Superintending Engineer, Electrical Circle, UPAVP
Superintending Engineer, Electrical Circle, UPAVP, Lucknow
Construction of 33/11 KV Indoor Type Sub station at Sector-19 and Interlinking of Praposed 33/11 KV S/S at Sector-19 to 132/33 KV S/S and Inter Linked to 33/11 KV S/S (MVVNL) Sector-10 Manjhola Yojna Moradabad.
2026_UPHDB_1210755_1
1083/M-6 ED-1/247 Dt. 13.11.2026
Open Tender
Electrical Works
Percentage
270 days
Sector-10 Manjhola Yojna Moradabad
Please refer Tender documents.
2 documents required · 2 mandatory
₹8,850
Executive Engineer ED-I UPAVP
₹23.5 L
Yes
20 Nov 2026
20 Nov 2026
18 Dec 2026
20 Nov 2026
18 Dec 2026
20 Nov 2026
90 days
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supply, Installation, tesing and commissioning of INDOOR TYPE 33KV, HT VCB Panel Board having 2 Nos. Incomers, 1 No. Bus-coupler and 2 Nos. Outgoing Vacuum Circuit Breakers with Motorized cum manual spring charging mechanism rated for 33KV, 1250Amp, 31.5kA rms-3s, pannel with SCADA compatibility Floor rolling type, Horizontal Isolation & Horizontal Draw-out type design confirming to IS 13118, IEC 62271-100, Mechanical Endurance of M2 class ensuring 10000 operating sequences and E2 class Electrical Endurance. The VCB Panel Board comprising Aluminum Bus - Bar of 1250Amp, Earthing Truck of suitable making capacity along with safety interlocking for complete board and control voltage of 110V DC. The Board shall consist of following panels : | |||||
| 1.1 | 33KV INCOMER VCB PANEL :
33KV, 1250Amp, 31.5KA rms-3s panel with SCADA compatibility Floor rolling type, Horizontal Isolation & Horizontal Draw-out type as per IS 13118, IEC 62271-100. Vacuum Circuit Breaker should have 3 Nos. encapsulated Vacuum Bottels of same manufacturer as of Circuit Breaker. Motorized spring charging mechanism (230V AC) with integral spring charging handle for manual spring charging associated Shunt Type Trip & Close Coils (110V DC)
Current Transformers : 1 set of 3 Nos. Single Phase, 33KV, 600/300/5+5A, Core 1 : Class 5P10, 15VA and Core 2 : Class 0.5, 15VA
Potential Transformers : 1 set of 3 Nos. Single Phase Fixed Type PTs having ratio 33KV/rt3/110V/rt3, Class 0.5/3P, 100VA along with associated HRC Fuses for Primary side protection
Accessories : TNC Switch, Panel Space Heater, Push Button Trip Circuit Healthy Check, Panel illumination lamp with switch, 3 Pin Plug with Socket of 15Amp., Local & Remote Switch, Emergency Trip Button, AC & DC control circuit through MCB, Auxiliary Contacts (6 NO + 6 NC), Anti Pumping Device
Indications : LED Type Indications for R - Y - B Phase, Breaker On/OFF, Spring Charged, Trip Circuit Healthy, Breaker Trip, Breaker Test / Service Position, AC & DC Healthy
Metering Instruments : 1 No. Tri-vector Meter (Acc. Cl. 0.5) of L&T/Secure make , 1 No. Digital Voltmeter (Acc. Cl. 0.5) of Rishabh, AE & Elmeasure make, 1 No. Digital Ammeter (Acc. Cl. 0.5) of Rishabh, AE & Elmeasure make | - | - | - | - |
| 1.2 | Protection & Auxiliary Relays :
1 No. Numerical 3 Over Current + 1 Earth Fault (50/51/50N/51N) Relay providing Over Current (Low Set : 5% - 200% / High Set : 50% - 1600% in steps of 1%), Earth Fault (Low Set : 5% - 200% / High Set : 50% - 1600% in steps of 1%).
1 No. Numerical Under Voltage + Over Voltage (27/59) Relay providing Over Voltage Protection (105% - 170% in steps of 1%), Under Voltage Protection (45% - 90% in steps of 1%), No Voltage Protection (3% - 20% in steps of 1V).
1 No. Trip Circuit Supervision Relay
1 No. High Speed Master Trip Relay
Additional Accessories and Features :
Electrical Interlocking between Incomers & Bus-coupler to prevent mixing of supplies
Standard features should include provision for connecting atleast one run of outgoing cables, Test Terminal Block for protection circuit. Panel fabrication shall preferably be made from sheet steel, safety shutters, continuous rated Close & Trip coils. VCB & Panel should be of same make. Control circuit shall operate on 110V DC except Spring Charging Motor & Space Heater which shall operate on 230V AC. (As Per Page No. Make:- ABB/Schneider/Siemens | 2 | No. | 14,23,700 | ₹28,47,400 |
| 1.3 | 33KV OUTGOING VCB PANEL :
Same description as INCOMER PANEL above except following changes :
Potential Transformer, Voltmeter, R - Y - B Phase Indication, Under Voltage + Over Voltage Relay are not required in Outgoing Panels
Current Transformers : 1 set of 3 Nos. Single Phase, 33KV, 400/200/5+5A PS Class, Core 1 : Class 5P10, 15VA, Core 2 : Class 0.5, 15VA and Core 3 : PS Class for Transformer Differential Protection (PS Class : Vk > 200V, Imag < 30mA @ Vk/2)
Additional Protection Relays :
1 No. Numerical Transformer Protection Relay shall have Transformer Differential Protection, Restricted Earth Fault Protection, Over Current + Earth Fault Protection. Relay shall have complete control features.
2 No. Auxiliary Relays for Transformer OTI, WTI & Buchholz - Alram & Trip Protection
1 No. Trip Circuit Supervision Relay
1 No. High Speed Master Trip Relay
Additional Accessories and Features :
8 Window Annunciator along with Hooter (As per page No. )Make:- ABB/Schneider/Siemens | 2 | No. | 13,83,000 | ₹27,66,000 |
| 1.4 | 33KV BUS-COUPLER VCB PANEL :
Same description as INCOMER PANEL above except following changes :
Current Transformer, Potential Transformer, Tri-vector Meter, Ammeter, Voltmeter, R - Y - B Phase Indication, Protection & Auxiliary Relays (As per page No. ) Make:- ABB/Schneider/Siemens | 1 | Nos. | 13,42,000 | ₹13,42,000 |
| 2Supply, Installation, tesing and commissioning of INDOOR TYPE 11KV, HT VCB 1250Amp 25KA rms-3sec pannel with SCADA Campatibility Board having 2 Nos. Incomers, 1 No. Bus-coupler and 9 Nos. Outgoing Vacuum Circuit Breakers with Motorized cum manual spring charging mechanism rated for 11KV, 800Amp, 18.4kA/3 Sec, Floor rolling type, Horizontal Isolation & Horizontal Draw-out type design confirming to IS 13118, IEC 62271-100, Mechanical Endurance of M2 class ensuring 10000 operating sequences and E2 class Electrical Endurance. The VCB Panel Board comprising Aluminum Bus - Bar of 1250Amp, Earthing Truck of suitable making capacity along with safety interlocking for complete board and control voltage of 110V DC.. The Board shall consist of following panels : | |||||
| 2.1 | 11KV INCOMER VCB PANEL :
11KV, 800Amp, 18.4KA/3 Sec, Floor rolling type, Horizontal Isolation & Horizontal Draw-out type as per IS 13118, IEC 62271-100. Vacuum Circuit Breaker should have 3 Nos. encapsulated Vacuum Bottels of same manufacturer as of Circuit Breaker. Motorized spring charging mechanism (230V AC) with integral spring charging handle for manual spring charging associated Shunt Type Trip & Close Coils (110V DC)
Current Transformers : 1 set of 3 Nos. Single Phase, 11KV, 800/400/5+5+PS Class, Core 1 : Class 5P10, 15VA, Core 2 : Class 0.5, 15VA and Core 3 : PS Class for Transformer Differential Protection (PS Class : Vk > 200V, Imag < 30mA @ Vk/2)
Potential Transformers : 1 set of 3 Nos. Draw-out Type Feeder Connected PTs having ratio 11KV/rt3/110V/rt3, Class 0.5/3P, 100VA along with associated HRC Fuses for Primary side protection
Accessories : TNC Switch, Panel Space Heater, Push Button Trip Circuit Healthy Check, Panel illumination lamp with switch, 3 Pin Plug with Socket of 15Amp., Local & Remote Switch, Emergency Trip Button, AC & DC control circuit through MCB, Auxiliary Contacts (6 NO + 6 NC), Anti Pumping Device
Indications : LED Type Indications for R - Y - B Phase, Breaker On/OFF, Spring Charged, Trip Circuit Healthy, Breaker Trip, Breaker Test / Service Position, AC & DC Healthy
Metering Instruments : 1 No. Tri-vector Meter (Acc. Cl. 0.5) of L&T/Secure make , 1 No. Digital Voltmeter (Acc. Cl. 0.5) of Rishabh, AE & Elmeasure make, 1 No. Digital Ammeter (Acc. Cl. 0.5) of Rishabh, AE & Elmeasure make | - | - | - | - |
| 2.2 | Protection & Auxiliary Relays :
1 No. Numerical 3 Over Current + 1 Earth Fault (50/51/50N/51N) Relay providing Over Current (Low Set : 5% - 200% / High Set : 50% - 1600% in steps of 1%), Earth Fault (Low Set : 5% - 200% / High Set : 50% - 1600% in steps of 1%).
1 No. Numerical Under Voltage + Over Voltage (27/59) Relay providing Over Voltage Protection (105% - 170% in steps of 1%), Under Voltage Protection (45% - 90% in steps of 1%), No Voltage Protection (3% - 20% in steps of 1V).
1 No. Trip Circuit Supervision Relay
1 No. High Speed Master Trip Relay
Additional Accessories and Features :
Electrical Interlocking between Incomers & Bus-coupler to prevent mixing of supplies
Standard features should include provision for connecting atleast one run of outgoing cables, Test Terminal Block for protection circuit. Panel fabrication shall preferably be made from sheet steel, safety shutters, continuous rated Close & Trip coils. VCB & Panel should be of same make. Control circuit shall operate on 110V DC except Spring Charging Motor & Space Heater which shall operate on 230V AC. (As per page No. )Make:- ABB/Schneider/Siemens | 2 | Nos. | 6,81,350 | ₹13,62,700 |
| 2.3 | 11KV OUTGOING VCB PANEL :
Same description as INCOMER PANEL above except following changes :
Potential Transformer, Voltmeter, R - Y - B Phase Indication, Under Voltage + Over Voltage Relay are not required in Outgoing Panels
Current Transformers : 1 set of 3 Nos. Single Phase, 11KV, 200/100/1+1, Core 1 : Class 5P10, 15VA, Core 2 : Class 0.5, 15VA. (As per page No. )Make:- ABB/Schneider/Siemens | 9 | Nos. | 6,25,800 | ₹56,32,200 |
| 2.4 | 11KV BUS-COUPLER VCB PANEL :
Same description as INCOMER PANEL above except following changes :
Current Transformer, Potential Transformer, Tri-vector Meter, Ammeter, Voltmeter, R - Y - B Phase Indication, Protection & Auxiliary Relays (As per page No. ) Make:- ABB/Schneider/Siemens | 1 | Nos. | 5,75,000 | ₹5,75,000 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 12.50 MB
BIDdocMo.pdf
Tender Documents • 13.31 MB
BOQ_2300319.xls
BOQ • 0.41 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .