| 1 | L1₹21.1 LAccepted-AOC 5 B 2 1ST FLOOR OPP METRO PILLOR 484 TILAK NAGAR DELHI 110018 | WEST | DELHI | 110018 | ₹21.1 L | L1 | Accepted-AOC L1 |
| 2 | L2₹21.6 L+₹43,320 (2.05%)Rejected-Finance | ₹21.6 L+₹43,320 (2.05%) | L2 | Rejected-Finance L2 |
Tender Value
₹21.6 L
EMD Value
₹43,170
Closing Date
23 Dec 2022, 3:00 pmClosed
Executive Engineer, Mechanical Division,PWD, Aga
Executive Engineer, Mechanical Division,PWD, Agartala
Providing, Installation, Testing and Commissioning of Fire Fighting Equipments Accessories and maintenance of existing Fire Protection System including Fire Pumps, Accessories etc. for complete Testing and Commissioning of the entire Fire Fighting Sy
2022_CEPWD_35265_1
101/EE/DNIeT/MECH.DIVN/AGT/20
Open Tender
Electrical Works
Works
1155 days
AGARTALA
Please refer Tender documents.
7 documents required · 7 mandatory
₹1,000
₹43,170
3 Jul 2023
16 Dec 2022
23 Dec 2022
16 Dec 2022
23 Dec 2022
16 Dec 2022
Amount
Supplying & fixing single headed internal/extraal yard hydrant valve/landing valve with 1 no. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling & cast-iron wheel, ISI marked ,conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required.
Single headed SS
Supply & fixing 63 mm dia,5m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, riverts etc. conforming to IS 636 (type-A) as required , as per approved make.
Stainless Steel
Supplying, erecting, testing & commissiong of standard Double door hose indoor cabinet 750mm x600mmx250mm to accommodate two piece of hose pipe along with one pair of male & female coupling,one branch pipe & 20mm dia. Nozzle confirming to IS903,suitable for inter connect to hose pipe couplingetc. complete as directed by the Engineer in charge. The cabinet is to be made of 20 SWG MS sheet, glass fronted door with hinged door, glass breaking hammer & locking arrangment by allan key etc. The cabinet is powder coated to scarlet red color etc. completed as directed by Engineer-In-charge , as per approved make.
Supplying,fixing , testing & commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers , gaskets conforming to IS 13095 of following sizes as required , as per approved make list
150 mm dia
Supplying , fixing , testing & commissioing of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS: 14846 of following sizes as required : 150mm dia
Supply, installtion , testing & commissioing of quartzoid, bulb sprinkle 68 deg C with required accessories Pendant type sprinkler
Providing, installation, testing & commisioing of Non Return Valve of following size conforming to IS 5312 complete with rubber, gsket, GI bolt, nuts, wsher etc. as required
CI handwheel for sluice valve 150 NB
Cleaning, checking greasing & servicing with necessary tighting, adjustment etc. of fire pumps (inlcluidng motors) as per requirement complete in all respect as per direction of the Engineer-In-Charge
Motor driven hydrant pump(75hp, 2955rpm 3phase induction motor)
motor driven sprinkler pump (75hp 2955rpm 3pahse induction motor)
Engine driven standby pump
Motor diven Jockey pump (12.5hp 2000rpm 3phase induction motor)
Checking , cleaning & servicing of Motor control centre with Diesel Engine Controller for operation of fire pumps including replacement of damaged / defected parts complete in all respect as per system requirement and direction of Engineer-In-charge
Cleaning & checking of pressue awitches including necessary adjustment of pressure switch for automatic operation of fire pumps complete in all respecy as per direction of the Engineer-In-Charge
Presure switch for automatic operation of Motor driven hydrant pump
Presure switch for automatic operation of Motor driven Sprinker pump
Pressure switch for automatic operation of Engine driven standby pump
Pressure switch for automatic operation of Motor driven Jockey pump
Replacement of damaged pressure guages (100/150mm dia ) inside Fire water Pump house including cost of material complete in all respect as per direction of the Engineer-In-Charge
Supply, fiting , fixing of Fan suitable for Jockey Pump Motor after repalcing the damaged one
Cleaning, servicing & painting of gland packing complete in all respect as per direction of the Engineer-In-Charge
Supply, Installation , testing & commissioning of ABC stored pressue type fire extinguisher including all fixtures & accessories complete with all respect , as per approved make as per direction of Engineer-In-Charge
4kg capacity
6kg capacity
Supply, Installation , testing & commissioning of carbon-di-oxide type fire extinguisher including all fixtures & accessories complete with all respect, as per approved make, as per diretion of Engineer-In-Charge
Supply, Installation, testing & commissioing of 9ltr capacity water type fire extinguisher inclduing all fixtures & accessories complete with all respect , as per approved make, as per direction of Engineer-In-Charge
Supply, Installation, testing & commissioing of wet chemeical fire extinguisher 6L capacity, as per approved make, as per diretion of Engineer-In-charge
Supply, Installation , testing & commissioing of Flow switch
Supply, installation, , testing & commissioing of 5 kg capacity DCP type extinguisher shall be of ABC type with monoaluminium phosphate
Supply, installation of 9ltr capacity GI sheet from 24 swg Fire bucket conforming to IS 2546 and wall mounting bracket for fire bucket
supply, Installation , testing & commissioing of Branch pipe-short, SS304, 63mm male installation , male threaded outlet, fitted with 20 mm bore nozzle , suitable to fit with standard installation type 63mm dia coupling ISI marked bearing IS 903
Supply and fitting of 4mm thick glass for hose cabinet
Design, supply , installation , testing & commisisioing of CO2 gas fire supression system with follwing capacity CO2 cylinder & required length of automatic bursting tube inside LT panel as specified i/c required modification & making the same LT panel as required for installation of complete system along with complete items as per specification as required as per site condition 4.5kg (minimum)
Supplying & fixing of firebrigade inlet connection with male instantanous inlet coupling complete with cap and chain for suitable dia MS pipe connection , ISI marked conforming to IS904 as required (material-copper/allominium alloy) 4way-150mm dia MS pipe.
Final testing & commisioing of the fire protection syste, upto the satisfaction of Engineer-In-charge & local fire authority to obtain NOC.
Comprehensive Annual Maintenance Contract(CAMC) of complete fire protection system from the date of final commissioing as per item at SL_26, with monthly checking , routine preventive maintennace, on call maintennace as per direction of engineer-In-Charge
1st year CAMC
2nd Year CAMC
3rd Year of CAMC
ARB Consultancy
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_35817.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .