Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.7 LAccepted-AOC FIRDOUS ABAD BATMALOO SRINAGAR PIN 190004 J K | SRINAGAR | SRINAGAR | J K | 190004 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹35.8 L+₹11,159 (0.31%)Rejected-Finance | L2 | Rejected-Finance Not being L1 | |
| 3 | L3₹38.2 L+₹2.6 L (7.30%)Rejected-Finance | L3 | Rejected-Finance Not being L1 | |
| 4 | L4₹43.8 L+₹8.1 L (22.9%)Rejected-Finance | L4 | Rejected-Finance Not being L1 | |
| 5 | L5₹44.6 L+₹8.9 L (25.1%)Rejected-Finance | L5 | Rejected-Finance Not being L1 |
Tender Value
₹39.7 L
EMD Value
₹79,390
Closing Date
27 Jul 2022, 6:00 pmClosed
CWE, HQ 133 WORKS ENGRS
HQ 133 WORKS ENGRS
REPAIR MAINTENANCE OF LT HT NETWORK INCLUDING TRANSFORMER, LT PANEL VCBS MCCB STARTER UG CABLE AND ACSR CONDUCTOR AT BARAMULLA AND PATTAN AND GULMARG UNDER GE 969 EWS
2022_MES_531797_1
CWEK-15/2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
PATTAN AND GULMARG
CLASS D CATEGORY b i
7 documents required · 7 mandatory
₹500
GE 969 EWS
₹79,390
6 May 2023
17 Jun 2022
3 Aug 2022
17 Jun 2022
27 Jul 2022
2 Jul 2022
17 Jun 2022 - 27 Jun 2022
Amount
Decarbonising / cleaning complete of HT 11KV 3 phase bus bar & bus bar chamber, all electrical connections complete HT VCBs/OCBs/Bus coupler arrangment after removing the bus bar spout, cleaning with petrol and CRC 226 spray solution and ensure proper de-carbonisation, refixing the same after completion complete all as directed by Engineer-in-Charge. Note:- Required spare parts are measured and paid separately
Calibration and testing of IDMT relays like earth fault, over load relay installed in sub station on HT VCBs/OCBs 11 KV panel and testing through recognised agencies by means of secondary injection method, setting of relay timings and play settings and fixing back the relays in position complete all as directed by Engineer-in-Charge.
Supply and fixing of steel tubular swaged poles erected truly vertical or planted as strut complete with 300x300x6 mm thick mild steel base plate, welded to pole, B-118 final, taper cap,bolts, nuts & screws, poles made out of ERW MS tubing conforming to IS-2713 Part-11 type 410 SP-55 (11.0 metres long) including drilling of holes of reqd size for fixing of cross arm, painting the exposed surfaces of pole with two coats of aluminium paint over one coat of red oxide zinc chrome primer and with black & bitumenous paint externally for portion embedded in concrete, making five black & red bands at lower portion of pole each 300 mm wide alternately,and marking pole NO.with black paint at suitable height complete all specified and directed.
Supply and fixing of steel tubular swaged poles erected truly vertical or planted as strut complete with 300x300x6 mm thick mild steel base plate, welded to pole, B-118 final, taper cap,bolts, nuts & screws,poles made out of ERW MS tubing conforming to IS-2713 Part-11 type 410 SP-31(9.0 metres long) including drilling of holes of reqd size for fixing of cross arm, painting the exposed surfaces of pole with two coats of aluminium paint over one coat of red oxide zinc chrome primer and with black & bitumenous paint externally for portion embedded in concrete, making five black & red bands at lower portion of pole each 300 mm wide alternately,and marking pole NO.with black paint at suitable height complete all specified and directed.
Dismantling /disconnecting and taking down insulaters of any size and capacity complete all as specified and directed.
S & F Pin type, porcelain, vitreous, brown insulator including one galvanised mild steel spindle, two galvanised washers and one galvanised iron nut, 150 mm height, 150 mm dia for 11000 volts grade HT over head line and including taking down old complete all as specified and as directed.
S & F single Disc type insulator, porcelain, vitreous 145 mm height and 225 mm dia ball and socket type, brown, assembly for tension with tension clamps for conductors, 11000 volts including taking down old unserviceable one complete all as specified and as directed.
M&L for shackle type Porcelain, vitreous, white, brown or green insulator including galvanised mild steel straps, washers, insulator bolts, washers and nuts,150 mm height, 150 mm dia for 11000 volts grade including dismantling /disconnecting and taking down old broken and unserviceable insulaters of any size and capacity complete all as specified and as directed.
M&L for Pin type Porcelain, vitreous, white brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100mm height, 65 mm dia for 1100 volts grade complete all as specified and directed.
Loop type insulator, vitreous porcelain, white, brown or green large size, with overall dimensions 90mm x 140mm, clearance of hole 25.5mm complete all as specified and as directed.
M&L for Switch air break, gang operated triple pole, mechanically operated, mounted on insulator and steel frame, with operating mechanism worked from ground level, for current rating upto 200 amps 11000 volts (12 Insulator) alongwith fuse system complete all as specified and as specified.
M&L for Switch air break, gang operated triple pole, mechanically operated, mounted on insulator and steel frame, with operating mechanism worked from ground level, for current rating upto 400 amps 11000 volts (12 Insulator) alongwith fuse system complete all as specified and as specified.
M&L for Lighting arresters expulsion type complete with all fittings transmission class, discharge capacity 65KA suitable for 11000 volts complete all as specified and directed.
Material and labour of danger notice plate of 1.6 mm thick mild steel sheets vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and inclusive fixed with MS flat clamps 25x3mm 2Nos, bolts, and nuts for HT 11KV 25x20cm including taking down of old one complete all as specified and directed.
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and directed.
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm complete all as specified and directed.
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and directed.
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 Sqmm complete all as specified and directed.
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and directed.
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm all as specified
S&F galvanised steel wire 4mm dia for guarding of HT/LT over head line unnecessary cradles, hexagonal/rectangular, fabricated complete with 3% auth sag and as directed including taking down of old one complete all as specified and directed.
Dismentling old and unserviceable stay assy complete comprising of stay clamp, stay wire, stay insulator, stay grip, thimble, bow, stay rod 16 mm dia and stay plate etc including breaking of cement concrete complete all as specified and as directed.
M&L for stay assembly complete with accessories as shown in electrical plate No 1 (Loop type insulator, stay clamps excavation and concrete measured separately) 20 mm dia complete comprising of stay clamps, stay wire, stay insulator, stay grip, thimbles, bow, stay rod and stay plate etc complete all as specified and as directed.
M&L for Galvanised stay strand wire of size 7/4mm fixed as in repair complete all as specified.
S & F Cross arms bracing supports, clamps and back plate fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts in any shape or size as indicated or directed and inclusive of one primer coat of red oxide zinc chrome, one under coat and one finishing coat of aluminum paint complete all as specified and directed.
M & L for cement concrete for foundation fillings and mass conctere type D2 1:4:8 (using 40 mm graded aggregate) complete all as specified and directed.
M & L for providing cement concrete 1:2:4 Type B1 (using 12.5mm graded aggregate) as in lintels upto 1.5m clear span, cills, steps; seismic and other similar bands, plinth, string, lacing courses, parapets and railings upto 60cm in height, copings, kneelers, apex stones, bed plates, water troughs and the like including weathering, slightly rounded or chamfered angles and throating complete all as specified and as directed.
M & for cement concrete for foundation fillings and mass conctere type C2 1:3:6 (using 40 mm graded aggregate) complete all as specified and directed.
M & L for Earthing complete with galvanised steel earth plate electrode 60x60cmx 6.3mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth strip 32x6mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel including PCC (concrete chamber) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate,with fair finish internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4,funnel with wire gauge of (0.68) 8 mesh per liner inch,80mm thick RCC pit cover 320 mmx320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM,JALLI and charcoal dust and common salt all as shown in electrical plate No.5 of MES SSR Part-1 and specified including provision of earth wire protected by 40 mm dia medium grade GI pipe and watering pipe shall be 20 mm bore medium graded GI pipe,and including all excavation and earth work & connecting the earthing to an earthing test point /transformer neutral/body/LT panel etc.and testing on completeion complete all as spec ified and directed. NOTE: The quoted rate of earthing shall be deemed to included cost of 7.5m long galvanised earth strip 32x6 mm and protection pipe of 40 mm bore medium graded ,GI light graded 20mm bore watering pipe
M&L PVC spacer suitable for 3 wire HT OH line including taking down of old one complete all as specified and directed.
M&L PVC spacer suitable for 4 wire LT OH line including taking down of old one complete all as specified and directed.
Dismantling old and unserviceable prestressed concrete poles/steel tublar poles of any type including breaking cement concrete complete and site clearance all as specified and directed.
Painting to existing steel tubular LT poles, 9m long including cross arms, channels, angle iron support, bracings, clamps etc. with two coats of aluminum paint superior quality of approved make on surfaces exposed to view and making 30cm wide strips (total 5 Nos) with white and black paint alternately on external surface above PCC benching including preparation of old painted surfaces by scraping etc complete and writing pole numbers. of 2 inches bold letters with black paint after painting, complete all as specified and directed.
Painting to existing steel tubular HT poles, 11m long including cross arms, channels, angle iron support, bracings, clamps etc. with two coats of aluminum paint superior quality of approved make on surfaces exposed to view and making 30cm wide strips (total 5 Nos) with white and black paint alternately on external surface above PCC benching including preparation of old painted surfaces by scraping etc complete and writing pole numbers. of 2 inches bold letters with black paint after painting, complete all as specified and directed.
Supply and laying GI pipe 80 mm bore light grade with fitting for cable protection at road crossing/under concrete including taking down of old one complete all as specified and directed.
Supply and laying GI pipe 50 mm bore light grade with fitting for cable protection at road crossing/under concrete including taking down of old one complete all as specified and directed.
Supply and laying GI pipe 40 mm bore light grade with fitting for cable protection at road crossing/under concrete including taking down of old one complete all as specified and directed.
Supply and fixing in replacement of lugs or thimbles suitable for 10 Sqmm to 70 sqmm aluminum coductor cable suitable 1100 volts LT Cable complete all as specified and directed.
Supply and fix in replacement of lugs or thimbles suitable for 95 Sqmm to 240 sqmm aluminum coductor cable suitable 1100 volts LT Cable complete all as specified and directed.
Disconnecting HT/LT cable and earthing connections of burnt/defective transformer of capacity 50 KVA to 500 KVA , 11 KV/433 volts 3 phase from pole/floor mounted, taking from site of installation carefully with the help of Crane and transportation of the same to workshop for repairs, draining out the transformer oil, dismantling complete and taking out the core assembly and removing burnt out windings, dehydrating the core assembly, reassembling transformer after repair, replacement of complete gasket set, refilling the oil duly filtered / dehydrated, topping up with new oil, carrying out routine tests, including transportation back to site, testing and commissioning of the repaired transformer at site on full load after making cable and earthing connections complete all as specified and directed.
M&L for Hiring, transportation, installation and testing of serviceable transformer of existing capacity on hired basis in place of unserviceable transformer which is under repair and shifting back to workshop on hire basis for 15 days when ordered complete all as specified and directed by engr in charge. Note:- (1) Repairing of transformer shall not exceed beyond 15 days from the date of dismantling from original site, (2) Contractor shall not be allowed to shift hired transformer untill it is replaced by orginal one. (3) Hired transformer will match with the existing transformer with same voltage, vector group, impendence etc. (4) Incase the defective/unservicable transformer is not repaired with in stipulated period of 15 days a penalty of Rs 1000/- per day will be deducted and no extra cost willl be paid to the contractor un less natural calamidity is occured.
Material and labour for rewinding of LT side winding with copper strip/wire of suitable size/gauge, fixing the coil in position in core assembly and making connection as per existing pattern including providing insulation, varnish etc complete all as specified and directed by Engr-in-Charge.
Material and labour for rewinding of HT side coil with supper enamelled Copper wire of suitable size/gauge, fixing the coil in position in core assembly and making connection as per existing pattern including providing insulation,varnish etc complete all as specified and directed by Engr-in-Charge.
Disconnecting HT/LT cable/busbar and Earthing connections complete of transformer capacity up to 63 KVA, 11 KV/433 Volts 3 phase from pole/floor/transformer shed with the help of Crane to carry out complete maint of transformer comprising of the following:- (i) Draining out oil from chamber. (ii) Opening top cover, disconnecting winding connection from bushings and taking out carefully core assembly complete with winding. (iii) Checking compactness of core & tightening the same where required. (iv) Chemical washing of winding to remove dirt,dust & carbon particles (v) Cleaning of oil tank to remove oil sludge followed by painting of inner surface of tank with zinc chromate base paint (vi) Refixing of core & winding assembly and making connection with HT/LT bushing . (vii Replacement of worn out gaskets & nut/bolts.
All as per item No.46 above but transformer capacity from 100 KVA to 200 KVA.
All as per item No.46 above but suitable for transformer capacity 250 KVA to 400 KVA.
Material and Labour for preparing the surfaces of transformer of capacity 63 to 100 KVA by rubbing old paint and applying two coats of spray painting with grey deco paint from outside complete all as specified and as directed. Note. Painting of transformer will be carried out for plinth mounted and pole mounted transformer. Necessary tools and plants shall be arranged by the contractor. Shut down schedule for painting of transformer will be submitted in advance to plan shut down in the station. including writing MES / SM No with enamelled paint complete all as specified and as directed for transformer of rating upto 100 KVA (Indoor/outdoor type).
All as per item No. 49 above but 200KVA to 250KVA (Indoor /outdoor type) complete all as specified.
All as per item No. 49 above but 250 KVA to 400 KVA (Indoor /outdoor type) complete all as specified.
Supply and fixing in replacement of silica gel breather assembly with vent pipe complete with fresh blue coloured, for transformer of capacity 50 KVA to 200 KVA complete all as specified and as directed.
All as per item No.52 above but suitable for transformer capacity 250 KVA to 400 KVA complete all as specified and directed.
Dismantling of old Burnt Tap changer and Supply and fixing new tap changing switch as per existing size including making connection to transformer of various capacities/make complete all as specified and as directed.
Supply and replacing HT/LT side cable box cover plate made out of MS sheet of 16 SWG complete with nuts, bolts, washers suitable for indoor/outdoor type transformer of capacity 63 KVA to 400 KVA complete all as specified and as directed.
Supply and fixing in replacement HT bush assembly brass complete with brass spindle, nuts, bolts, washers etc with bushing insulators suitable for transformer of capacity 50 KVA to 63 KVA complete all as specified and as directed.
All as per item No.56 above but transformer capacity from 100 KVA to 400 KVA complete all as specified and as directed.
Supply and fixing in replacement LT bush assembly brass complete with brass spindle, nuts, bolts, washers etc with bushing insulators suitable for transformer of capacity 50 KVA to 63 KVA complete all as specified and as directed.
All as per item No.58 above but transformer capacity from 100 KVA to 400 KVA complete all as specified and directed.
Supply and fixing in replacement 11KV porcelain bushing insulators for HT side of outdoor/indoor type transformer complete all as specified and directed.
Supply and fixing in replacement drain plug of suitable size, complete all as specified and as directed.
Supply and fixing in replacement of rubberized cork sheet gasket 6mm thick for top cover and HT/LT bushes for transformer upto 400 KVA capacity including replacement of Nuts & Bolts where required complete all as Specified and directed by Enge-in-Charge.
Supply and replacement of Oil level indicator complete with glass, gasket, Bolt nuts, washer etc suitable for any make and capacity transformer complete all as specified and directed.
M&L loose filling with broken trap stone aggregates of size exceeding 7 cms upto 15 cms in substations, around 4 pole/2 pole structures all as specified and directed by Engineer-in-Charge. Note :- The contractor has to stack the graves/stones near the substation as per directed for necessary measurement and instructions.
Supply and fixing of D.F. Buchholz Relay complete all as specified and directed.
M&L for Insulator suitable for 200A Gang Operating Device Insulator complete all as specified.
M&L for Male and Female Blade suitable for 200A Gang Operating Device complete all as specified.
S&F MCCB 3 Pole, 415 V, fixed type, 63 Amps with breaking capacity 16 KA complete all as specified and directed by Engr-in-Charge.
S&F MCCB 3 Pole, 415 V, fixed type, 100 Amps with breaking capacity 16 KA complete all as specified and directed by Engr-in-Charge.
S&F MCCB 4 Pole, 415 V, Adjustable type, 160 Amps with breaking capacity 36 KA complete all as specified and directed by Engr-in-Charge.
S&F MCCB 4 Pole, 415 V, Adjustable type, 200 Amps with breaking capacity 36 KA complete all as specified and directed by Engr-in-Charge.
S&F MCCB 4 Pole, 415 V, Adjustable type, 400 Amps with breaking capacity 36 KA complete all as specified and directed by Engr-in-Charge.
Supply and laying in cable, XLPE insulated , screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 3.5 Core 120 Sqmm, ISI marked complete, all as specified and as directed.
Supply and laying in cable, XLPE insulated , screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 3.5 Core 95 Sqmm, ISI marked complete, all as specified and as directed.
Supply and laying in cable, XLPE insulated , screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 3.5 Core 70 Sqmm, ISI marked complete, all as specified and as directed.
Supply and laying in cable, XLPE insulated , screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 3.5 Core 35 Sqmm, ISI marked complete, all as specified and as directed.
Supply and laying in cable, XLPE insulated , screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 4 Core 25 Sqmm, ISI marked complete, all as specified and as directed.
Supply and laying in cable, XLPE insulated , screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 2 Core 16 Sqmm, ISI marked complete, all as specified and as directed.
Supply and laying in cable, XLPE insulated , screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 2 Core 10 Sqmm, ISI marked complete, all as specified and as directed.
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade, of size 3 core 120 sq mm ISI marked complete, all as specified and as directed.
Excavation in trenches in soft/loose soil not exceeding 1.5 mtr in width and not exceeding 1.5 mtr in depth for laying of cables up to proper level complete all as specified and directed by Engr-in-charge.
Returning, filling in including spreading, leveling, watering and well ramming in layers not exc 25 cm in soft/loose soil complete all as specified and directed by Engr-in-charge.
Removing surplus exacavated material from excavation not exc 50 meter and depositing where directed at a level not exc 1.5 meter above the starting point complete all as specified and directed.
Sand cushioning to underground cables 8 cm below the cable before laying and 15 cm above the cable after laying, complete all as specified in clause 19.75 of SSR Part-I. Note :- 1. Dry fine sand of best available quality shall be used. 2. Punned thickness shall be measured and paid.
M & L Sub class ‘B brick, old size, brick covering laid dry, flat, transversally along the length of cable on sand cushioning, with width equal to the length of the brick, complete all as specified and directed.
M/S Sky Engineers
M/S Himalayan Construction and Co.
Rajindera Enterprises
M/s Habib Electronics
M/S KULBIR SINGH SODHI AND CO
stage.html
html • 0.06 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .