Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.5 LAccepted-AOC 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹14.6 L+₹12,748 (0.88%)Rejected-AOC 901 GH 83 SECTOR 20 PANCHKULA 134116 | PANCHKULA | HARYANA | 134116 | L2 | Rejected-AOC Other than Lowest Bidder | |
| 3 | L3₹15.9 L+₹1.4 L (9.75%)Rejected-AOC | L3 | Rejected-AOC Other than Lowest Bidder |
Tender Value
Refer Docs
Closing Date
23 Aug 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE (AF) CHANDIGARH
HQ CWE (AF) CHANDIGARH PIN-160003
PROVISION OF CERTAIN WORKS FOR IPSS AT AIR FORCE STATION CHANDIGARH
2021_MES_441787_4
CWE/AF CHD/CHD/T-05/2021-2022
Open Tender
Civil Works
Item Rate
180 days
Chandigarh
As per NIT
8 documents required · 8 mandatory
₹500
GE (AF) Chandigarh
Exempted
10 Sept 2021
5 Aug 2021
30 Aug 2021
5 Aug 2021
23 Aug 2021
6 Aug 2021
60 days
Amount
Supply, installing testing and commissioning of step down transformer 11/0.433 KV, of capacity 100 KVA, 3 phase 50 Hz , ONAN cooling type , vector group DYN-11, copper wound indoor type with cable boxes both HV and LV side including first filling of oil ON load tap changer etc complete all as per IS-2026 fitting and accessories of transformer shall comform to IS-363 - 1966 and oil of the transformer shall comply with IS-335 - 1983 and comprising with the following :-
(a) Rating plate and terminal marking plate (b) Two earthing terminalS for body earthing and two additional terminals for neutral, brought on bushing. (c) Lifitng lugs (d) Draining valve with plug (e) Dehydrating breather (f) Oil level indicator with minimum and maximum marking with resetting device (g) Cooling radiator (h) winding Termperature indicator (j) Conservator (k) Oil filling hole with cover (l) Air release devide on transfomer fitted with conservator (m) Roller
Supply, installing testing and commissioning of step down transformer 11/0.433 KV, of capacity 63 KVA, 3 phase 50 Hz , ONAN cooling type , vector group DYN-11, copper wound indoor type with cable boxes both HV and LV side including first filling of oil ON load tap changer etc complete all as per IS-2026 fitting and accessories of transformer shall comform to IS-363 - 1966 and oil of the transformer shall comply with IS-335 - 1983 and comprising with the following :-
(a) Rating plate and terminal marking plate (b) Two earthing terminalS for body earthing and two additional terminals for neutral, brought on bushing. (c) Lifitng lugs (d) Draining valve with plug (e) Dehydrating breather (f) Oil level indicator with minimum and maximum marking with resetting device (g) Cooling radiator (h) winding Termperature indicator (j) Conservator (k) Oil filling hole with cover (l) Air release devide on transfomer fitted with conservator (m) Roller
Disconnecting the electrical conections of transformer 63 KVA capacity, lowering the same, transporting from existing site, and refixing the same on proposed new site with new electrical connections complete, testing and commissiong complete all as specified and directed.
Supply and fixing/erecting in true vertical position, steel tubular pole, swaged, type 410-SP-55 (11.00 metres long), complete with cast iron base plate of size 300mmx300mm, finial taper plug, bolts, nuts, washer and screws including painting with two coats of aluminium paint over one coat of red oxide primer on all exposed surfaces and tarring with black bituminous paint to portion embedded in PCC including painting the pole with alternate black and yellow paint strip band 30cm long 5 Nos with synthetic enameled paint and numbering of poles with paint, complete all as specified and directed. Note : Earth work and PCC shall be measured and paid separately.
Material and Labour for cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminium paint complete all as specifed and directed by Engr-in-charge.
Material and Labour for Anti-climbing device; spikes type fabricated out of M.S. bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole complete all as specifed and directed .
Supply and fixing switch air break, triple pole, gang operated, outdoor type, vertical mounting fixed type, mechanically operated, mounted on 9 insulators of rating upto 200 Amps and steel channel frame with all fittings & accessories, with 25mm bore GI pipe as operatig rod of suitable length for operating mechanism worked from ground level, including drop out fuse unit assembly HT 11KV grade, for current rating upto 200Amps suitable for 11000 volts grade, AC supply, including locking arrangement for opertaing handle, complete all as specified and directed.
Supply and fixing Lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp complete all as specified and directed.
Supply, laying, jointing, testing and commissioning of High Tension (HT), 11000 Volts (earthed) grade, XLPE insulated, screened, PVC bedded, galvanized steel strip armoured, electric power cable (heavy duty) with stranded aluminum conductor, cross sectional area 95 Sqmm, 3 core underground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and directed. Note : Excavation and earth work, sand cushioning and precast concrete cable cover/bricks for protection of cable shall be measured and paid separately.
Supply and fixing cable jointing kit for 11 KV grade cable for outdoor end termination , heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Aluminium conductor cable of size 95 sq mm to 120 sqmm complete all as specified and directed.
Material and labour for earthing complete with GI earth plate electrode of size 600mm x 600mm x 6mm thick burried directly in ground vertically (depth of pit not less than 2.25 m below normal ground level), with top edge of earth plate not less than 1.5m below normal ground level, earth plate surrounded from all sides by 15cm thick packed alternate layers of charcoal dust and common salt, electrode connections using galvanized iron wire 4mm dia (upto body of equipment) by means of nuts, bolts, check nuts & GI washers, connected to main switch board or main control board or test point, protected by galvanized iron pipe light grade 40mm dia bore, and watering pipe 20mm dia bore GI medium grade with funnel & wire mesh including all necessary excavation & earth work, PCC chamber in PCC (1:2:4) type B-1 & RCC cover, all as shown in electrical plate No 3 of MES Schedule Part-I (2009), testing on completion, complete all as specified and directed. Note(s) :- (i) RCC pit cover shall be pre-cast of RCC (1:2:4) type B-1, 80mm thick reinforced with XPM not less than 4Kg/Sqm. (ii) PCC chamber shall be constructed 500 mm away from the edge of earth pit. (iii) Rate shall include GI strip and protection pipe of length 7.5m, excess beyond 7.5m length required at site shall be measured and paid separately. (iv) Earth resistance should be less than 3Ohm. In case the test results are not found below 3Ohm, complete earthing will be redone without any extra cost to Govt.
Material and labour for earthing complete with GI earth plate electrode of size 600mm x 600mm x 6mm thick burried directly in ground vertically (depth of pit not less than 2.25 m below normal ground level), with top edge of earth plate not less than 1.5m below normal ground level, earth plate surrounded from all sides by 15cm thick packed alternate layers of charcoal dust and common salt, electrode connections using galvanized iron strip of size 32mmx6mm thick (upto body of equipment) by means of nuts, bolts, check nuts & GI washers, connected to main switch board or main control board or test point, protected by galvanized iron pipe light grade 40mm dia bore, and watering pipe 20mm dia bore GI medium grade with funnel & wire mesh including all necessary excavation & earth work, PCC chamber in PCC (1:2:4) type B-1 & RCC cover, all as shown in electrical plate No 3 of MES Schedule Part-I (2009), testing on completion, complete earthing all as specified and directed. Note(s) :- (i) RCC pit cover shall be pre-cast of RCC (1:2:4) type B-1, 80mm thick reinforced with XPM not less than 4Kg/Sqm. (ii) PCC chamber shall be constructed 500 mm away from the edge of earth pit. (iii) Rate shall include GI strip and protection pipe of length 7.5m, excess beyond 7.5m length required at site shall be measured and paid separately. (iv) Earth resistance should be less than 3Ohm. In case the test results are not found below 3Ohm, complete earthing will be redone without any extra cost to Govt.
Material and labour, factory made (CPRI approved), HT bus bar Panel, size 1500mmx1200mmx900mm, cubical, outdoor type (Kiosk), weather proof, dust proof and vermin proof, IP-65 protection, fabricated out of 3.15mm thick MS CRCA sheet mounted on frame of appropriate size angle iron, welded on 50mmx50mmx6mm size angle iron frame & having four Nos legs made out of 50mmx50mmx6mm size of angle iron - 75cm long each welded below frame, front & back openable with front double door having locking arrangements, bottom space for cable entry, provision of glands, with copper bus bars 630 Amps rating - 02 sets (set of three) mounted on 6 Nos HT epoxy type insulators, 11000 volts grade, suitable size (not less than 130mmx70 mm), duly sleeved with relevant colour code insulation & provision for 01No incoming & 02Nos outgoing cables, including spray painted dark grey with two coats of synthetic enamel paint over a coat of red oxide primer duly provided with danger notice board 1100 volts, legs embedded in ground in PCC (1:3:6) bed block of size 30cmx30cmx30cm up to the height of 60 cm , including dismantling of foundation, taking out old material and removal complete outside defence land complete all as specified and directed.
Supply and fixing danger notice plate of 1.6 mm thick mild steel sheet vitreous enamelled white with letters figures and conventional skull and bones in signal red colour and fixed with MS clamps bolts and nuts of approved size for HT 250 x 200 mm size complete all as specified and directed.
Supply, fixing, connecting, testing and commissioning in replacement LT cubical panel of size 750x600x 450 mm, factory made, compartment type, dust and vermin proof (IP-55), indoor type, suitable for 1100 volts grade, 3 phase, 4 wire supply, floor mounted fabricated out 3.15 mm thick (14 SWG) CRCA Sheet duly powder coated and grouted, with 50mm X 50mm X 5mm angle iron frame, 120 cm long angle iron legs on PCC foudation with cement concrete PCC 1:2:4 and front & rear double door type inclusive locking arrangement & two coat of supper enameled paint first grade quality over red oxide primer with provision of all incoming/outgoing cable entries along with hanging provision ,suitable size of double compression type cable gland for incomming & out going cable marking of cable with marked MCCB of Bldg all as specified and comprising the following:-
Supply, laying, jointing, testing and commissioning of Low Tension (LT), 1100 Volts (earthed) grade, XLPE insulated, screened, PVC bedded, galvanized steel strip armoured, electric power cable (heavy duty) with stranded aluminum conductor, cross sectional area 70 Sqmm, 3.5 core underground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and directed. Note : Excavation and earth work, sand cushioning and precast concrete cable cover/bricks for protection of cable shall be measured and paid separately.
Excavation in trenches in soft/loose soil not exceeding 1.5 metre wide and not exceeding 1.5 metre deep for laying/taking out of cables and foundation of poles etc. and getting out, complete all as specified and directed.
Returning, filling in trenches (soil), including spreading, leveling and well ramming in layers not exceeding 25 cm thick, complete all as specified and directed.
Removal of surplus excavated soil to a distance not exceeding 50metre and depositing where directed at a level not exceeding 1.5metre above the starting point, complete all as specified and directed.
Material and labour for sand cushioning with a layer of dry river sand, 80mm thick before laying of cable and 150mm thick (punned down to 100mm thick) after laying of cables, in trenches/ducts, complete all as specified and directed. Note : Punned down thickness (overall 18cm), shall be considered for measurement and payment.
Supplying and laying, unreinforced precast concrete cable cover HV type-1, flat, of size 300x180x40mm,complete as directrd by Engr-in-charge
Material and labour for bricks as in protection of cable laid dry and flat adjacent to each other perpendicular to direction of cable complete all specified and directed by Engineer-in-Charge.
Supply and laying / fixing , GI pipe light grade 80mm dia for protection of HT cable complete with nuts, bolts, clamps etc complete all as specified and directed.
Material and labour for construction of platform for transformer of size 2m x 1.5 m x1.5 m of brick work with sub class "B" bricks in cement contrete type D2 1:4:8 using 40 mm graded aggregate in foundation filling and mass concrete, rendering 15 mm thick plaster in cement mortar (1:6) on brick/concrete surface of walls , finished even and smooth without using extra cement, PCC (1:2:4) type B-0 using 12.5 mm graded crushed stone aggregate as in coping, kneelers, apex stones, bed plates, kerbs, water troughs and incl weathering, slightly rounded or chamfered angles and throating and preparation of new surfaces of wall and applying two coats of cement base paint and including dismantling of old existing platform complete all as specified.
Material and labour for point wiring complete with single core multi stranded Copper conductor cable of size 1.5 sqmm PVC insulated unsheathed 1100 volt grade in and including PVC conduit of size 20 mm dia or higher as required, including Tee, junction, bends etc, concealed in wall/fixed on ceiling, including M.S modular boxes of suitable size for housing modular switches, sockets etc including 1.5 sqmm green PVC insulated copper wire for earth continuity complete for One five pin 5 amp socket outlet multipurpose on independent board complete all as specified and directed. .
All as per item No 25 hereinabove but with 2.5 sqmm cable insulated for 3 pin 15 amp multipurpose outlet .
Supply and fixing switch modular type, single pole, one module, 6 Amps, 230volts, complete all as specified and directed.
Supply and fixing switch modular type, single pole, one module, 16 Amps, 230volts, complete all as specified and directed.
Supply and fixing socket outlet, modular type, multi purpose, 2/3 pin, 6Amps, two module, 230volts, complete all as specified and directed.
Supply and fixing socket outlet, modular type, multi purpose, 2/3 pin, 6Amps and 16Amps, two module, 230volts, complete all as specified and directed.
Supply and fixing white cover plate with frame 2 module, complete all as specified and directed.
Material and labour for Sub Main Wiring with two single core 4 Sqmm (nominal area) multi stranded copper conductor FRLS PVC insulated and unsheathed colour code cables, drawn in and including non-metalic rigid PVC conduit, heavy duty of 25 mm dia, including standard fittings such as Tees, junction, bands etc., conduit concealed in wall & fixed on ceiling with suitable clamps with and including one run of continuous multi stranded copper conductor 2.5 Sqmm (nominal area) FRLS PVC insulated and unsheathed colour code cable for earth continuity, 1100 volts grade , complete all as specified and directed. Note(s): (i) Two runs of 4 Sqmm main cable + one run of 2.5 Sqmm cable for earth continuity and PVC conduit shall be measured as one unit/one Running Metre. (ii) Rate quoted shall be deemed to include cutting chases for concealing conduit and making good in cement mortar (1:4) or PCC (1:2:4) as required.
Supply and fixing sheet metal enclosure for MCBs, factory made double door , SPN 240 Volt, 8 ways, with 200 Amps bus bar, with IP 43 protection complete in all specified and dirceted by Engr-in-charge.
Supply and fixing sheet metal enclosure for incoming TPN MCCB and out going MCB,s factory made double door,VTPN 415 V 4 way with 200 Amps bus bar with IP 43 protection complete in all specified and dirceted by Engr-in-charge.
Supply and fixing sheet metal enclosure, SPN, with a two pin socket and earth plug, with one MCB single pole, 240 Volts, 32 Amps, complete all as specified and directed.
Supply and fixing MCB SP 6-32 Amps 240 Volt 10 KA, 'C' curve complete all as specifed and directed.
Supply and fixing isolator SPN 40 Amps, 240 Volt, 10 KA 'C' curve complete all as specified and directed.
Supply and fixing MCB TPN 63 Amps ,25 KA , 415 Volt grade complete all as specified and dircetde by Engr-in-charge.
Supply and fixing split unit air conditioner, manufactured with invertor technology, having copper condenser coil, with warrenty of compressor as minimum five years, electric driven, single phase, of capacity of 2 TR, BEE 5 star rated complete all as specified and dircetde by Engr-in-charge. Make - Blue Star, Carrier, Voltas, Samsung or substantially equivalent as approved.
Supply and fixing Voltage stabilizer of capacity 5 KVA for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% complete all as specified and dircetde by Engr-in-charge.
Material and labour for plain cement concrete 1:4:8 type D-2 using 40mm graded crushed stone aggregate as in foundation filling and mass concrete, complete all as specified and directed.
Material and labour for Plain cement concrete (1:3:6), Type C-2, using 40 mm graded stone aggregate as in coping of pole, including weathering, slightly rounded or chamfered angle and throating, finished the surface even and fair, complete all as specified.
HARISH SALES CORPORATION
Shivalik Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .