Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹24.6 L
EMD Value
₹50,000
Closing Date
8 Dec 2026, 5:00 pm
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Assistant Executive Engineer
Office of the Assistant Executive Engineer, Substation Subdivision, Aluva
constructing 2 nos of aditional bays in 110 kV substation, kizhakkambalam - Electrical works
2026_KSEB_890849_1
SSDA/etender05/26-27/20.11.26
Open Tender
Electrical Works
Percentage
180 days
110 kV Substation, Kizhakkambalam
Please refer Tender documents.
4 documents required · 4 mandatory
₹5,900
₹50,000
21 Nov 2026
21 Nov 2026
11 Dec 2026
21 Nov 2026
8 Dec 2026
23 Nov 2026
180 days
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1.01 | Welding the ground electrode with the main electrode , after cleaning the surface neatly. Charges includes cost of low hydrogen content DC electrodes (No. E7018), hire charges of DC arc welding set, tools and plants, current charges, labour charges for holding MS rod in position and applying two coats of anti corrosive paints at the welded joints etc. complete as per the directions of departmental officers. (cost index(e) : 1.3132 included in Rate) | 30 | E | 429.58 | ₹12,887.29 |
| 1.02 | Welding one end of the bended GI strip of size 50x6mm with the riser of the already laid earth mat, welding 150mm in length, 6mm thick on both sides & end of the strip & other end of the strip with yard structure at 2 points 50mm apart each welding points having 50mm length and 6mm thick on both sides & end of the strip including the charges for connecting the strip with structure using bolted joints as per the directions of the department officers. Charges includes hire charges of DC arc welding set, current charges, cost of low hydrogen content DC arc welding electrodes(No.E7018) cost of anti corrosive paint etc. complete. (cost index(e) : 1.3132 included in Rate) | 130 | E | 595.52 | ₹77,417.61 |
| 1.03 | Welding overlapping joints of 50x6mm GI strip with 50mm long, 6mm thick welding on all three sides after doing 2 Nos. bolted joints at the centre as specified after cleaning the surface. Charges includes hire charges of DC arc welding set, current charges, cost of low hydrogen content DC arc welding electrodes( No.E7018) cost of anti corrosive paint etc. complete. (cost index(e) :1.3132 included in Rate) | 25 | E | 311.52 | ₹7,787.93 |
| 1.04 | Preparing wiring schedule per transformer / feeder bay of 110 or 66 kV with details of type of cable core and colour ferrule No and terminal no of equipments/panels including giving full details in A4 sheet with computer print providing outer border line and sheet no etc. and supplying in the shape of book with special binding etc. and assisting the departmental officers at the time of relay testing and commissioning (cost index(e) : 1.3132 included in Rate) | 1 | E | 9,189.98 | ₹9,189.98 |
| 1.05 | Additional copy of the wiring schedule with spiral binding (cost index(e) : 1.3132 included in Rate) | 1 | E | 230 | ₹230 |
| 1.06 | Uncoiling 20/19 core 2.5sqmm, 12 core 4 sqmm control cable (Armoured or unarmoured) from cable drums cutting to required length and laying through trench/pipe/cable tray grouping the same neatly using cable tie and carefully including for providing loop wherever necessary and providing cable marker at both ends of cable as per direction of departmental staff at site. (cost index(e) : 1.3132 included in Rate) | 1,000 | m | 59.27 | ₹59,269.6 |
| 1.07 | Uncoiling 12/7/6 core 2.5 sq mm control cable (armoured and unarmoured) from cable drums and cutting to required length and laying through trench/pipe/cable tray grouping the same neatly using cable tie and carefully including for providing loops wherever necessary and cable marker, at both ends of cable as per direction of departmental staff at site.
(cost index(e) : 1.3132 included in Rate) | 1,000 | m | 44.5 | ₹44,504.3 |
| 1.08 | Uncoiling 5/4/3/2 core 4sqmm control cable(armoured or unarmoured) from cable drums and laying through trench/pipe/cable tray neatly and carefully including for providing loops wherever necessary and cable marker at both ends of cable as per direction of departmental staff at site. (cost index(e) : 1.3132 included in Rate) | 500 | m | 41.49 | ₹20,743.7 |
| 1.09 | Uncoiling 4/2 core 2.5sqmm control cable (armored or unarmored) from cable drums and cutting to required length and laying through trench/pipe/cable tray neatly and carefully including for providing loops wherever necessary and cable marker at both ends of cable as per direction of departmental
staff at site. (cost index(e) :
1.3132 included in Rate) | 1,000 | m | 43.24 | ₹43,243.7 |
| 1.1 | Termination of cables in panel by using cable glands of fixing the cable rigidly by any means as per direction of departmental staff at site charges include for providing necessary suitable hole in the gland plate etc. for 20/19 core
2.5sqmm cable/12 core 4 sqmm cable (using gland of size 28-32mm) (cost index(e) : 1.3132 included in Rate) | 30 | E | 279.74 | ₹8,392.12 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.41 MB
generalconditions.pdf
Tender Documents • 0.96 MB
tenderspecifications.pdf
Tender Documents • 0.64 MB
BOQ_1523567.xls
BOQ • 0.30 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .