Superintending Engineer-I
CANDP Office, PTCUL Vidyut Bhawan Dehradun Uttarakhand
Construction of 132 kV GIS Switching Substation for Rail Vikas Nigam Limited (RVNL) at Rishikesh and 132KV GIS Switching Substation for Rail Vikas Nigam Limited (RVNL) at Ranihat (Srinagar)
2024_PTCU1_74871_1
PTCUL/CANDP-I/SS-09/2024-25
Open Tender
Electrical Works
540 days
Rishikesh and Srinagar Ranihat
Please refer Tender documents.
3 documents required · 3 mandatory
₹29,500
Yes
MD PTCUL
₹83.8 L
Yes
Dehradun
23 Nov 2024
22 Aug 2024
20 Nov 2024
22 Aug 2024
19 Nov 2024
2 Sept 2024
27 Aug 2024
Amount
Construction of 132 kV GIS Switching Substation for RVNL at Rishikesh.
Part-A (Supply of Material )
400kVA 11/0.433KV three phase transformer including bushing, accessories and first filling of oil
145kV GIS Equipment
145kV, SF6 gas insulated Feeder Bay Module each comprising of SF6 gas insulated Circuit Breaker, Current Transformer, one bus-bar disconnector with grounding switch and one busbar disconnector without grounding switch, line disconnector with safety grounding switch, high speed fault making grounding switch, SF6 gas monitoring system for complete bay, LCC, GIS Duct, SF6/Air Bushing termination and accessories with GIS etc. to complete Feeder Bay Module.
145KV, 3Phase units, SF6 gas insulated, metal enclosed Bus Bars each enclosed in bus enclosures running along the length of the switchgear to interconnect each of circuit breaker bay module. Each bus bar set shall be complete with voltage transformer complete with safety grounding switch.
145KV, SF6 gas insulated Bus Coupler Bay Module comprising of SF6 gas insulated cirucit breaker, current transformer, two disconnectors with safety grounding switches, SF6 gas monitoring system for complete bay, LCC etc.
145kV AIS Equipment
145 KV CVT with Junction Box
145 KV lightning Arrester with counter and leakage meter
145 kV Post Insulator
145kV CT Single phase of ratio 200/100/1 A with 1 No Junction Box for set of 3 Nos CTs
Miscellaneous Materials (Insulators Strings/ Disc Insulator, Hardwares, Conductor, Bus Bar materials, Cable Tray, Clamps, Connector including equipments connectors and all accessories etc.
11kV AIS Equipments
11kV Indoor Switchgear panel (AIS Type) with VCB, CTs and PTs
Miscellaneous Materials (Hardwares, poles, Cable Trays, Clamps, Connector including equipments connectors and all accessories etc.) for station Transformers.
11kV 3 phase AB switch
11kV Outdoor LA
Complete Substation Automation System including hardware and software for the substation & remote control stations alongwith all necessary associated equipments as per Technical Specifications and Detailed Engineering.
Bay Control Units
132kV system
250kVA DG set with AMF panel
Online Monitoring, Data Acquisition and ABT Analysis System
ABT meters 0.2 Cl with TCP/IP, Optical Communication Port
Industrial Grade Network Switch -8 Port, unmanaged
UPS 2 KVA online with 30 Min back up on 100% load
DCU & Accessories
Workstation : Application & Database server
Database - Microsoft SQL Server Standard Edition
MS office - Standard Edition
MacAfee Virus Scan Enterprise Desktop Edition - Per Year
Local Energy Monitoring Software - Professional Edition
Lan cable ( average one roll per S/S 300 Meters)
PVC conduit Pipe - 3/4"
Enclosure for Lan Switch
3G/4G Data enable SIM
Integration of Station Metering System with Centralized Data System including all hardware and software required.
132kV Control and Relay panel
Circuit Breaker Control Panel with Auto Reclose
Circuit Breaker Control Panel without Auto Reclose
Line Protection Panel
132kV Bus Bar Protection Panel for Main-1 and Main-2 Bus
PLCC for 132kV Line feeder
Line Traps (132kV 0.5 mH/ 1.0 mH)
Coupling device
HF Cable
Carrier Equipment for (Speech + Protection)
Carrier Equipment for (Speech + Data)
Protection Coupler
Time synchronisation equipment
Air-conditioner and ventilation System
Split AC (Capacity-2T) with Cassettee type Indoor Unit, Max Star rating as per latest ammendments of BEE (ISEER)
Ventillation system for 132 kV GIS Hall
Miscellaneous items
Air Blinds/Curtain for Control Room Building
Interactive Smart Screen for Control Room Building 75inch LED Board Android
LT Switchboard
415V main switchboard
415V ACDB
110V DCDB
48V DCDB
Batteries
110V 500AH VRLA Type
48V 300AH VRLA Type
Battery charger
110V 100 Amps FCBC
48V 60 Amps FCBC
Fire Protection system
Fire Alarm system for 132kV GIS Hall,Control Room and Other rooms
45 Ltr. Foam Type
ABC type fire Extinguisher 10 Kgs
6 Fire Bucket with stand
Fire Hut and sand pit
CO2 type fire Extinguisher 20 Kgs
CO2 type fire Extinguisher 4.5Kgs
llumination sytem
LED Lights for Control Room / Store Room / Offices Ilumination with complete fittings
LED Lights for Switchyard Lighting with complete fittings, Junction Box & mounting accessories
Solar Light System for Street Light (LED Type Lights) with Pole and other mounting accessories
LED light for 132 kV GIS hall- High bay Type 170Watts
1.1kV Aromoured Power Cables (Al) and Aromoured Control Cables (Copper) alongwith multidiameter moulded cable sealing, Lugs, Glands and straight joints, etc.
AL Power cable (PVC)
3.5cx70Sq.mm
3.5cx35Sq.mm
4cx16 Sq.mm
4cx6 Sq.mm
Copper Control cable (PVC)
2Cx2.5Sq.mm
4Cx2.5Sq.mm
6Cx2.5Sq.mm
10Cx2.5Sq.mm
132kV XLPE Cable Al 630 Sq. mm
132kV Outdoor Termination Bushing
11kV Power cables Copper (XLPE) and Accessories
3X400 Sq.mm
11 kV Indoor Termination
11 kV Outdoor Termination
Grounding/Earthing system
40mm MS rod for earthmat
40mm MS 03 metre Electrodes
40mm 03 meter deep driven pipe electrode (treated pit)
GS Flats 50 x 6mm size
GS shield Wire
Steel Structure
Lattice structure (Main Structures, Auxiliary Equipments Structures & Lightning Mast Structure)
Pipe structure (Auxiliary Equipments Structure)
EOT Crane for 132kV GIS Hall
Mandatory spares as per Technical specifications
Testing & Maintenance Equipment
Insulation Tester Meter 5kV Multirange (Motorized)
Insulation Tester Meter 1kV Multirange (Motorized)
Thermo Vision Camera
Digital Multi meter
Leakage tester (Tong type)
Gas Evacuating and refilling Plant for 132 kV GIS
Gas Leakge Monitor
Portable Partial dischange monitoring system
Gas Mask
D-Spanner set (Insulated)
Ring-Spanner set (Insulated)
Torque Wrench set
Insulating Gloves & Helmets
Spliced ladders 5mtr.
Spliced ladders 10mtr.
Spliced ladders 20mtr.
Helmet
Polyamide or Braided white nylon ropes 14mm
Rubber mat in Control room, Battery Room & LT Panel Room etc. as per Site requirements
Shock treatment chart & artificial respiratory system
First-aid box complete with first filling of required medicines, instruments and tools
Danger / Man on line / Break-Down boards of appropriate size
Rain coat, Gum boot and Safety Harness Belt with adequate straps
Moveable ladder of suitable capacity for 132kV GIS Hall
Description of Work / Item(s)
Amount
Construction of 132 kV GIS Switching Substation for RVNL at Rishikesh.
Part-B (Erection of Materials)
400kVA 11/0.433KV three phase transformer including bushing, accessories and first filling of oil
145kV GIS Equipment
145kV, SF6 gas insulated Feeder Bay Module each comprising of SF6 gas insulated Circuit Breaker, Current Transformer, one bus-bar disconnector with grounding switch and one busbar disconnector without grounding switch, line disconnector with safety grounding switch, high speed fault making grounding switch, SF6 gas monitoring system for complete bay, LCC, GIS Duct, SF6/Air Bushing termination and accessories with GIS etc. to complete Feeder Bay Module.
145KV, 3Phase units, SF6 gas insulated, metal enclosed Bus Bars each enclosed in bus enclosures running along the length of the switchgear to interconnect each of circuit breaker bay module. Each bus bar set shall be complete with voltage transformer complete with safety grounding switch.
145KV, SF6 gas insulated Bus Coupler Bay Module comprising of SF6 gas insulated cirucit breaker, current transformer, two disconnectors with safety grounding switches, SF6 gas monitoring system for complete bay, LCC etc.
145kV AIS Equipment
145 KV CVT with Junction Box
145 KV lightning Arrester with counter and leakage meter
145 kV Post Insulator
145kV CT Single phase of ratio 200/100/1 A with 1 No Junction Box for set of 3 Nos CTs
Miscellaneous Materials (Insulators Strings/ Disc Insulator, Hardwares, Conductor, Bus Bar materials, Cable Tray, Clamps, Connector including equipments connectors and all accessories etc.
11kV AIS Equipments
11kV Indoor Switchgear panel (AIS Type) with VCB, CTs and PTs
Miscellaneous Materials (Hardwares, poles, Cable Trays, Clamps, Connector including equipments connectors and all accessories etc.) for station Transformers.
11kV 3 phase AB switch
11kV Outdoor LA
Complete Substation Automation System including hardware and software for the substation & remote control stations alongwith all necessary associated equipments as per Technical Specifications and Detailed Engineering.
Bay Control Units
132kV system
250kVA DG set with AMF panel
Online Monitoring, Data Acquisition and ABT Analysis System
ABT meters 0.2 Cl with TCP/IP, Optical Communication Port
Industrial Grade Network Switch -8 Port, unmanaged
UPS 2 KVA online with 30 Min back up on 100% load
DCU & Accessories
Workstation : Application & Database server
Database - Microsoft SQL Server Standard Edition
MS office - Standard Edition
MacAfee Virus Scan Enterprise Desktop Edition - Per Year
Local Energy Monitoring Software - Professional Edition
Lan cable ( average one roll per S/S 300 Meters)
PVC conduit Pipe - 3/4"
Enclosure for Lan Switch
3G/4G Data enable SIM
Integration of Station Metering System with Centralized Data System including all hardware and software required.
132kV Control and Relay panel
Circuit Breaker Control Panel with Auto Reclose
Circuit Breaker Control Panel without Auto Reclose
Line Protection Panel
132kV Bus Bar Protection Panel for Main-1 and Main-2 Bus
PLCC for 132kV Line feeder
Line Traps (132kV 0.5 mH/ 1.0 mH)
Coupling device
HF Cable
Carrier Equipment for (Speech + Protection)
Carrier Equipment for (Speech + Data)
Protection Coupler
Time synchronisation equipment
Air-conditioner and ventilation System
Split AC (Capacity-2T) with Cassettee type Indoor Unit, Max Star rating as per latest ammendments of BEE (ISEER)
Ventillation system for 132 kV GIS Hall
Miscellaneous items
Air Blinds/Curtain for Control Room Building
Interactive Smart Screen for Control Room Building 75inch LED Board Android
LT Switchboard
415V main switchboard
415V ACDB
110V DCDB
48V DCDB
Batteries
110V 500AH VRLA Type
48V 300AH VRLA Type
Battery charger
110V 100 Amps FCBC
48V 60 Amps FCBC
Fire Protection system
Fire Alarm system for 132kV GIS Hall,Control Room and Other rooms
45 Ltr. Foam Type
ABC type fire Extinguisher 10 Kgs
6 Fire Bucket with stand
Fire Hut and sand pit
CO2 type fire Extinguisher 20 Kgs
CO2 type fire Extinguisher 4.5Kgs
llumination sytem
LED Lights for Control Room / Store Room / Offices Ilumination with complete fittings
LED Lights for Switchyard Lighting with complete fittings, Junction Box & mounting accessories
Solar Light System for Street Light (LED Type Lights) with Pole and other mounting accessories
LED light for 132 kV GIS hall- High bay Type 170Watts
1.1kV Aromoured Power Cables (Al) and Aromoured Control Cables (Copper) alongwith multidiameter moulded cable sealing, Lugs, Glands and straight joints, etc.
AL Power cable (PVC)
3.5cx70Sq.mm
3.5cx35Sq.mm
4cx16 Sq.mm
4cx6 Sq.mm
Copper Control cable (PVC)
2Cx2.5Sq.mm
4Cx2.5Sq.mm
6Cx2.5Sq.mm
10Cx2.5Sq.mm
132kV XLPE Cable Al 630 Sq. mm
132kV Outdoor Termination Bushing
11kV Power cables Copper (XLPE) and Accessories
3X400 Sq.mm
11 kV Indoor Termination
11 kV Outdoor Termination
Grounding/Earthing system
40mm MS rod for earthmat
40mm MS 03 metre Electrodes
40mm 03 meter deep driven pipe electrode (treated pit)
GS Flats 50 x 6mm size
GS shield Wire
Steel Structure
Lattice structure (Main Structures, Auxiliary Equipments Structures & Lightning Mast Structure)
Pipe structure (Auxiliary Equipments Structure)
EOT Crane for 132kV GIS Hall
Description of Work / Item(s)
Amount
Construction of 132 kV GIS Switching Substation for RVNL at Rishikesh.
Part-C (Civil)
Buildings
Construction of 132 KV GIS Control cum Relay Room and Cable Vault (Plinth area to be measured) Ground Floor (Minimum Ceiling height-4.50 M)
(i) Control cum Relay Room (Minimum Ceiling height-4.50 M)
(ii) Cable Vault (Minimum room height 2.40 M )
Construction of 132 KV GIS Hall and Cable Vault (Plinth area to be measured)
(i) 132 KV GIS Hall (Minimum Ceiling height-9.00 M)
(ii) Cable Vault (Minimum room height 2.40 M )
Construction of LT Switchgear, Electrical Room, Battery Room (Plinth area to be measured) Ground Floor (Minimum Ceiling height-4.50 M)
Construction of SCADA Room, Conference Room & Office (Plinth area to be measured) First Floor (Minimum Ceiling height-4.50 M)
Construction of store shed (Plinth area to be measured) (Minimum Ceiling height-4.20 M)
Security Guard Room (Minimum Ceiling Height- 2.90 M)
Construction of foundation of following structures including excavation and back filling of earth, CC/RCC works, reinforcement , supply & Fixing foundation bolts etc. complete.
145 KV Gantry Column Foundation
145 KV CVT Foundation
145 KV LA Foundation
145 KV BPI Foundation
Foundations for Bus Duct support structure.
Foundation for Lightening Mast
Plinth for 250KVA Transformer
Bushing foundations
RCC Cable trenches with trench covers (all Sections) including all type of crossing and all metallic work to support cables and trench covers.
600 mm size trench with minimum depth 600 mm
1050 mm size trench with minimum depth 600 mm
600 mm size trench with minimum depth 1000 mm
1050 mm size trench with minimum depth 1000 mm
Cement concrete roads including all type of crossings.
5.00 metre wide
3.80 metre wide
Security (Chain link) Fencing 3.6 m high along with Gate
Security (Chain link) Fencing 3.6 m high
Gate (5.0M wide)
Storm water drainage including culverts & chambers.
AC junction box for Switchyard lighting
Switch yard turfing and antiweed treatment including leveling and dressing of area, PCC and gravels
Land development including necessary cutting /filling and construction of all retaining walls for complete switch yard area maintaining required terraces levels, approach road, culverts.
Carriage of Earth by mechanical transport including loading, unloading and stacking up to 5.0 KM lead (DSR No. 1.1.2)
Filling with available fly ash and earth (excluding rock) in trenches or embankment in layers (each layer should not exceed 15 cm), with intermediate layer of compacted earth (soil density of 98%) after every four layers of compacted depth of fly ash, sides & top layer of filling shall be done with earth having total minimum compacted thickness 30 cm or as decided by Engineer-in-charge, including compacting each layer by rolling/ramming and watering, all complete as per drawing and direction of Engineer in charge. (D.S.R. No. 2.38)
Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead upto 50 m and lift upto 1.5 m, disposed earth to be levelled and neatly dressed.Ordinary rock (DSR No. 2.7.1)
Excavation work in foundation trenches or drains not exceeding 1.5 m in width or 10 sqm on plan including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soils as directed, within a lead of 50m. Ordinary rock (DSR No. 2.9.1)
Extra for every additional lift of 1.5 m or part thereof in. Ordinary or hard rock (DSR No. 2.26.2)
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level. 1:2:4 ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) (DSR No. 4.1.3)
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level. 1:4:8 ( 1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) (DSR No. 4.1.8)
Providing and laying in position specified grade of reinforced cement concrete excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level. 1:1.5:3 ( 1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size). (DSR No. 5.1.2)
Providing and laying in position specified grade of reinforced cement concrete excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level. 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size). (DSR No. 5.1.3)
Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up to floor five level excluding cost of centering, shuttering, finishing and reinforcement. 1:1.5:3 ( 1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size). (DSR No. 5.2.2)
Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15 degree landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral staircases up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement. 1:1.5:3 ( 1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) (DSR 5.3)
Centering and shuttering including strutting, propping etc. and removal of form for : Foundations, footing, bases of columns, etc. for mass concrete. (DSR No. 5.9.1)
Centering and shuttering including strutting, propping etc. and removal of form for : Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. (DSR No. 5.9.2)
Centering and shuttering including strutting, propping etc. and removal of form for : Suspended floors, roofs, landing, balconies and access platform(DSR 5.9.3)
Centering and shuttering including strutting, propping etc. and removal of form for : Columns, Pillars, Piers, Abutments, Posts and Struts. (DSR No. 5.9.6)
Centering and shuttering including strutting, propping etc. and removal of form for : Edges of slabs and breaks in floors and walls. Under 20 cm wide (DSR No. 5.9.16)
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. Cold twisted bars (DSR No. 5.22.3)
Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with : Cement mortar 1:6 (1 cement : 6 coarse sand) (DSR No. 7.1.1)
Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works (DSR No. 10.25.2)
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.(i) Single socketed pipes. 110 mm diameter (DSR No. 12.41.2)
Supplying and stacking at site. 90 mm to 45 mm size stone aggregate. (DSR No. 16.3.1)
Supplying and stacking at site. 63 mm to 45 mm size stone aggregate. (DSR No. 16.3.2)
Laying spreading and compacting stone aggregate of specified sizes to WBM specifications including spreading in uniform thickness, hand picking , rolling with 3 wheeled road / vibratory roller 8-10 tonne in stages to proper grade and camber, applying and brooming requisite type of screening / binding material to fill up interstices of coarse aggregate watering and compacting to the required density. (DSR No. 16.4)
Description of Work / Item(s)
Amount
Construction of 132 kV GIS Switching Substation for RVNL at Ranihat (Srinagar).
Part-D (Supply of Material )
400kVA 11/0.433KV three phase transformer including bushing, accessories and first filling of oil
145kV GIS Equipment
145kV, SF6 gas insulated Feeder Bay Module each comprising of SF6 gas insulated Circuit Breaker, Current Transformer, one bus-bar disconnector with grounding switch and one busbar disconnector without grounding switch, line disconnector with safety grounding switch, high speed fault making grounding switch, SF6 gas monitoring system for complete bay, LCC, GIS Duct, SF6/Air Bushing termination and accessories with GIS etc. to complete Feeder Bay Module.
145KV, 3Phase units, SF6 gas insulated, metal enclosed Bus Bars each enclosed in bus enclosures running along the length of the switchgear to interconnect each of circuit breaker bay module. Each bus bar set shall be complete with voltage transformer complete with safety grounding switch.
145KV, SF6 gas insulated Bus Coupler Bay Module comprising of SF6 gas insulated cirucit breaker, current transformer, two disconnectors with safety grounding switches, SF6 gas monitoring system for complete bay, LCC etc.
145kV AIS Equipment
145 KV CVT with Junction Box
145 KV lightning Arrester with counter and leakage meter
145 kV Post Insulator
145kV CT Single phase of ratio 200/100/1 A with 1 No Junction Box for set of 3 Nos CTs
Miscellaneous Materials (Insulators Strings/ Disc Insulator, Hardwares, Conductor, Bus Bar materials, Cable Tray, Clamps, Connector including equipments connectors and all accessories etc.
11kV AIS Equipments
11kV Indoor Switchgear panel (AIS Type) with VCB, CTs and PTs
Miscellaneous Materials (Hardwares, poles, Cable Trays, Clamps, Connector including equipments connectors and all accessories etc. for station Transformers.
11kV 3 phase AB switch
11kV Outdoor LA
Complete Substation Automation System including hardware and software for the substation & remote control stations alongwith all necessary associated equipments as per Technical Specifications and Detailed Engineering.
Bay Control Units
132kV system
250kVA DG set with AMF panel
Online Monitoring, Data Acquisition and ABT Analysis System
ABT meters 0.2 Cl with TCP/IP, Optical Communication Port
Industrial Grade Network Switch -8 Port, unmanaged
UPS 2 KVA online with 30 Min back up on 100% load
DCU & Accessories
Workstation : Application & Database server
Database - Microsoft SQL Server Standard Edition
MS office - Standard Edition
MacAfee Virus Scan Enterprise Desktop Edition - Per Year
Local Energy Monitoring Software - Professional Edition
Lan cable ( average one roll per S/S 300 Meters)
PVC conduit Pipe - 3/4"
Enclosure for Lan Switch
3G/4G Data enable SIM
Integration of Station Metering System with Centralized Data System including all hardware and software required.
132kV Control and Relay panel
Circuit Breaker Control Panel with Auto Reclose
Circuit Breaker Control Panel without Auto Reclose
Line Protection Panel
132kV Bus Bar Protection Panel for Main-1 and Main-2 Bus
PLCC for 132kV Line feeder
Line Traps (132kV 0.5 mH/ 1.0 mH)
Coupling device
HF Cable
Carrier Equipment for (Speech + Protection)
Carrier Equipment for (Speech + Data)
Protection Coupler
Time synchronisation equipment
Air-conditioner and ventilation System
Split AC (Capacity-2T) with Cassettee type Indoor Unit, Max Star rating as per latest ammendments of BEE (ISEER)
Ventillation system for 132 kV GIS Hall
Miscellaneous items
Air Blinds/Curtain for Control Room Building
Interactive Smart Screen for Control Room Building 75inch LED Board Android
LT Switchboard
415V main switchboard
415V ACDB
110V DCDB
48V DCDB
Batteries
110V 500AH VRLA Type
48V 300AH VRLA Type
Battery charger
110V 100 Amps FCBC
48V 60 Amps FCBC
Fire Protection system
Fire Alarm system for 132kV GIS Hall,Control Room and Other rooms
45 Ltr. Foam Type
ABC type fire Extinguisher 10 Kgs
6 Fire Bucket with stand
Fire Hut and sand pit
CO2 type fire Extinguisher 20 Kgs
CO2 type fire Extinguisher 4.5Kgs
llumination sytem
LED Lights for Control Room / Store Room / Offices Ilumination with complete fittings
LED Lights for Switchyard Lighting with complete fittings, Junction Box & mounting accessories
Solar Light System for Street Light (LED Type Lights) with Pole and other mounting accessories
LED light for 132 kV GIS hall- High bay Type 170Watts
1.1kV Aromoured Power Cables (Al) and Aromoured Control Cables (Copper) alongwith multidiameter moulded cable sealing, Lugs, Glands and straight joints, etc.
AL Power cable (PVC)
3.5cx70Sq.mm
3.5cx35Sq.mm
4cx16 Sq.mm
4cx6 Sq.mm
Copper Control cable (PVC)
2Cx2.5Sq.mm
4Cx2.5Sq.mm
6Cx2.5Sq.mm
10Cx2.5Sq.mm
132kV XLPE Cable Al 630 Sq. mm)
132kV Outdoor Termination Bushing
11kV Power cables Copper (XLPE) and Accessories
3X400 Sq.mm
11 kV Indoor Termination
11 kV Outdoor Termination
Grounding/Earthing system
40mm MS rod for earthmat
40mm MS 03 metre Electrodes
40mm 03 meter deep driven pipe electrode (treated pit)
GS Flats 50 x 6mm size
GS shield Wire
Steel Structure
Lattice structure (Main Structures, Auxiliary Equipments Structures & Lightning Mast Structure)
Pipe structure (Auxiliary Equipments Structure)
EOT Crane for 132kV GIS Hall
Mandatory spares as per Technical specifications
Testing & Maintenance Equipment
Insulation Tester Meter 5kV Multirange (Motorized)
Insulation Tester Meter 1kV Multirange (Motorized)
Thermo Vision Camera
Digital Multi meter
Leakage tester (Tong type)
Gas Evacuating and refilling Plant for 132 kV GIS
Gas Leakge Monitor
Portable Partial dischange monitoring system
Gas Mask
D-Spanner set (Insulated)
Ring-Spanner set (Insulated)
Torque Wrench set
Insulating Gloves & Helmets
Spliced ladders 5mtr.
Spliced ladders 10mtr.
Spliced ladders 20mtr.
Helmet
Polyamide or Braided white nylon ropes 14mm
Rubber mat in Control room, Battery Room & LT Panel Room etc. as per Site requirements
Shock treatment chart & artificial respiratory system
First-aid box complete with first filling of required medicines, instruments and tools
Danger / Man on line / Break-Down boards of appropriate size
Rain coat, Gum boot and Safety Harness Belt with adequate straps
Moveable ladder of suitable capacity for 132kV GIS Hall
Description of Work / Item(s)
Amount
Construction of 132 kV GIS Switching Substation for RVNL at Ranihat (Srinagar).
Part-E (Erection of Materials)
400kVA 11/0.433KV three phase transformer including bushing, accessories and first filling of oil
145kV GIS Equipment
145kV, SF6 gas insulated Feeder Bay Module each comprising of SF6 gas insulated Circuit Breaker, Current Transformer, one bus-bar disconnector with grounding switch and one busbar disconnector without grounding switch, line disconnector with safety grounding switch, high speed fault making grounding switch, SF6 gas monitoring system for complete bay, LCC, GIS Duct, SF6/Air Bushing termination and accessories with GIS etc. to complete Feeder Bay Module.
145KV, 3Phase units, SF6 gas insulated, metal enclosed Bus Bars each enclosed in bus enclosures running along the length of the switchgear to interconnect each of circuit breaker bay module. Each bus bar set shall be complete with voltage transformer complete with safety grounding switch.
145KV, SF6 gas insulated Bus Coupler Bay Module comprising of SF6 gas insulated cirucit breaker, current transformer, two disconnectors with safety grounding switches, SF6 gas monitoring system for complete bay, LCC etc.
145kV AIS Equipment
145 KV CVT with Junction Box
145 KV lightning Arrester with counter and leakage meter
145 kV Post Insulator
145kV CT Single phase of ratio 200/100/1 A with 1 No Junction Box for set of 3 Nos CTs
Miscellaneous Materials (Insulators Strings/ Disc Insulator, Hardwares, Conductor, Bus Bar materials, Cable Tray, Clamps, Connector including equipments connectors and all accessories etc.
11kV AIS Equipments
11kV Indoor Switchgear panel (AIS Type) with VCB, CTs and PTs
Miscellaneous Materials (Hardwares, poles, Cable Trays, Clamps, Connector including equipments connectors and all accessories etc.) for station Transformers.
11kV 3 phase AB switch
11kV Outdoor LA
Complete Substation Automation System including hardware and software for the substation & remote control stations alongwith all necessary associated equipments as per Technical Specifications and Detailed Engineering.
Bay Control Units
132kV system
250kVA DG set with AMF panel
Online Monitoring, Data Acquisition and ABT Analysis System
ABT meters 0.2 Cl with TCP/IP, Optical Communication Port
Industrial Grade Network Switch -8 Port, unmanaged
UPS 2 KVA online with 30 Min back up on 100% load
DCU & Accessories
Workstation : Application & Database server
Database - Microsoft SQL Server Standard Edition
MS office - Standard Edition
MacAfee Virus Scan Enterprise Desktop Edition - Per Year
Local Energy Monitoring Software - Professional Edition
Lan cable ( average one roll per S/S 300 Meters)
PVC conduit Pipe - 3/4"
Enclosure for Lan Switch
3G/4G Data enable SIM
Integration of Station Metering System with Centralized Data System including all hardware and software required.
132kV Control and Relay panel
Circuit Breaker Control Panel with Auto Reclose
Circuit Breaker Control Panel without Auto Reclose
Line Protection Panel
132kV Bus Bar Protection Panel for Main-1 and Main-2 Bus
PLCC for 132kV Line feeder
Line Traps (132kV 0.5 mH/ 1.0 mH)
Coupling device
HF Cable
Carrier Equipment for (Speech + Protection)
Carrier Equipment for (Speech + Data)
Protection Coupler
Time synchronisation equipment
Air-conditioner and ventilation System
Split AC (Capacity-2T) with Cassettee type Indoor Unit, Max Star rating as per latest ammendments of BEE (ISEER)
Ventillation system for 132 kV GIS Hall
Miscellaneous items
Air Blinds/Curtain for Control Room Building
Interactive Smart Screen for Control Room Building 75inch LED Board Android
LT Switchboard
415V main switchboard
415V ACDB
110V DCDB
48V DCDB
Batteries
110V 500AH VRLA Type
48V 300AH VRLA Type
Battery charger
110V 100 Amps FCBC
48V 60 Amps FCBC
Fire Protection system
Fire Alarm system for 132kV GIS Hall,Control Room and Other rooms
45 Ltr. Foam Type
ABC type fire Extinguisher 10 Kgs
6 Fire Bucket with stand
Fire Hut and sand pit
CO2 type fire Extinguisher 20 Kgs
CO2 type fire Extinguisher 4.5Kgs
llumination sytem
LED Lights for Control Room / Store Room / Offices Ilumination with complete fittings
LED Lights for Switchyard Lighting with complete fittings, Junction Box & mounting accessories
Solar Light System for Street Light (LED Type Lights) with Pole and other mounting accessories
LED light for 132 kV GIS hall- High bay Type 170Watts
1.1kV Aromoured Power Cables (Al) and Aromoured Control Cables (Copper) alongwith multidiameter moulded cable sealing, Lugs, Glands and straight joints, etc.
AL Power cable (PVC)
3.5cx70Sq.mm
3.5cx35Sq.mm
4cx16 Sq.mm
4cx6 Sq.mm
Copper Control cable (PVC)
2Cx2.5Sq.mm
4Cx2.5Sq.mm
6Cx2.5Sq.mm
10Cx2.5Sq.mm
132kV XLPE Cable Al 630 Sq. mm
132kV Outdoor Termination Bushing
11kV Power cables Copper (XLPE) and Accessories
3X400 Sq.mm
11 kV Indoor Termination
11 kV Outdoor Termination
Grounding/Earthing system
40mm MS rod for earthmat
40mm MS 03 metre Electrodes
40mm 03 meter deep driven pipe electrode (treated pit)
GS Flats 50 x 6mm size
GS shield Wire
Steel Structure
Lattice structure (Main Structures, Auxiliary Equipments Structures & Lightning Mast Structure)
Pipe structure (Auxiliary Equipments Structure)
EOT Crane for 132kV GIS Hall
Description of Work / Item(s)
Amount
Construction of 132 kV GIS Switching Substation for RVNL at Ranihat (Srinagar).
Part-F (Civil)
Buildings
Construction of 132 KV GIS Control cum Relay Room and Cable Vault (Plinth area to be measured) Ground Floor (Minimum Ceiling height-4.50 M)
(i) Control cum Relay Room (Minimum Ceiling height-4.50 M)
(ii) Cable Vault (Minimum room height 2.40 M )
Construction of 132 KV GIS Hall and Cable Vault (Plinth area to be measured)
(i) 132 KV GIS Hall (Minimum Ceiling height-9.00 M)
(ii) Cable Vault (Minimum room height 2.40 M )
Construction of LT Switchgear, Electrical Room, Battery Room (Plinth area to be measured) Ground Floor (Minimum Ceiling height-4.50 M)
Construction of SCADA Room, Conference Room & Office (Plinth area to be measured) First Floor (Minimum Ceiling height-4.50 M)
Construction of store shed (Plinth area to be measured) (Minimum Ceiling height-4.20 M)
Security Guard Room (Minimum Ceiling Height- 2.90 M)
Construction of foundation of following structures including excavation and back filling of earth, CC/RCC works, reinforcement , supply & Fixing foundation bolts etc. complete.
145 KV Gantry Column Foundation
145 KV CVT Foundation
145 KV LA Foundation
145 KV BPI Foundation
Foundations for Bus Duct support structure.
Foundation for Lightening Mast
Plinth for 250KVA Transformer
Bushing foundations
RCC Cable trenches with trench covers (all Sections) including all type of crossing and all metallic work to support cables and trench covers.
600 mm size trench with minimum depth 600 mm
1050 mm size trench with minimum depth 600 mm
600 mm size trench with minimum depth 1000 mm
1050 mm size trench with minimum depth 1000 mm
Cement concrete roads including all type of crossings.
5.00 metre wide
3.80 metre wide
Security (Chain link) Fencing 3.6 m high along with Gate
Security (Chain link) Fencing 3.6 m high
Gate (5.0M wide)
Storm water drainage including culverts & chambers.
AC junction box for Switchyard lighting
Switch yard turfing and antiweed treatment including leveling and dressing of area, PCC and gravels
Land development including necessary cutting /filling and construction of all retaining walls for complete switch yard area maintaining required terraces levels, approach road, culverts.
Carriage of Earth by mechanical transport including loading, unloading and stacking up to 5.0 KM lead (DSR No. 1.1.2)
Filling with available fly ash and earth (excluding rock) in trenches or embankment in layers (each layer should not exceed 15 cm), with intermediate layer of compacted earth (soil density of 98%) after every four layers of compacted depth of fly ash, sides & top layer of filling shall be done with earth having total minimum compacted thickness 30 cm or as decided by Engineer-in-charge, including compacting each layer by rolling/ramming and watering, all complete as per drawing and direction of Engineer in charge. (D.S.R. No. 2.38)
Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead upto 50 m and lift upto 1.5 m, disposed earth to be levelled and neatly dressed.Ordinary rock (DSR No. 2.7.1)
Excavation work in foundation trenches or drains not exceeding 1.5 m in width or 10 sqm on plan including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soils as directed, within a lead of 50m. Ordinary rock (DSR No. 2.9.1)
Extra for every additional lift of 1.5 m or part thereof in. Ordinary or hard rock (DSR No. 2.26.2)
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level. 1:2:4 ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) (DSR No. 4.1.3)
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level. 1:4:8 ( 1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) (DSR No. 4.1.8)
Providing and laying in position specified grade of reinforced cement concrete excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level. 1:1.5:3 ( 1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size). (DSR No. 5.1.2)
Providing and laying in position specified grade of reinforced cement concrete excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level. 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size). (DSR No. 5.1.3)
Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up to floor five level excluding cost of centering, shuttering, finishing and reinforcement. 1:1.5:3 ( 1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size). (DSR No. 5.2.2)
Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15 degree landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral staircases up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement. 1:1.5:3 ( 1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) (DSR 5.3)
Centering and shuttering including strutting, propping etc. and removal of form for : Foundations, footing, bases of columns, etc. for mass concrete. (DSR No. 5.9.1)
Centering and shuttering including strutting, propping etc. and removal of form for : Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. (DSR No. 5.9.2)
Centering and shuttering including strutting, propping etc. and removal of form for : Suspended floors, roofs, landing, balconies and access platform(DSR 5.9.3)
Centering and shuttering including strutting, propping etc. and removal of form for : Columns, Pillars, Piers, Abutments, Posts and Struts. (DSR No. 5.9.6)
Centering and shuttering including strutting, propping etc. and removal of form for : Edges of slabs and breaks in floors and walls. Under 20 cm wide (DSR No. 5.9.16)
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. Cold twisted bars (DSR No. 5.22.3)
Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with : Cement mortar 1:6 (1 cement : 6 coarse sand) (DSR No. 7.1.1)
Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works (DSR No. 10.25.2)
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.(i) Single socketed pipes. 110 mm diameter (DSR No. 12.41.2)
Supplying and stacking at site. 90 mm to 45 mm size stone aggregate. (DSR No. 16.3.1)
Supplying and stacking at site. 63 mm to 45 mm size stone aggregate. (DSR No. 16.3.2)
Laying spreading and compacting stone aggregate of specified sizes to WBM specifications including spreading in uniform thickness, hand picking , rolling with 3 wheeled road / vibratory roller 8-10 tonne in stages to proper grade and camber, applying and brooming requisite type of screening / binding material to fill up interstices of coarse aggregate watering and compacting to the required density. (DSR No. 16.4)
Description of Work / Item(s)
Amount
Total Part-A (Supply ) from BoQ1 sheet WITHOUT GST
Total Part-B (Erection Work ) from BoQ2 WITHOUT GST
Total Part-C Civil Work from BoQ3 WITHOUT GST
Total Part-D (Supply ) from BoQ4 sheet WITHOUT GST
Total Part-E (Erection Work ) from BoQ5 sheet WITHOUT GST
Total Part-F Civil Work from BoQ6 sheet WITHOUT GST
Add GST* Amount on (Total of Part-A + Total of Part-B + Total part C+Total Part D+Total Part E+ Total Part F) above
Kanti Prasad Mittal (BID ID -344626)
Lumino Industries Limited (BID ID -336862)
Shyama Power India Limited (BID ID -344173)
Kanti Prasad Mittal (BID ID -344626)
Kanti Prasad Mittal (BID ID -344626)
Shyama Power India Limited (BID ID -344173)
Kanti Prasad Mittal (BID ID -344626)
Lumino Industries Limited (BID ID -336862)
Shyama Power India Limited (BID ID -344173)
Kanti Prasad Mittal (BID ID -344626)
Kanti Prasad Mittal (BID ID -344626)
Shyama Power India Limited (BID ID -344173)
Kanti Prasad Mittal (BID ID -344626)
Lumino Industries Limited (BID ID -336862)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid