Loading…
Loading…
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹1.1 Cr
EMD Value
₹2.2 L
Closing Date
29 Oct 2026, 3:00 pm
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
GM, INRPK
GM, INRPK Kalpakkam
Design, Supply, Fabrication, Installation and Testing of SS 316 Plate Type Heat Exchangers for WIP and UOF, INRP, Kalpakkam.
2026_BARC_929390_1
BARCF/IN-MA/WM/TR/71/2026
Open Tender
Miscellaneous Works
Item Rate
180 days
INRP, NRB, BARCF, Kalpakkam
Design, Supply, Fabrication, Installation and Testing of SS 316 Plate Type Heat Exchangers for WIP and UOF, INRP, Kalpakkam.
7 documents required · 7 mandatory
₹0
₹2.2 L
9 Oct 2026
9 Oct 2026
5 Nov 2026
10 Oct 2026
29 Oct 2026
19 Oct 2026
12 Oct 2026 - 16 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Design, Fabrication, Inspection of Heat Exchanger at firm’s premises, Supply, Installation, Commissioning, Performance testing and guarantee of complete PHE assembly made of SS 316 and minimum of 0.6 mm thick plates along with EPDM gasket to meet the parameters and technical specification given in tender. (Which inclusive of Design, Fabrication, Supply, Installation, Commissioning of Heat Exchanger, 100% light box Testing plates at firms premises, Supply of 10% of Spare HX Plates along with EPDM Gasket for each PHE, Supply of End Spool pieces for connecting PHE with Inlet / Outlet lines, Supply of Companion flanges, Foundation bolts, Dummy flanges, Fasteners, Isolation valves, One set of Heavy Duty spanner kit / Suitable Pneumatic wrench for maintenance of Heat Exchanger etc. as per detailed tender specification.)
PHE -1 (Low Temp. Train Loop)
Heat load -700 KW to meet given parameters.
Primary system: Flow - 120 CMH, Inlet - 40 Deg. C and Outlet - 35 Deg.C
Secondary System: Flow - 150 CMH, Inlet - 32 Deg. C and Outlet - 36 Deg.C
Other Technical specification as given in tender. | 2 | Nos. | - | - |
| 2 | Design, Fabrication, Inspection of Heat Exchanger at firm’s premises, Supply, Installation, Commissioning, Performance testing and guarantee of complete PHE assembly made of SS 316 and minimum of 0.6 mm thick plates along with EPDM gasket to meet the parameters and technical specification given in tender. (Which inclusive of Design, Fabrication, Supply, Installation, Commissioning of Heat Exchanger, 100% light box Testing plates at firms premises, Supply of 10% of Spare HX Plates along with EPDM Gasket for each PHE, Supply of End Spool pieces for connecting PHE with Inlet / Outlet lines, Supply of Companion flanges, Foundation bolts, Dummy flanges, Fasteners, Isolation valves, One set of Heavy Duty spanner kit / Suitable Pneumatic wrench for maintenance of Heat Exchanger etc. as per detailed tender specification.)
PHE 02 (Low Temp. Train Loop)
Heat load -700 KW to meet given parameters.
Primary system: Flow -120 CMH, Inlet - 45 Deg. C and Outlet - 40 Deg.C
Secondary System: Flow - 120 CMH, Inlet - 35 Deg. C and Outlet - 40 Deg.C
Other Technical specification as given in tender. | 2 | Nos. | - | - |
| 3 | Design, Fabrication, Inspection of Heat Exchanger at firm’s premises, Supply, Installation, Commissioning, Performance testing and guarantee of complete PHE assembly made of SS 316 and minimum of 0.6 mm thick plates along with EPDM gasket to meet the parameters and technical specification given in tender. (Which inclusive of Design, Fabrication, Supply, Installation, Commissioning of Heat Exchanger, 100% light box Testing plates at firms premises, Supply of 10% of Spare HX Plates along with EPDM Gasket for each PHE, Supply of End Spool pieces for connecting PHE with Inlet / Outlet lines, Supply of Companion flanges, Foundation bolts, Dummy flanges, Fasteners, Isolation valves, One set of Heavy Duty spanner kit / Suitable Pneumatic wrench for maintenance of Heat Exchanger etc. as per detailed tender specification.)
PHE 03 (High Temp. Train Loop)
Heat load -350 KW to meet given parameters.
Primary system: Flow -60 CMH, Inlet - 55 Deg. C
and Outlet - 50 Deg. C
Secondary System: Flow - 75 CMH, Inlet - 32 Deg. C and Outlet - 36 Deg.C
Other Technical specification as given in tender. | 2 | Nos. | - | - |
| 4 | Design, Fabrication, Inspection of Heat Exchanger at firm’s premises, Supply, Installation, Commissioning, Performance testing and guarantee of complete PHE assembly made of SS 316 and minimum of 0.6 mm thick plates along with EPDM gasket to meet the parameters and technical specification given in tender. (Which inclusive of Design, Fabrication, Supply, Installation, Commissioning of Heat Exchanger, 100% light box Testing plates at firms premises, Supply of 10% of Spare HX Plates along with EPDM Gasket for each PHE, Supply of End Spool pieces for connecting PHE with Inlet / Outlet lines, Supply of Companion flanges, Foundation bolts, Dummy flanges, Fasteners, Isolation valves, One set of Heavy Duty spanner kit / Suitable Pneumatic wrench for maintenance of Heat Exchanger etc. as per detailed tender specification.)
PHE 04 (High Temp. Train Loop)
Heat load -350 KW to meet given parameters.
Primary system: Flow - 60 CMH, Inlet - 85 Deg. C and Outlet - 80 Deg. C
Secondary System: Flow - 60 CMH, Inlet - 50 Deg. C and Outlet - 55 Deg.C
Other Technical specification as given in tender. | 2 | Nos. | - | - |
| 5 | Design, Fabrication, Inspection of Heat Exchanger at firm’s premises, Supply, Installation, Commissioning, Performance testing and guarantee of complete PHE assembly made of SS 316 and minimum of 0.6 mm thick plates along with EPDM gasket to meet the parameters and technical specification given in tender. (Which inclusive of Design, Fabrication, Supply, Installation, Commissioning of Heat Exchanger, 100% light box Testing plates at firms premises, Supply of 10% of Spare HX Plates along with EPDM Gasket for each PHE, Supply of End Spool pieces for connecting PHE with Inlet / Outlet lines, Supply of Companion flanges, Foundation bolts, Dummy flanges, Fasteners, Isolation valves, One set of Heavy Duty spanner kit / Suitable Pneumatic wrench for maintenance of Heat Exchanger etc. as per detailed tender specification.)
PHE 05 (UOF)
Heat load - 2566 KW to meet given parameters.
Primary system: Flow - 400 CMH, Inlet - 40 Deg. C and Outlet -34.50 Deg. C
Secondary System: Flow - 400 CMH, Inlet - 32.80 Deg. C and Outlet -38.30 Deg.C
Other Technical specification as given in tender. | 1 | Nos. | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 10.10 MB
BOQ_976662.xls
BOQ • 0.29 MB
GCC14.pdf
Additional Documents • 1.50 MB
TENDERDOCTR71.pdf
Tender Documents • 1.54 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .