Loading…
Loading…
Tender Value
₹1.2 Cr
EMD Value
₹2.1 L
Closing Date
18 Dec 2025, 3:00 pmClosed
Electrical General work in connection with "Construction of 4 Lane Road Over Bridge at Level Crossing No. NN-1 (Manned) at Km 2/2-3 in between NJP-ABFC."
RT-EL_GS_23_25-26~NFR
RT-EL_GS_23_25-26
Open
Works - General
6 Months
Katihar, Bihar
₹0
₹2.1 L
18 Dec 2025
25 Nov 2025
4 Dec 2025
A- Electrical General work in connection with "Construction of 4
Level Crossing No. NN-1 (Manned) at Km 2/2-3 in between NJP-ABFC."
Item- 1 Pls see in item breakup
S No. Item Description of Item Unit Qty Rate Amount
1 1 "Supply & testing of GI octagonal pole 6 mt Numbers 70.00 12942.00 905940.00
long with foundation bolt, loop box of bakelite
sheet with one 6A SP MCB and 16 sq mm stud
type connector etc. The octagonal pole shall be
hot dip galvanized in single dip. Technical
specification of pole as following:- Height - 6 mt
Top dia (A/F) - 70 mm Bottom dia (A/F) - 130
mm Sheet thickness - 3 mm Base plate (L x B x
T) - (200 x 200 x 12) mm Foundation Bolt size
(no.x dia) - 4 x 20 dia mm Pitch Circle Dia
(PCD) - 200 mm Bolt length - 600 mm
Projected Bolt Length - 100 mm . "
KATIHAR DIVISION-ELECTRICAL/N F RLY
2 2 "Supply of 9 Mtr Hot Dip Galvanized Street Numbers 130.00 19999.00 2599870.00
Light Octagonal Pole with Foundation Type
Base Plate & Foundation Bolts, loop box of
bakelite sheet with one 6A SP MCB and 16 sq
mm stud type connector etc(Dimensions for
pole as Top Diameter 70 mm, Bottom Diameter
155 mm, Section Length- 9000 mm, Thickness-
3 mm, Foundation Type Base Plate
(250X250X16 mm), Foundation Bolts (M24 X
700/750 MM 4Nos) Pitch Circle Dia (PCD) - 250
m m Bolt length - 700 mm Projected Bolt
Length - 100 mm . "
3 3 Supply & fixing of 1 mtr GI Single arm bracket Numbers 200.00 1487.00 297400.00
(header) and holder with Nut & bolt
4 4 Erection of Street light pole (Octagonal pole) Numbers 200.00 1432.00 286400.00
with CC foundation including digging & refilling
of earth to a suitable height above ground level
in ratio 1:3:6 by cement sand & Chips 19 mm
& down including excavation of earth including
fixing of SA/DA bracket etc.
5 5 Supply, installation, testing & commissioning of Numbers 210.00 11000.00 2310000.00
100 watt LED street light luminaire with heat
resistant glass with connecting lead (IP
protection- IP 66 class-I, System efficacy 105
lm/w, Housing- Pressure die cast aluminium
powder coated, THD<10%, p.f.>0.95, Surge
protection- 5 kV) as per instruction of Engineer
incharge at site.
6 6 Supply, fixing, testing & commissioning of IP 54 Numbers 200.00 5005.00 1001000.00
and above thermoplastic cable junction box /
loop box of size (210 x 310 x 116) mm with
knockouts & 04 nos terminals
7 7 Supply, laying, commissioning & testing of Metre 4000.00 351.00 1404000.00
HDPE pipe 110 mm dia PN-6 grade to be laid
partly along the pole /underground with
suitable fixing arrangement by MS clamp made
of MS flat of size 50x6 mm and suitable size
nut , bolt, washer and required bend, joints.
8 8 Supply, erection, testing ,commissioning & Set 4.00 12947.00 51788.00
painting of Wall/floor mounted powder coated
cubicle panel board (Modular look), outdoor
type with double door made of suitable size
MS/GI angle 50 x 50 x 6 mm, MS/GI flat 50 x 6
mm, 14 SWG MS sheet/Powder coated CRCA
sheet with provision of weather proof, rust
proof, dust proof, water proof having internal
rubber gasket and connection by suitable size
9 9 Copper bus bar 100 amps made of electrolytic Set 8.00 821.00 6568.00
grade copper consisting of 4 bars ( 3 Ph and
Neutral ) ( Bus bar should have insulation
11 11 Supply, installation and testing of Astro Set 8.00 9003.00 72024.00
(Analog) time switch with 3 pole 63 amp
contractor and suitable thermoplastic box and
fitted on mounting plate/DIN rail.
Conforms to IS/IEC 60898 - 1:2002 (For
light/Fan/6 Amp Plug point circuit) (6-10 Amp-
14 14 Cutting of Road/ Pucca/ hard soil below (0.3 X Metre 1000.00 274.00 274000.00
1) mt from ground level and make it good as
original with supply & execution of CC work
(1:3:6) as per instruction of Engineer in charge
KATIHAR DIVISION-ELECTRICAL/N F RLY
15 15 Supply , erection, testing & commissioning of Set 3.00 675000.00 2025000.00
16 mt long High Mast Tower with 8 nos. x 250
watt LED luminaries in symmetrical
arrangement complete with all accessories
(Double drum winch, SS wire rope, integral
power tool motor, head frame, junction box,
foundation bolt, LED aviation light, Fedder
pillar with single dial timer & raising lowering
mechanism etc.) including shallow foundation
with M20 grade concrete etc. as per instruction
of Engineer Incharge at Site.
16 16 Supply, installation, testing & commissioning of Numbers 20.00 7842.00 156840.00
120 watt LED flood light luminaires complete
with pressure die cast aluminium housing, IP
65, Luminous efficacy 100 lm/watt with heat
sink feature, surge protection etc including
wire connection as per instruction of Engineer
incharge at site.
17 17 Supply & erection of earth by 80 mm dia 3 Mtr. Numbers 30.00 2572.00 77160.00
Long (medium) GI earth electrode, 8 SWG GI
wire, GI nuts, bolts including masonry materials
for earthing pit, salt, charcoal etc and
construction of earth pit covered with cement
concrete plate having locking arrangement and
watering pipe as per drg. No.- CEE/STD/1.
18 18 Supply, erection & commissioning of earth Numbers 60.00 314.00 18840.00
spike made of 16 mm dia 1.8 mt long GI rod &
connection metal body with the earth spike rod
by 6 SWG GI earth wire with nut, bolt & washer
19 19 Supply , & fixing o f GI earth bar by MS clamp Metre 4500.00 64.00 288000.00
made of MS flat of size 50x6 mm and suitable
size nut , bolt, washer etc as per instruction of
Engineer Incharge at site.
20 20 Supply, installation, testing & commissioning of Set 1.00 4651.00 4651.00
outdoor type weather proof shaded feeder
pillar box of suitable size made of powder
coated 14 SWG MS/CRCA sheet, angle, flat etc.
The feeder pillar box four legs should be
grouted on CC foundation (1:3:6). Cable entry
should have PVC glands. Feeder pillar box
should have double door system with locking
arrangement with fixing of rubber gasket for
protection of entry of dust and water along
with supply and fixing of following MCCB as per
instruction of Engineer In charge at site.
22 22 Copper bus bar 100 amps made of electrolytic Set 1.00 821.00 821.00
grade copper consisting of 4 bars ( 3 Ph and
Neutral ) ( Bus bar should have insulation
24 24 Supply, Fixing & Testing of LED multifunction Set 1.00 9641.00 9641.00
meter, Accuracy Class 1.0, Input voltage
measurement range 50-550 VAC (P-P), Aux
supply 90-300VAC/DC for measuring of V, A, F,
PF, kW, kVA, kVAR, kWh, kVAh, kVARh,
Runhours, On hours, Interrupts, THD, neutral
current etc. parameters along with supply &
fixing of 3 nos. suitable CTc.
KATIHAR DIVISION-ELECTRICAL/N F RLY
25 25 Supply, installation, testing & commissioning of Set 4.00 4651.00 18604.00
oudoor type weather proof sheded feeder pillar
box of suitable size made of powder coated 14
SWG MS/CRCA sheet, angle, flat etc. The
feeder pillar box four legs should be grounted
on CC foundation (1:3:6). Cable entry should
have PVC glands. Feeder pillar box should have
double door system with locking arrangement
with fixing of rubber gasket for protection of
entry of dust and water alongwith supply and
fixing of following MCCB as per instruction of
Engineer Incharge at site.
27 27 Copper bus bar 100 amps made of electrolytic Set 4.00 821.00 3284.00
grade copper consisting of 4 bars ( 3 Ph and
Neutral ) ( Bus bar should have insulation
28 28 "Supply of swaged type GI tubular pole 11 mt Numbers 6.00 23538.00 141228.00
long conforms to IS - 2713/1980 with following
technical specification and complete with base
plate and cap: - a) Length of section : - Bottom
- 5.60 mt, Middle - 2.70 mt, Top - 2.70 mt b)
Outside diameter and thickness of section : -
Bottom - 165.1 x 4.85 mm, Middle - 139.7 x
29 29 Supply of "Base plate and GI cap" for above Numbers 6.00 1707.00 10242.00
tubular pole as per instruction of Engineer
incharge at site.
30 30 Erection of rail/tubular pole to 1/5 th of its Numbers 6.00 1576.00 9456.00
height with CC foundation from base block (30
cm x 30 cm x 15 cm) including digging &
refilling of earth to a height of 30 cm above
ground level as per drawing
no.CEE/OH@47'40@FGA) in ratio 1:3:6 by
cement sand & Chips 19 mm & down including
excavation of earth (Rail pole will be supplied
31 31 Supply & fixing of MS channel bracket (75 x 40 Metre 100.00 295.00 29500.00
x 40 x 6) mm to be clamped with the pole by
clamp made of 50x5 mm MS flat and 50x 16
mm MS nut,bolt & washer including drilling of
32 32 Supply & fixing of MS angle bracket (50 x 50 x Metre 100.00 251.00 25100.00
6) mm to be clamped with the pole by clamp
made of 50x5 mm MS flat and 50x 16 mm MS
33 33 Supply & erection of FRP fencing of S/stn Square 300.00 462.00 138600.00
(Approx fencing size- 20 Ft x 20 Ft) with Foot
corrosion resistant, acid proof, fire retardant,
non-magnetic, high quality fiber glass FRP with
gate and locking arrangement.
34 34 Supply , laying , commissioning & testing of CI Metre 50.00 1469.00 73450.00
Pipe 200 mm dia Class LA type (IS 1536-2001)
to be laid partly along the pole and partly
through ground under railway track/road in
cable trench for protection of cable with
suitable fixing arrangement by MS clamp,
nut,bolt,washer etc.as per instruction of
Engineer incharge at site.
35 35 Horizontal machine boring of 300 mm dia hole Metre 40.00 2323.00 92920.00
across track/Road/High drain etc. at a depth of
1.0 mtr below of ground level with suitable
boring instruments & neessary arrangement
and as per technical procedure.
36 36 Dismantling of existing poles, light fitting and Job 1.00 31344.00 31344.00
other electrical accessories and deposit the
same to power house store
KATIHAR DIVISION-ELECTRICAL/N F RLY
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .