Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.1 LAccepted-AOC ASHOKA PARK PALLAVA PARK BVT INS VISHWAKARMA INDIAN NAVY OF GE ND VISAKHAPATNAM | VISAKHAPATANAM | ANDHRA PRADESH | 530001 | L1 | Accepted-AOC Being Lowest | |
| 2 | L2₹32.9 L+₹4.4 L (15.3%)Rejected-Finance | L2 | Rejected-Finance Other Than Lowest Bidder | |
| 3 | L3₹44.5 L+₹16.0 L (55.9%)Rejected-Finance 411 STREET NO 4 PANCHVATI NAGAR BATHINDA 151001 | BATHINDA | PUNJAB | 151001 | L3 | Rejected-Finance Other Than Lowest Bidder | |
| 4 | L4₹48.2 L+₹19.7 L (68.8%)Rejected-Finance | L4 | Rejected-Finance Other Than Lowest Bidder |
Tender Value
₹49.9 L
EMD Value
₹99,800
Closing Date
6 Jun 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE Chandigarh
GE Chandigarh N Area Pin-160003
REPAIR TO DBs EARTHING,SUBMAIN AND SERVICE CONNECTIONS TO CERTAIN BLDGs AT N AREA, K AREA AND HALLOMAJRA UNDER GE CHANDIGARH
2023_MES_594304_1
GE/CHD-19/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Chandigarh
Class D category b(i) for contractor enlisted in MES
7 documents required · 7 mandatory
₹500
GE Chandigarh
₹99,800
Yes
10 Jul 2023
10 May 2023
8 Jun 2023
10 May 2023
6 Jun 2023
25 May 2023
10 May 2023 - 20 May 2023
Amount
Excavation in trenches in any type of soil not exceeding 1.50 metre wide and not exceeding 1.50 metre in depth; for laying of cable,poles stay etc. and getting out complete all as specified.
Returning filling, in including spreading ,leveling, watering and well ramming in layers not exc 25 cm each all as required.
Removing excavated spoil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified.
Sand cushioning with clean dry sand to cables with layer of sand 8cm before laying of cable and 15cm thick after laying of cable complete all as specified. Note : For payment purpose punned thickness of 18cm shall be measured against spread thickness of 23cm as mentioned in para 19.75 of SSR part-I
M&L for Sub class ‘B’ bricks old size. laid dry flat over the cable abutting each other, length of cable equal to width of brick all as required.
Supply and fixing 4 sqmm 2 core 1100 volts grade heavy duty cable PVC insulated stranded alumn conductor, served with an inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 mtr apart including 4mm suspension wire or drawn in and including medium grade non metallic rigid PVC conduit as per site requirement, flat or circular including taking down old unserviceble all as required or directed.
Supply and fixing 6 sqmm 2 core 1100 volts grade heavy duty cable PVC insulated stranded alumn conductor, served with an inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 mtr apart including 4mm suspension wire or drawn in and including medium grade non metallic rigid PVC conduit as per site requirement, flat or circular including taking down old unserviceble all as required or directed.
Supply and fixing 10 sqmm 2 core 1100 volts grade heavy duty cable PVC insulated stranded alumn conductor, served with an inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 mtr apart including 4mm suspension wire or drawn in and including medium grade non metallic rigid PVC conduit as per site requirement, flat or circular including taking down old unserviceble all as required or directed.
Supply, laying in trenches or fixed to poles or passing through pipes and testing cable XLPE Insualted screened PVC bedded, galvanised steel strip or wire armored, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 6 sqmm 4 core complete all as specified and directed.
All as per item no. 9 above but size 16 sqmm 2 core
Supply & fix sheet metal enclosure MCB distribution board, single pole & neutral 240 volts 12 way with IP-43 IK-09 protection double door complete with aluminium bus bar and neutral link, fixed flush in wall including chases wall for fixing DB and making good distributed wall surfaces to match with existing specification .
Supply & fix sheet metal enclosure MCB distribution board. Single pole & neutral 240 volts 8 way with IP-43 IK-09 protection double door complete with aluminium bus bar and neutral link, fixed flush in wall including chases wall for fixing DB and making good distributed wall surfaces to match with existing specification .
Supply and fix sheet metal enclosure MCB distribution board, double door with IP-43 protection single phase 240 volts 4 way, including suitable size aluminium bus bar and neutral link fixed flush in wall including chases wall for fixing DB and making good distributed wall surfaces to match with existing specification .
S&F distribution board iron clad, double door with IP-43 1K-09 protection suitable for MCCB as incommer and MCB as outgoing 415 Volts 3 phase 50 C/S 4 way, TPN, complete with appropriate size aluminium bus bar and neutral link, complete with one MCCB 3 pole 415 Volts 63 Amps rating with rupturing cap 16 KA of the same make as of distribution board & including cutting chases to wall for fixing DB and making good the disturbed wall surface all as required at site or directed by Engr-in-Charge.
Supply and fix in replacement MCB single pole 240 volts any rating from 5 to 30 amps, with rupturing capacity 10 KA,including providing thimble for out going cables.
Supply and fix in replacement MCB double pole 240 volts any rating from 5 to 30 amps, with rupturing capacity 10 KA, including providing thimble for out going cables.
Supply and fix in replacement MCB double pole 240 volts any rating above 30 amps up to 63 amps, with rupturing capacity 10 KA, including providing thimble for out going cables.
Supply and fix in replacement MCB three pole 415 volts any rating from 40 to 60 amps, with rupturing capacity 10 KA, including providing thimble for out going cables.
Material and labour for GI tubing light grade 50mm bore laid for protection of cable under road crossing fixed to walls or pole complete all as specified and as directed.
Supply and fix in repair house service bracket, hook type, complete with 0.90mtr long GI pipe 50mm dia med grade including two No 90º bends complete with hook and stay or guy with flat iron clamp made out of 50x6 mm flat with 02 Nos 16mm dia roggel bolts with 16mm dia metal and 6mm thick washer all as specified in SSR or directed by Engr in Charge.
M&L for earthing with steel earth plate electrode of size 60x60cmx6mm thick buried directly in ground to a depth not less than 2.25 mtr deep below normal ground level with top edge of the earth plate not less than 1.5 mtr deep below normal ground level connected to galvanized iron wire of size 4mm dia as earthing lead by means of nuts, bolts and washers of steel after welding of GI wire to earth electrode , 20mm dia GI watering pipe with funnel and wire mesh, PCC pit 1:3:6 with pit cover of size 30X30cm made of RCC 1:3:6 with suitable handle,angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate, removal of surplus soil and returning filling in all as required at site including test point made out of steel plate of size 75x75x6mm fixed to wall all as specified in plate No 3 of SSR Part-I and directed by Engr-In-Charge.
Cutting chases, pining in. making good to brick wall facings where required and pointing in cement mortar 1:3 to ends or edges of landings, steps, cills, sunshades, shelves, lintels, etc and cutting chases for concealed tubing or concealed conduit etc, and making good to match with existing specifications for cuttings exceeding 10 cm but not exceeding 20cm girth all as required at site or directed by engr in charge.
Cutting chases, pining in. making good to PCC floor/ roads of any specifications, facings where required and pointing in cement mortar 1:3 to ends or edges of landings, steps, cills, sunshades, shelves, lintels, etc and cutting chases for concealed tubing or concealed conduit etc, and making good to match with existing specifications for cuttings exceeding 10 cm but not exceeding 20cm girth all as required at site or directed by engr in charge.
Cutting chases, pining in. making good to tiled wall facings where required and pointing in cement mortar 1:3 to ends or edges of landings, steps, cills, sunshades, shelves, lintels, etc and cutting chases for concealed tubing or concealed conduit etc, and making good to match with existing specifications including tiles for cuttings exceeding 10 cm but not exceeding 20cm girth all as required at site or directed by engr in charge.
Supply and fix MCCB 3 Pole, 415 V, adjustable thermal (40% to 100%) and adjustale magenetic release TPN 415 volt, bracking capacity 35 KA, ICS =100 ICU, 200Amps complete all as specifired and as directed by Engr-in-Charge.
Supply and fix MCCB 3 Pole, 415 V, adjustable thermal (40% to 100%) and adjustale magenetic release TPN 415 volt, bracking capacity 35 KA, ICS =100 ICU, 160Amps complete all as specifired and as directed by Engr-in-Charge.
Supply and fix MCCB 3 Pole, 415 V, adjustable thermal (40% to 100%) and adjustale magenetic release TPN 415 volt, bracking capacity 35 KA, ICS =100 ICU, 125Amps complete all as specifired and as directed by Engr-in-Charge.
Supply and fix MCCB 3 Pole, 415 V, adjustable thermal (40% to 100%) and adjustale magenetic release TPN 415 volt, bracking capacity 35 KA, ICS =100 ICU, 100Amps complete all as specifired and as directed by Engr-in-Charge.
Taking out existing damage/unservisable PVC\ XLPE insulated, armoured, aluminium conductor 1100V grade cable of any size and core from trenches, pipes, walls and/or poles, complete all as specified . NOTE: Excavation and earthwork shall be measured and paid for separaetly
Supply & Laying of PVC insulated,armoured heavy duty, electric cable with stranded aluminum conductor of size 3.5 core 240 sqmm 1100 volts grade, laying in trenches, passing through pipes, fixed along walls and/or poles complete all as specified of size complete all as specified and directed.
All as per item No 30 above but cable of size 185 Sq.mm, 3.5 core
All as per item No 30 above but cable of size 150 Sq.mm, 3.5 core
All as per item No 30 above but cable of size 120 Sq.mm, 3.5 core
All as per item No 30 above but size 3.5 core 70 sqmm
All as per item No 30 above but cable of size 50 Sq.mm, 3.5 core
All as per item No 30 above but cable of size 35 Sq.mm, 3.5 core
All as per item No 30 above but cable of size 25 Sq.mm,3.5 core
All as per item No 30 above but cable of size 10 Sq.mm, 2 core
All as per item No 30 above but cable of size16 Sq.mm, 4 core
S & F in repair heat shrinkable straight through joint for 1100 volt grade XLPE cable of size 70 Sqmm to 150 Sqmm, 3.5 core complete all as specified
S & F in repair heat shrinkable straight through joint for 1100 volt grade XLPE cable of size185 Sqmm to 300 Sqmm, 3.5 core complete all as specified
S&F in repair heat shrinkable straight through joint for 1100 volt grade XLPE cable of size 25 Sqmm to 50 Sqmm, 3.5 core complete all as specified
S&F in repair 100 mm bore Tubes ‘light grade’, galvanized , laid in trenches or fixed along poles with mild steel clamps, as protection to cable, complete all as specified .
S&F in repair 80 mm bore Tubes ‘light grade’, galvanized , laid in trenches or fixed along poles with mild steel clamps, as protection to cable, complete all as specified .
S & F in repair 40 mm bore Tubes ‘light grade’, galvanized , laid in trenches or fixed along poles with mild steel clamps, as protection to cable, complete all as specified .
Taking out old unsv GI earthing , earthing strip etc complete incl diamantling of PCC earth chamber and making good the disturbe d surface
Supply , and laying in repair Copper earth plat of size 60cmx60cmx 3 mm thick (having drilled two Nos holes of dia 10 mm one at centre and other in between top and centre for fixing of GI strip/ GI wire any size ) laid vertically in centre of a earth pit of depth 4.5 Mtrs complete al as specified and as directed.
Supply , and laying in repair GI earth plat of size 60cmx60cmx6 mm thick (having drilled two nos holes of dia 10 mm one at centre and other in between top and centre for fixing of GI strip/ GI wire any size ) laid vertically in centre of a earth pit of depth 4.5 Mtrs complete al as specified and as directed.
Supply and fixing in repair GI Strip of size 32x6 mm with GI earth plate under item ser no 48 above complete al as specified and as directed
Supply and fixing in repair Copper Strip of size 25x4 mm with copper plate earth plate under item ser no 47 above complete al as specified and as directed
Supply and fixing in repair GI Strip of size 25x4 mm with GI earth plate under item ser no 48 above complete al as specified and as directed
Supply and fixing in repair GI wire of size 4 mm with GI earth plate under item ser no 48 above complete al as specified and as directed
Supply and fixing GI bolt( full thread) ,Nut and wahsers of size 10 mm thick 25 mm long
Supply and fixing brass bolt( full thread) ,Nut and wahsers of size 10 mm thick 25 mm long Note :( One GI bolt,one nut and two nos washers shall be considered as one set)
Supply and fixing in repair GI watering funnel with wire mesh
Supply and filling sea salt in earth pit complete all as specified in SSR part -I and as directed by Engr-in-Charge
Supply and filling charcoal dust in earth pit complete all as specified in SSR part -I and as directed by Engr-in-Charge
Supply and filling bentonite powder in earth pit complete all as specified in SSR part -I and as directed by Engr-in-Charge
M&L PCC 1:3:6 Type C-1 using 20 mm graded black stone aggregate including necesary form work for repair of earth pit complete all as specified in SSR part I and as directed by Engr-in-charge
Taking down unserviceable sub main wiring 10/6/4 Sqmm aluminium cable all as directed.
M&L for Sub main wiring/power wiring complete with two runs of 10 Sqmm, single core, PVC insulated, unsheathed FRLS cable, 1100 Volts grade, multistranded with copper conductor, drawn through and including suitable size of rigid non metallic PVC conduit pipe and accessories on surface wall/floors/concealed etc. with one run of PVC insulated, 10 Sqmm FRLS copper conductor for earth continuity all as specified and as directed. NOTE :- For item no 61, 62 & 63 Two runs of main copper conductor, one run of copper conductor for earth continuity and one run of conduit shall be measured as one unit length.
All as per item No 61 here in above but with 6 Sqmm .
All as per Item No 61 here in above but of 4 Sqmm.
M&L for 3x1.5 Sqmm PVC insulated, unsheathed FRLS cable, 1100 Volts grade, multistandard with copper conductor drawn in the existing metal/PVC conduit & Casing capping including connecting of the ends into the switch / socket/ DB complete.
Disconnection and removing the u/s casing caping conduit and S&F PVC casing caping of size 20mm including cut to shape and size to match the existing conduits suitable for LT electric supply along with necessary fixing arrangements complete.
Supply and fix in replacement MCB single pole 240 volts any rating from 63 amps, with rupturing capacity 10 KA,including providing thimble for out going cables
All as per Item No 66 here in above but of capacity MCB SP 40 Amps
Taking down existing control board (Meter Box) and supply and fixing sheet metal box made of 1.6mm thick metal sheet and painting 2 coats with synthic enamel paint over a coat of primer including aluminium bus bar and fixed with wall for fixing meter complete with wiring, fitting and accessories, locking arrangements with handle (minimum size of box 65cmx75cm and adequate depth for the following equipments, internal wiring and termination of external cable, lugs and glands and conduits as required) comprising of following. (a) Incoming 100Amp 4 pole MCCB 25 KA-01 Nos. (b) Bus bar 100 Amp Aluminium (d) 10Amp DP MCB-01 No (Outgoing for stair case and garage) (c ) 40Amp DP MCB-04 Nos (for Qtr meters) (e) Fixing only arrangement for electronic type energy meters single phase 240Volt 40Amps 50HZ -04Nos. MAKE: Indo asian/ M/S Power System and controls Note : Elect meter will be issued under Sch 'B' free for fixing only.
Disconnection & taking down the unserviceable GI bracket of size 32 mm dia from the pole / building and M&L for street light bracket made out of 5/32 mm dia GI tubing medium grade upto 0.90 mtr long including bending, welding ,drilling holes as required and fixing with flat iron clamps 50x6mm thick (02 Nos) with suitable nut, bolts and washers to steel tubular /concrete poles/building complete all as specified and as directed.
Disconnection & taking down the unserviceable building light high wattage (30/25 Watts) street light fittings and Supply & fixing energy efficient Intergral type LED 25W Street light luminaire comprising of epoxy powder coated hsg, enclosed with glass cover in frame mounted testing compelte all as specified and directed.
Arun enterprises
M/s Super Trading Corporation
Bharat Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .