Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.7 LAccepted-AOC | ₹4.7 L | L1 | Accepted-AOC Lowest Bidder |
| 2 | L2₹6.5 L+₹1.8 L (38.6%)Rejected-Finance | ₹6.5 L+₹1.8 L (38.6%) | L2 | Rejected-Finance Second Lowest |
| 3 | L3₹7.2 L+₹2.5 L (53.0%)Rejected-Finance | ₹7.2 L+₹2.5 L (53.0%) | L3 | Rejected-Finance Third Lowest |
Tender Value
Refer Docs
EMD Value
₹15,600
Closing Date
10 Dec 2021, 9:00 amClosed
Major Sameer Wadekar
Holta Cantt, Palampur
REPAIR/MAINTENANCE OF INTERNAL WIRING, MCBs, DBs, SUB MAIN WIRING AND ELECTRICAL FITTINGS IN OFFICER MARRIED AND CENTRAL INSTITUTE AT PALAMPUR MIL STN.
2021_MES_487863_1
GEP/ - /2021-22
Open Tender
Civil Works
Item Rate
180 days
Palampur Mil Stn
As per tender documents
8 documents required · 8 mandatory
₹500
Yes
GE Palampur
₹15,600
Yes
25 Jan 2022
12 Nov 2021
13 Dec 2021
12 Nov 2021
10 Dec 2021
26 Nov 2021
Amount
Taking down old unsv copper/aluminium point wiring concealed / batten (light, fan, socket or power) complete, including fixture and fittings such as switches, sockets, ceiling roses, bell push, bell electric, lamp holder, bulk head fitting, pendants, regulators, sockets, light fitting and any type switch board wooden/iron, round block etc removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc complete all as specified and directed.
M&L for point wiring for one light/fan/call bell point controlled by one 5/6 Amp switch with 1.5 Sqmm PVC (FRLS-H) insulated unsheathed multi stranded copper conductor cable 1100 volts grade single core conforming to IS-694-1990 and including one run of continous earth wire to common earth and connected to earth with 1.5 Sqmm PVC (FRLSH) insulated unsheathed multi stranded copper conductor cable draw in & incl PVC surface casing 'N' capping double lock type to be fixed with the help of rawal plugs & screws incl all fittings such as Tee, connector pieces, L-junction etc on joints including CI/MS/PVC sunk boxes for mounting switches, sockets, regulators etc with 3 mm thick plastic laminated sheet cover of adequate size for one light/fan/bell point controlled by one switch and making good disturbed surfaces with CM (1:4) to match with the existing surface complete all as specified and directed. Notes : (a) Wiring shall be done by using proper colour coding.(b) Earth wire shall be of green colour. (c) On RCC roof/celing PVC casing 'N' capping shall be provided on surface with proper fixing clamps all as directed.
All as per the description of Serial item No 02 here-in-before but one 5 pin socket outlet, 5/6 amps on the same board complete all as specified and directed.
All as per the description of Serial item No 02 here-in-before but one 5 pin socket outlet, 5/6 amps, independent complete all as specified and directed.
All as per the description of Serial item No 02 here-in-before but for one 5 pin socket outlet 16 Amps on Independent board with cables 2.5 sqmm size complete all as specified and directed.
M&L for point wiring for one light/fan/call bell point controlled by one 5/6 Amp switch with 1.5 Sqmm single core multistranded copper conductor FRLS, PVC insulated (unsheathed) heavy duty cable including continuous earth wire of size 1.5 sqmm copper conductor multistrand FRLSH, PVC insulated (unsheathed) drawn into and including new concealed PVC rigid / 1.8mm wall thickness ISI marked including new CI/pressed steel terminal boxes including 3.00mm thick hylam brand IS-2036 marked, laminated sheet cover for mounting switches, sockets, fan regulators etc complete all as specified and as directed. Note : (a) Wiring shall be done by using proper colour coding.(b) Earth wire shall be of green colour. (c) On RCC roof/celing PVC conduit shall be provided on surface with proper fixing clamps all as directed by Engr-in-Charge.
All as per the description of Serial item No 6 here-in-before but 5/6 Amp socket outlet on same board complete all as specified and directed.
All as per the description of Serial item No 6 here-in-before but socket outlet 5/6 Amps independent board complete all as specified and directed.
All as per the description of Serial item No 6 here-in-before but for one 6 pin socket outlet 16 Amps on independent board with cables 2.5 sqmm size complete all as specified and directed.
M&L for point wiring for one light/fan/call bell point controlled by one 5/6 Amp switch with 1.5 Sqmm single core multistranded copper conductor FRLSH, PVC insulated (unsheathed) heavy duty cable including continuous earth wire of size 1.5 sqmm copper conductor multistrand FRLSH, PVC insulated (unsheathed) drawn into and including new concealed PVC rigid conduit of 1.8mm wall thickness ISI marked including modular metal flush box (Modular Metal flush Boxes of any way i.e. 1 to 8 way as per site requirement) for mounting switches, sockets, fan regulators etc complete all as specified and as directed for the following:- (a) Wiring shall be done by using proper colour coding (b) Earth wire shall be of green colour (c) On RCC roof/celing PVC conduit shall be provided on surface with proper fixing clamps all as directed.
All as per the description of Serial item No 10 here-in-before but 6 Amp socket outlet on same board complete all as specified and directed.
All as per the description of Serial item No 10 here-in-before but socket outlet 6 Amps independent board complete all as specified and directed.
All as per the description of Serial item No 10 here-in-before but for one 6 pin socket outlet 16 Amps on independent board with cables 2.5 sqmm size complete all as specified and directed.
S&F switch piano, flush type single pole one way 6 Amp, 240 volts ISI marked complete all as specified and as directed.
S&F socket outlet 2 in 1, 3 pin, 6A complete all as specified and directed.
S&F switch socket combination 2 in 1, 3 pin 6 amp and 16 amp flush type universal, 240 volts ISI marked complete all as specified and directed.
S&F ceiling rose, 3 terminal surface type complete all as specified and directed.
S&F lamp holder, PVC/Polycarbonate type with back plate suitable for batten fittings complete all as specified and directed.
S&F bell, AC 230 Volts, single pole complete all as specified and directed.
S&F bell push flush type single pole one way 5 amp complete all as specified and directed.
S&F stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc. as required complete all as specified and directed.
S&F modular switch 1 way 6 A,1 module, 240 volts ISI marked complete all as specified and directed.
S&F modular switch 1 way 16 A, 1 module, 240 volts ISI marked complete all as specified and directed.
S&F socket, 6A - 2/3 pin combined 2 module, 240 volts ISI marked complete all as specified and directed.
S&F socket 6A/16A - 2/3 pin combined 2 module, 240 volts ISI marked complete all as specified and directed.
S&F modular Fan step regulator, 120W 1 module, 240 volts ISI marked complete all as specified and directed.
Supply & fixing surface /wall mounted 18W LED tube light fitting pre wired suitable for single T8 LED tube and 01 No. 18W ultra bright LED polycarbonate tube rod with THD<10% with very high efficacy suited for installation in existing T8 fitting with G13 lamp holders, Lumen out put - 2100 Lm, Colour Temp - 6500 Kelvin, Size & Length - G13/ T8/ 4 Feet with integral/in built driver, having short circuit and surge protection including making connection with two core PVC insulated, sheathed copper conductor cable of size 23/0.0076 complete all as specified and directed. Make:-(i) Cat Part No for batten:- REGALBATTENT8UPTO1X22WSSBSWH of Havells or equivalent make and Cart Part as approved by GE. (ii) Make:- Cat Part No for Tubelight:- PHOTONULTRA2.01213T8SSTL18WLED 865SPC of Havells or equivalent make and Cat Part as approved by GE
S&F worn out ceiling light with enviromental friendly, new generation, aesthetically designed, ultra modern recessed mounted LED light luminaries of size (595x595x70)mm an independent Isolated, electronic LED driver (SMPS based constant current supply) housed in CRCA powder coated sheet of system wattage - 40/42 Watt, Lumen out put- 4000-4300 Lm, THD < 10%, PF > 0.9, having short circuit and surge protection suitable for Armstrong/ Grid ceiling with all connected accessories including making connection with three core PVC insulated, sheathed copper conductor cable of size 23/0.0076 complete all as specified and directed. Make:- Cat Part No: PLUTONEO2X2PLR42WLED857S of Havells or equivalent make and Cat Part as approved by GE.
S&F Sheet metal enclousers, TPN Distribution board 4 way, double door complete with appropriate size bus bar, neutral link and Earth Bar fixed flush in wall including chases wall for fixing DB and making good distributed wall surfaces to match with existing specification complete all as specified and directed. Note:- Distribution board and MCB's should be same make.
M&L distribution board sheet steel powder coated for MCB with copper bus bar and neutral link earthing stud SPN 12 way 240 volts double door complete all as specified and directed. Note:- Distribution board and MCB's should be same make.
M&L distribution board sheet steel powder coated for MCB with copper bus bar and neutral link earthing stud SPN 8 way 240 volts double door complete all as specified and directed. Note:- Distribution board and MCB's should be same make.
M&L distribution board sheet steel powder coated for MCB with copper bus bar and neutral link earthing stud SPN 4 way 240 volts double door complete all as specified and directed. Note:- Distribution board and MCB's should be same make.
S&F MCB SP 6 to 32 Amp, 240V, 10 KA 'B' curve, in the MCB DB, connection testing and commissioning complete all as specified and directed.
S&F MCB SP 32 Amp rating 240V, 10KA 'C' curve connection testing and commissioning complete all as specified and directed.
S&F MCB SPN 40 to 63 Amp rating 240V, 10KA 'B' curve in the MCB DB, connection testing and commissioning complete all as specified and directed.
S&F MCB, TPN 63 Amp, 415V 10KA 'B' curve in the MCB DB connection testing and commissioning complete all as specified and directed.
M&L in replacement for sub main wiring with proper colour coding, insulated, unsheathed, multistranded, copper conductor FRLS, cable of 2 run 6 Sq mm for phase and neutral and one run of 6.0 Sq mm for earth wire unsheathed, multistranded, copper conductor FRLS, drawn through the existing rigid PVC concealed conduit fixed on wall. Two runs of cable for phase/neutral and one run of cable for earth will be measured and paid as one unit length complete all as specified and directed. Note:- Wiring shall be done in proper colour coding.
M&L in replacement for sub main wiring with proper colour coding, insulated, unsheathed, multistranded, copper conductor FRLS, cable of 2 run 4 Sq mm for phase and neutral and one run of 4 Sq mm for earth wire unsheathed, multistranded, copper conductor FRLS, drawn through the existing rigid PVC concealed conduit fixed on wall. Two runs of cable for phase/neutral and one run of cable for earth will be measured and paid as one unit length complete all as specified and directed. Note:- Wiring shall be done in proper colour coding.
Earthing complete with galvanised iron earth plate electrode of size 600mm x 600mm x 6mm thick buried directly under ground vertically to a depth not less than 2.25 metre below ground level with top edge of the earth plate at a depth not less than 1.5 metre below ground level ,connected to galvanised earth lead wire 4.0mm by means of bolts, nuts, check nuts, washer including test point by means of bolts, nuts, check nuts, and washers of galvanized iron and connected to main switch / control board up to 7.5 metre away from earth electrode and including GI pipe light grade 40mm bore protection pipe & necessary excavation and earth work in any strata, PCC chambers in PCC 1:3:6 type B1, RCC 1:2:4 type B1 cover slab 50mm thick with 8mm dia TMT bars at 140mm C/C both ways, with lifting handle, watering pipe of GI medium grade 40mm dia, wire mesh, funnel, lugs and charcoal, salt etc all as applicable and as per plate No 3 of SSR Part-I and all as specified.
Charges for attending E/M petty complaint in respect repair/rectification of fault in electric fitting MCB DB's, internal wiring LT Panel and fixture and rectify the faults and replacement of unsv any type of fitting/fixture, MCB's, any type, bakalite sheet restore the electric supply and made the item functionable light point, fan point, socket point 6A/16A, switches sockets, fan regulator, light fixtures any type of lamp, MCB DB's and all electrical acessories and day to day /door to door maintenance, making the points/accessories serviceable in all respect with replacement of any minor parts like small length of wires (not more than 1 mtr) and other connected minor accessories. Work shall also include to check and removal of leakage in service connection / submains of houses all as specified and as directed. The scope also include cutting of existing bakelite sheet to accommodate new wiring acessories all type electric fitting/fixture. (Accessories shall be paid under respective items as supply only). Notes : Any other replacement of major items shall be measured & paid under respective items as supply only. Fixing charge of fitting/fixture and MCB's of any type is deemed to be included in the above item.
(i) Contractor representative/supervisor will report to complaint cell for morning and afternoon to collect routine/urgent nature of complaint related to internal electric supply till completion of contract. The work shall be attended by the contractor immediately. The contractor will ensure deployed of sufficient manpower with equipped all sort of petty items such as insulation tape, galvanised screws, nuts, bolts, washers etc required to accomplish the job. The contractor will also ensure as availability of every type of requisite T&P items to his tradesman. All routine / urgent job received on job slip will be repaired and got signature of user's and will be deposited to complaint cell within 24 hrs. In case of any delay in attending the complaint more than 48 hrs after handing over of routine / urgent works, the contractor shall be liable to pay the penalty as per the item rate.(ii) Contractor shall maintain the maintenance register showing all daily complaints received and shall maintain job card for attending complaints. The signature of the user shall be obtained on the job card showing the materials used in the work after completion of the job. (iii) If the Contractor did not attend complaints, a penalty of Rs 300/- per day per complaint recovery shall be made from the work done amount. (iv) The MES Department is not responsible for the payment of staff hired by contractor for complaint rates for attending the complaints by the electrician are deem to included in the item for repair i.e. Electrician/Helper, as all the items of CA are to be supply and fixed by the contractor. (v) All the complaint slip, register and connected document will be provided by the contractor without any extra cost. (vi) After any repair the site has to be cleaned and make the surface good.
Supply only Modular switch 1 way 6A, 1 module complete all as specified and directed.
Supply only Modular socket outlet 2/3 pin 6 amps, 2 module complete all as specified and directed.
Supply only Modular switch 1 way 16A, 1 module complete all as specified and directed.
Supply only Modular socket outlet 6/16 Amps, 2/3 pin combined 2 module complete all as specified and directed.
Supply only Modular fan regulator step type, 120W-2 module complete all as specified and directed.
Taking down of existing unserviceable flood light of any type and any description, supply & fix 30W LED, energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium flood light with high power LEDs as light source, suitable for highlighting architectural features or area lighting complete all as specified and directed by Engineer-in-Charge. Make:- Havells Cat Part No. JETAQUANTOPLUSFLP30WLED757SYMLENS or equivalent make and Cat Part as approved by GE.
Taking down of existing unserviceable bolard fitting of any type and any description, supply and fix 9W LED bolard fitting in cylinderal shape with opal acrylic diffuser and IP65 protection complete incl fixing arrangement on 300x300x300mm PCC (1:2:4) and necessary connection complete all as specified and directed. Make:- Bajaj Cat Part No BGBOL 605 9W LED WW or equivalent make and Cat Part as approved by GE
Taking down of existing unserviceable bolard fitting of any type and any description, supply and fix 15W new generatoion, post-top, energy saving, environmental friendly, aesthetically designed with symmetrical light distribution, spun aluminium landscape luminaire with high power LEDs as light source, IP65 protection complete incl fixing arrangement with 50mm dia GI tube medium grade of suitable length and 300x300x300mm PCC (1:2:4) for foundation of pipe and necessary connection complete all as specified and directed. Make:- Havells Cat Part No. CORALMINIPT15WLED757PSYMTOPC or equivalent make and Cat Part as approved by GE.
Taking down un-serviceable DB of any size and capacity including MCB etc, and removing materials to store for keeping in safe custody or for taking credit and making good disturbed surfaces of walls,floors, etc, complete all as specified and directed.
KISHAN CONTRACTOR
BHARDWAJ BUILDERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .