boltd, nuts, cutting rivets, welding etc. including dismembering and stacking within 50 metres lead.
Dismantling roofing including ridges, hips, velleys and gutters etc., and stacking the material within 50 metres lead of :G.S. Sheet
Dismantling wood work in frames, trusses, purlins and rafters up to 10 metres span and 5 metres height including stacking the material within 50 metres lead:Of sectional area below 40 square centimeters
Dismantling aluminium / Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable surplus material and stacking of serviceable material with in 50 metres lead as directed by Engineer - in-Charge
Dismantling tile work in floors and roofs laid in cement mortar including stacking material within 50 metres lead.For thickness of tiles 10 mm to 25 mm
Dismantling of flushing cistern of all types (C.I. / PVC/ Vitrous China) including stacking of useful materials near the site and disposal of unserviceable materials within 50 metres lead
Dismantling W.C. Pan of all sizes including disposal of dismantled materials i/c malba all complete as per directions of Engineer-in-Charge
Dismantling of plumbing pipe lines of 15mm dia to 110mm dia pipes including stacking of useful materials near the site and disposal of unserviceable materials within 50 metres lead as per the direction of engineer in-charge.
Dismantling of wash basin/ Sink, closing the pipeline with end cap if necessary, including stacking of useful materials near the site and disposal of unserviceable materials within 50 metres lead
PLAIN CEMENT CONCRETE
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering -All work above plinth level up to floor five level:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size)
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size)
RCC WORK
Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up tot floor five level excluding cost of centering, shuttering, finishing and reinforcement :1:1.5:3( 1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size)
Reinforced cement concrete work in beams, suspended floors, roofs, having slope up to 15<sup>0</sup> landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement, with1:1.5:3 (1 cement : 1.5 coarse sand (Zone III) : 3 graded stone aggregate 20 mm nominal size).
Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete above plinth level.Thermo - Mechanically Treated bars of grade Fe-500D or more
FORM WORK
Centering and shuttering including strutting, etc. and removal of form for:Lintels, beams, plinth beams, girders bressumers and cantilevers
Centering and shuttering including strutting, etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts
Centering and shuttering including strutting, etc. and removal of form for:Weather shade, Chajjas, corbels etc., including edges
MASONRY WORKS
Providing and laying autoclaved aerated cement blocks masonry with 150mm/ 230mm/300 mm thick AAC blocks in super structure above plinth level up to floor V level with RCC band at sill level and lintel level with approved block laying polymer modified adhesive mortar all complete as per direction of Engineer-in-Charge. (The payment of RCC band and reinforcement shall be made for seperately).
PLASTERING
12 mm cement plaster of mix:1:4 ( 1 cement : 4 fine sand)
6 mm cement plaster of mix:1:3 ( 1 cement : 3 fine sand)
STEEL WORK
Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete.Hot finished welded type tubes
Providing and fixing plain Multipurpose Cement board (High Pressure steam cured) as per IS : 14862, with suitable screws for fibre cement board as false ceiling, side covering, work slab support etc. complete (frame work to be paid separately) :6 mm thick cement board
Providing and fixing M.S. Grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete.Fixed to steel windows by welding
Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
DOORS AND WINDOWS
Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length (hold fast lugs or dash fastener shall be paid for separately).Second class teak wood
Providing and fixing panelled or panelled and glazed shutters for shutters for doors, windows and clerestory windows, including ISI marked M.S. pressed butt hinges bright finished of required size with necessery screws, excluding panelling which will be paid for separately, all complete as per direction of Engineer - in-charge.30 mm thick shutters
Providing 40x5 mm flat iron hold fast 40 cm long including fixing to frame with 10 mm diameter bolts, nuts and wooden plugs and embeddings in cement concrete block 30x10x15 cm 1:3:6 mix ( 1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size)
Providing and fixing aluminium tower bolts, ISI marked, anodised(anodic coating not less than grade AC 10 as per : 1868), transparent or dyed to required colour or shade, with necessary screws complete:250x10 mm
Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width form 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete.
Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete:125 mm
Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS: 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.Twin rubber stopper
Extra for providing ISI marked Stainless Steel butt hinges instead of M.S. pressed butt hinges bright finished of required size with necessary screws. (Shutter area to be measured)
Providing and fixing bright finished 100 mm mortice lock with 6 levers without pair of handles of approved quality for aluminium door, with necessary screws etc complete as per direction of Engineer- in- charge.
Providing and fixing factory made uPVC door frame made of uPVC extruded sections having an overall dimension as below (tolerance ±1 mm), with wall thickness 2.0mm (±0.2 mm), corners of the door frame to be jointed with galvanized brackets and stainless steel screws, joints mitred and plastic welded. The hinge side vertical of the frames reinforced by galvanized M.S. tube of size 19 x 19 mm and 1 mm (± 0.1 mm) wall thickness and 3 nos. stainless steel hinges fixed to the frame complete as per manufacturer's specification and direction of Engineer-in-chargeExtruded section profile size 48x40 mm
Providing and fixing to existing door frames24 mm thick factory made PVC door shutters made of styles and rails of a uPVC hollow section of size 59x24 mm and wall thickness 2 mm (± 0.2 mm) with inbuilt edging on both sides. The styles and rails mitred and joint at the corners by means of M.S. galvanised/plastic brackets of size 75x220 mm having wall thickness 1.0 mm and stainless steel screws. The styles of the shutter reinforced by inserting galvanised M.S. tube of size 20x20 mm and 1 mm (± 0.1 mm) wall thickness. The lock rail made up of 'H' section, a uPVC hollow section of size 100x24 mm and 2 mm (± 0.2 mm) wall thickness,fixed to the shutter styles by means of plastic/galvanised M.S. 'U' cleats. The shutter frame filled with a uPVC multi-chambered single panel of size not less than 620 mm, having over all thickness of 20 mm and 1 mm (± 0.1 mm) wall thickness. The panels filled vertically and tie bar at two places by inserting horizontally 6 mm galvanised M.S. rod and fastened with nuts and washers, complete as per manufacturer's specification and direction of Engineer-in-charge( For W.C. and bathroom door shutter).
Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete:75 mm
Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-in-charge ( Door handle, lock and mstopper etc to be paid separately)
Providing and fixing Steel S.S- 304 (D) Door Pull Both Side Handle of 12 inch, one Set (2 Handles) ( best make of approved quality ) for Glass, Wooden or similar doors including necessary cutting and making good etc. complete
Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of cross section 90 mm x 45 mm having single rebate of 32 mm x 15 mm to receive shutter of 30 mm thickness. The laminated shall be moulded with fire resistant grade unsaturated polyester resin and chopped mat. Door frame laminate shall be 2 mm thick and shall be filled with suitable wooden block in all the three legs. The frame shall be covered with fiber glass from all sides. M.S. stay shall be provided at the bottom to steady the frame.
Providing and fixing to existing door frames.30 mm thick Glas Fibre Reinforced Plastic (FRP) panelled door shutter of required colour and approved brand and manufacture, made with fire - retardant grade unsaturated polyester resin, moulded to 3 mm thick FRP laminate for forming hollow rails and styles, with wooden frame and suitable blocks of seasoned wood inside at required places for fixing of fittings, cast monolithically with 5 mm thick FRP laminate for panels conforming to IS : 14856, including fixing to frames.
Providing and fixing aluminium tower bolts, ISI marked, anodised(anodic coating not less than grade AC 10 as per : 1868), transparent or dyed to required colour or shade, with necessary screws complete:100x10 mm
ALUMINIUM WORKS
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS : 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminnium snap beading for glazing /paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge.(Glazing, paneling and dash fasteners to be paid for separately): For fixed portionPowder coated aluminium (minimum thickness of powder coating 50 micron)
For shutters of doors, windows & ventilators including providing and fixing hinges / pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber/ neoprene gasket required (Fittings shall be paid for separately)Powder coated aluminium (minimum thickness of powder coating 50 micron)
Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS : 12823 Grade I Type II, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of Engineer - in- Charge.Pre- laminated particle board with decorative lamination on both sides
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 4.0 mm thickness
Providing and fixing 100 mm brass locks ( best make of approved quality ) for aluminium doors including necessary cutting and making good etc. complete
Providing and fixing glazing in door, window, ventilator shutters and partitions etc. with EPDM rubber /neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item): toughened glass of 6 mm thickness.
Providing and Fixing Aluminium Double U channel of required size for sliding doors.
MULTIWOOD WORKS
Providing and fixing Thomson Multi wood board or equivalent make, in shelves with screws and fittings wherever required, edges to be painted with polyurethane primer (fittings to be paid separately) as per the direction of site Engineer-in-charge.
Providing and fixing aluminium round shape handle of outer dia 100 mm with SS screws etc. complete as per direction of Engineer-in-Charge.Polyester powder coated minimum thickness 50 micron aluminium
Providing and fixing magnetic catcher of approved quality in cupboard/ward robe shutters, including fixing with necessary screws etc. complete.Triple strip vertical type.
Providing and fixing concealed hinge of approved quality for 19-20mm thick door with stainless steel screws complete :
TILE WORKS
Grouting the joints of flooring tiles having joints of 3 mm width, using epoxy grout mix 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg). including filling /grouting and finishing complete as per direction of Engineer-in-charge.Size of Tile 600x600 mm
Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600 x 600 mm.
Providing and laying Vitrified tiles indifferent sizes (thickness to be specified bymanufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete.Size of Tile 600x600 mm
Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), including pointing the joints with white cement and matching pigment etc., complete.
Providing and fixing I st quality ceramic glazed wall tiles conforming to IS : 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer -in Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3 kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
Providing and fixing 18 mm thick gang saw cut, mirror, polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations, of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 ( 1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.Area of slab over 0.50 sqm
Extra for providing opening or required size & shape for wash basin/kitchen sink in kitchen platform, vanity counter and similar location in marble/granite/ stone work, including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete.
PUF WORKS
Supply, Installation, Testing & Commissioning (SITC) of modular sandwiched doors of width 0.8m to 1m width and 2.1m to 2.3m height both side GI powder coated sheet of 0.4mm thickness duly flushed with the walls, with 45 mm thick PUF, sandwiched between GI sheets, with seal door, including flushed hinges, view panels (as per the site requirement), SS 304 handle/ push plates and hydraulic door closers. Including Stainless steel hinges, Stainless Steel 'D' type handles on pull side, Stainless steel push plates on push side, Dorma make standard arm door closure (TS-68), View panel along with self-adhesive tape and silicon sealant, both side key operated locking arrangement, Door seal at the bottom & Sides, Stainless Steel kick plates, Filler material: Puff Insulation, Rock wool. Door complete with all necessary hardware, accessories, fittings and fixtures, as per description in individual items, technical specifications, Colour, drawings and instructions of the Engineer-In charge.
Supply Installation Testing & Commissioning (SITC) partitions with powder coated Galvanized Iron of 0.4 mm thick sheet on both sides, 50 mm thick class 'O' PUF of min.38kg/m3 density sandwiched in between. The surface shall be coated with 80-micron thick powder coating by hot dip galvanizing with zinc coating not less than 180gm/sqm both side of the panel. Scope includes bottom runner, covings, interconnecting profiles, fixing arrangements, silicon sealant application and all other accessories required to complete the work as per site requirement. Internal GI framework if necessary for support, Silicon Sealant (Clear/White/Winsel Gray), complete with all necessary hardware, accessories, fittings and fixtures, as per description in individual items, technical specifications, drawings and instructions of the Engineer-In charge.
Supply Installation Testing & Commissioning (SITC) of modular false ceiling with powder coated Galvanized Iron of 0.4 mm thick sheet on both sides, 50 mm thick class 'O' PUF of min.38kg/m3 density sandwiched in between. The surface shall be coated with 80-micron thick powder coating by hot dip galvanizing with zinc coating not less than 180gm/sqm both side of the panel. Scope includes runner, covings, interconnecting profiles, fixing arrangements, silicon sealant application and all other accessories required to complete the work as per site requirement. Internal GI framework if necessary for support, Silicon Sealant (Clear/White/Winsel Gray), complete with all necessary hardware, accessories, fittings and fixtures, as per description in individual items, technical specifications, drawings and instructions of the Engineer-In charge.
ROOFING
Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+0.05%), total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineer-in-charge. The sheet shall be fixed using self drilling/self tapping screws of size (5.5x55mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required.
Providing and fixing precoated galvanised steel sheet roofing accessories 0.50 mm (+ 0.05%) total coated thickness, zinc coating 120 grams per sqm as per IS:mm(+0.05%) total coated thickness, Zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/self tapping screws complete:Ridges plain (500-600 mm)
Providing and fixing square rain water gutter pipes including jointing.& 150 mm diameter
FALSE CEILING
Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/ sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37 mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50 mm long with 6 mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25 mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5x25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound, jointing tapes, finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with:12.5 mm thick tapered edge gypsum moisture resistant board
Providing and fixing tiled false ceiling of approved materials of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections (galvanized @ 120 grams per sqm, both side inclusive) consisting of main "T" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200mm center to center and cross "T" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main "T" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross "T" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main "T" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x 1.6 mm fixed to ceiling with 12.5mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85x 30x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer -in-charge.GI Metal Ceiling Lay in perforated Tegular global white color tiles of size 595x595 mm and 0.5mm thick with 8 mm drop; made of GI sheet having glavanizing of 100 gms/ sqm (both sides inclusive) and 20% perforation area with 1.8 mm dia holes and having NRC (Noise Reduction Coefficient) of 0.5, electro statically polyster powder coated of thickness 60 microns (minimum), including factory painted after bending and perforation, and backed with a black Glass fiber acoustical fleece.
Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/ sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37 mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50 mm long with 6 mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25 mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5x25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound, jointing tapes, finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with:12.5 mm thick tapered edge gypsum plain board conforming to IS : 2095-Part 1
PAINTING WORKS
Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete.
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
Finishing with Deluxe Multi surface paint system for interiors and exteriors using primer as per manufacturers specifications:Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.80 ltr/10 sqm of approved brand and manufacture
Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade:Two or more coats on new work
Finishing with Deluxe Multi surface paint system for interiors and exteriors using primer as per manufacturers specifications:Two or more coats applied on walls @ 1.25 ltr/10 sqm over and including one coat of special primer applied @ 0.75 ltr /10 sqm
Removing white or colour wash by scrapping and sand papering and preparing the surface smooth including necessary repairs to scratches etc. complete.
PLUMBING AND SANITARY INSTALLATION
Providing and fixing PTMT Bottle Trap for Wash basin and sink.Bottle trap 38 mm single piece moulded with height of 270 mm, effective length of tail pipe 260 mm from the center of the waste coupling, 77 mm breadth with 25 mm minimum water seal, weighing not less than 263 gms
Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:White Vitreous China Wash basin size 630x450 mm with a pair of 15 mm C.P. brass pillar taps
Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS 13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required: Kitchen sink with drain board510x1040 mm bowl depth 250 mm
Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required:W.C. pan with ISI marked white solid plastic seat and lid
Supplying and fixing CP Health Faucet superior quality ( Jagur or equvalent make ) including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge.
Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS: 893115 mm nominal bore
Supplying and fixing CP Towel rod 60cm or nearest available length including cost of materials and labour charges etc complete as per the direction of site Engineer-in charge
Providing and fixing PTMT liquid soap container 109 mm wide, 125 mm high and 112 mm distance from wall of standard shape with bracket of the same materials with snap fittings of approved quality and colour, weighing not less than 105 gms
Flexible pipe 40 mm dia
Providing and fixing PTMT Waste Coupling for wash basin and sink, of approved quality and colour.Waste coupling 31 mm dia of 79 mm length and 62 mm breadth weighing not less than 45 gms
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.15 mm nominal outer dia pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.20 mm nominal outer dia pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.32 mm nominal outer dia pipes
Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete:20 mm nominal bore
Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete:25 mm nominal bore
Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms.15 mm nominal bore
Providing and fixing PVC pipes includings jointing of pipes with one step PVC solvent cement, trenching, refilling & testing of Joints complete as per direction of engineer in charge.110 mm dia 6Kgf/cm2
Providing and fixing PVC pipes including fixing the pipe with clamps/ clips/ at 1.00 m spacing . This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 110 mm dia 6 Kgf/cm2 - External work- Exposed on wall
Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing . This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 50 mm dia 6 Kgf/cm2 - Internal work- Exposed on wall
Providing and fixing PTMT grating of approved quality and colour. Circular type100 mm nominal dia
Providing and fixing C.P brass long nose bib cock of approved quality conforming to IS standards and weighing not less than 810 gms.15 mm nominal bore
Providing and fixing unplasticised P.V.C. connection pipe with PTMT Nuts, Collar and bush approved quality and colour .15 mm nominal bore with 45 cm length
PASS BOX
Pass Box shall be provided at required locations for transfer of samples, chemicals and materials into the laboratory Pass box with UV to be provided. The Pass Box shall be constructed in 18 swg SS 304. The corners inside the Pass Box chamber shall be coved for easy cleaning. The pass box chamber dimension shall be approximately 610 mm x 610 mm x 610 mm. The unit shall be complete with HEPA filters, blower, motor, door electromagnets, door interlock, UV Lamp with timer, necessary wiring, controls and all other accessories. Etc. complete.
SIGNAGES
NAME BOARD ACP SHEET WITH MULTIWOOD LETTERING :Design, Supplying and fixing Name Board as per the technical specifications given -1 Inch GI pipe frame (16Guage) for Frame (Size proportional), Primer Paint & Black Painted Pipes for Frame.,5mm ACP sheets (Aluminum Composite Panel) for Box area, 18mm thick Multi wood Lettering for Name Board as approved by<br> Engineer in charge .<br>For Measurement purpose, only area of ACP sheet to be measured.
Design, providing and fixing Digital Printed vinyl signage boards with transparent 3mm acrylic Sheet with 4 nos. SS Studs of Size 16 x 10 Complete as per the per the direction of Engineer in charge.
Electrical
POINT WIRING
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group B
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C
CIRCUIT WIRING
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required4 X 16 sq. mm + 2 X 6 sq. mm earth wire
SWITCHES,SOCKETS AND BOXES
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm)
Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A SP switch with indicator
Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3pin Shuttered socket
DB ENCLOSURE AND ITS ACCESSORIES
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required8 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43)
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - three phase double cover (IP 42/43)
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - three phase double cover (IP 42/43)
Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.125 Amp,16 KA,TPMCCB
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
Supplying and fixing 40A / 63A, TP MCB, 415 Volts, "C" curve, miniature circuit breaker in the existing MCB DB complete with connections, testing and commissioning etc as required.
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker with overcurrent protection (RCBO), having a sensitivity current upto 100 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40A, 4P, 30/100mA
Supplying and fixing FP CRCA sheet steel enclosure with provision to mount MCB/Isolator/RCCB/RCBO and other modular devices on surface/ recess complete with connections, testing and commissioning etc. as required.
CABLES AND LAYING
Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).3.5 core 95 sqmm
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 35 sq mm with factory made clamp
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 95 sq mm
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 25 sq mm with factory made clamp
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
CABLE TERMINATION
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 95 sq. mm (45mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
EARTHING
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required.
Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG)
Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required.
LIGHT FIXTURES
SITC of 4 feet surface mounted batten type luminaire with a power consumption not more than 20 W, luminaire lumen output of 2400 lumens, luminaire efficacy > 120 lm/W with an operating voltage range from 140 V - 270 V. The luminaire shall have a white CRCA housing with a poly carbonate diffuser to provide uniform light and a sleek design with width not more than . The luminaire shall have a CCT of 4000K ,6500 K , CRI > 80, power factor >0.95, SDCM < 5, THD <10% and 50,000 burning hours as per L70B50 criteria. The luminaire shall have flicker content <5% and shall have high and low cut off with auto restart feature. The luminair shall be EMI/ EMC compliant and shall have a internal surge protection of 4 kV. The luminaire shall have Class - 1 Electrical Insulation, Class - B Serviceability (Thedriver can be replaced at site level). The luminaire and driver shall be BIS approved and test certificates of LM79 and LM80 reports from NABL accredited labs.
SITC of LED Recess mounted glare free luminaire (2x2) with a nominal system lumen output of 3600 lumens and a minimum system efficacy of 110 lm/W. The luminaire wattage shall not exceed 36 W. The luminaire should have a color temperature of 6500K and CRI>80. Driver of the luminaire shall have THD<10% and PF >0.9. The luminaire must be flicker free with ripple content less than 5 %. The luminaire housing should be made of powder coated metallic CRCA with high efficiency prismatic diffuser so that the UGR should be less than 19. The luminaire optics shall have a high efficiency diffuser with more than 85 transmittance. The luminaire must have a life class of 50,000 burning hours as per L70B50 criteria, 4 kV surge protection. The luminaire shall be EMI/ EMC compliant. The luminaire and driver shall be BIS and test certificates of LM79 and LM80 reports shall be submitted (Make: Philips RC380B LED36S-6500 G5 L60W60 PSU OD SG or equivalent)
Supply and Installation of Low glare, high effeciency surface/ recess mounted 12W LED down light circular profile.
SITC of 2 feet surface mounted batten type luminaire with a power consumption not more than 10 W, luminaire lumen output of 1200 lumens, luminaire efficacy > 120 lm/W with an operating voltage range from 140 V - 270 V. The luminaire shall have a white CRCA housing with a poly carbonate diffuser to provide uniform light and a sleek design with width not more than . The luminaire shall have a CCT of 4000K ,6500 K , CRI > 80, power factor >0.95, SDCM < 5, THD <10% and 50,000 burning hours as per L70B50 criteria. The luminaire shall have flicker content <5% and shall have high and low cut off with auto restart feature. The luminaire shall be EMI/ EMC compliant and shall have a internal surge protection of 4 kV. The luminaire shall have Class - 1 Electrical Insulation, Class - B Serviceability (The driver can be replaced at site level). The luminaire and driver shall be BIS approved and test certificates of LM79 and LM80 reports from NABL accredited labs.
Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
SITC of EXHAUST FAN,SHUTTER TYPE white colour, 9" OR 10" star rated as per BEE complete with its all accessories including mounting accessories.
SITC FLOOD LIGHT Ascetically designed LED Flood Light Lumiere(50W-75W),5000lm, equipped with specially designed heat sink, reliable integrated energy efficient electronic driver, suitable for easy replacement of conventional flood light, driven by AC-220-240V, 50/60 Hz,Operating voltage range : 90-305 V,High Surge Protection : 4KV, Average life 50,000 hrs,PMMA modular lens plate,No harmful UV & IR radiations,Operating temperature: -10°C to +45°C, Approved Dimension (220X50X311) including GI arm pipe of minimum1 mtr length. as directed by The Engineer in charge
DG SET
Providing, Installing, Testing and Commissioning of ‘Silent Type’ Diesel Generating set along with having Prime Power Rating of 82.5 KVA, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system & for 0.85 Load Factor and consisting of Diesel engine 4 stroke water cooled, electric start, of suitable BHP at 1500 RPM suitable for above output of alternator at 40 Degree C, 50% RH & at 1000 Meter MSL and conforming to BS 5514, BS 649, IS 10000, capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will be fitted complete with all the required accessories and Synchronous alternator rated at 82.5 KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor at 40 Degree C, 50% RH & at 1000 Meter MSL. The alternator shall be having SPDP enclosure, brushless, continuous duty, self-excited and self-regulated through AVR conforming to IS: 4722/BS 2613 suitable for tropical conditions and with class- F/H insulation, Including CPWD/EI/EB approved AMF panel, Base Frame, Fuel Tank, Battery with leads and other accessories with type competent approved Canopy as a complete set. Contractor has to arrange load test at site or at factory without any additional cost or claim. Including First fill of lube oil and Engine safeties – LLOP, HWT, Initial filling of diesel for standard testing procedure up to 6 hours minimum and 12 hours maximum.
SAFETY MEASURES
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
Supply & fixing Laminated drawings of electrical layout, schematic drawing etc. with teakwood frame work on wall as approved by the directorate of electricity
Supply and fixing of Shock treatment chart duly mounted on a wooden frame with glass on front as required in 2 languages (Hindi & English).
Supply and fixing of 4 Kg ABC Dry Powder (Stored Pressure) Type Fire Extinguisher. pressurized with dry nitrogen gas at 15 bar. Design, construction and testing as per IS 2171-1999 external epoxy powder coating with PO Red Shade No. 538 of IS 5, Supplied with standard accessories.
SITC OF ISI marked (IS:2878) fire extinguisher CO2 type capacity 4.5kg. Flat base including valve, discharge hose of not less than 10mm dia , 1 meter long and complete in all respects including initial fill with CO2 gas conforming to IS:307-1996 filled to filling rate of not more than 0.667 and wall bracket (fixed with anchorFastner) or floor mounted
Providing & fixing in position 1000 mm wide , Electrical Insulating Mats as per IS 15652:2006, 2.0mm thick, suitable for 1.1 KV , fire retardant,no effect of acids alkalies and transformer oils, moisture proof, high tensile strength and texture finish/ cloth impression (Anti slip , marking on top)
DISMANTLING
Dismantling of Fluorescent tube light fittings with all accessories including pvc conduit, and conveying the same to the section store without any damage as required. (upto 50m)
Dismantling of ceiling fan and painting the same with with one or more coats of spray painting with synthetic enamel paint of approved brand and manufacture to give an even shade, including cleaning of surface with detergent and replacing the damaged rubber reel, nuts and bolts with washers and safety pins reinstalling the same as required.
Dismantling of brass batten/ angle holder with all accessories including pvc conduit, and conveying the same to the section store without any damage as required.(upto50m)
Dismantling of Exhaust fan with all accessories including pvc conduit, and conveying the same to the section store without any damage as required.(upto 50m)
DOCUMENTATION AND APPROVAL
DOCUMENTATION AND APPROVAL - "Charges for Preparation of all drawings submitting and getting approval from KSEB, submitting of Completion certificates and arranging inspection, getting sanction from KSEB, obtaining power allocation if necessary & power connection etc. for commissioning of the whole installation in the premises. All statutory payments will be reimbursed on production of the original receipts
UPS SYSTEM
Supply installation, testing and commissioning of following three phase to three phase UPS with inbuilt battery backup, indoor (IP20) in stand alone configuration, true online double conversion DSP based UPS system, with min 30 min backup battery with, input pf>.9, less input current consumption, IGBT rectifier and IGBT inverter. It shall be 100% generator compatible with efficiency > 90% and output power factor > 0.8 and including all accessories etc as required. The UPS system shall be with manual maintenance bypass switch facility. The system shall comply to IEC /EN 62040-1 and relevant IS standard and.The acoustic noise of the system should be less than 58dB. The system shall comply to IEC /EN 62040-1, EN/IEC 62040-2, EN/IEC 62040-3 and relevant IS standard. 10kVA UPS - 1 Nos, Battery Circuit Breaker-1 nos, Battery Required nos. of SMF for providing 30Minutes Backup and Battery Accessories like battery rack, interconnecting cables etc.
NETWORKING
Supply & fixing of CAT6 (RJ-45) I/O Ports
Supplying and fixing following size/ modules, GI box alongwith modular base &cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
Supply, Installation, Testing & Commissioning of 8 Port Network Switch with 8 No's of 10/100/1000 ports and 2 Gigabit Copper/ SFP Combo ports for uplink
SITC OF 4U Rack with PDU unit with Suitable for all type of DVR Box & Double DVR / Network Switch / Server Rack with 4 Power Socket & Cable , Tray (1No) - 1 Cooling Fan Lock & Key.
Supplying and drawn of UTP 4 pair CAT 6 LAN cable in the existing surface/recessed steel/PVC conduit as required1 run of Cable
EPABX
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required..Telephone socket outlet
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
Supply, Installation, Integration and Commissioning of 8 Lines EPABX Intercom System along with krone module as per the direction from Engineer in charge
Supply of User Phone- Analog phone
Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor,unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required.2 Pair
FIRE ALARM
FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)Supplying, installation, testing & commissioning of smoke detector with built-in LED and mounting base complete with all connections etc. as required.
FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)Supplying, installation, testing & commissioning of manual call box of ABS type in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required.
Supplying, installation, testing & commissioning sector panel suitable for following zones, complete with visual indications for short circuit fault, open circuit fault, fire condition and all other standard facilities as per IS:2189 with mimic diagram for all area/zone covered, complete with all connections, interconnections as required.4 Zone
CABLING & WIRINGSupplying & laying of 2x1.5 sq mm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.
FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in M.S. box (16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required.
ACCESS CONTROL SYSTEM
"Supply, Laying, Testing & Commissioning of 4 Core Multi Stranded Cable for biometric device to EM Lock & Contact connection with below specifications as minimum and all the necessary accessories - 4 x 1.0 Sqmm - Unarmored - PVC FRLS - Unshielded"
EXIT PUSH BUTTON SWITCH
Supply and installation of U Clamp for Fitting Purpose. Make: ESSL/ALGETEC
Supply and installation of Electromagnetic Lock for Securing Doors during idle time With L Clamp for Fitting Purpose. Make: ESSL/ALGETEC
Supply and installation of 12V 20 A Power Supply for the device. Make: ERD/PROTEK
SITC Of Network based Biometric Access Control System with RFID Reader, Fingerprint, LAN, USB and Battery Backup with Pushdata and web based monitoring and management software and External powersupply of 12vDC,1.5 Amps
PVC CONDUITING
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
AHU SYSTEM FOR VIROLOGY LAB FIRST FLOOR
Supply, Installation, Testing and Commissioning of AHUs factory built,3400CFM, 8.5TR with 125 mm S.P. with HEPA filters, Double skin AHU complete 6 row cooling coil made of 40 mm thick panels consisting of G.I casing of thickness 0.8mm outside and 0.8mm inside Aluminium sheet with factory injected PUF injected between them by injection molding machine, complete with Plug Fan with VFD with minimum 2 bend GSS/PVC eliminators, cooling coil section with aluminum finned copper tubes filter section with 50 mm thick metal viscous/washable synthetic type air pre-filters, mixing box, VCDs on Fresh air Return air & Supply air opening, TEFC drive motor suitable for 415 ± 10% volts, 50 Hz 3 phase, A.C supply, drain connection, drain pan, necessary vibration isolation arrangement, expansionvalve, drier, AHU Kit, UVC Lamp with airborne inactivation option (Dosage should be proposed by manufacturer), Strip heater with thermostat and RH Sensor (Strip Heater Capacity has to be proposed by manufacturer. A separate control panel with thermostat and Humidistat should be provided for strip heater. If there are three coils of strip heater, one should connect to the thermostat and the other two should connect to the humidistat, i.e., one strip heater should cutoff once the temperature reaches the set point) etc. complete as required as per specifications and drawings capacities as given below. AHUs Should be Eurovent/AHRI Certified
Supply, installation, testing and commissioning (SITC) of 8.5TR capacity air cooled inverter type Outdoor condensing unit with single/multi scroll compressor as per specifications complete with suitable capacity drive motor, air cooled condenser with all accessories, hermetically sealed scroll compressor, electronic microprocessor pendant controller with digital display, first charge R 407A/R410A refrigerant gas, vibration isolator pads and saftey devices like thermal protector, pressure relief valve, over load relays single phase preventor, high-low pressure cut out, suitable for three phase 440V Supply.
Supply and fixing of suitable factory fabricated AHU control panel. Panel should include ON/OFF switch with indicator, bypass DOL/star delta starter for VFD. The panel should have change over switch with indication lamp for manually change over from VFD to DOL/star delta starter. The panel shall have contactors and breaker for the heater banks with required power and control wiring to maintain Indoor RH%.
Supply, Installation, testing and commissioning of 28.6 mm copper pipes for connection for VRV/VRF ODU and IDU with half hard copper tubes (one end expanded type) conforms ASTM: C12200, EN BS:106, ROHS approved and as per manufacturer recommendations, with necessary insulation as recommended. The pipes shall be neatly clamped on wall/cable trays and each supports shall be protected with uPVC pipe of suitable size as required but not less than 150mm length per piece. Maximum spacing between two supports shall be 1500mm if exposed or the pipe shall be concealed on wall including cutting the wall, making good the damages and colour washing etc. as required with necessary Isolating Valves and Driers in Liquid Line as required. [Schematic diagram shall be submitted for Approval before the Installation of Piping].
Supply, Installation, testing and commissioning of 15.9mm copper pipes for connection for VRV/VRF ODU and IDU with half hard copper tubes (one end expanded type) conforms ASTM: C12200, EN BS:106, ROHS approved and as per manufacturer recommendations, with necessary insulation as recommended. The pipes shall be neatly clamped on wall/cable trays and each supports shall be protected with uPVC pipe of suitable size as required but not less than 150mm length per piece. Maximum spacing between two supports shall be 1500mm if exposed or the pipe shall be concealed on wall including cutting the wall, making good the damages and colour washing etc. as required with necessary Isolating Valves and Driers in Liquid Line as required. [Schematic diagram shall be submitted for Approval before the Installation of Piping].
Supply,installation,testing and commissioning of control cum transmission wiring of 6Cx4Sqmm with suitable gauge wire in suitable PVC conduits between indoor and out door unit.
Supply installation testing and commissioning of Insulated inline Circular/ Cabinet fan of 800cfm capacity & 50mmwg external static pressure.
Supply, Installation, Testing and Commissioning of HEPA Filter,Grade H-14, AirFlow Capacity 2500 CFM @ 250 Pa minimum allowable initial pressure drop. With differential pressure gauge to monitor the pressure drop across the filter.
Supply, Installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular / round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports, etc as per approved drawings and specifications of following sheet thickness complete as required.Site fabricated GSSsheet metal rectangular ducting as per IS 655-2006 for 0.63 mm thick
Supply, Installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular / round ducting complete with neoprene rubber gaskets, elbows,splitter dampers, vanes, hangers, supports, etc as per approved drawings and specifications of following sheet thickness complete as required.Site fabricated GSS sheet metal rectangular ducting as per IS 655-2006 for 0.8. mm thick
Supply, Insulation, testing and commissioning of GI volume control duct dampercomplete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications. GI volume control duct damper
Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminum with aluminum volume control dampers with anti smudge ring and removable core.
Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminum without volume control dampers with anti smudge ring and removable core.
Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (class "O") insulation on existing duct after applying two coats of cold setting adhesive (CPRX compound). The joints shall sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per pecifications and as required.Nitrille rubber insulation - 25 mm
Supply and fixing of acoustic insulation on plenum and initial portion of the duct upto mtrs or as suggested from the Ductable units mouth with open cell type 10 mm thick nitrile sheet, with density 140- 180kg/m3 and anti Microbial Properties fixed with manufacturer recommended adhesive and tightened with necessary accessories etc. as required.
Fusible link type Fire Damper of Galvanized Steel Sheet construction, 16G GI casing and 16G GI blades 150 mm wide, 3 V type in 18G 600 mm sleeve complete with chrome plated spindles ,self lubricating bushes,120 minutes fire rating as per UL-555.
Manufacturing and fixing- hanging of Fire retardant flexible Canvass connection at outlet of each Ducted IDU with zipper to facilitate temperature measurement. Rates is per Machine, not per Outlet.
Supply and installation of Fresh Air/ Exhaust Air Louvre of aluminium powder coated with bird Screen as per specifications and drawings.
Supply and fixing in position of 25mm condensate drain water pipe from indoor unit drain to the floor trap piping with 19mm thick nitrile rubber insulation and with necessary fittings like elbows, tees and reducers etc. Openings as good as same.
Magnehelic Gauge of Dial size 4" and Pressure Range of -50 to 50 Pa.
Supply installation testing and commissioning of wired Remote Controller for controlling Indoor Units with it all accessories
Supply and installation of 8.5TR ODU support for mounting the condenser units, as required by erecting suitable structure made up of minimum MS 50x50x6 'L’ sections and 75x40 Channel, suitable cross section neatly painted with epoxy based primer and two coats of epoxy paint of approved colour with placing vibration isolators of 12 mm thick ribbed rubber pads. [GA drawings shall be submitted for approval].
SPLIT AC FOR SECOND FLOOR OFFICE ROOMS
Supply, Installation, Testing and Commissioning of 1.0TR - 3 Star rated Inverter type split AC units , Hi-wall mounted, preferably with anti corrosive / powder coated outdoor units, fitted with hermitically sealed suction cooled energy efficient Scroll / Rotary compressor operating on R-32 / HFC-134a / 407 C / 410 A refrigerant suitable for operation on 220 V, 1 Ph, 50 Hz A/C supply. The units shall be inclusive of all standard accessories like power & control cables, good quality copper tubing of minimum 3 meter length to interconnect the outdoor unit with indoor unit for refrigerant lines, elastomeric Nitrile rubber insulation, clamps etc. Notes: (1) Condenser tubes, Evaporator tubes & connecting pipes should be made out of good quality copper.(2) High-energy efficient compressor of rotary / Scroll type (3) Cordless remote for setting Temp, on time, off time, power saving mode, auto mode operation, sleep mode, auto setting with memory backup, time delay feature, programmable timer, etc. with real time clock. (4) Warranty: 5 Years on PCB, 10 years warranty on compressor and one year warranty for the total system from the date of handing over/ commissioning Make: Blue Star / Voltas / Carrier Midea / Hitachi / Daikin / Panasonic / Mitsubishi /Toshiba / Trane / O General or equivalent
Supply, Installation, Testing and Commissioning of 1.5TR - 3 Star rated Inverter type split AC units , Hi-wall mounted, preferably with anti corrosive / powder coated outdoor units, fitted with hermitically sealed suction cooled energy efficient Scroll / Rotary compressor operating on R-32 / HFC-134a / 407 C / 410 A refrigerant suitable for operation on 220 V, 1 Ph, 50 Hz A/C supply. The units shall be inclusive of all standard accessories like power & control cables, good quality copper tubing of minimum 3 meter length to interconnect the outdoor unit with indoor unit for refrigerant lines, elastomeric Nitrile rubber insulation, clamps etc. Notes: (1) Condenser tubes, Evaporator tubes & connecting pipes should be made out of good quality copper. (2) High-energy efficient compressor of rotary / Scroll type (3) Cordless remote for setting Temp, on time, off time, power saving mode, auto mode operation, sleep mode, auto setting with memory backup, time delay feature, programmable timer, etc. with real time clock. (4) Warranty: 5 Years on PCB, 10 years warranty on compressor and one year warranty for the total system from the date of handing over/ commissioning Make: Blue Star / Voltas / Carrier Midea / Hitachi / Daikin / Panasonic / Mitsubishi / Toshiba / Trane / O General or equivalent
Supply and fixing of M.S OUTDOOR STAND for Split ACs. The work involves supply of heavy duty powder coated mounting bracket for outdoor unit with mounting bolts, complete as required and as directed by the Engr.-in-Charge
Supply & installation of Stabilizer suitable for 1.0TR/1.5TR Capacity Split AC units inclusive of all necessary wiring/connection. Stabilizer should comply with the detailed specification mentioned below. Intelligent Time Delay System, Latest IC Technology - Assures reliable protection, Wall Mounting Cabinet Design - Elegant and easy to install, Low & High Voltage cut-off Protection, Built-In Thermal Overload Protection - Protects the stabilizer and compressors during high-temperature burnout, Working Rage Voltage - 170 VAC - 270 VAC Make: V-Guard/Vstab / Microtek or Equivalent with ISI Standard.
Drain Piping for Split ACs: Supply & installation of PVC insulated piping for condensate drain Including wall chasing, necessary supports, Clamps etc complete as required
Additional refrigerant Copper piping Kit for Split ACs : Supplying and installation of additional refrigerant piping kit consisting of power and control cables, good quality copper tubing, Elastomeric Nitrile rubber insulation etc. for Split AC units.
JAGATHALAPRATHAPAN
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .