Loading…
Loading…
Tender Value
₹1.6 Cr
EMD Value
₹2.3 L
Closing Date
28 Sept 2026, 6:00 pm
CWE Dehradun
HQ CWE Dehradun
PROVN OF AUTOMATION / SCADA SYSTEM FOR TUBE WELL / PUMP HOSUE AT IMA DEHRADUN.
2026_MES_786210_1
1027/IMA/E8
Open Tender
Electrical and Maintenance Works
Item Rate
3830 days
GE IMA Dehradun
Please refer Tender documents.
6 documents required · 6 mandatory
₹1,000
GE IMA Dehradun
₹2.3 L
Yes
28 Sept 2026
25 Aug 2026
30 Sept 2026
25 Aug 2026
28 Sept 2026
21 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Sch 'A' Part-I (Ph-I: Provn of Automation/SCADA System) | |||||
| 2Supply, installation, testing and commissioning SCADA system alongwith various analysing equipments for water supply system as indicated in the layout diagram enclosed and as per details attached at table. It includes DLP of two years. The SCADA system shall comprise of the followings:- | |||||
| 2.01 | Supply, installation, testing and commissioning of Pressure Transmitter with proper wiring including necessary power pack for supply of DC complete all as specified and directed:-
Power supply : 24 V DC
Enclosure : IP 65
Temperature : 0 to 80 Celsius
Accuracy : Maximum 1 %
Pressure Range : 0 - 40 bar
Output Signal : 4-20 mA
Response Time : 4 ms
Make : I &S/Endress+Hauser/Yokogawa/Rosemount | 9 | Each | - | - |
| 2.02 | Supply, Installation,Testing and Commissioning of Smart Hydrostatic Level Transmitter at Sump and overhead tank for measurement of level with following specification complete all as specified and directed:-
Range : 0-10 meters
Accuracy : 0.2 % minimum
Supply Voltage : 24 V DC
Output : 4-20 mA
Operating Temprature : 0 to 50°C
Response Time : Minimum 150 ms
NOTE :-
1). The Level Sensor Indicator need to be covered in a polycarbonate box of suitable size before installation on OHT or Sump.
2). The Programming of Level Sensor, e.g. Changes in range of sensor, changes in operational features etc. shall be carried out by authorized system integrator of the provided makes. The programmer shall submit a letter from the OEM as proof of his being an authorized system integrator of the OEM. The programmer shall also submit a signed report on original letterhead of the OEM that testing & commissioning has been carried out by him.
Make: I&S / Endress+Hauser / Siemens. | 10 | Each | - | - |
| 2.03 | Supply, Installation, Testing & Commissioning of Indoor type PLC (Programmable Logic Controller) based Pump and Valve Automation, Protection Panel comprising with Wirelesss GSM based Communication suitable for control and monitoring of 01 No Submersible Pump, 02 Nos Motorized Butterfly Valve, 02 Nos Electrical Actuator for Sluice Gate Valve, 01 No Pressure Transmitter, 01 Nos Hydrostatic Level Transmitter, 01 Nos Flow Meter complete all as specified and directed. The panel should be of minimum size 1100(H) X 1000(W) X 300(D) mm fabricated with 2 mm thick CRCA Sheet. (Location :- Pump House No. 1,2,8,10, Polo, Panditwari, Ranghanwala, OTCT, MT)
(i) The Panel should also comprising the following items:-
(a) Water Level Sensing & Display
(b) Automatic Pump On/Off
(c) Automatic Operation of Motor Actuated Sluice & Butterfly Valves
(d) Single Phasing Prevention
(e) Auto Mode Operation (all connected sub systems including all valves in pump houses and pumps) from the PLC based Control Panel.
(ii) 01 No PLC with follwing specifications:- (MAKE : HORNER/L&T/GE AUTOMATION/PHOENIX CONTACT)
(a). 1 Nos RS 485 communication port and 1 No Ethernet communication port.
(b). Suitable Nos of digital / analog input and outputs.
(c). Programming Software based on IEC to facilitate building of custom build function blocks.
(d). Industrial Grade Processor, Web Server and SMTP E-mail service.
(e). Protocol : Master/Slave Modbus; Expandable upto 248 I/O’s and 7 expansion module.
(iii) 01 No HMI - 4" Graphical Touch screen display with follwing specifications:- (MAKE: HORNER/ L&T/ GE AUTOMATION/ SCHNEIDER) | 9 | Each | - | - |
| 0.000 | (a). 01 No RS 485 communication port and 01 No. USB port
(b). Serial multilink and USB downloading port
(c). Support external data storage on a USB memory stick for storing production data and backing up applications.
(iv) 01 No SMPS of 5A rating suitable according to panel design. (MAKE : MEAN WELL / SCHNEIDER / TTPL/ PHOENIX CONTACT / OMRON)
(v) Suitable Nos of interposing relays of 220VAC & 24 VDC coil rating and 6 A contact rating.
(vi) Suitable Nos of relay cards with operating voltage 24VDC, with continuous current of 5A. Card must be of 8 channel & having 8 relays.
(vii) MCB rating 16A, 10A, 6A as suitable according to panel design. (viii) Illuminiated push button, Indicator lamp, Selector switches as suitable according to panel design.
(ix) Audio visual alarm indicator as suitable according to panel design.
CRCA Enclosure
Make of the PLC based panel (MAKE : I&S / Adlec / Tricolite / Rockwell Automation /ABB )
NOTE : (i) The Programming, Testing, Commissioning & Integration of PLC Panel shall be carried out by authorized system integrator of the provided makes. The programmer shall submit a letter from the OEM as proof of his being an authorized system integrator of the OEM. The programmer shall also submit a signed report on original letterhead of the OEM that Programming, Testing, Commissioning & Integration has been carried out by him.
(ii) The quotatd rate shall be included the rate for testing commissioning and integration of PLC. | - | - | - | - |
| 2.04 | Supply, installation, testing and commissioning and Programming of Master Control Station (SCADA Software).
The scope includes:-
Services for programming, configuration and customisation of the Smart Station Platform with respect to the Water supply Module as per actual site conditions and requirement of the engineer.
(a). Landing Page to depict criritcal paramters viz. - Level of water in all tanks, pump status ON/OFF/FAIL
(b). Creation of drop down tabs to monitor the all Pump houses and Remote PLC Panel systems individually
(c). Creation of individual PLC Panel wise schematics and layouts for the Water Supply system as per the actual site including display of all relevant parameters viz. Water level, Pump ON/OFF/FAIL status, Valve OPEN/CLOSE/FAIL status
(d). Soft keys for remote manual operation of all pumps and motorised valves from the Master Control station.
(e). Creation of Day wise Reports for :-
(i) Run hours of pumps
(ii) Pump / valve operation failures
(iii) Active/Return status of each equipment with date and time.
(iv). Configuring notifications, alerts and alarms as per preset logic.
(v) Consumption Patterns - Daily, Weekly, Monthly and Annually.
Make of SCADA: - Schneider Electric, GE Automation, Siemens, Rockwell Automation, L&T / Phoenix Contact.
(f). Personal Computer as central Server for development version of the scada software and reporting the software with following specifiaction:- Intel 8th Gen Core I5, 16 GB RAM, 1 TB HDD, Keyboard / Mouse. Make:- Dell, HP, Lenovo & 32 inches LED monitor/ LED TV Make:- Sony, Samsung, LG.
(g). 2KVA UPS including batteries for 1/2 Hr backup
NOTE:- Contractor shall provided 02 Nos trained operator in each server room (02 Nos) during defect liability period of 02 years without any extra cost. | 2 | Each | - | - |
| 2.05 | Supply, Installation, testing and Commissioning of 150 mm dia, single phase, Motor Actuated Butterfly valve with disc material SS - 304, Stem Material SS - 410, Seat EPDM, hand wheel for manual operation and having 02 nos. limit switches for Open / Close condition, valve position indicator. The housing of actuator should be of Aluminium Dicast. The actuator must have planetary gear set to transfer the largest torque in the most compact form. The mounting shall be indirect on valve type.
Input Voltage : 24V DC
Designed Line Pressure : 16 kg/sq cm.
1). Wiring & Testing of Mototrized Butterfly Valve shall be carried out by authorized system integrator of the provided makes. The engineer shall submit a letter from the OEM as proof of his being an authorized system integrator of the OEM. The engineer shall also submit a signed report on original letterhead of the OEM that wiring & testing has been carried out by him.
Make of Actuator - I&S / EMERSON / ROTORK / AUMA
Make of Butterfly - I&S / AUDCO / KIRLOSKAR | 16 | Each | - | - |
| 2.06 | Supply, Installation, testing and Commissioning of 100 mm dia, single phase, Motor Actuated Butterfly valve with disc material SS - 304, Stem Material SS - 410, Seat EPDM, hand wheel for manual operation and having 02 nos. limit switches for Open / Close condition, valve position indicator. The housing of actuator should be of Aluminium Dicast. The actuator must have planetary gear set to transfer the largest torque in the most compact form. The mounting shall be indirect on valve type.
Input Voltage : 230V AC
Designed Line Pressure : 16 kg/sq cm.
Gear Set Type : Planetary Gear Set
1). Wiring & Testing of Mototrized Butterfly Valve shall be carried out by authorized system integrator of the provided makes. The engineer shall also submit a letter from the OEM as proof of his being an authorized system integrator of the OEM. The engineer shall also submit a signed report on original letterhead of the OEM that wiring & testing has been carried out by him.
Make of Actuator - I&S / EMERSON / ROTORK / AUMA
Make of Butterfly - I&S / AUDCO / KIRLOSKAR | 2 | Each | - | - |
| 2.07 | Supply, Installation, Testing and Commissioning of 150 mm dia, Water Flow Meter, along with all necessary installation accessories like barrel piece, double nipple, elbows/bends etc with following specification complete all as specified and directed:-
Accuracy: - ± 0.5% of reading
Flow velocity range, m/s: - 0.02 - 5
Output: - 4-20mA output.
Maximum pipeline pressure, MPa / bar: - 25
Ambient temperature range, °С: 0 - 65
Power Supply: - 230 vAC
Protection: - IP 65
Technical Specification: - Less than 0.01 m/s starting velocity, Two line digital LCD accumulative flow and for instantaneous flow, Date cumulative record and data acquisition function, Various of Units selected, including Cubic meter, USA gallon, Cubic feet and Litre,
Display parameters: - Flow Rate, Totalizer - Forward, Reverse.
NOTE :-
1). Supply, wiring & testing, commissioning, programming of Water Flow Meter shall be carried out by authorized system integrator of the provided makes. The engineer shall submit a letter from the OEM as proof of his being an authorized system integrator of the OEM. The engineer shall also submit a signed report on original letterhead of the OEM that programming, wiring & testing, commissioning has been carried out by him.
Make: I&S /EMERSON/KROHNE MARSHALL/ YOKOGAWA ELECTRIC | 8 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.56 MB
1027Tenderdoc.pdf
Tender Documents • 1.81 MB
Drwg.pdf
Additional Documents • 1.18 MB
BOQ_881016.xls
BOQ • 3.55 MB
DATECORRIGENDUM.pdf
PDF • 0.23 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .