Loading…
Loading…
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹132.6 Cr
EMD Value
₹1.3 Cr
Closing Date
2 Nov 2026, 6:00 pm
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Superintending Engineer, Project Implementation Unit, Health & Family Welfare Department.
Construction of Staff Quarters Class (1 to 3 ) at New Civil Hospital Campus, Surat
354452
2026-27/99/01
Open
Civil Works - Buildings
Works
Surat
1 document required · 1 mandatory
₹30,000
PIU-General Fund A/c 11-114
₹1.3 Cr
12 Oct 2026
12 Oct 2026
12 Oct 2026
2 Nov 2026
12 Oct 2026
Name of Work :- Construction of Staff Quarters Class (1 to 3 ) At New Civil Hospital Campus,Surat.
Memorandum showing items of works to be carried out
Quantities (Sor 2024-25 & Ele Sor 2026-27) Total Amount
Quantities (Sor 2024-25 & Ele Sor 2026-27) Total Amount
Item Estimated According to
Item of Works Unit
No. But may Be In Figures Estimated Quantites
More Or Less In Words Rs.Ps.
1 3.47 Clearing and grubbing road including uprooting rank vegetation grass bushes, shrubs , sapling and trees girth upto 300mm 34889.38 Rupees Thirty Four Thousand Eight Hectare
removal stumps of trees cut earlier and disposal of unserviceable (D) By mechanical means in area of thorny jungle. Hundred Eighty Nine And Paise
Thirty Eight Only
2 12078.00 Excavation for foundation upto 1.5 m depth including sorting out and stacking of useful materials and disposing off the 212.52 Rupees Two Hundred Twelve And cum
excavated stuff upto any lead and lift..(A)Loose or soft soil Paise Fifty Two Only
3 8634.00 Excavation for foundation for depth from 1.5 m to 3.0 m including sorting out and stacking of useful materials and disposing 295.10 Rupees Two Hundred Ninety Five cum
off the excavated stuff up to any lead and lift (B) Dense or Hard soil And Paise Ten Only
4 4143.00 Excavation for foundation for depth from 3.0 m to 5.0 m including sorting out and stacking of useful materialsand disposing 317.62 Rupees Three Hundred Seventeen cum
off the excavated stuff upto any lead and lift.(B) Dense or Hard soil And Paise Sixty Two Only
5 12078.00 Filling available excavated earth (Excluding rock) in trenches,plinth, sides, of foundation etc. in layer not exceeding 20 cm. in 136.92 Rupees One Hundred Thirty Six cum
depth consolidating each deposited layer by ramming and watering. And Paise Ninety Two Only
6 594.30 Filling in plinth with (good quality) sand under floors including watering, ramming, consolidating and dressing etc. complete. 481.80 Rupees Four Hundred Eighty One cum
And Paise Eighty Only
7 12094.00 Filling in foundation and plinth with murrum or selected soil in layers of 20cm. thickness including watering, ramming and 301.78 Rupees Three Hundred One And cum
consolidating etc. complete. Paise Seventy Eight Only
8 5984.00 Carring out plinth treatment to post construction / during construction by spraying chemical solution for termite control 87.03 Rupees Eighty Seven And Paise sqm
treatment including labour and material consistment with I.S.I specification. Using Chlordene and Chiorpurfiles 20 EC. As Per Three Only
6131_paret-II Consentration Weight one percent is recommended i.e one litre 20EC chemical emulsion with 19 liter give 1%
concrentration inclusive of one litre chemical emulsion appication at the rate of 5Litre chemical / Sqm of surface is
recommended as per I.S.
9 2125.00 Providing and laying cement concrete 1:2:4 (1- Cement : 2- Coarse sand : 4- graded stone aggregates 20 mm nominal size) and 3741.69 Rupees Three Thousand Seven cum
curing complete Including cost of formwork in (A) Foundation and Plinth Hundred Forty One And Paise Sixty
10 14340.00 Providing throating or plaster drip / Groove and moulding to R.C.C. Chhajja. 43.74 Rupees Forty Three And Paise rmt
Seventy Four Only
11 3534099.00 Providing TMT Bar FE 550D Reinforcement for R.C.C. work including bending, binding and placing in position complete for 101.29 Rupees One Hundred One And kg
all Floor Level Paise Twenty Nine Only
12 5135.22 Providing and laying in position Ready Mixed M-300 grade concrete for reinforced cement conctere work , using cement 4891.96 Rupees Four Thousand Eight cum
content as per approved Design Mix manufactured in fully automatic batching plant and transported to site of work in transit Hundred Ninety One And Paise
mixer with all lead having continuous agitated mixer, manufactured as per mix design of specified grade for reinforced cement Ninety Six Only
concrete work including pumping of R.M.C. from transit mixer to site of laying, including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in recommended proportions as per IS: 9103 to accelerate/
retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer - in -
charge. Without Fly Ash (Min cement level as per latest IS 456 shall be maintained) (Cement level 410 kg ) for Footing/Raft
13 227.40 Providing and laying in position Ready Mixed M-300 grade concrete for reinforced cement conctere work , using cement 6576.01 Rupees Six Thousand Five Hundred cum
content as per approved Design Mix manufactured in fully automatic batching plant and transported to site of work in transit Seventy Six And Paise One Only
mixer for with all lead having continuous agitated mixer, manufactured as per mix design of specified grade for reinforced
cement concrete work including pumping of R.M.C. from transit mixer to site of laying, including the cost of centering
shuttering finishing and excluding reinforcement including cost of admixtures in recommended proportions as per IS: 9103 to
accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the
Engineer - in - charge. Without Fly Ash (Min cement level as per latest IS 456 shall be maintained) (Cement level 410kg ) for
Columns up plinth level .
14 3382.80 Providing and laying in position Ready Mixed M-250 grade concrete for reinforced cement conctere work including all lift & 6357.58 Rupees Six Thousand Three cum
lead , using cement content as per approved Design Mix manufactured in fully automatic batching plant and transported to site Hundred Fifty Seven And Paise
of work in transit mixer for with all lead having continuous agitated mixer, manufactured as per mix design of specified grade Fifty Eight Only
for reinforced cement concrete work including pumping of R.M.C. from transit mixer to site of laying, including the cost of
centering shuttering finishing and excluding reinforcement including cost of admixtures in recommended proportions as per
IS: 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per
direction of the Engineer - in - charge. Without Fly Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 380 kg ) Columns for above plinth level for all Floor
15 94.33 Providing and laying in position Ready Mixed M-300 grade concrete for reinforced cement conctere work , using cement 5527.95 Rupees Five Thousand Five cum
content as per approved Design Mix manufactured in fully automatic batching plant and transported to site of work in transit Hundred Twenty Seven And Paise
mixer forwith all lead up having continuous agitated mixer, manufactured as per mix design of specified grade for reinforced Ninety Five Only
cement concrete work including pumping of R.M.C. from transit mixer to site of laying, including the cost of centering
shuttering finishing and excluding reinforcement including cost of admixtures in recommended proportions as per IS: 9103 to
accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the
Engineer - in - charge. Without Fly Ash (Min cement level as per latest IS 456 shall be maintained) (Cement level 410 kg ) for
Vertical surface -up to plinth level
16 1919.88 Providing and laying in position Ready Mixed M-250 grade concrete for reinforced cement conctere work , including all lift & 5309.52 Rupees Five Thousand Three cum
lead using cement content as per approved Design Mix manufactured in fully automatic batching plant and transported to site Hundred Nine And Paise Fifty Two
of work in transit mixer for with all lead having continuous agitated mixer, manufactured as per mix design of specified grade Only
for reinforced cement concrete work including pumping of R.M.C. from transit mixer to site of laying, including the cost of
centering shuttering finishing and excluding reinforcement including cost of admixtures in recommended proportions as per
IS: 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per
direction of the Engineer - in - charge. Without Fly Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 380 kg ) for Vertical surface above plinth level up for all floor level.
17 774.56 Providing and laying in position Ready Mixed M-300 grade concrete for reinforced cement conctere work , using cement 6250.71 Rupees Six Thousand Two cum
content as per approved Design Mix manufactured in fully automatic batching plant and transported to site of work in transit Hundred Fifty And Paise Seventy
mixer for a lead up to 10 kms having continuous agitated mixer, manufactured as per mix design of specified grade for One Only
reinforced cement concrete work including pumping of R.M.C. from transit mixer to site of laying, including the cost of
centering shuttering finishing and excluding reinforcement including cost of admixtures in recommended proportions as per
IS: 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per
direction of the Engineer - in - charge. Without Fly Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 410kg ) for Beam upto plinth level (Plinth Beam)
18 5243.48 Providing and laying in position Ready Mixed M-250 grade concrete for reinforced cement conctere work , including all lift & 6561.59 Rupees Six Thousand Five Hundred cum
lead using cement content as per approved Design Mix manufactured in fully automatic batching plant and transported to site Sixty One And Paise Fifty Nine
of work in transit mixer for with all lead up having continuous agitated mixer, manufactured as per mix design of specified Only
grade for reinforced cement concrete work including pumping of R.M.C. from transit mixer to site of laying, including the cost
of centering shuttering finishing and excluding reinforcement including cost of admixtures in recommended proportions as per
IS: 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per
direction of the Engineer - in - charge. Without Fly Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 380 kg ) For Slab Beam up to all flor level.
19 7489.17 Providing and laying in position Ready Mixed M-250 grade concrete for reinforced cement conctere work , including all lift & 6551.86 Rupees Six Thousand Five Hundred cum
lead using cement content as per approved Design Mix manufactured in fully automatic batching plant and transported to site Fifty One And Paise Eighty Six
of work in transit mixer for with all lead having continuous agitated mixer, manufactured as per mix design of specified grade Only
for reinforced cement concrete work including pumping of R.M.C. from transit mixer to site of laying, including the cost of
centering shuttering finishing and excluding reinforcement including cost of admixtures in recommended proportions as per
IS: 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per
direction of the Engineer - in - charge. Without Fly Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 380 kg ) slab above plinth level for up to all floor level.
20 518.05 Providing and laying in position Ready Mixed M-250 grade concrete for reinforced cement conctere work , including all lift & 6913.74 Rupees Six Thousand Nine cum
lead using cement content as per approved Design Mix manufactured in fully automatic batching plant and transported to site Hundred Thirteen And Paise
of work in transit mixer for with all lead having continuous agitated mixer, manufactured as per mix design of specified grade Seventy Four Only
for reinforced cement concrete work including pumping of R.M.C. from transit mixer to site of laying, including the cost of
centering shuttering finishing and excluding reinforcement including cost of admixtures in recommended proportions as per
IS: 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per
direction of the Engineer - in - charge. Without Fly Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 380 kg ) Lintel & Rcc Bend for all floor level.
21 104.87 Providing and laying in position Ready Mixed M-250 grade concrete for reinforced cement conctere work , including all lift & 6408.79 Rupees Six Thousand Four cum
lead using cement content as per approved Design Mix manufactured in fully automatic batching plant and transported to site Hundred Eight And Paise Seventy
of work in transit mixer for with all lead having continuous agitated mixer, manufactured as per mix design of specified grade Nine Only
for reinforced cement concrete work including pumping of R.M.C. from transit mixer to site of laying, including the cost of
centering shuttering finishing and excluding reinforcement including cost of admixtures in recommended proportions as per
IS: 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per
direction of the Engineer - in - charge. Without Fly Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 380kg) Chhajjas for all floor level.
22 540.54 Providing and laying in position Ready Mix M-250 grade concrete for reinforced cement concrete work, including all lift & 6151.50 Rupees Six Thousand One Hundred cum
lead using cement content as per approved design Mix manufactured in fully automatic batching plant and transported to site Fifty One And Paise Fifty Only
of work in transit mixer for with all lead up having continous agitated mixer, manufactured as per mix design of specified
grade for reinforced cement concrete work including grade for reinforced cement concrete work including pumping of R.M.C.
from transit mixer to site of laying and the cost of centering shuttering finishing and excluding reinforcement iincluding
providing and mixing admixture in recommanded proportions as per IS : 9103 to accelerate/ retard setting of concrete,
improve workability without impairing strength and durability as per direction of the Engineer In Charge , Without Fly Ash
(Cement level 380 Kg.) Stair Case up to all floor level.
23 16580.10 Extra for additional lift of concrete for all R.C.C. work above floor two level excluding cost of reinforcment for all Floor level 245.73 Rupees Two Hundred Forty Five cum
And Paise Seventy Three Only
24 274.00 Brick work using common burnt clay building bricks having crushing strength not less than 35 kg./Sq.Cm. in foundation and 4245.09 Rupees Four Thousand Two cum
plinth in Cement Mortar 1:5 (1- Cement : 5 -fine sand)(B) Conventional Hundred Forty Five And Paise Nine
25 10485.00 Masonary work using Aerated light weight concrete block having crushing strength not less than 35 kg/sqcm for super 4867.08 Rupees Four Thousand Eight cum
structure above plinth level in cement mortar 1:5 ( 1 cement : 5 fine sand ) complete as per Technical Specification for all floor Hundred Sixty Seven And Paise
As per inctruction of in chrge. Eight Only
26 1644.00 Provinding and fixing chicken wire mesh of gauge 0.18mm and 200 mm wide with necessary screws and nail at joints cracks 192.40 Rupees One Hundred Ninety Two sqm
of brick work R.C.C work as per drawing and specification and direction of Engineer incharge. And Paise Forty Only
27 1396.00 Providing and fixing 18mm thick gang saw cut mirror polished premoulded and prepolished) for wall lining (veneer work), 4235.68 Rupees Four Thousand Two sqm
backing filled with a grout of average 12 mm thick in cement mortar 1:3 (1 cement : 3 coarse sand) including pointing with Hundred Thirty Five And Paise
white cement mortar 1:2 (1 white cement : 2 marble dust) with an admixture of pigment to match the marble shade: The rate Sixty Eight Only
shall include the cost of copper pin, cramps, dash fastners etc complete.Granite of any colour and shade and any size of stone
slab..(Red Lakha)
28 6840.00 Providing and laying 18 mm to 20 mm thick polished granite stone,telephonic Z black machine cut in single piece (maximum 3109.79 Rupees Three Thousand One sqm
available size), in sill and jambs of door, window and ventilation frames, laid over 10 mm thick cement mortar in proportion Hundred Nine And Paise Seventy
1:3 (1 cement:3 coarse sand) with Cement base Adhesives, jointed with grey cement slurry with matching pigment, including Nine Only
rubbing, polishing, and providing a 3 mm × 3 mm chamfer or Round Edge to all exposed edges, complete in all respects, with
colour and shade as approved by the Architect/Engineer-in-Charge, at all floor levels.
29 2082.00 Constructing Sandwitch Platform of 18-20 mm thick Polished telephonic Z Black Granite at top and 25 mm thick Kota 3748.11 Rupees Three Thousand Seven sqm
stone slab one side polished at bottom with cementing Materials / adhsives including makeing necessary grooves in Hundred Forty Eight And Paise
walls with Vertical sandwich two Kotastone 25 mm support every 60 cm centre to centre or as required including all labour Eleven Only
material of approved quality incl. full moulded round front edge granite strip of one side polished and jointed with grey
cement slurry including rubbing and polishing etc. including providing cutting for fixing kitchen/Laoratory sink (as directed)
600 mm x 450 mm x 200 mm size stainless steel sink / viterious china sink(as directed by engineer incharge) at required
position etc complete
30 4664.00 Flush Door (Laminated ) Providing and fixing of 35mm solid cored flush door with 1mm thick both side laminate in 5748.26 Rupees Five Thousand Seven sqm
approved shade as per selection on both side as shown in the drg. All exposed edges covered with Batten lipping of matching Hundred Forty Eight And Paise
shade of laminate . Rate shall Include Frame of Indian teak wood as per architect drawing ,SS Handle, Lock , Door Stopper, Twenty Six Only
S.S. heavy duty hinges etc. all materials and labour etc. complete as per detail drawing and instruction of engineer‐in charge
and consultant.
31 4378.00 Providing and fixing factory made single extruded WPC (Wood Polymer Composite) solid door/window/Ceosetory windows 803.13 Rupees Eight Hundred Three And mtr
& other Frames/Chowkhat comprising of virgin PVC polymer of K value 58- 60 (Suspension Grade), calcium carbonate and Paise Thirteen Only
natural fibers (wood powder/ rice husk/wheat husk) and non toxic additives (maximum toxicity index of 12 for 100 gms)
fabricated with miter joints after applying PVC solvent cement and screwed with full body threaded star headed SS screws
having minimum frame density of 750 kg/ cum, screw withdrawal strength of 2200 N (Face) & 1100 N (Edge), minimum
compressive strength of 58 N/mm2, modulus of elasticity 900 N/mm2 and resistance to spread of flame of Class A category
with property of being termite/borer proof, water/moisture proof and fire retardant and fixed in position with M.S hold
fast/lugs/SS dash fasteners of required dia and length complete as per direction of Engineer-In- Charge. including M.S hold
fast/lugs or SS dash fasteners For WPC solid door/window frames, minus 5mm tolerance in dimensions i.e depth and width of
profile shall be acceptable. Variation in profile dimensions on plus side shall be acceptable but no extra payment on this
account shall be made.Frame size 50 x 100 mm
32 1614.00 Providing and fixing factory made single extruded WPC (Wood Polymer Composite) solid plain flush door shutter of required 4250.29 Rupees Four Thousand Two sqm
size comprising of virgin polymer of K value 58-60 (Suspension Grade), calcium carbonate and natural fibers (wood powder/ Hundred Fifty And Paise Twenty
rice husk/wheat husk) and non toxic additives (maximum toxicity index of 12 for 100 gms) having minimum density of 650 Nine Only
kg/cum and screw withdrawal
strength of 1800 N (Face) & 900 N (Edge), minimum compressive strength 50 N/mm2, modulus of elasticity 850 N/mm2 and
resistance to spread of flame of Class A category with property of being termite/ borer proof, water/moisture proof and fire
retardant and fixing with stainless steel butt hinges of required size including all fixtures and fastners and accessories with
necessary full body threaded star headed counter sunk S.S screws, all as per direction of Engineer-In- Charge.
33 766.00 3648.12 Rupees Three Thousand Six sqm
Provoding and fixing Decorative flush door shutters, solid core construction with frame of first class hardwood withcross Hundred Forty Eight And Paise
board and face veneer or plywood face panels,both side laminated(1.00mm thick) including S.S fixtures and fastners like Twelve Only
Handle, Lock , Door Stopper, Door Closer, S.S. heavy duty hinges necessary screws with all fitting & fixtures including (0.3
Sqm opening with Covering of s.s jali) all materials and labour etc. complete as per detail drawing and instruction of
engineer‐in charge and consultant/Architect. 35 mm thick.
34 45822.00 Providing and fixing M.S. grill of required pattern of windows etc. with M.S.. flats at required spacing and frame alround 115.77 Rupees One Hundred Fifteen And kg
square or round headed bolts and nuts or by screws.including applying a priming coat of red lead paint and two coats of oil Paise Seventy Seven Only
painting etc complete (A) Plain grill including Oil paint
35 401.00 Fire Rated DOOR 9267.61 Rupees Nine Thousand Two sqm
Supply of Single/Double Leaf galvanized steel fire rated doors as per IS 3614 : 2021 for 120min fire rating insulated door Hundred Sixty Seven And Paise
tested from NABL/Govt approved Lab. Door frames to be Single rebate profile of minimum section 100 x 57mm Sixty One Only
manufactured from minimum 18 gauge galvanized steel sheet, profile to have bending radius of 1.4 mm supplied in assembled
form ready to install at site. door shutter in 46mm +2 mm thick manufactured from minimum 18 gauge galvanized steel sheets,
lock seam jointed at stile edges to form a double skin fully flush shell. Infilled fire insulation ( mineralwool) material to be
provided for structural rigidity & additional reinforcements & sound Insulation. The internal construction of the door should
be appropriate for all hardware fixtures as required, vision panel grooves wherever applicable shall be provided as per
recommendations with beading and screw. The frame shall be infill with Mineralwool of density 96 Kg/ m3 MAKE Pacific
Fire door/Navair/Shakti Harmonn
36 37.00 Steel work, welded in built up sections framed work including cutting, hoisting, fixing in position and applying a priming coat 9108.48 Rupees Nine Thousand One qtl
of red lead paint and two or more coat synthetic enamel paint . (A)In beams and joists, channels angles Tees, flats, with Hundred Eight And Paise Forty
connecting plates or angle cleats as in main and cross beams. Hip and jack rafters, purlins conneted to common rafters and the Eight Only
37 78.00 Supply and installation of polycarbonate multilayered system, a complete assembly of extruded multilayer UV protected 4393.32 Rupees Four Thousand Three sqm
polycarbonate panels incorporated into a complete system. Co-extruded UV protected polycarbonate panel system of min 18 Hundred Ninety Three And Paise
mm thick panel of 1200 mm width. Panels shall have six –seven layers with opaque and translucent clear combination as per Thirty Two Only
required lux level with all fixing accessories to ensure best performance for wind uplift, vibration, oil canning and visual
appearance. Panels shall be manufactured with vertical offset standing seam at both sides of the panel. Panels shall be fixed on
Purlin with snap on connectors with grip lock locking mechanism and will be secured on MS structure (will be paid Separately)
with 3 numbers self drilling screws & trapezoid SS fasteners holding the base of the standing seam offering best stability
having a pull-out load of min. 7000N (7KN) tested as per ISO 6892:1998 and IS 1608: 2005. Panels to satisfy Dart drop
impact test as per IS 14443-97 shall show no sign of breakage on Polycarbonate sheets which have been exposed to UV for a
min. of 500 Hours as per ASTM G 155.Panels shall not have Yellowness Index as per ASTM D 1925 of 15 units when tested
on a sample exposed to UV for 500 Hours as per ASTM G 155. U value shall not be more than 2.0 W/m2K as per EN ISO
10077-2:2018. Panel shall be with additional End cap / Aluminium U / F Profile / Glazing Bar (mill finish) for ends as
required. Panel shall be fixed over M S structural steel / MS purlin (paid separately) conforming to the detail technical
specifications as per approved architectural drawings. Trained and factory authorized labour with supervision to complete the
entire panel installation as per drawing & direction of the engineer in charge.
38 75101.00 Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, 654.58 Rupees Six Hundred Fifty Four KG
grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts And Paise Fifty Eight Only
and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of
required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-
in_x0002_charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing
accessories such as nuts, bolts, fasteners etc.).
39 4502.00 Providing and fixing S S Mosquito jali of approved quality for window and ventilations as and where required and directed by 454.50 Rupees Four Hundred Fifty Four sqm
engineer in charge. And Paise Fifty Only
40 6636.00 Providing and laying polished Kota stone slab flooring over 20mm (Average) thick base of cement mortar 1:6 (1-cement : 6- 1019.39 Rupees One Thousand Nineteen sqm
coarse sand) or L.M. 1.1.5 (1-Lime putty And Paise Thirty Nine Only
:1.5 - coarse sand) laid over and jointed with grey cement slurry mixed with pigment to match the shade ofslab including
rubbing and polishing etc. complete. (A)25mm thick
41 996.00 Providing and laying polished kota stone slab 25mm thick in risers of steps,skirting Dedo and pillars laid on10mm thick 1130.79 Rupees One Thousand One sqm
cement mortar 1:3 (1-Cement : 3 coarse sand) and jointed with gray cement slury mixed withpigment to match the shade of Hundred Thirty And Paise Seventy
slab including rubbing Nine Only
and polishing etc. complete.
42 4151.00 Providing and laying rough chiseled dressed stone flooring over 20mm average thick base of cement mortar 1:5 (1-Cement : 5- 576.79 Rupees Five Hundred Seventy Six sqm
coarse sand) or L.M. 1:1.5 (1-Limeputty : 1.5 - coarse sand) including pointing with cementmortar 1:2 (1-cement : 2-stone And Paise Seventy Nine Only
dust) etc. complete. (A)25mm to 30 mm thick kota stone
43 33976.00 P & L 24" x 24" vitrified 8 to 10 mm thick tile flooring over 20 mm (average) base of cement mortar 1:6 ( 1 cement: 6 coarse 1092.37 Rupees One Thousand Ninety Two sqm
sand) on new surface or fixing on existing flooring by adhesive material including dismentaling of existing flooring and jointed And Paise Thirty Seven Only
with color cement slurry including finised with flush pointing & cleaning the surface etc. complete for light shade for all
floor.complete selection as directed by Architect/E.IC
44 2993.00 P & L 24" x 24" vitrified 8 to 10 mm thick tile flooring over 20 mm (average) base of cement mortar 1:6 ( 1 cement: 6 coarse 1467.72 Rupees One Thousand Four sqm
sand) on new surface or fixing on existing flooring by adhesive material including dismentaling of existing flooring and jointed Hundred Sixty Seven And Paise
with color cement slurry including finised with flush pointing & cleaning the surface etc. complete for antiskit for all floor Seventy Two Only
45 3397.00 Providing and laying Vitrified tiles 8 to 10 mm thick , 24''x 24'' in skrting risers of steps and dedo on 10mm thickcement 1135.80 Rupees One Thousand One sqm
plaster 1:3 (1-cement : 3-coarse sand) and jointed with white cement slurry for all floor complete selection as directed by Hundred Thirty Five And Paise
Architect/E.IC Eighty Only
46 20004.00 Providing and laying coloured glazed tiles of the size 300 mm x 200 mm x 8 mm / 300 mm x 450 mm x 8 mm in skirting, 1513.28 Rupees One Thousand Five sqm
risers of steps and dedo including 10mm thick cement plaster 1:3 (10cement: 3 sand ) on wall surface and wall tiles laid with Hundred Thirteen And Paise
cement based high polymer modified quick set tile adhesive (water based) conforming to IS: 15477, in average 6 mm Twenty Eight Only
thickness, including grouting of joints complete. (rate include of Tile Bonder in stand of cement)
47 4159.00 Providing and laying polished granite stone flooring in required design and pattern in linear as well as carvilinear portion of 2602.59 Rupees Two Thousand Six sqm
the building, all complete as per the architectural drawings with 18 -20 mm thick stone slab jet black, cherry red, elite brown, Hundred Two And Paise Fifty Nine
cat eye or any desired shade by engineer in charge over 20mm average thick base of cement mortar 1:4 (1 cement : 4 coarse Only
sand) laid and jointed with cement slurry admixed with pigment of matching shade including rubbing, curing and polishing
and pre finished nosing in treads of steps etc complete as specified and as directed by the engineer in charge .for all floor
48 2151.00 Providing and laying kota stone for shelves in cupboard and walls in single piece (Miximum 1.50 mt.) 18 mm-20 mm 609.03 Rupees Six Hundred Nine And sqm
including cutting grooves in walls and fixing the stone with neat cement slurry in true line and level as directed by the engineer Paise Three Only
in charge etc. complete for Shelves for all floor
49 2994.08 Providing and fixing eco-friendly light weight calcium silicate false ceiling tiles having Tegular edge & 15 mm Thick 1674.15 Rupees One Thousand Six Hundred sqm
Densified edges on the Tile Periphery for Extra Strength The Light weight calcium silicate ceiling tiles shall have , light Seventy Four And Paise Fifteen
reflection 85% non-combustible as perB.S. 476 part IV, 100% humidity resistance and alsohaving thermalconductivity0.043° Only
w/m KC.for the bestthermal Insulation . The Light weight calcium Silicatetile shall be of approved texture Fine
fissured/Spintone/Cosmos having NRC value of 0.5 & Globehaving NRC value of 0.75 NRC or equivalent of size 595X
mm to be laid on true horizontal level suspendedinter locking metal grid of hot dipped galvanized steel
sections (galvanizing @120 grams per sqm includingboth side) consisting of main ‘T’ runner suitablyspacedat joints to get
required length and size of 24X38mmmade from 0.30 mm thick (minimum) sheet, 1200mmcentre to centre, and cross ‘T’ of
size 24X28mm madeout of 0.33mm (Minimum) sheet spaced 1200mm alongspaced between main ‘T’ at 600mm centre to
centre toform agrid of 1200X600mm and secondary cross ’T’ oflength 600mm and size 24x28mm made of 0.30 mm
thick(Minimum) sheet to be interlocked at middle of the1200X600mm panel to form grid of size 600X600mm resting on
periphery walls/partitions on a perimeter wall angle pre-coated steel of size (24X24X3000mm made of 0.40mm thick
(minimum) sheet with the help of rawl plugs at 450mm centreto centre with 25mm long drywall screws @ 230mm interval and
laying 15mm thick
Densified edges light weight calcium silicate ceiling tiles of approved texture (Fine Fissured/Cosmos/Spintone) inthe grid
including, cutting /making opening for serviceslike diffusers, grills, light fittings, fixtures, smokedetectors etc., wherever
required, Main ‘T’ runners to be
suspended from ceiling using G.I. slotted cleats of size25X35X1.6mm fixed to ceiling with 12.5mm dia and50mm long dash
fasteners, 4mm G.I. adjustable rodswith galvanized steel level clips of size 85X30X0.8mm,spaced at 1200mm centre to centre
long main ‘T’ bottomexposed with 24mm of all T-sections shall be pre-paintedwith polyester baked paint, for all heights, as
perspecifications, drawings and as directed byengineer-in-charge.Note:- Only calcium silicate falseceiling area will be
measured from wall to wall. Nodeduction shall be made for exposed frames/opening (cutouts) having area less than 0.30 sqm.
The calciumsilicate ceiling tiles shall have NRC. Value of 0.50(Minimum) for Fine fissured/Spintone/Cosmos and 0.75NRC
for Globe, light reflection 85% non-combustible asper B.S. 476 part IV, 100% humidity resistance and alsohaving thermal
conductivity. 0.043° w/m KC.for the best
thermal Insulation
50 74046.00 Providing 10 mm thick Cement Plaster in single coat on brick/concrete wall/Ceiling for interior plastering at various level as 322.10 Rupees Three Hundred Twenty sqm
below finished even and smooth in(i) Cement mortar 1:3 (1‐cement :3‐ sand) as required to receive specified architectural Two And Paise Ten Only
finish (like Grooves, pattern if any, drip mould etc.) to correct line, plumb .etc this item shall be including all heights and levels
51 94937.10 Providing 15mm thick cement plaster in single coat on Rough (Similar)side of single or half brick walls for interior plastering 346.15 Rupees Three Hundred Forty Six sqm
upto floor two level and finished even and smooth in (i) Cement mortar 1:3 (1-cement:3-sand) for all floor And Paise Fifteen Only
52 49401.45 20mm thick sand faced cement plaster /Mala plaster on walls upto consisting of 12mm thick backing coat of C.M. 1:3 (1- 487.71 Rupees Four Hundred Eighty Seven sqm
cement : 3-sand) and 8mm thick finishing coat of C.M. 1:1 (1-cement : 1-sand) etc. complete for all floor level Heights And Paise Seventy One Only
53 168983.73 Applying two coats of putty & two coats of primer of approved brand and manufacture on new wall surface to give an even 40.59 Rupees Forty And Paise Fifty Nine sqm
shade including thoroughly brushing the surface free from mortar dropping and other foreign matter and sand papered Only
smooth.for all floor
54 94937.10 Wall painting (Three coats) with plastic emulsion paint of approved brand & manufacture on under coated wall surface to give 83.36 Rupees Eighty Three And Paise sqm
an even shade including thoroughly brushing the surface free from mortar dropping and other foreign matter and sand papered Thirty Six Only
smooth.for all floor
55 74046.36 Ceilling painting (Three coats) with plastic emulsion paint of approved brand & manufacture on under coated wall surface to 89.04 Rupees Eighty Nine And Paise Four sqm
give an even shade including thoroughly brushing the surface free from mortar dropping and other foreign matter and sand Only
papered smooth.for all floor
56 3600.00 Applying priming coat over new steel and other metel surface after and including preparing the surface by throughly cleaning, 105.31 Rupees One Hundred Five And sqm
oil,grease, dirt and other foreign matter and scoured with brushes fine steel wood, scrapers and sand paper with ready mixed Paise Thirty One Only
priming paint brushing red lead. & Painting two coats (excluding priming coat) on new steel and other metal surface with
synthetic enamel paint, brushing to give an even shade including cleaning the surface of all dirt, dust and other foreign matter
57 54346.25 Finishing walls with textured exterior paint of required shade :New work (Two or more coats applied @ 3.28 ltr/10 sqm for 189.50 Rupees One Hundred Eighty Nine sqm
each coat) over and including priming coat of exterior primer applied @ 2.20kg/10 sqm.(Note : This item included exterior And Paise Fifty Only
paint of required shade over textured surface).
58 2052.30 Providing and fixing Glass reinforced concrete (GRC) screens synthetic rubber /FRP moulded in size, pattern, design, 3988.59 Rupees Three Thousand Nine sqm
thickness and colour of approved quality/make. The screens made of 53 grade white cement, quartz, fine silica sand, alkali Hundred Eighty Eight And Paise
resistant glass fibre, super plasticiser, polymers and UV resistant synthetic inorganic pigments etc including dry fixing with Fifty Nine Only
stainless steel 304 grade "L" shaped cramps , dash fasteners etc complete.
59 3654.80 Providing and fixing window having extruded aluminum Colour anodized section frame main outer size 95mm x 24mm x 2140.59 Rupees Two Thousand One sqm
1.17mm @ wt.of 0.738 Kg/mt , horizontal Three track member size 92mm x 31.75mm x 1.30mm,@ Wt.1.07 Kg/mt , vertical Hundred Forty And Paise Fifty
member of size 92mm x 31.75mm x 1.50mm @ Wt. 1.06 Kg/mt with sliding\ shutters of horizontal member size 40 Nine Only
mmx18mm x1.29mm @ wt.of 0.456 Kg/mt, vertical member of size 40mm x 18mm x 1.29 mm @ wt.of 0.456Kg/mt/ with
mm thick transparent bronze colour tinted float glass with powder coated aluminum fittings and fixtures including stainless
steel mosqito net jali shutter and transparent silicon sealant fixing to frame as per details etc
60 842.20 Providing and fixing standared extruded of alluminium section of size 63mm x 38.10mm x 1.2mm , @ Wt. 0.643 Kg/mt with 1175.56 Rupees One Thousand One sqm
colour Powder Coated alluminium frame for ventilation with 5 mm thick frosted glass as details etc complete for Ventilation Hundred Seventy Five And Paise
61 4471.00 Providing Brick Bat Water Proofing treatment to floor and walls of water tank, w.c. & bath area, through approved agencies 808.00 Rupees Eight Hundred Eight Only sqm
preparing floor and wall for water proofing work/ by chasing/cutting as per the companies requirement. Providing a layer of
plaster with waterproofing compound/ admixture about 25 mm thick in the floor / depression and about 1`8 mm on the
sidewalls / depression upto the floor level. The waterproof plaster about 18 mm thick to be continued on the walls above the
floor level for a height of 600 mm with surface suitable to receive further finishing treatment all complete as per companies
Specifications and instructions and as directed for all heights and floors. The round vata shall be included in this in SMT and
shall be taken upto top of round on wall etc complete as directed by EIC at For All Floor
62 5479.00 Providing and laying water proofing treatment on terrace including applying neat cement slurry 2.75kg/cm2 on cement 1187.76 Rupees One Thousand One sqm
admixed with water proofing component after cleaning the surface /laying cement concrete with brick bat 75 mm to 100 mm Hundred Eighty Seven And Paise
thick with 50%of C.M. 1:5 to required slope including ramming at junction of wall and slab after two days of proper curing Seventy Six Only
applying broken china mosaic flooring for plain and curve surface 12mm to 20mm white colour broken piece of glazed tiles
to be laid over 12mm thick cement mortar bedding of CM (1:3) to plain and slop and to be tampered to bring mortar cream up
to surface with using white cement and incl. Rounding of junctions and extending them up to 15 cm along the wall and curing
with bends any patterns or design as per drawing and direction incl. cleaning with water and oxalic acid. and Providing and
laying broken chine mosaic flooring for terrace using 12 mm to 20 mm broken pieces of glazed tiles to be laid over
cement mortar 1:3 to plain or slope and to be tempered to bring mortar creme out upto surface using white cement
including rounding off junctions and extending them upto 15 cm along the wall,clearing with water and oxalic acid etc. as
63 300000.00 Providing erecting and fixing double coated ISI water tank of required capacity each with all necessary fittings and connection 3.95 Rupees Three And Paise Ninety ltr
etc. complete on terrace Five Only
64 2100.00 Providing and fixing pre-cast Rubber Dye/ steel Dye interlocking concrete block 60mm thick with grade of concrete M300 706.93 Rupees Seven Hundred Six And sqm
pnumatic compressed/ vibrated mechanically and as per approved design Confirming to IS15658:2006 including 35mm Sand Paise Ninety Three Only
layer for levelling and filling the joint with sand in proper line and level as per guidlines of IRC : SP 63-2018 etc. Complete.
65 2500.00 Providing and ixing pre-cast concrete kerb stone of gray cement based concrete block 30cm length,30cm height and 15cm 404.21 Rupees Four Hundred Four And Rmt
thick of M200 grade concret as per approved design and including excavation for fixing in proper line and level ,filling the Paise Twenty One Only
joint with C:M 1:3(1cement:3 fine sand) etc complete.
66 210.00 Providing and applying 2.5 mm thick road marking strips (retro_x005f_x005f_x005f_x0002_reflective) of specified shade/ 633.72 Rupees Six Hundred Thirty Three sqm
colour using hot thermoplastic material by fully/ semi automatic thermoplastic paint applicator machine fitted with profile And Paise Seventy Two Only
shoe, glass beads dispenser, propane tank heater and profile shoe heater, driven by experienced operator on road surface
including cost of material, labour, T&P, cleaning the road surface of all dirt, seals, oil, grease and foreign material etc.
complete as per direction of Engineer-in-charge and accordance with applicable specifications.
67 2400.00 Providing laying (to level or slopes) and jointing reinforced concrete heavy duty non-pressure pipes I.S. class NP2 of the 1077.15 Rupees One Thousand Seventy Rmt
following internal diameter with collars Seven And Paise Fifteen Only
and butt ends prepared for collar joints including testingof joints complete.(E) 450mm
68 1551.00 Supplying and stacking at site dump manure from approved source, including carriage (manure measured in stacks will be 256.69 Rupees Two Hundred Fifty Six And sqm
reduced by 8% for payment) : Screened through sieve of I.S. designation 20mm Paise Sixty Nine Only
69 1250.00 Providing laying (to level or slopes) and jointing reinforced concrete heavy duty non-pressure pipes I.S.class NP2 of the 678.02 Rupees Six Hundred Seventy Eight Rmt
following internal diameter with collars and butt ends prepared for collar joints including testingof joints complete.(D) 300mm And Paise Two Only
70 13955.00 Spreading of sludge, dump manure and / or good earth in required thickness as per direction of Engineer -in-charge (Cost of 52.87 Rupees Fifty Two And Paise Eighty sqm
sludge, dump manure and / or good earth to be paid separately). Seven Only
71 13955.00 Mixing earth and sludge or manure in the required proportion specified or directed by the Engineer -in-charge. 36.92 Rupees Thirty Six And Paise sqm
Ninety Two Only
72 41315.70 Grassing with selection No.1 grass including watering and maintenance of the lawn for 30 days or more till the grass forms a 13.43 Rupees Thirteen And Paise Forty sqm
thick lawn, free from weeds and fit for mowing including supplying good earth, if needed -With grass Turf Three Only
73 250.00 Preparation of beds for hedging and shrubbery by excavating 60 cm deep and trenching the excavated base to a further depth 225.08 Rupees Two Hundred Twenty Five sqm
of 30 cm, refilling the excavated earth after breaking clods and mixing withsludge or manure in the ratio of 8:1 (8 parts of And Paise Eight Only
stacked volume of earth after reduction by 20% : one part of stacked volume of sludge or manure after reduction by 8%),
flooding with water, filling with earth if necessary, watering and finally fine dressing, leveling etc.including stacking and
disposal of materials declared unserviceable and surplus earth by spreading and leveling as directed, within a lead of 50 m, lift
up to 1.5 m complete (cost of sludge, manure or extra earth to be paid for separately).
74 41315.70 Supplying & Stacking of Selection No.1 doob grass turf at site fresh & free from weeds having proper roots in green including 51.31 Rupees Fifty One And Paise Thirty sqm
loading, unloading, carriage and all taxes paid etc.and as per direction of Engineer - in -charge. One Only
75 842.00 Providing and fixing white vitreous china wall mounting water closet of size 64X35.5X38.5 cm of approved shape including 10152.52 Rupees Ten Thousand One each
providing & fixing cistern with dual flush fitting, of flushing capacity 2 litre/ 4 litre (adjustafle to 4 litre/8 litres), including Hundred Fifty Two And Paise Fifty
seat cover, and cistern fittings, nuts, bolts and gasket etc complete Make -20151-Hindware./Eqivalent brand As Per Approved Two Only
by Engineer InCharge .
76 842.00 Providing and fixing toilet paper holder : C.P. brass As Per Approved by Engineer InCharge . 680.65 Rupees Six Hundred Eighty And each
Paise Sixty Five Only
77 842.00 Providing and fixing white vitreous china wash basin counter Top basin, with including 32 mm CP brass waste coupling, 4619.74 Rupees Four Thousand Six each
including painting of fittings and brackets, cutting and making good the walls wherever required all complete Hundred Nineteen And Paise
Seventy Four Only
78 842.00 Providing and fixing CP brass single lever basin mixer without popo with 450mm long braided hose (connection pipe) 2668.42 Rupees Two Thousand Six each
basin pillar tap of Jaquar LYR-38001B or Equivalent as approved by Engineer- In Charge Hundred Sixty Eight And Paise
79 842.00 Providing and fixing CP Brass 32mm size Bottle Trap of approved quality & make and as per the direction of Engineer-in- 876.95 Rupees Eight Hundred Seventy Six each
charge. And Paise Ninety Five Only
80 842.00 Providing and fixing 600mm x 450mm bevelled edge mirrror of superior glass mounted on 6mm thick A.C. sheet or plywood 859.41 Rupees Eight Hundred Fifty Nine each
sheet and fixing to wooden pluge with C.P. brass screws and washers.as per the direction of Engineer-in-charge. And Paise Forty One Only
81 330.00 Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS : 13983 with C.I. brackets and stainless steel plug 5886.10 Rupees Five Thousand Eight each
40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required Kitchen sink Hundred Eighty Six And Paise Ten
with drain board:510x1040 mm bowl depth 250 mm As Per Approved by Engineer InCharge . Only
82 2225.00 Providing and laying S&S centrifugally cast (spun) iron pipes (Class150 mm dia pipe (used in Basement Ceiling LVL) 1726.27 Rupees One Thousand Seven meter
Hundred Twenty Six And Paise
Twenty Seven Only
83 9726.76 Providing, laying and jointing in true line and level 75 diametre U.P.V.C (TypeB) conforming to IS13592-1992 with one end 443.39 Rupees Four Hundred Forty Three rmt
plain and othe rend socketed with rubberring, & fittings conforming to ISI14735-1999 of approved make for drainage system And Paise Thirty Nine Only
pipe line, pipe shall be jointed with each other with rubber lubricant, pipe shall be fixed on wall using of PVC clamp of the size
75 mm diametre x149mm length x145mm heigh at every 2000 mm center to center or shall be concealed in walls as directed
including necessary fittings such as bends, shoes etc.including testing of pipes and joints and jointed with adhesive solvent
cement including cost of all materials.
84 26843.36 Providing, laying and jointing in true line and level 110 diametre U.P.V.C (TypeB) conforming to IS13592-1992 with one end 834.38 Rupees Eight Hundred Thirty Four rmt
plain and othe rend socketed with rubberring, & fittings conforming to ISI14735-1999 of approved make for drainage system And Paise Thirty Eight Only
pipe line, pipe shall be jointed with each other with rubber lubricant, pipe shall be fixed on wall using of PVC clamp of the size
110 mm diametre x149mm length x145mm heigh at every 2000 mm center to center or shall be concealed in walls as directed
including necessary fittings such as bends, shoes etc.including testing of pipes and joints and jointed with adhesive solvent
cement including cost of all materials.
85 3032.00 Providing, laying and jointing in true line and level 160 diametre U.P.V.C (TypeB) conforming to IS13592-1992 with one end 878.57 Rupees Eight Hundred Seventy rmt
plain and othe rend socketed with rubberring, & fittings conforming to ISI14735-1999 of approved make for drainage system Eight And Paise Fifty Seven Only
pipe line, pipe shall be jointed with each other with rubber lubricant, pipe shall be fixed on wall using of PVC clamp of the size
110 mm diametre x149mm length x145mm heigh at every 2000 mm center to center or shall be concealed in walls as directed
including necessary fittings such as bends, shoes etc.including testing of pipes and joints and jointed with adhesive solvent
cement including cost of all materials.
86 145.00 Providing and fixing in position cowel went to pipes.(B)75mm dia. 393.04 Rupees Three Hundred Ninety EACH
Three And Paise Four Only
87 145.00 Providing and fixing in position cowel went to pipes.(C)100mm dia 653.09 Rupees Six Hundred Fifty Three EACH
And Paise Nine Only
88 145.00 Providing and fixing S.W. gully trap with C.I. grating brick masonry chamber and water tight C.I. cover with frame of 300mm 1246.92 Rupees One Thousand Two EACH
x 300mm size (inside) with standard weight.(i) Square mouth traps.(B) 150mm x 100mm size P or R type E Hundred Forty Six And Paise
Ninety Two Only
89 40.00 Constructing brick masonry chamber for underground C.I. Inspection chamber and bends with bricks having crushing strength 2932.93 Rupees Two Thousand Nine EACH
not less than 35Kg/Cm2 in C.M. 1:5 C.I. cover with frame (Light duty) 455mm x 610mm intenal dimensions total weight of Hundred Thirty Two And Paise
cover with frame to be not less than 38Kg. (Wt. of cover 23 Kg.) and Wt. of frame 15Kg. ) (R.C.C. top slabe with 1:2:4 mix (1- Ninety Three Only
cement :2- coarse sand :4-graded stone aggregate 20mm size) foundation concrete 1:5:10 inside plaster 15mm thick with
cement mortar 1:3 finished smooth with a floating coat of neat cement on walls and bed concrete etc. complete.(i) Inside
dimensions 455mmx 610mm and 450mm deep for single pipe line
90 40.00 Constructing brick masonry chamber for underground C.I. Inspection chamber and bends with bricks having crushing strength 3660.76 Rupees Three Thousand Six EACH
not less than 35Kg/Cm2 in C.M. 1:5 C.I. cover with frame (Light duty) 455mm x 610mm intenal dimensions total weight of Hundred Sixty And Paise Seventy
cover with frame to be not less than 38Kg. (Wt. of cover 23 Kg.) and Wt. of frame 15Kg. ) (R.C.C. top slabe with 1:2:4 mix (1- Six Only
cement :2- coarse sand :4-graded stone aggregate 20mm size) foundation concrete 1:5:10 inside plaster 15mm thick with
cement mortar 1:3 finished smooth with a floating coat of neat cement on walls and bed concrete etc. complete.(ii) Inside
dimensions 500mm x 700 mm and 450mm deep for pipe line with one or two inlets.
91 2436.00 Providing and fixing floor drain consisting of 100x50mm s/s elbow (grating to be paid separately), complete as per 557.52 Rupees Five Hundred Fifty Seven each
instructions. And Paise Fifty Two Only
92 4740.00 Providing and fixing 125 mm dia S/S grating (with or without hole)for floor or Nahani trap. 349.46 Rupees Three Hundred Forty Nine each
And Paise Forty Six Only
93 842.00 Providing and fixing of 600mm long towel rail (SS-316 grade), all complete with required acceessories as directed by the 1963.44 Rupees One Thousand Nine each
Engineer-in-Charge. Hundred Sixty Three And Paise
Forty Four Only
94 842.00 Providing and fixing CP brass with soap dish holder with all complete as directed by the Engineer-in-Charge. 957.48 Rupees Nine Hundred Fifty Seven each
And Paise Forty Eight Only
95 421.00 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes under floor for soil and waste water , complete with 439.62 Rupees Four Hundred Thirty Nine metre
fittings and clamps, i/c cutting and making good the walls etc.32 mm dia nominal bore And Paise Sixty Two Only
96 421.00 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes under floor for soil and waste water , complete with 595.72 Rupees Five Hundred Ninety Five metre
fittings and clamps, i/c cutting and making good the walls etc. 40 mm dia nominal bore And Paise Seventy Two Only
97 421.00 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes under floor for soil and waste water , complete with 791.65 Rupees Seven Hundred Ninety One metre
fittings and clamps, i/c cutting and making good the walls etc.50 mm dia nominal bore And Paise Sixty Five Only
98 3116.00 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, 283.90 Rupees Two Hundred Eighty Three metre
including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing.This includes jointing of And Paise Ninety Only
pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing
of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall20 mm nominal outer dia Pipes
99 4507.00 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, 339.83 Rupees Three Hundred Thirty Nine metre
including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing.This includes jointing of And Paise Eighty Three Only
pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing
of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall25 mm dia nominal bore
100 2404.00 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, 439.62 Rupees Four Hundred Thirty Nine metre
including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing.This includes jointing of And Paise Sixty Two Only
pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing
of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall32 mm dia nominal bore
101 3279.00 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, 595.72 Rupees Five Hundred Ninety Five metre
including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing.This includes jointing of And Paise Seventy Two Only
pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing
of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall40 mm dia nominal bore
102 1003.00 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, 791.65 Rupees Seven Hundred Ninety One metre
including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing.This includes jointing of And Paise Sixty Five Only
pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing
of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall50 mm dia nominal bore
103 1539.00 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, 1472.58 Rupees One Thousand Four metre
including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing.This includes jointing of Hundred Seventy Two And Paise
pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing Fifty Eight Only
of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall65 mm dia nominal bore
104 2520.00 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, 1676.60 Rupees One Thousand Six Hundred metre
including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing.This includes jointing of Seventy Six And Paise Sixty Only
pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing
of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall80 mm dia nominal bore
105 7072.00 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, 421.87 Rupees Four Hundred Twenty One metre
including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing.This includes jointing of And Paise Eighty Seven Only
pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing
of joints complete as per direction of Engineer in Charge.Concealed work,including cutting chases and making good the wall
etc.15 mm nominal outer dia Pipes
106 5300.00 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, 455.59 Rupees Four Hundred Fifty Five metre
including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing.This includes jointing of And Paise Fifty Nine Only
pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing
of joints complete as per direction of Engineer in Charge.Concealed work,including cutting chases and making good the wall
etc.20 mm nominal outer dia Pipes
107 4402.00 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, 531.56 Rupees Five Hundred Thirty One metre
including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing.This includes jointing of And Paise Fifty Six Only
pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing
of joints complete as per direction of Engineer in Charge.Concealed work,including cutting chases and making good the wall
etc.25 mm dia nominal bore
108 3064.00 Providing and fixing Forged Brass Ball Valve (Screwed). with setting and gland of superior quality having minimum working 537.67 Rupees Five Hundred Thirty Seven each
pressure of 16 kg/cm2. 20 mm nominal bore And Paise Sixty Seven Only
109 157.00 Providing and fixing Forged Brass Ball Valve (Screwed). with setting and gland of superior quality having minimum working 595.80 Rupees Five Hundred Ninety Five each
pressure of 16 kg/cm2. 25 mm nominal bore And Paise Eighty Only
110 10.00 Supply ,Erection , Testing & Commissioning of Automatic water level control panel & related accessories for pumping 21616.02 Rupees Twenty One Thousand Six each
automation with consisting of automatic water level controller , level sensor with stainless steel probe, motorized butterfly Hundred Sixteen And Paise Two
valve, motorized valve controller with complete in all respect.upto 50 mm dia. nominal bore Only
111 6042.00 Providing and fixing Stainless steel braided connection pipe with brass 235.33 Rupees Two Hundred Thirty Five each
unions :45 cm length15 mm nominal bore And Paise Thirty Three Only
112 6042.00 Providing and fixing C.P. brass angle valve / Angular stop cock with wall flange for basin mixer and geyser points of approved 767.60 Rupees Seven Hundred Sixty Seven each
quality CP brass extension pipe all of approved engineer-in-charge And Paise Sixty Only
113 842.00 Providing and fixing hand held ablution fitting (health faucet) with one meter long flexible tube and wall hook, all complete 2072.52 Rupees Two Thousand Seventy each
approved engineer-in-charge Two And Paise Fifty Two Only
114 1645.00 Providing and fixing screw down bib taps of followingsize.(B) Brass chromium plated screws down Bib Tap. (ii)20mm dia 214.81 Rupees Two Hundred Fourteen each
And Paise Eighty One Only
115 25.00 Providing and fixing ball cock of approved. quality asdirected.(A) Copper Metal (ii) 50mm dia. 189.84 Rupees One Hundred Eighty Nine each
And Paise Eighty Four Only
116 842.00 Supply and fixing of 15mm CP brass 2 -Way Bib Cock with wall flange and suitable length CP brass extension pipe all of 1272.60 Rupees One Thousand Two each
approved engineer-in-charge Hundred Seventy Two And Paise
117 330.00 Providing and fixing Sink Mixer With Regular Swinging Spout(Wall Mounted Model) With ConnectingLegs & Wall Flanges ( 4228.87 Rupees Four Thousand Two each
cat. No. LYR-38309 equivalent ) of approved quality Hundred Twenty Eight And Paise
Eighty Seven Only
118 330.00 Providing and fixing Sink Cock with Regular SwingingSpout (Wall Mounted Model) With 1682.66 Rupees One Thousand Six Hundred each
Wall Flange ( cat. No. LYR-38347S equivalent ) of approved quality Eighty Two And Paise Sixty Six
119 842.00 Providing and fixing C.P. brass overhead shower 150 x 150 mm square shape multi flow (ABS Body chrome plated with gray 3158.27 Rupees Three Thousand One each
face plate ) with rubit cleaning system with wall flange etc ( Hindware Cat No : F160216CP) ( Hindware Cat No : Hundred Fifty Eight And Paise
F160157)/Eqivalent brand As Per Approved by Engineer InCharge . Twenty Seven Only
120 842.00 Providing and fixing C.P Bath and Shower Wall mixer 3 in 1 System with Provision for Both Heand Shower and Overhead 5670.14 Rupees Five Thousand Six Hundred each
Shower with 115mm long Bend pipe wall Flange. ( Hindware Cat No : F280022)Eqivalent brand As Per Approved by Seventy And Paise Fourteen Only
Engineer InCharge .
121 6.00 Supplying, installing, testing and commissioning of flooded Vertical Inline cetrifugal pump set with stainless steel body , 96969.09 Rupees Ninety Six Thousand Nine set
stainless steel impller and SS shaft capable to deliver of following capacity and head. given by TFC squirrels induction motor Hundred Sixty Nine And Paise
suitable for operation on 415 volt , 50 HZ AC power supply running speed 2900 RPM .The installation shall be complete with Nine Only
all necessary ancillaries & accessories including base plate , coupling guard etc complete as required. Flow rate :
LPM Head : 70 MtsRequired for : UG T ( Domestic Water & Flusing Water )
122 4.00 Supply, installation, testing and commissioning of continuous duty submersible centrifugal non-clogging drainage pumps 75750.00 Rupees Seventy Five Thousand set
complete with 3 phase motor with all necessary protection and mechanical seal etc. complete with all ancillaries etc Seven Hundred Fifty Only
required.Flow rate : 100 LPM Head : 15 Mts Solid Handling : 10 – 12 MM Purpose :
Drainage MOC : CI
123 4.00 (a) Supplying, installation, testing and commissioning of Electric driven Main Fire Pump conforming to IS 12469: 2019 363062.48 Rupees Three Lakh(s) Sixty Three Set
suitable for automatic operation and consisting of following, complete in all respects, as required ,(b) Horizontal type, Thousand Sixty Two And Paise
multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal as Forty Eight Only
required. (c) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on
volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation,
conforming to IS-12615: 2018. (d) M.S. fabricated Common base plate, coupling,coupling guard, foundation bolts etc. as
required. (e)Suitable cement concrete foundation duly plastered with anti vibration pads. Note: *The head of the pump is
selected in a manner so as to give a minimum 3.5kgf/cm2 pressure at the highest/farthest point. 2280 lpm at 88 m Head
124 4.00 (a) Supplying, installation, testing and commissioning of diesel engine driven main fire pump conforming to IS 12469: 2019 570931.60 Rupees Five Lakh(s) Seventy Set
suitable for automatic operation and consisting of following,complete in all respects, as required : (Diesel Driven Pump) (b) Thousand Nine Hundred Thirty
Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical One And Paise Sixty Only
seal as required. (c) Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard
complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m
outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential
silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio
indications, painted with post office red colour etc. as required. (d) M.S fabricated, common base plate, coupling,coupling
guard, foundation bolts etc. as required. (e) Suitable cement concrete foundation duly
plastered and with anti vibration pads.2280 lpm at 88M. head
125 4.00 (a) Supplying, installation, testing and commissioning of electric driven pressurisation pump conforming to IS 12469: 2019 114841.28 Rupees One Lakh(s) Fourteen Set
suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump) (b) Thousand Eight Hundred Forty One
Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal And Paise Twenty Eight Only
as required. (c) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC
supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class- 'F' insulation, conforming to IS-
12615: 2018. (d) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. (e) Suitable
cement concrete foundation duly plastered and with anti vibration pads180 lpm, at 88M head
126 4.00 Designing, Supply, Installation, Testing and Commissioning of system controller to control operation of Main Electric Fire 401899.54 Rupees Four Lakh(s) One Thousand Set
Pump, Diesel Pump, Pressurisation Pump, in sequence as per specification consisting of relays, times, sensors, annunciation Eight Hundred Ninety Nine And
window for fault indication, complete as per specification. Paise Fifty Four Only
127 8.00 Supplying and making end termination with brass Compression Gland & Al.lugs for following sizes of PVC insulated, PVC 1143.52 Rupees One Thousand One Set
sheathed/XLPE Al.conductor cables of 1.1 KV grade as required3.5x300 sq.mm Hundred Forty Three And Paise
128 8.00 Supplying and making end termination with brass Compression Gland & Al.lugs for following sizes of PVC insulated, PVC 414.27 Rupees Four Hundred Fourteen Set
sheathed/XLPE Al.conductor cables of 1.1 KV grade as required3.5x50 sq.mm And Paise Twenty Seven Only
129 48.00 Supplying and making end termination with brass Compression Gland & Al.lugs for following sizes of PVC insulated, PVC 319.26 Rupees Three Hundred Nineteen Set
sheathed/XLPE Al.conductor cables of 1.1 KV grade as required4x25 sq.mm And Paise Twenty Six Only
130 32.00 Supplying and making end termination with brass Compression Gland & Al.lugs for following sizes of PVC insulated, PVC 594.02 Rupees Five Hundred Ninety Four Set
sheathed/XLPE Al.conductor cables of 1.1 KV grade as required 3x120 sq.mm And Paise Two Only
131 60.00 Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more 587.17 Rupees Five Hundred Eighty Seven Meter
than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts And Paise Seventeen Only
& nuts, painting suspenders etc. as required.150 mm width x 50mm depth x 1.6 mm thickness.
132 200.00 Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more 741.24 Rupees Seven Hundred Forty One metre
than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts And Paise Twenty Four Only
& nuts, painting suspenders etc. as required.300 mm (W) x 50 mm (D) x 1.6 mm (T)
133 480.00 Supplying & laying one number XLPE insulated PVC sheathed Aluminium Conductor armoured UG cable of 1.1 KV grade 457.53 Rupees Four Hundred Fifty Seven Meter
Conforming to IS 7098/1988 with upto date ammendment of following size in the existing RCC/HUME/ METAL /GI /CI And Paise Fifty Three Only
/Stoneware/DWC pipe/ masonary Open Duct/ cable tray/ open in air etc. as requred. 4 core, 25 sq.mm. Aluminium
134 400.00 Supplying & laying one number XLPE insulated PVC sheathed Aluminium Conductor armoured UG cable of 1.1 KV grade 685.79 Rupees Six Hundred Eighty Five Meter
Conforming to IS 7098/1988 with upto date ammendment of following size in the existing RCC/HUME/ METAL /GI /CI And Paise Seventy Nine Only
/Stoneware/DWC pipe/ masonary Open Duct/ cable tray/ open in air etc. as requred. 3.5 core, 50 sq.mm. Aluminium
135 200.00 Supplying & laying one number XLPE insulated PVC sheathed Aluminium Conductor armoured UG cable of 1.1 KV grade 1198.87 Rupees One Thousand One Meter
Conforming to IS 7098/1988 with upto date ammendment of following size in the existing RCC/HUME/ METAL /GI /CI Hundred Ninety Eight And Paise
/Stoneware/DWC pipe/ masonary Open Duct/ cable tray/ open in air etc. as requred. 3 core, 120 sq.mm. Aluminium Eighty Seven Only
136 300.00 Supplying & laying one number XLPE insulated PVC sheathed Aluminium Conductor armoured UG cable of 1.1 KV grade 3246.14 Rupees Three Thousand Two Meter
Conforming to IS 7098/1988 with upto date ammendment of following size in the existing RCC/HUME/ METAL /GI /CI Hundred Forty Six And Paise
/Stoneware/DWC pipe/ masonary Open Duct/ cable tray/ open in air etc. as requred. 3.5 core, 300 sq.mm. Aluminium Fourteen Only
137 8.00 Earthing with GI Earth plate 600 mm x 600 mm x 6 mm th.including accessories and providing masonry enclosure with cover 7147.89 Rupees Seven Thousand One Set
plate having locking arrangement and watering pipe with charcoal or coke and salt complete as required. Hundred Forty Seven And Paise
Eighty Nine Only
138 300.00 Providing & fixing 25 mm x 5 mm G.I. Strip in 40 mm dia GI pipe from earth electrode including connections with GI nut, 646.23 Rupees Six Hundred Forty Six And metre
bolt, spring, washer excavation and re-filling etc. as required. Paise Twenty Three Only
139 200.00 Providing & fixing 25 mm x 5 mm G.I. Strip in on surface or in recess for connections etc as required. 245.65 Rupees Two Hundred Forty Five metre
And Paise Sixty Five Only
140 200.00 Providing and fixing 6 SWG dia G.I wire on surface or in recess for loop earthing as required. 71.90 Rupees Seventy One And Paise metre
141 583.00 Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like 4368.67 Rupees Four Thousand Three metre
elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including excavation & providing cement concrete blocks as Hundred Sixty Eight And Paise
supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete Sixty Seven Only
as required.(150 mm dia)
142 118.80 Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like 2543.18 Rupees Two Thousand Five metre
elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including excavation & providing cement concrete blocks as Hundred Forty Three And Paise
supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete Eighteen Only
as required.(100 mm dia)
143 115.00 Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like 2313.91 Rupees Two Thousand Three metre
elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including excavation & providing cement concrete blocks as Hundred Thirteen And Paise Ninety
supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete One Only
as required.(80 mm dia)
144 115.50 Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589 and 1239 including fittings 5666.27 Rupees Five Thousand Six Hundred metre
like elbows, tees, flanges, tapers, nuts bolts, gaskets etc., fixing the pipe on the wall/ceiling with suitable clamps and painting Sixty Six And Paise Twenty Seven
with two or more coats of synthetic enamel paint of required shade complete as required.(200 mm dia) Only
145 346.50 Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589 and 1239 including fittings 3679.65 Rupees Three Thousand Six metre
like elbows, tees, flanges, tapers, nuts bolts, gaskets etc., fixing the pipe on the wall/ceiling with suitable clamps and painting Hundred Seventy Nine And Paise
with two or more coats of synthetic enamel paint of required shade complete as required.(150 mm dia) Sixty Five Only
146 798.16 Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589 and 1239 including fittings 2633.71 Rupees Two Thousand Six metre
like elbows, tees, flanges, tapers, nuts bolts, gaskets etc., fixing the pipe on the wall/ceiling with suitable clamps and painting Hundred Thirty Three And Paise
with two or more coats of synthetic enamel paint of required shade complete as required.100 mm dia Seventy One Only
147 682.66 Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589 and 1239 including fittings 1948.96 Rupees One Thousand Nine metre
like elbows, tees, flanges, tapers, nuts bolts, gaskets etc., fixing the pipe on the wall/ceiling with suitable clamps and painting Hundred Forty Eight And Paise
with two or more coats of synthetic enamel paint of required shade complete as required.(80 mm dia) Ninety Six Only
148 92.40 Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589 and 1239 including fittings 1673.35 Rupees One Thousand Six Hundred metre
like elbows, tees, flanges, tapers, nuts bolts, gaskets etc., fixing the pipe on the wall/ceiling with suitable clamps and painting Seventy Three And Paise Thirty
with two or more coats of synthetic enamel paint of required shade complete as required.(65 mm dia) Five Only
149 154.00 Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589 and 1239 including fittings 1332.68 Rupees One Thousand Three metre
like elbows, tees, flanges, tapers, nuts bolts, gaskets etc., fixing the pipe on the wall/ceiling with suitable clamps and painting Hundred Thirty Two And Paise
with two or more coats of synthetic enamel paint of required shade complete as required.50 mm dia Sixty Eight Only
150 115.50 Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589 and 1239 including fittings 787.46 Rupees Seven Hundred Eighty metre
like elbows, tees, flanges, tapers, nuts bolts, gaskets etc., fixing the pipe on the wall/ceiling with suitable clamps and painting Seven And Paise Forty Six Only
with two or more coats of synthetic enamel paint of required shade complete as required.(25 mm dia)
151 96.00 Supplying and fixing single headed internal hydrant valve with instantanous Gun metal couplings of 63mm dia with cast iron 7025.49 Rupees Seven Thousand Twenty each
wheel ISI marked conforming to IS 5290 (Type-A) with blank Gunmetal cap and chain as required Five And Paise Forty Nine Only
152 7.00 Supplying, fixing, testing and commissioning of following size butterfly valve (manual) with CI body SS disc nitrile sheet & O- 3521.30 Rupees Three Thousand Five each
ring & PN 1.6 pressure rating as specified.50 mm dia Hundred Twenty One And Paise
153 21.00 Supplying, fixing, testing and commissioning of following size butterfly valve (manual) with CI body SS disc nitrile sheet & O- 4627.17 Rupees Four Thousand Six each
ring & PN 1.6 pressure rating as specified.80 mm dia Hundred Twenty Seven And Paise
154 14.00 Supplying, fixing, testing and commissioning of following size butterfly valve (manual) with CI body SS disc nitrile sheet & O- 6223.48 Rupees Six Thousand Two each
ring & PN 1.6 pressure rating as specified.100 mm dia Hundred Twenty Three And Paise
Forty Eight Only
155 7.00 Supplying, fixing, testing and commissioning of following size butterfly valve (manual) with CI body SS disc nitrile sheet & O- 8334.21 Rupees Eight Thousand Three each
ring & PN 1.6 pressure rating as specified.150 mm dia Hundred Thirty Four And Paise
Twenty One Only
156 7.00 Supplying, fixing, testing and commissioning of double flanged sluice valve of rating PN with non rising spindle, bronze/gun 20514.98 Rupees Twenty Thousand Five each
metal seat, ISI marked complete with nuts bolts washers, gaskets and conforming to IS 780 of following size asrequired: 150 Hundred Fourteen And Paise
mm dia Ninety Eight Only
157 7.00 Supplying, fixing, testing and commissioning of double flanged sluice valve of rating PN with non rising spindle, bronze/gun 35423.61 Rupees Thirty Five Thousand Four each
metal seat, ISI marked complete with nuts bolts washers, gaskets and conforming to IS 780 of following size asrequired: 200 Hundred Twenty Three And Paise
mm dia Sixty One Only
158 82.00 Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted 1229.12 Rupees One Thousand Two each
between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 Hundred Twenty Nine And Paise
complete as required. Twelve Only
159 7.00 Supplying, fixing, testing and commissioning, of following sizes of non return valve with C I body.(80 mm dia) 7065.72 Rupees Seven Thousand Sixty Five each
And Paise Seventy Two Only
160 42.00 Supplying, fixing, testing and commissioning, of following sizes of non return valve with C I body.(100 mm dia) 10145.37 Rupees Ten Thousand One each
Hundred Forty Five And Paise
Thirty Seven Only
161 28.00 Supplying, fixing, testing and commissioning, of following sizes of non return valve with C I body.(150 mm dia) 16163.42 Rupees Sixteen Thousand One each
Hundred Sixty Three And Paise
162 7.00 Supplying, fixing, testing and commissioning of following size Y-Strainer of ductile CI body flanged ends with stainless steel 9999.00 Rupees Nine Thousand Nine each
strainer as specified.(150 mm dia) Hundred Ninety Nine Only
163 14.00 Supplying, fixing, testing and commissioning of following size Y-Strainer of ductile CI body flanged ends with stainless steel 20175.17 Rupees Twenty Thousand One each
strainer as specified.(200 mm dia) Hundred Seventy Five And Paise
164 82.00 Supplying and fixing 63mm dia, 15mtr. Long RRL hose pipe with 63mm dia Male and Female Gun metal couplings duly 4669.11 Rupees Four Thousand Six each
binded with GI wire, rivets etc. conforming to IS 636 (type-A) as required. Hundred Sixty Nine And Paise
165 82.00 Supplying and fixing First-Aid-Hose Reel with MS construction spray painted in Post office Red, conforming to IS 884 with 9534.40 Rupees Nine Thousand Five each
upto date amendments, complete with the following as required.30 m long 20mm (nominal internal) dia water hose Hundred Thirty Four And Paise
Thermoplastic (Textile reinforced) Type-2 as per IS: 1258520 mm (nominal internal) dia gun metal globe valve & Forty Only
nozzle.Drum and brackets for fixing the equipments on wall.Connections from riser with 40 mm dia stop valve (gun metal) &
166 82.00 Providing and fixing Fire hose cabinet door (40mm x 40mm x 5mm) angle depth fabricated with 2100mm x 1200mm MS 24891.45 Rupees Twenty Four Thousand each
sheet. Complete in all respect with 25mmx25mmx3mm angle frame all around and stiffened in between i/c hinges, handle, Eight Hundred Ninety One And
locking arrangement, painting with approved synthetic enamel paint i/c sign writing on glass at internal hydrant including Paise Forty Five Only
providing & fixing S.S. sheet 2mm thick on remaining portion above door to close opening i/c painting etc. as required. Glass
shall be 6 mm thick.
167 82.00 Supply and fixing 63mm dia Gun Metal branch pipe with 20mm (nominal internal diameter) size Gun Metal nozzle 4259.98 Rupees Four Thousand Two each
conforming to IS 903, suitable for instantaneous connection to interconnect hose pipe coupling as required. Hundred Fifty Nine And Paise
Ninety Eight Only
168 7.00 Supplying and fixing following fire brigade connection of cast iron body with Gun metal male instantaneous inlet couplings 6215.78 Rupees Six Thousand Two each
complete with cap and chain as required for 150mm dia MS pipe connection, conforming to IS 904 as required.2 Way FBC of Hundred Fifteen And Paise Seventy
Cl body Eight Only
169 7.00 Supplying and fixing following fire brigade connection of cast iron body with Gun metal male instantaneous inlet couplings 12684.91 Rupees Twelve Thousand Six each
complete with cap and chain as required for 150mm dia MS pipe connection, conforming to IS 904 as required.4 Way FBC of Hundred Eighty Four And Paise
Cl body Ninety One Only
170 21.00 Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with Air release valve on top 16606.79 Rupees Sixteen Thousand Six each
and flanged connection to riser, drain arrangement with 25 mm dia Gun metal wheel valve, with required accessories, pressure Hundred Six And Paise Seventy
gauge and painting with synthetic enamel pain of approved shade as required. Nine Only
171 21.00 Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. 1429.40 Rupees One Thousand Four each
Hundred Twenty Nine And Paise
172 14.00 Providing & fixing Auto Air release valve for fire hydent and sprinkler, suitable for pressure not less than 15 Kg/Sq.cm.25 4169.28 Rupees Four Thousand One each
mm dia Hundred Sixty Nine And Paise
Twenty Eight Only
173 96.00 Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required 1276.20 Rupees One Thousand Two each
Hundred Seventy Six And Paise
174 96.00 Providing and fixing stainless steel standard Fireman's Axe with heavy insulated rubber handle tested to 20000 volts as per IS : 847.39 Rupees Eight Hundred Forty Seven each
926 complete. And Paise Thirty Nine Only
175 7.00 Providing, installing, testing & commisioning of fire brigade draw out connection (fire department connection) with suction 9175.85 Rupees Nine Thousand One each
pipe MS class 'C' 100 mm dia. & 100 mm dia. foot valve & steel chain including wall mounted box M.S. construction made Hundred Seventy Five And Paise
out of 16 gauge MS Sheet with glass door to house the above mentioned componenets. It should be complete as per Eighty Five Only
manufacturer's specifications & as directed by Engineer- in-charge. (to be connected to static water tank) It should be complete
as per manufacturer's specifications & as directed by Engineer- in-charge.
176 93.00 Providing and fixing mechanical foam type(ISI marked) fire extinguishers consisting of welded M.S. cylindrical body squeeze 3512.78 Rupees Three Thousand Five each
lever discharge valve 30 cm long high pressure discharge hose, discharge nozzle suspension bracket ISI marked as per IS 933 Hundred Twelve And Paise Seventy
finished externally with red enamel paint and fixed to wall with brackets complete with internal charger.Capacity 6 kg. Eight Only
177 93.00 Providing and fixing Carbon-di-oxide fire extinguishers consisting of welded M.S cylinderical body,squeeze lever discharge 10174.74 Rupees Ten Thousand One each
valve fitted with internal dischargetube, 30cms long high pressure discharge hose, discharge nozzle, suspension bracket, Hundred Seventy Four And Paise
confirming to IS : 934 finished externally with red enamel paint and fixed to wall with brackets with rawl plug/dash fasteners Seventy Four Only
complete with internal charge.Capacity 4.5 kg. I.S.I. Marked.
178 13710.00 Point wiring for light/bell with 2X1.5 sq. mm & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade FRLS 582.77 Rupees Five Hundred Eighty Two point
PVC insulated multi strand copper wires up to 10 mtr length in below type of pipe erected with 6A Modular type switch/bell And Paise Seventy Seven Only
push & accessories and earth continuity of following type erected on PVC/metallic/wooden Box single mounting base frame,
covered with textured/metalic white front plate modules erected on / in wall / ceiling as per pipe erected with necessary lamp
holder/ ceiling rose/ H.D Connector as directed.(f) with medium class Rigid PVC pipe and accessories erected concealed in
wall/ceiling complete. Cat III
179 3104.00 Point wiring for Tissino / Modular secondary light point with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (green) both are of ISI 200.99 Rupees Two Hundred And Paise point
marked 1.1 KV grade FRLS PVC insulated multi strand copper wires, in below type of pipe to be erected complete with earth Ninety Nine Only
continuity and necessary connection with primary light with accessories erected on Metal / PVC / wooden box covered with
mm thick PC(Polycarbonate) / Acrylic sheet for open / concealed wiring. with necessary Lamp holder / ceiling rose /
H.D.Connector as directed.Note:- Maximum up to 6 mtrs length, excess will be considered as Mains for Secondary Point.(f)
with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling complete
180 3564.00 Point wiring for Fan with 2X1.5 sq. mm & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade FRLS PVC 809.01 Rupees Eight Hundred Nine And point
insulated multi strand copper wires up to 10 mtr length in below type of pipe erected with 6A Modular type switch and num Paise One Only
free EME four or more step type electronic fan regulator with separately mounted and accessories with earth continuity of
following type erected on PVC/ metallic /wooden Box single mounting base frame, covered with textured/ metalic white front
plate modules erected on / in wall / ceiling as per pipe erected with necessary ceiling rose/ H.D Connector as directed.(f) with
medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling complete.Cat III
181 6286.00 Providing following type of Modular type Accessories mounted with PVC/metallic.wooden box, single mounting base frame 151.50 Rupees One Hundred Fifty One each
covered with textured / metallic / white front plate, modules erected with necessary connections as per site situation directed by And Paise Fifty Only
Engineer in charge.(1)One No. SP 6 Amp. Cat III
182 6286.00 Providing following type of Modular type Accessories mounted with PVC/metallic.wooden box, single mounting base frame 151.50 Rupees One Hundred Fifty One each
covered with textured / metallic / white front plate, modules erected with necessary connections as per site situation directed by And Paise Fifty Only
Engineer in charge. (2) One No 5 pin plug -Cat III
183 1326.00 Providing following type of Modular type Accessories mounted with PVC/metallic.wooden box, single mounting base frame 160.59 Rupees One Hundred Sixty And each
covered with textured / metallic / white front plate, modules erected with necessary connections as per site situation directed by Paise Fifty Nine Only
Engineer in charge.(4) TV Co-axial Socket outlet -Cat III
184 5376.00 Providing following type of Modular type Accessories mounted with PVC/metallic.wooden box, single mounting base frame 180.79 Rupees One Hundred Eighty And each
covered with textured / metallic / white front plate, modules erected with necessary connections as per site situation directed by Paise Seventy Nine Only
Engineer in charge.(9) 16 Amp. SP one way switch-Cat III
185 5376.00 Providing following type of Modular type Accessories mounted with PVC/metallic.wooden box, single mounting base frame 199.98 Rupees One Hundred Ninety Nine each
covered with textured / metallic / white front plate, modules erected with necessary connections as per site situation directed by And Paise Ninety Eight Only
Engineer in charge.(10) 6/16Amp. Universal socket-Cat III
186 2020.00 Providing following type of Modular type Accessories mounted with PVC/metallic.wooden box, single mounting base frame 170.69 Rupees One Hundred Seventy And each
covered with textured / metallic / white front plate, modules erected with necessary connections as per site situation directed by Paise Sixty Nine Only
Engineer in charge.(12) 6Amp. / 16 Amp. Two Way switch-Cat III
187 668.00 Providing following type of Modular type Accessories mounted with PVC/metallic.wooden box, single mounting base frame 310.07 Rupees Three Hundred Ten And each
covered with textured / metallic / white front plate, modules erected with necessary connections as per site situation directed by Paise Seven Only
Engineer in charge..(13) 6A/10A/16A/20A/25A/32A Single pole Modular MCB Switch-Cat III
188 1274.00 Providing following type of Modular type Accessories mounted with PVC/metallic.wooden box, single mounting base frame 410.06 Rupees Four Hundred Ten And each
covered with textured / metallic / white front plate, modules erected with necessary connections as per site situation directed by Paise Six Only
Engineer in charge.(14) 6A/ 10A/ 16A/ 20A/ 25A/ 32A Double Pole Modular MCB Switch-Cat III
189 330.00 Providing following type of Modular type Accessories mounted with PVC/metallic.wooden box, single mounting base frame 329.26 Rupees Three Hundred Twenty each
covered with textured / metallic / white front plate, modules erected with necessary connections as per site situation directed by Nine And Paise Twenty Six Only
Engineer in charge.(19) Modular Indicating Call Bell-Cat III
190 330.00 Providing following type of Modular type Accessories mounted with PVC/metallic.wooden box, single mounting base frame 149.48 Rupees One Hundred Forty Nine each
covered with textured / metallic / white front plate, modules erected with necessary connections as per site situation directed by And Paise Forty Eight Only
Engineer in charge.(20) Modular Buzzer-Cat III
191 27400.00 Providing & erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked standard copper conductor wire in following 104.03 Rupees One Hundred Four And metre
type of pipe to be erected concealed in / flushed on wall / ceiling, with 1.5 sq.mm copper conductor FRLS PVC insulated Paise Three Only
standard wire of green colour for earth continuity of following size.(A) With medium class Rigid PVC pipe and accessories.(b)
2 wire 2.5 sq. mm
192 179270.00 Providing & erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked standard copper conductor wire in following 140.39 Rupees One Hundred Forty And metre
type of pipe to be erected in / on wall / ceiling, with 2.5 sq.mm copper conductor FRLS PVC insulated standard wire of green Paise Thirty Nine Only
colour for earth continuity of following size.(A) with medium class Rigid PVC pipe and accessories (a) 2 wire 4 sq. mm
193 490.00 Providing & erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked standard copper conductor wire in following 184.83 Rupees One Hundred Eighty Four metre
type of pipe to be erected in / on wall / ceiling, with 2.5 sq.mm copper conductor FRLS PVC insulated standard wire of green And Paise Eighty Three Only
colour for earth continuity of following size.(A) with medium class Rigid PVC pipe and accessories(b) 2 wire 6 sq. mm
194 25080.00 Providing & erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked standard copper conductor wire in following 326.23 Rupees Three Hundred Twenty Six metre
type of pipe to be erected in / on wall / ceiling, with 2.5 sq.mm copper conductor FRLS PVC insulated standard wire of green And Paise Twenty Three Only
colour for earth continuity of following size.(A) with medium class Rigid PVC pipe and accessories (h) 4 wire 6 sq. mm
195 160.00 providing and erecting Mains with ISI marked, 1.5KV grade electrolyte multi stranded, annealed copper conductor with heat 295.93 Rupees Two Hundred Ninety Five Mtr.
resistant PVC insulated conforms to IS 694, IEC - 227 erected in existing pipe of following size (Specifically for control And Paise Ninety Three Only
panel, relays, power switchgears, motor starters & control wiring) with required size of copper lugs, nuts and bolts if
required.(h) One wire 25.00 sq. mm
196 160.00 providing and erecting Mains with ISI marked, 1.5KV grade electrolyte multi stranded, annealed copper conductor with heat 376.73 Rupees Three Hundred Seventy Six Mtr.
resistant PVC insulated conforms to IS 694, IEC - 227 erected in existing pipe of following size (Specifically for control And Paise Seventy Three Only
panel, relays, power switchgears, motor starters & control wiring) with required size of copper lugs, nuts and bolts if
required.(i) One wire 35.00 sq. mm
197 240.00 providing and erecting Mains with ISI marked, 1.5KV grade electrolyte multi stranded, annealed copper conductor with heat 588.83 Rupees Five Hundred Eighty Eight Mtr.
resistant PVC insulated conforms to IS 694, IEC - 227 erected in existing pipe of following size (Specifically for control And Paise Eighty Three Only
panel, relays, power switchgears, motor starters & control wiring) with required size of copper lugs, nuts and bolts if
required.(j) One wire 50.00 sq. mm
198 240.00 providing and erecting Mains with ISI marked, 1.5KV grade electrolyte multi stranded, annealed copper conductor with heat 837.29 Rupees Eight Hundred Thirty Mtr.
resistant PVC insulated conforms to IS 694, IEC - 227 erected in existing pipe of following size (Specifically for control Seven And Paise Twenty Nine Only
panel, relays, power switchgears, motor starters & control wiring) with required size of copper lugs, nuts and bolts if
required.(k) One wire 70.00 sq. mm
199 400.00 providing and erecting Mains with ISI marked, 1.5KV grade electrolyte multi stranded, annealed copper conductor with heat 1149.38 Rupees One Thousand One Mtr.
resistant PVC insulated conforms to IS 694, IEC - 227 erected in existing pipe of following size (Specifically for control Hundred Forty Nine And Paise
panel, relays, power switchgears, motor starters & control wiring) with required size of copper lugs, nuts and bolts if Thirty Eight Only
required.(l) One wire 95.00 sq. mm
200 65700.00 Providing & Erecting approved make following size of TV Co-axial flexible cable comprising inner conductor of solid bare 39.39 Rupees Thirty Nine And Paise RM
copper insulated with Foam PE & Secondary conductor made of poly - Aluminium film bonded Al. Braids @ suitable Thirty Nine Only
coverage overall sheathed with black PVC insulation.(b) RG-6
201 205.00 Providing & fixing approved make Perforated C type Cable tray, made from sheet steel. The cable tray should be single or 424.20 Rupees Four Hundred Twenty Four RM
double bended as per required and as per IS 2062 / 1079 and shall be coated with hot dip galvanizing as per IS 2629/4759 And Paise Twenty Only
with max 17.5% perforation with coupler plate / fish plate and GI hardware like nut - bolt and washers etc. erection with
necessary support included) as per specification and as per instruction of Engineer In charge.(3) 150 X 50 X 1.6 mm Thick
202 410.00 Providing & fixing approved make Perforated C type Cable tray, made from sheet steel. The cable tray should be single or 622.16 Rupees Six Hundred Twenty Two RM
double bended as per required and as per IS 2062 / 1079 and shall be coated with hot dip galvanizing as per IS 2629/4759 And Paise Sixteen Only
with max 17.5% perforation with coupler plate / fish plate and GI hardware like nut - bolt and washers etc. erection with
necessary support included) as per specification and as per instruction of Engineer In charge.(5) 300 mm X 50 mm X 2.0 mm
203 830.00 Providing & fixing approved make Perforated C type Cable tray, made from sheet steel. The cable tray should be single or 1006.97 Rupees One Thousand Six And RM
double bended as per required and as per IS 2062 / 1079 and shall be coated with hot dip galvanizing as per IS 2629/4759 Paise Ninety Seven Only
with max 17.5% perforation with coupler plate / fish plate and GI hardware like nut - bolt and washers etc. erection with
necessary support included) as per specification and as per instruction of Engineer In charge. (7) 600 X 50 X 2.0 mm Thick
204 440.00 Supplying and laying UPVC cable trunking system comprising unplasticised polyvinyl, chloride rigid material with ignition 188.87 Rupees One Hundred Eighty Eight RM
free and flame proof confirming BS with necessary end caps Internal and external bend, flat bends, coupler, tee etc..All And Paise Eighty Seven Only
necessary accessories and measuring of following sizes (3) 50 mm x 50 mm trunking
205 7.00 Fabrication, supply, installation, testing and commissioning of wall/floor maounted cubicle type LT panels suitable for 415 V 3 196773.25 Rupees One Lakh(s) Ninety Six each
phase, 4 wire, 50 Hz AC supply system (IP 42 degree of protection) fabricated in compartmentalized design from CRCA sheet Thousand Seven Hundred Seventy
made out of 2 mm thick for frame work & covers 3mm thick for gland plates including cleaning & finishing complete with 7 Three And Paise Twenty Five Only
tank process for powder coating in approved shade, having TPN Al alloy bus bars of high conductivity, DMC/SMC bus bar
supports with short circuit withstand capacity of 31 MVA for 1 sec, bottom base channel of MS section. Entire panel shall
have a common copper earth bar of size as per CPWD specification at the rear with 2 Nos earth stud, interconnections from
main busbar to switch gears with required size of AL bus bar and control wiring with PVC insulated FRLS copper conductor
single core cable, cable alleys, cable gland plates etc. providing following switch gears:Note: All the MCCBs of capacity more
than 250 Amp should be Microprocessor based and below 250Amp it should be Thermal Magnetic based MDB- E- DG
Supply Panel-Incoming:315 A, FP MCCB 25 KA - 1 No.400 A TPN AL. bus bar with coloured heat shrinkable PVC sleeve -
1 Set-Outgoings:63 A FP MCB, - 2 Nos.63 A TPN MCCB, 25 KA - 4 Nos.200 A FP MCCB, 35 KA - 1 Nos.Instruments:
Multi Function Meter (MFM) with CTs & Fuses/MCB/Selecter Switch -1 Set Indication lamp RYB with Fuses/MCB etc. as
206 7.00 Fabrication, supply, installation, testing and commissioning of wall/floor maounted cubicle type LT panels suitable for 415 V 3 117310.49 Rupees One Lakh(s) Seventeen each
phase, 4 wire, 50 Hz AC supply system (IP 42 degree of protection) fabricated in compartmentalized design from CRCA sheet Thousand Three Hundred Ten And
made out of 2 mm thick for frame work & covers 3mm thick for gland plates including cleaning & finishing complete with 7 Paise Forty Nine Only
tank process for powder coating in approved shade, having TPN Al alloy bus bars of high conductivity, DMC/SMC bus bar
supports with short circuit withstand capacity of 31 MVA for 1 sec, bottom base channel of MS section. Entire panel shall
have a common copper earth bar of size as per CPWD specification at the rear with 2 Nos earth stud, interconnections from
main busbar to switch gears with required size of AL bus bar and control wiring with PVC insulated FRLS copper conductor
single core cable, cable alleys, cable gland plates etc. providing following switch gears:Note: All the MCCBs of capacity more
than 250 Amp should be Microprocessor based and below 250Amp it should be Thermal Magnetic based-Lift Panel - 3 Lifts-
Incoming:200 A, FP MCCB 25 KA - 1 No.300 A TPN AL. bus bar with coloured heat shrinkable PVC sleeve -1 Set,
Outgoings:32 A DP MCB, - 3 Nos.63 A, FP MCCB 25 KA - 4 No.Instruments: Multi Function Meter (MFM) with CTs &
Fuses/MCB/Selecter Switch -1 Set Indication lamp RYB with Fuses/MCB etc. as req.
207 2.00 Fabrication, supply, installation, testing and commissioning of wall/floor maounted cubicle type LT panels suitable for 415 V 3 35100.53 Rupees Thirty Five Thousand One each
phase, 4 wire, 50 Hz AC supply system (IP 42 degree of protection) fabricated in compartmentalized design from CRCA sheet Hundred And Paise Fifty Three
made out of 2 mm thick for frame work & covers 3mm thick for gland plates including cleaning & finishing complete with 7 Only
tank process for powder coating in approved shade, having TPN Al alloy bus bars of high conductivity, DMC/SMC bus bar
supports with short circuit withstand capacity of 31 MVA for 1 sec, bottom base channel of MS section. Entire panel shall
have a common copper earth bar of size as per CPWD specification at the rear with 2 Nos earth stud, interconnections from
main busbar to switch gears with required size of AL bus bar and control wiring with PVC insulated FRLS copper conductor
single core cable, cable alleys, cable gland plates etc. providing following switch gears:Note: All the MCCBs of capacity more
than 250 Amp should be Microprocessor based and below 250Amp it should be Thermal Magnetic based-MDB L&P -
Higher Class Residences-Incoming:100 A, FP MCCB 25 KA - 1 No, 200 A TPN AL. bus bar with coloured heat shrinkable
PVC sleeve -1 Set, Outgoings:63 A DP MCB, - 3 Nos.63 A, FP MCCB 25 KA - 3 No.Instruments: Multi Function Meter
(MFM) with CTs & Fuses/MCB/Selecter Switch -1 Set , Indication lamp RYB with Fuses/MCB etc. as req.
208 72.00 Providing & erecting weather proof, dust & vermin proof, floor mounted front operated indoor type cubical panel board 14902.55 Rupees Fourteen Thousand Nine Sq.Mtr
necessary IP-42 and above protection as per approval from engineer incharge made from 14 SWG thick CRC M.S. sheet for Hundred Two And Paise Fifty Five
outer body & doors, 16 SWG thick CRC M.S.sheet for internal partitions with necessary accesories , supporting angles/ flats Only
channel including cutting, bending, drilling, welding, riveting with internal partitions & cable alley as per requirements &
instruction of engineer-in-charge with erection of supplied switch gears, BUSBARS, suitable size of inter connecting PVC
copper wire / copper-aluminium strips, rubber grommets, rib, bakelite control fuses/MCB for measuring instruments, earth bus
& earth bolts, foundation flange - bolts-base Plates, sufficient nos. of hinged doors, handles with locking arrangement and
rubber gasket,heavy duty end terminal connection,danger notice board,necessary ventilation,earthing strip complete. The
Panel shall be painted with epoxy powder coating.(The rates excludes the cost of switchgears, bus bars, inter connecting mains
& Copper Aluminium strips, meters, Fuses etc. The dimension shall be measured excluding base beams) The panel shall be
supplied with following approved manufacturers with following size. (B) The standard companies switch gear shall be used
and only manufacturers at CPRI approved factory (i) with 350mm depth
209 13.50 Providing & erecting weather proof, dust & vermin proof, floor mounted front operated indoor type cubical panel board 19387.96 Rupees Nineteen Thousand Three Sq.Mtr
necessary IP-42 and above protection as per approval from engineer incharge made from 14 SWG thick CRC M.S. sheet for Hundred Eighty Seven And Paise
outer body & doors, 16 SWG thick CRC M.S.sheet for internal partitions with necessary accesories , supporting angles/ flats Ninety Six Only
channel including cutting, bending, drilling, welding, riveting with internal partitions & cable alley as per requirements &
instruction of engineer-in-charge with erection of supplied switch gears, BUSBARS, suitable size of inter connecting PVC
copper wire / copper-aluminium strips, rubber grommets, rib, bakelite control fuses/MCB for measuring instruments, earth bus
& earth bolts, foundation flange - bolts-base Plates, sufficient nos. of hinged doors, handles with locking arrangement and
rubber gasket,heavy duty end terminal connection,danger notice board,necessary ventilation,earthing strip complete. The
Panel shall be painted with epoxy powder coating.(The rates excludes the cost of switchgears, bus bars, inter connecting mains
& Copper Aluminium strips, meters, Fuses etc. The dimension shall be measured excluding base beams) The panel shall be
supplied with following approved manufacturers with following size. (B) The standard companies switch gear shall be used
and only manufacturers at CPRI approved factory (ii) with 550 mm. Depth
210 14.00 Providing and erecting approved make Four pole moulded case circuit breaker having breaking capacity ICU of 25 KA at 415 6790.23 Rupees Six Thousand Seven each
V, having normal current rating up to 25A to 100A, with fixed thermal & magnetic release suitable to work on AC supply Hundred Ninety And Paise Twenty
50c/s with all internal connections & cpomplete erected in existing 16 G.M.S housing.ICS=100% of ICU only Cat III Three Only
211 16.00 Providing and erecting Approved make Four pole moulded case circuit breaker having breaking capacity ICU of 35 KA. at 17843.67 Rupees Seventeen Thousand Eight each
415 V. having Normal current rating 200A.with variable Thermal & magnetic release suitable to work on A.C.supply 50 Hz. Hundred Forty Three And Paise
with all internal connections, spreader tinned copper & complete erected in existing 16 G.M.S.housing ICS=100% of ICU Sixty Seven Only
212 14.00 Providing and erecting Approved make Four pole moulded case circuit breaker having breaking capacity ICU of 50 KA and 27751.77 Rupees Twenty Seven Thousand each
above at 415 V having Normal current rating 400A. with variable Thermal & magnetic release suitable to work on Seven Hundred Fifty One And
A.C.supply 50 Hz. With all internal connections, spreader tinned copper & complete erected in existing 16 G.M.S. housing. Paise Seventy Seven Only
ICS=100% of ICU only Cat III
213 363.00 Providing and erecting Approved make RCCBs conforming to IS: 12640 and having sensitivity of 30 mA and Short Circuit 3344.11 Rupees Three Thousand Three each
withstand capacity of 10 KA and suitable for operation on 3 phase and neutral 415V,50Hz. having characteristic of quick Hundred Forty Four And Paise
action & tripping with all advance feature & do not incorporate any electronic component for following Max. rating erected as Eleven Only
directed.(iii) 63 Amps. FP Cat. III
214 2200.00 Providing , erecting , fabricating the M.S. structure as per requirement on site incorporating proper size of M.S. 77.77 Rupees Seventy Seven And Paise Kg
angles,square,round, flats, bars, channels, sections complete with cutting, welding, grinding & finishing duly painted with one Seventy Seven Only
coat of red oxide with erection on site as per direction of engineer in charge with necessary grouting, cementing, plastering &
finishing complete.
215 225.00 Supplying and erecting HYLAM sheet on existing angle iron frame.for following thickness (F) 12mm 2311.89 Rupees Two Thousand Three Sq.Mtr
Hundred Eleven And Paise Eighty
216 44.00 Providing & erecting sheet steel powder coated MCB distribution board - flush / surface mounted fitted with busbar, neutral 1152.41 Rupees One Thousand One each
link, earth bar and DIN rail, confirms to IS 8623-1 & 3, IEC 61439-1 & 3 without MCB to house appropriate nos. of Hundred Fifty Two And Paise Forty
MCBs.(The DBs should be used of same company of MCB to be used) suitable for (A) single phase incoming and horizontal One Only
single phase outgoing (b) sheet steel double door (IP-43)(iii)8 way
217 356.00 Providing & erecting sheet steel powder coated MCB distribution board - flush / surface mounted fitted with busbar, neutral 3412.79 Rupees Three Thousand Four each
link, earth bar and DIN rail, confirms to IS 8623-1 & 3, IEC 61439-1 & 3 without MCB to house appropriate nos. of Hundred Twelve And Paise Seventy
MCBs.(The DBs should be used of same company of MCB to be used) suitable for Three phase incoming and single phase Nine Only
horizontal type outgoing per phase isolation type (PPI).(b) sheet steel double door (iii)8 way
218 6.00 Providing & erecting sheet steel powder coated MCB distribution board - flush / surface mounted fitted with busbar, neutral 3874.36 Rupees Three Thousand Eight each
link, earth bar and DIN rail, confirms to IS 8623-1 & 3, IEC 61439-1 & 3 without MCB to house appropriate nos. of Hundred Seventy Four And Paise
MCBs.(The DBs should be used of same company of MCB to be used) suitable for Three phase incoming and single phase Thirty Six Only
horizontal type outgoing per phase isolation type (PPI).(b) sheet steel double door (iv)12 way
219 44.00 supplying & erecting sheet steel powder coated cable end termination Box to be mounted on Top or Bottom of MCB 326.23 Rupees Three Hundred Twenty Six each
Distribution Box for housing / Covering Extra wires & cables suitable for following size of MCB Db Box. (C) Single Phase 8 And Paise Twenty Three Only
220 356.00 supplying & erecting sheet steel powder coated cable end termination Box to be mounted on Top or Bottom of MCB 689.83 Rupees Six Hundred Eighty Nine each
Distribution Box for housing / Covering Extra wires & cables suitable for following size of MCB Db Box. (G) Three Phase 8 And Paise Eighty Three Only
221 6.00 supplying & erecting sheet steel powder coated cable end termination Box to be mounted on Top or Bottom of MCB 796.89 Rupees Seven Hundred Ninety Six each
Distribution Box for housing / Covering Extra wires & cables suitable for following size of MCB Db Box. (H) Three Phase 12 And Paise Eighty Nine Only
222 9024.00 Providing & erecting Miniature circuit breaker single pole 6A to 25A suitable to operate on 240 V A.C system and having 123.22 Rupees One Hundred Twenty Three each
breaking capacity 10 KA to be erected in existing box confirming to IS 8826/1996 with ISI mark. cat III And Paise Twenty Two Only
223 44.00 Providing & erecting 240 V MCB double pole switch for motor & inductive load (C Curve) having 10 KA breaking capacity 329.26 Rupees Three Hundred Twenty each
& confirms to IS : 8828 in existing box having following capacity (A) 6 to 32 Amp. Cat III Nine And Paise Twenty Six Only
224 362.00 Providing & erecting Four pole Miniature Isolator A.C.22 duly confirms to IS 13947-3 in existing box. (b) for 63 amps cat III 655.49 Rupees Six Hundred Fifty Five And each
Paise Forty Nine Only
225 1086.00 Providing & erecting approved make ELCBs / RCCBs confirming to IS : 12640 and having sensitivity of 30 mA and short 2919.91 Rupees Two Thousand Nine each
circuit withsatnd capacity of 10KA and suitable for operation on single phase 240 V, 50 Hz having characterstic of quick Hundred Nineteen And Paise
action & tripping with all advance feature & do not incorporate any electronic component for following Max rating erected as Ninety One Only
directed.63 Amps DP -cat III
226 406.00 Providing & erected metallic vitrified danger notice board as per language suggested by Engineer Incharge for MEDIUM 69.69 Rupees Sixty Nine And Paise Sixty each
VOLTAGE installation to be erected as per IS-2551. Nine Only
227 490.00 Providing and erecting XLPE (IS:7098) - BB ISI armoured cable multistrand aluminium conductor for 1.1 KV . To be laid on 589.84 Rupees Five Hundred Eighty Nine metre
wall with necessary clamps or in existing trench / pipe of following size of cables. (E) 3 1/2 core 95 Sq. mm (50 Sq. mm 1/2 And Paise Eighty Four Only
228 1540.00 Providing and erecting XLPE (IS:7098) - BB ISI armoured cable multistrand aluminium conductor for 1.1 KV . To be laid on 648.42 Rupees Six Hundred Forty Eight metre
wall with necessary clamps or in existing trench / pipe of following size of cables.(F) 3 1/2 core 120 Sq. mm ( 70 Sq. mm 1/2 And Paise Forty Two Only
229 400.00 Providing and erecting XLPE (IS:7098) - BB ISI armoured cable multistrand aluminium conductor for 1.1 KV . To be laid on 2096.76 Rupees Two Thousand Ninety Six metre
wall with necessary clamps or in existing trench / pipe of following size of cables. (K) 3 1/2 core 400 Sq.mm ( 185 Sq. mm And Paise Seventy Six Only
230 500.00 Providing and erecting XLPE (IS:7098) - BB ISI armoured cable multistrand aluminium conductor for 1.1 KV . To be laid on 184.83 Rupees One Hundred Eighty Four metre
wall with necessary clamps or in existing trench / pipe of following size of cables.(A) 4 core 16 Sq. mm And Paise Eighty Three Only
231 490.00 Providing and erecting XLPE (IS:7098) - BB ISI armoured cable multistrand aluminium conductor for 1.1 KV . To be laid on 307.04 Rupees Three Hundred Seven And metre
wall with necessary clamps or in existing trench / pipe of following size of cables.(B) 4 core 35 Sq. mm Paise Four Only
232 46.00 END TERMINATIONS : Providing & fixing heavy duty flange type brass double compression type cable gland with rubber 75.75 Rupees Seventy Five And Paise each
ring for PVC insulated armoured cable complete with outgoing tails insulating tape etc. for following size of cables. (B) 3.5 Seventy Five Only
core 35/50 sq. mm
233 14.00 END TERMINATIONS : Providing & fixing heavy duty flange type brass double compression type cable gland with rubber 131.30 Rupees One Hundred Thirty One each
ring for PVC insulated armoured cable complete with outgoing tails insulating tape etc. for following size of cables. (D) 3 & And Paise Thirty Only
1/2 core 95 Sq. mm
234 14.00 END TERMINATIONS : Providing & fixing heavy duty flange type brass double compression type cable gland with rubber 140.39 Rupees One Hundred Forty And each
ring for PVC insulated armoured cable complete with outgoing tails insulating tape etc. for following size of cables.(E) 3 & Paise Thirty Nine Only
1/2 core 120 Sq. mm
235 16.00 END TERMINATIONS : Providing & fixing heavy duty flange type brass double compression type cable gland with rubber 369.66 Rupees Three Hundred Sixty Nine each
ring for PVC insulated armoured cable complete with outgoing tails insulating tape etc. for following size of cables. (J) 3 & And Paise Sixty Six Only
1/2 core 400 Sq. mm
236 184.00 Solder less crimping type Aluminium lugs confirming to IS suitable for cable of following size evenly climped with high 20.20 Rupees Twenty And Paise Twenty each
pressure tool & connected to switchgear terminals with brass / cadmium plated nut bolts in an approved manner.(D) 35/50 sq. Only
237 56.00 Solder less crimping type Aluminium lugs confirming to IS suitable for cable of following size evenly climped with high 40.40 Rupees Forty And Paise Forty Only each
pressure tool & connected to switchgear terminals with brass / cadmium plated nut bolts in an approved manner.(F) 95 Sq.mm.
238 56.00 Solder less crimping type Aluminium lugs confirming to IS suitable for cable of following size evenly climped with high 45.45 Rupees Forty Five And Paise Forty each
pressure tool & connected to switchgear terminals with brass / cadmium plated nut bolts in an approved manner.(G) 120 Five Only
239 64.00 Solder less crimping type Aluminium lugs confirming to IS suitable for cable of following size evenly climped with high 110.09 Rupees One Hundred Ten And each
pressure tool & connected to switchgear terminals with brass / cadmium plated nut bolts in an approved manner.(L) 400 Paise Nine Only
240 80.00 Making trench in soft soil of suitable width of 90 cm deep for laying cable or locating the fault all over the run and back filling 55.55 Rupees Fifty Five And Paise Fifty metre
the same and making the surface as normal ground. Five Only
241 700.00 Making trench in Hard Murrum / Tar Road of suitable width of 90 cm or required depth for laying any size of cable or 74.74 Rupees Seventy Four And Paise metre
locating the fault all over the run and back filling the same and making the surface as normal ground. Seventy Four Only
242 90.00 (B) If additional machinery like hammer driller or JCB use [Add] 357.54 Rupees Three Hundred Fifty Seven metre
And Paise Fifty Four Only
243 495.00 Providing & laying approved make Double walled corrugated pipes (DWC) of polyethylene(conforming to IS 14930 II )with 62.62 Rupees Sixty Two And Paise Sixty metre
necessary connecting accessories of same material at required depth in existing trench for laying of cable. below ground / Two Only
road surface for enclosing cable (A)50 mm outer dia
244 450.00 Providing & laying approved make Double walled corrugated pipes (DWC) of polyethylene(conforming to IS 14930 II )with 95.95 Rupees Ninety Five And Paise metre
necessary connecting accessories of same material at required depth in existing trench for laying of cable. below ground / Ninety Five Only
road surface for enclosing cable (C))90 mm outer dia
245 385.00 Providing & laying approved make Double walled corrugated pipes (DWC) of polyethylene(conforming to IS 14930 II )with 137.36 Rupees One Hundred Thirty Seven metre
necessary connecting accessories of same material at required depth in existing trench for laying of cable. below ground / And Paise Thirty Six Only
road surface for enclosing cable (D)120 mm outer dia.
246 9770.00 Supplying and erecting LED Indoor fittings with LEDs of wattage 0.2 watt to 0.5 watt assembled on single MCPCB, with 427.23 Rupees Four Hundred Twenty each
housing used as a heat sink shall be made of thick sheet steel confirming to IS: 513/CRCA/aluminium pressure die cast powder Seven And Paise Twenty Three
coated and high U.V. & corrosion resistance with diffuser housed in aluminium casted body with company mark/name 120 to Only
300 V, power factor more than 0.9, THD< 10%, CCT 3000 K to 65 K. Luminiare efficacy > 85 lumens/watt. LED efficiency
110 lumens/watt, LED driver efficiency > 85%. CREE/OSRAM/PHILIPS Lumileds/ NICHIA/ SEOUL/ Bridgelux make LED
used for luminiare (fitting required LM-79 & LM-80 certificates )( Note: below description have shown ranges of wattage
capacity of LED fittings. The Engineer Incharge may select any wattage capacity between the ranges shown).(A) Square/
Circular shaped Surface/Recessed Mount Downlight with provision for spring loaded mounting clips complete.IP20.(b) 11-15
watts, surge-2 KV Cat - III
247 1034.00 Supplying and erecting LED indoor fittings with LEDs of wattage 0.2 Watt to 0.5 Watt assembled on single MCPCB, with 165.64 Rupees One Hundred Sixty Five each
housing used as a heat sink shall be made of thick sheet Steel conforming to IS: 513/CRCA/ aluminium die cast powder And Paise Sixty Four Only
coated and high U.V. & corrosion resistance with diffuser with company mark/name 160V to 270V, Power Factor more than
0.95, THD < 15%, CCT 3000 K to 6500K, Luminaire efficacy> 85 lumens/watt ,LED , LED driver efficiency > 85 % (
fitting required LM-79 & LM-80 Certificates)(NOTE: Below description have shown ranges of Wattage capacity of LED
fittings.The Engineer incharge may select any wattage capacity between the ranges shown.)(A) Tube light with integral
driver(i) 5-10 Watts, Surge-2 KV, IP-20, conventional 1 to 2 feet Cat - III
248 1980.00 Supplying and erecting LED indoor fittings with LEDs of wattage 0.2 Watt to 0.5 Watt assembled on single MCPCB, with 535.30 Rupees Five Hundred Thirty Five each
housing used as a heat sink shall be made of thick sheet Steel conforming to IS: 513/CRCA/ aluminium die cast powder And Paise Thirty Only
coated and high U.V. & corrosion resistance with diffuser with company mark/name 160V to 270V, Power Factor more than
0.95, THD < 15%, CCT 3000 K to 6500K, Luminaire efficacy> 85 lumens/watt ,LED , LED driver efficiency > 85 % (
fitting required LM-79 & LM-80 Certificates)(NOTE: Below description have shown ranges of Wattage capacity of LED
fittings.The Engineer incharge may select any wattage capacity between the ranges shown.)(A) Tube light with integral driver
(v) 36-40 Watts, Surge-2 kV, IP-20, conventional 4 feet -Cat - III
249 338.00 Supplying and erecting led lamps with following wattage capacity of 220 to 240 voltage, minimum 15000 burning hours life, 188.87 Rupees One Hundred Eighty Eight each
500 V in built-surge protection,Polycarbonate diffuser, mounting suitable for E14 / E27 / B22 lamp holders, pf >= 0.5(iii) 10 And Paise Eighty Seven Only
to 15 watts, Cat-III
250 3346.00 Providing and erecting decorative wall bracket fittings complete with LED lamp and rust free fittings components mounted in 1712.96 Rupees One Thousand Seven each
chrome finish housing with holder ,clear/opaque glass diffuser complete erected with lead wires with minimum 15 wattage Hundred Twelve And Paise Ninety
capacity as per instruction engineer incharge/architect/authority .cat-III Six Only
251 272.00 Providing and erecting PVC body surface or pendant mounting LED Bulk type 9 watt Lighting fitting with electronic driver 787.80 Rupees Seven Hundred Eighty each
and lumen output from luminiare 720 lm, input voltage range 90-300 VAC, 50 Hz cool white (3000 to 6500 K), inbuilt driver, Seven And Paise Eighty Only
20 degree C to + 60 deg C working temperature, AL frame with Beam Angle 120 deg.
252 1448.00 Supply, Installation, Testing and Commissioning of 1200 mm (48") sweep, BEE 5 Star rated, Ceiling fan with Brush Less 2885.57 Rupees Two Thousand Eight each
Direct Current (BLDC) permanent ferrite magnet Motor, class of insulation: B, Rust free 3 nos.Aluminium blades, 2 nos. Hundred Eighty Five And Paise
canopies, shackle kit with earthing provision, copper winding, Power factor not < 0.9, Service Value (CMM/W) minimum Fifty Seven Only
6.85, Air delivery minimum 215 CMM, 350 RPM,230v (tolerance as per IS : 374-2019), THD < 10%, with remote unit for
Speed Control and all remaining accessories including safety pin, nut bolts, washers, temperature rise = 75 degree C (Max.),
suitable for 140 to 285 Voltage and rectifier circuit with surge, over current and overload protection , 50 Hz, Single phase AC
Supply, earthing etc. Complete as required.[ Make shall be approved by Engineer in Charge]
253 1000.00 Supply, Installation, Testing and Commissioning of 1400 mm (56") sweep, BEE 5 Star rated, Ceiling fan with Brush Less 3356.23 Rupees Three Thousand Three each
Direct Current (BLDC) permanent ferrite magnet Motor, class of insulation: B, Rust free 3 nos.Aluminium blades, 2 nos. Hundred Fifty Six And Paise
canopies, shackle kit with earthing provision, copper winding, Power factor not < 0.9, Service Value (CMM/W) minimum Twenty Three Only
6.85, Air delivery minimum 215 CMM, 350 RPM,230v (tolerance as per IS : 374-2019), THD < 10%, with remote unit for
Speed Control and all remaining accessories including safety pin, nut bolts, washers, temperature rise = 75 degree C (Max.),
suitable for 140 to 285 Voltage and rectifier circuit with surge, over current and overload protection , 50 Hz, Single phase AC
Supply, earthing etc. Complete as required.[ Make shall be approved by Engineer in Charge]
254 1122.00 Supplying & erecting Single phase approved make industrial exhaust fan suitable for medium duty ring mounted low noise 2054.34 Rupees Two Thousand Fifty Four each
operation suitable for medium duty having following dia size and maximum speed in RPM(A) 305 mm dia. 900 RPM, Cat II And Paise Thirty Four Only
255 1122.00 Providing suitable M.S. louver shutter of the Exhaust Fan. 368.65 Rupees Three Hundred Sixty Eight each
And Paise Sixty Five Only
256 20.00 Supplying and erecting approved make Octagonal pole made from HR sheet steel. The pole should be made as per IS. and 7561.87 Rupees Seven Thousand Five each
shall be coated with hot dip galvanizing as per IS 2629/2633/4759, suitable suspend local wind speed with integral Junction Hundred Sixty One And Paise
box consist of terminal plate of min 6mm Hylam sheet, standard profile 35mmX7.5mm Din-Rail for MCB Mounting, stud Eighty Seven Only
type terminal and arrangement for cable termination to be erected With Suitable foundation (Included) as per details given by
manufacturer considering site requirement. (C) 5 Mtr. Long 70 mm Top X 130 mm bottom dia, 3 mm thickness with
200mmX200mmX12mm base plate, 4-M16 Bolts and 600mm long with necessary G.I. J Bolts .Approx Pole weight 46 kg
257 20.00 Providing and erecting Street Light pole bracket comprising main B Class MS pipe of 4.2 cm/require outside dia. complete 626.20 Rupees Six Hundred Twenty Six each
with suitable B Class M.S. sleeve tubing of approx. 45cms.length and suitable for 76.5 mm /80mm / required size of pole top And Paise Twenty Only
having sufficient fasteners for fixing the brackets and having spread of 1.5.mtr. length with 110 deg.with vertical plane &
suitable welded stays, reducer and with check nuts complete painted with one coat of Red oxide / PU base primer and two
coats of Aluminium / PU paint. paint with following nos of arms. [A] Single Arm Bracket 1.5 Mtr
258 1.00 Supplying & erecting approved make Digital time switch having lithium cell 6 years operative and operate battery backup 1 3168.37 Rupees Three Thousand One each
channel day clock with 14 memory programme, suitable to operate on 240V + 5%, 16A with, floating contacts Minimum Hundred Sixty Eight And Paise
switching setup time 1 minimum & LCD display. Also comprised permanent ON/OFF switching. Programming switches & Thirty Seven Only
housed in fire proof thermoplastic enclosure & transparent cover erected as required with necessary connection erected as
259 20.00 Supplying and erecting LED street light / Flood light fittings with High power White LEDs wattage of 3 Watt and above 4248.06 Rupees Four Thousand Two each
assembled on single MCPCB, efficiency more than 130 lm/w and corrosion free High pressure die cast aluminum housing with Hundred Forty Eight And Paise Six
smooth finish powder coated and heat sink extruded aluminium with diffuser and Polycarbonate optics/ lenses, with toughened Only
glass with company mark/name engraved or embossed 160 to 270 V,Power Factor more than 0.95, THD < 10 %, CCT
K to 5700K,Uniformity ratio >0.45, Luminaire efficacy> 100 lumens/watt . LED driver efficiency > 85 %.( fittings required
LM-79 & LM-80 certificates)(NOTE: Below description have shown ranges of Wattage capacity of LED fittings.The Engineer
incharge may select any wattage capacity between the ranges shown.)(A) Street Light (IP-65), Surge protection -4KV integral
and ,Light must have 440VAC line supply with over-voltage protection. (ii) 48 - 59 Watts Cat-III
260 7.00 SITC of LED type twin Dome red Aviation obstacle light fixture min. 10 W low intensity type B as per ICAO annex-14, IP 66 11711.96 Rupees Eleven Thousand Seven each
operationg on 230 V AC 50 or 60 Hz input supply direct mounting tyoe complete as required as per specifications. Hundred Eleven And Paise Ninety
261 30.00 Supplying & erecting approved make SMC press moulded composite FRP. loop-in, loop-out approx. 2mm thick box 898.90 Rupees Eight Hundred Ninety Eight each
complete with Bakelite connector strip 5way(3P+N+E),DIN rail for mounting mob & hinged doors as per requirement having And Paise Ninety Only
locking arrangements with mounting clamp with nuts, bolts & washers suitable for erection on pole with cable clamps& earth
bolt of following size of box.(A) 300mm x 200mm x 100mm [deep]
262 140.00 Supplying and erecting Flexible PVC insulated multi strand multi core 1.1 kV grade ISI marked copper wires of following size 58.58 Rupees Fifty Eight And Paise Fifty Mtr.
to be erected as directed.(e) 1.50 Sq.mm 3 core round PVC sheathed Eight Only
263 4.00 Supplying & erecting funnel type earthing having earth plate of following size burried in specifically prepared earth pit 3 mtr, 7874.97 Rupees Seven Thousand Eight each
below ground with 40 kg charcoal and salt with alternate layers of charcoal & salt, 20 mm dia GI pipe with funnel with a wire Hundred Seventy Four And Paise
mesh for watering & bricks masanory block CI cover complete as per para 7.3 of IS 3043 with necessary length of double Ninety Seven Only
Galvanized Iron / copper earth wire no. 6 SWG bolted with lug to the plate and covered in 12 mm dia. G.I pipe 2.5 mtr long
complete connected to the nearest switch gear with end socket as per direction & duly tested by earth tester confirming to IS
(As per drawing) with following Specification. (C) with 60 x 60x 0.315 cms. Copper earth Plate
264 74.00 Supplying & erecting earth pit of minimum bore dia.150mm size approved make Earthing Electrode consisting Pipe-in-Pipe 8636.51 Rupees Eight Thousand Six each
Technology as per IS 3043-1987 made of corrosion free hot dipped G.I.Pipes having Outer pipe dia of 50mm having 80-200 Hundred Thirty Six And Paise Fifty
Micron galvanising, Inner pipe dia of 25 mm having 200-250 Micron galvanising, connection terminal dia of 12mm with One Only
constant ohmic value surrounded by highly conductive compound with high charge dissipation suitable for following type of
applications with chamber and heavy duty cover. (A)(approved make OEM has to submit test certificate including value of
earth resistance of installation duly stamped and signed by agency and officer Incharge has to ensure the value of earthing
resistane mentioned in test Certificate) & having back filling compound of (B) Inner chemical (CCM Compound)- Resistivity:-
0.2 ohm / meter testing as per IEC 62561-2017, Voltage drop:- < 1 volt at no load & dry form, Sulphar content:- <2%(C)
Back fill Compound :- Earthing compound should be capable to retain moisture for long time Necessary test report must be
submitted by Agency. (c) For Electrical Installation covering Transformer Neutrals, Lightning arrester Earthing, A.C.Plant &
Sensitive Computer System(like Automation, SCADA) i.e independent Earthing in normal soil. Length of Pipe : 3.00 mtrs,
Back filling Compound :2 nos Bags of 25 Kg.
265 2615.00 Providing and erecting required size HOT deep galvanized iron strip for earthing of H.T, OCB/ACB/Transformer LT panel 77.77 Rupees Seventy Seven And Paise Kg
board, motors etc. using proper clamp. Seventy Seven Only
266 245.00 Providing and erecting required size Copper strip for earthing of H.T, OCB/ACB/Transformer LT panel board, motors etc. 794.87 Rupees Seven Hundred Ninety Four Kg
using copper clamp. And Paise Eighty Seven Only
267 288.00 Providing and erecting Annealed bare Copper wire 8 to 16 SWG. 794.87 Rupees Seven Hundred Ninety Four Kg
And Paise Eighty Seven Only
268 660.00 Providing and erecting Hot deep Galvanized Iron strip wire 8 to 16 SWG. 77.77 Rupees Seventy Seven And Paise Kg
Seventy Seven Only
269 44.00 SITC of Vertical Air Terminal Solid aluminium with base-10 mm dia and 3000 mm long. Air Termination base tested for 9416.23 Rupees Nine Thousand Four each
conditioning, ageing test & Lightening impulse current withstand test: 100 KA of 10/350 Us waveform in an accerdited third Hundred Sixteen And Paise Twenty
party laboratory as per 6.3 & 6.4 of IEC 62561-1 2017 protocol with MAST 34 mm dia 3000 mm long-Cold Galvanized. Three Only
270 1600.00 SITC of 8 mm dia solid Aluminium Conductor for roof top mesh grid and tested as per IEC 62561- 2 conducted in the Govt. 299.97 Rupees Two Hundred Ninety Nine metre
accredited thirty party laboratory to meet the requirement of IS/IEC 62305 with Required Accessories - Aluminium Holding And Paise Ninety Seven Only
clamp at every 1 mtr distance, Aluminium/SS cross splicer at every crossing of Alu. conductor, Expansion piece with
connectors at every 20 mtr distance, Aluminium straight Splicer to connect conductors. All Accessories should be tested as
per IEC 62561-1 2018 Cl. 6.3 for conditioning & Ageing Test & 6.4 for Lightning impulse current withstand test: 100 kA of
10/350µs waveform(Ageing & Electrical test ) conducted in a sequence manner & tested in the Govt. accredited Third party
laboratory to meet the requirements of IS/IEC
271 1390.00 SITC of 10 mm MS Round solid conductor having smooth surface should be tested and use exclusively for lightening 728.21 Rupees Seven Hundred Twenty metre
protection (vertical Riser / down conductor which shall be concealed in column) to meet the requirement of IS IEC 62305 with Eight And Paise Twenty One Only
accessories. Earthing stud of dimensions SS-75 mm OD plate with 10 mm dia tail connector used in structural steel ring
earthing system to meet the requirement of IS / IEC 62305. (For interconnecting the column and Terrace AL Conductor / strip/
flat SS cross connector to connect Earth fixing oint to vertical raiser / down conductor. SS straight splicer at every 4 mtr to
connect MS conductor in column. Bonding / Rehar clamp at every 3 mtr suitable for innerconnecting round conductor with
reinforcement inside the concrete for structural earthing system, SS connector - To connect external conductor 8-10 mm with
earth fixing point. All accessories shall be test as per IEC 62561 I 2018 CI.6.3 for conditioning & ageing test & 6.4 for
lightening impulse current withstand test:100 KA of 10/350 Us waveform (Ageing & Electrical test) conducted in a sequence
manner & tested in the Govt. accerdited Third party laboratory to meet the requirements of IS/IEC6230.
272 950.00 SITC of Galvanized steel flat 25X6 mm thickness from earth electrode directly in ground as required. Zinc coating 500 g/m 154.53 Rupees One Hundred Fifty Four metre
square (approx 70 micron coating) tested used exclusively for lightening protection earthing system and ring equipment And Paise Fifty Three Only
273 32.00 SITC of 14.2 mm dia 3 mtr long earth electrode of high tensile steel electrode with 250 micron copper bonding & 1 bag of 5992.33 Rupees Five Thousand Nine Per Set
carbon fill based environment friendly backfill tested as per IEC 62561-7 in NABL accerdited Laboratory and suitable Hundred Ninety Two And Paise
stainless steel double sided clamp. Eco friendly rust proof heavy duty weather proof polythylene earth pit chamber with Thirty Three Only
following dimensions: 254 mm dia (top) 330 mm dia (bottom) & 260 mm (height).
274 44.00 SITC of stainless steel cross connector for 8 mm dia aluminium alloy round conductor & 10 mm copper bonded conductor at 1073.63 Rupees One Thousand Seventy each
cross junction, test parameter salt spray test (IEC 62561-1)-No sign of corrosion complete as required. Three And Paise Sixty Three Only
275 21100.00 Providing & erecting ISI mark Medium class RIGID PVC Pipes of following size complete to be erected on / in wall or ceiling 24.24 Rupees Twenty Four And Paise metre
erected with necessary PVC fittings & junction boxes fixed with adhesive solution & clamps with following dia of pipes, in Twenty Four Only
approved manner as directed.(a) 20 mm
276 116300.00 Providing & erecting ISI mark Medium class RIGID PVC Pipes of following size complete to be erected on / in wall or ceiling 33.33 Rupees Thirty Three And Paise metre
erected with necessary PVC fittings & junction boxes fixed with adhesive solution & clamps with following dia of pipes, in Thirty Three Only
approved manner as directed.(b) 25 mm
277 65000.00 Supplying, drawing, Testing and commissioning of Cat6A UTP 4 pair, 23 AWG solid copper cable in existing conduit/ on 63.63 Rupees Sixty Three And Paise metre
surface, U/FTP, LSZH, Non- Plenum, Horizontal (solid) Cable suitable for high speed data networking application supporting Sixty Three Only
upto 10Gbps over a 100 meter channel. The 4 Unshielded Twisted Pairs (UTP) cable with color coded insulation for easy
indentification should have FLAME PROPERTIES i.e. Flammability Test - IEC 60332-1, Smoke Density - IEC 61034, LSZH
standards compliance: ANSI/TIA-568 C.2, ISO/IEC 11801, IEEE 802.3an, RoHS. Delay Skew should be < 45NS. The outer
Cable Diameter should be 7.5 + 2 mm. Cable should have been tested and verified by UL/ ETL etc. complete as required.-1
Run of cable-Note: Wiring/Fiber installation shall include numbering, Ferruling, termination and testing of cables at both ends.
Fiber Splicing, Testing with OTDR etc. shall be the part of installation of the fibers.Test Reports of Passive Items with dully
authorized by OEM shall be submitted for 25 years warranttee.All Active devices shall have minimum 5 years of support from
the date of handover.
278 31100.00 Supplying, drawing, Testing and commissioning of Cat6A UTP 4 pair, 23 AWG solid copper cable in existing conduit/ on 106.05 Rupees One Hundred Six And metre
surface, U/FTP, LSZH, Non- Plenum, Horizontal (solid) Cable suitable for high speed data networking application supporting Paise Five Only
upto 10Gbps over a 100 meter channel. The 4 Unshielded Twisted Pairs (UTP) cable with color coded insulation for easy
indentification should have FLAME PROPERTIES i.e. Flammability Test - IEC 60332-1, Smoke Density - IEC 61034, LSZH
standards compliance: ANSI/TIA-568 C.2, ISO/IEC 11801, IEEE 802.3an, RoHS. Delay Skew should be < 45NS. The outer
Cable Diameter should be 7.5 + 2 mm. Cable should have been tested and verified by UL/ ETL etc. complete as required.-2
Run of cable-Note: Wiring/Fiber installation shall include numbering, Ferruling, termination and testing of cables at both ends.
Fiber Splicing, Testing with OTDR etc. shall be the part of installation of the fibers.Test Reports of Passive Items with dully
authorized by OEM shall be submitted for 25 years warranttee.All Active devices shall have minimum 5 years of support from
the date of handover.
279 2509.00 Supplying, Installation, Testing and commissioning of CAT6A Copper Information Outlet (IO) with face plate of color as per 258.56 Rupees Two Hundred Fifty Eight each
site requirement, should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D. All copper And Paise Fifty Six Only
Cable and Components should be from same OEM to maintain compatibility and interoperability etc. complete as required.-
Note: Wiring/Fiber installation shall include numbering, Ferruling, termination and testing of cables at both ends. Fiber
Splicing, Testing with OTDR etc. shall be the part of installation of the fibers.Test Reports of Passive Items with dully
authorized by OEM shall be submitted for 25 years warranttee.All Active devices shall have minimum 5 years of support from
the date of handover.
280 30.00 Supplying and fixing of 15U size Wall Mount Rack having Fixed Structure with 0.8mm CRCA Sheet, completely knocked- 11409.97 Rupees Eleven Thousand Four each
down condition (CKD) Shape, Vertical Mounting Rail 1.6 mm with 'U'Marking, Minimum 2 cable entry/exit provision at Top Hundred Nine And Paise Ninety
and bottom with rubber protection, Front 5mm Toughened Glass with lock, wall mounting kit, Powder coated Color- RAL- Seven Only
7035, complied with UL & RoHS, 2 x 6 sockets 16A power distribution units, 3 numbers closed cable organizer, Hardware
mounting screws packet of 20 x 1 number, etc. complete as required.-Note: Wiring/Fiber installation shall include numbering,
Ferruling, termination and testing of cables at both ends. Fiber Splicing, Testing with OTDR etc. shall be the part of
installation of the fibers.Test Reports of Passive Items with dully authorized by OEM shall be submitted for 25 years
warranttee.All Active devices shall have minimum 5 years of support from the date of handover.
281 7.00 Supplying and fixing 42U Rack with 6 inch Castor wheels and front brake Floor Standing Rack with Main Frame Pillar of 28206.27 Rupees Twenty Eight Thousand each
1.6mm CRCA Sheet with removable side panels, L- Shape adjustable Vertical Mounting Rail of 2mm with 'U'Marking Two Hundred Six And Paise
completely knocked-down condition (CKD) Shape, fitted with 4 number cooling fans, minimum 8nos two line cable entry /exit Twenty Seven Only
provision at top and bottom with rubber protection, Front door 5mm Toughened Glass with MS frame or MS perforated with
lock, Rear MS vented or perforated door, Powder coated Color- RAL- 7035 or black, complied with UL & RoHS, 2 x
sockets 16A power distribution units, 3 numbers closed cable organizer, Hardware mounting screws packet of 20 x 1 number,
etc. complete as required.-Note: Wiring/Fiber installation shall include numbering, Ferruling, termination and testing of cables
at both ends. Fiber Splicing, Testing with OTDR etc. shall be the part of installation of the fibers.Test Reports of Passive Items
with dully authorized by OEM shall be submitted for 25 years warranttee.All Active devices shall have minimum 5 years of
support from the date of handover.
282 2509.00 Supplying, Installation, Testing and commissioning of following CAT6A Patch Cord should have ETL/UL verification 148.47 Rupees One Hundred Forty Eight each
program certificate for compliance with ANSI/TIA-568.2-D etc. complete as required.-Copper Patch Cords of length 1m (3ft)- And Paise Forty Seven Only
Note: Wiring/Fiber installation shall include numbering, Ferruling, termination and testing of cables at both ends. Fiber
Splicing, Testing with OTDR etc. shall be the part of installation of the fibers.Test Reports of Passive Items with dully
authorized by OEM shall be submitted for 25 years warranttee.All Active devices shall have minimum 5 years of support from
the date of handover.
283 2509.00 Supplying, Installation, Testing and commissioning of following CAT6A Patch Cord should have ETL/UL verification 346.43 Rupees Three Hundred Forty Six each
program certificate for compliance with ANSI/TIA-568.2-D etc. complete as required.-Copper Patch Cords of length 3m And Paise Forty Three Only
(10ft)-Note: Wiring/Fiber installation shall include numbering, Ferruling, termination and testing of cables at both ends. Fiber
Splicing, Testing with OTDR etc. shall be the part of installation of the fibers.Test Reports of Passive Items with dully
authorized by OEM shall be submitted for 25 years warranttee.All Active devices shall have minimum 5 years of support from
the date of handover.
284 119.00 Supply, Installation, Testing & Commissioning of Staggred 24 Port Unshielded, Loaded with Category 6A RJ45 Unshielded 20430.28 Rupees Twenty Thousand Four each
Modular Jack, Keystone information outlet (I/O) in accordance with ANSI/TIA 568.2-D, IEC 60603-7-4 2nd Edition, Hundred Thirty And Paise Twenty
ISO/IEC 11801, ROHS Compliant. The I/O should have minimum 750 mating cycle and 200 insertion cycle and ETL 04- Eight Only
Connector Channel Verified, 1U height, Black with integrated cable support bar, clear label marks and earthing plug for UTP
cable termination at rack end complete etc as required.-Note: Wiring/Fiber installation shall include numbering, Ferruling,
termination and testing of cables at both ends. Fiber Splicing, Testing with OTDR etc. shall be the part of installation of the
fibers.Test Reports of Passive Items with dully authorized by OEM shall be submitted for 25 years warranttee.All Active
devices shall have minimum 5 years of support from the date of handover.
285 2700.00 SITC of O. F. Cable 06F Outdoor - Armoured Unitube SM - HDPE Sheath [Approved by Competent Authority i.e. not Below 50.50 Rupees Fifty And Paise Fifty Only Mtrs.
the rank of Executive Engineer ]-Note: Wiring/Fiber installation shall include numbering, Ferruling, termination and testing of
cables at both ends. Fiber Splicing, Testing with OTDR etc. shall be the part of installation of the fibers.Test Reports of
Passive Items with dully authorized by OEM shall be submitted for 25 years warranttee.All Active devices shall have minimum
5 years of support from the date of handover.
286 60.00 SITC of LIU 12 PORT Rack Mount - Loaded (LC) SM 6901.33 Rupees Six Thousand Nine each
[Approved by Competent Authority i.e. Hundred One And Paise Thirty
not Below the rank of Executive Engineer ]-Note: Wiring/Fiber installation shall include numbering, Ferruling, termination and Three Only
testing of cables at both ends. Fiber Splicing, Testing with OTDR etc. shall be the part of installation of the fibers.Test Reports
of Passive Items with dully authorized by OEM shall be submitted for 25 years warranttee.All Active devices shall have
minimum 5 years of support from the date of handover.
287 720.00 SITC of PIGTAIL LC SM SIMPLEX LENGTH- 1m 779.72 Rupees Seven Hundred Seventy each
[Approved by Competent Authority i.e. not Nine And Paise Seventy Two Only
Below the rank of Executive Engineer ]-Note: Wiring/Fiber installation shall include numbering, Ferruling, termination and
testing of cables at both ends. Fiber Splicing, Testing with OTDR etc. shall be the part of installation of the fibers.Test Reports
of Passive Items with dully authorized by OEM shall be submitted for 25 years warranttee.All Active devices shall have
minimum 5 years of support from the date of handover.
288 236.00 SITC of PATCH CORD LC-LC SM DUPLEX LENGTH- 3m 1901.83 Rupees One Thousand Nine each
[Approved by Competent Hundred One And Paise Eighty
Authority i.e. not Below the rank of Executive Engineer ]-Note: Wiring/Fiber installation shall include numbering, Ferruling, Three Only
termination and testing of cables at both ends. Fiber Splicing, Testing with OTDR etc. shall be the part of installation of the
fibers.Test Reports of Passive Items with dully authorized by OEM shall be submitted for 25 years warranttee.All Active
devices shall have minimum 5 years of support from the date of handover.
289 14.00 SITC of 20 x SFP ports 647939.24 Rupees Six Lakh(s) Forty Seven each
4 x Combo 10/100/1000BASE-T/SFP ports Thousand Nine Hundred Thirty
4 x 10G SFP+ ports Nine And Paise Twenty Four Only
6 kV surge protection on all RJ-45 access ports
Switch Resource Management (SRM) for flexible management of system resources
Redundant Power Supply (RPS) support
MPLS L2VPM/L3 VPN support
Full L3 routing protocol support including OSPF, BGP, and ISIS for IPv4/IPv6
SDN-enabled switch, compatible with Openflow
10-GbE SFP+ to SFP+ 1M Direct Attach Cable [Approved by Competent Authority i.e. not Below the rank of Executive
Engineer ]-Note: All Active devices shall have minimum 5 years of support from the date of handover.
290 119.00 SITC of 24 x 10/100/1000BASE-T PoE ports 4 x Gigabit RJ45/SFP Combo ports Advanced L2 switching and security 31996.80 Rupees Thirty One Thousand Nine each
features L2+ Static Routing Optional “standard mode” or “surveillance mode” management user interface 193 W PoE budget Hundred Ninety Six And Paise
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]Note: All
Active devices shall have minimum 5 years of support from the date of handover.
291 476.00 SITC of Maximum distance of up to 10 km Hot-pluggable Single-mode fiber 1000BASE-LX (IEEE 802.3z standard) Duplex 4801.54 Rupees Four Thousand Eight each
LC connector MSA, RoHS-compliant [Approved by Competent Authority i.e. not Below the rank of Executive Engineer Hundred One And Paise Fifty Four
]Note: All Active devices shall have minimum 5 years of support from the date of handover. Only
292 13.00 SITC of Digital / PCM / TDM EPABX System having SMT design, system with flexible universal slots. Inbuilt Auto 174606.78 Rupees One Lakh(s) Seventy Four each
attendant facility, Minimum 15 Nos. conference, Analog extension line, Calling GSM, E&M line, PRI / EI & VOIP program Thousand Six Hundred Six And
me through Analog telephone digital key from Ethernet, public address cord, shall have unrestricted simultaneous dialing Paise Seventy Eight Only
facility, QSIG protocol on PRI, 95 / STD / ISD / Local-Locking, Class of Service, Quick Dial-Single Digit dialing of any two
external number, Once only ring device, Chairman / Secretary - Do not disturb Facility, Power Down Mode, Hot Line, Hot
Outward Dialing, Day Night Mode, Auto Call Back, Barge-in, Call Pick Up & Call Transfer, Call transfer while Ringing with
Voice Guide System, (DISA), Caller ID (CLI), CLI Base ECF, CLI Base routing Internet Ready Port, External Music Port,
Call Budgeting, Call Most Calculation (ASMDR), DID Direct Inverse Dialing, External Music Input, Fax Homing, Global
Directory Printing with following capacities [[Approved by Competent Authority i.e. not Below the rank of Executive
Engineer ] [E] No of Extension 128, No of Junctions 24, No of expandable ports : 512, Operators Console - 01 Compatible :
ISDN and Networking
293 996.00 Providing and erecting IP Phone with display with all IP system supported [[Approved by Competent Authority i.e. not Below 5649.94 Rupees Five Thousand Six Hundred each
the rank of Executive Engineer ] Forty Nine And Paise Ninety Four
294 Supplying Installation Testing and Commissioning of 5MP/6 MP IP IR Bullet Camera having following specifications, type of
lens and features etc :-
1) Type of Camera: Bullet Camera
2) Image Sensor: 1/2.8" or better progressive Scan CMOS get color image even at night condition
3) Signal System: PAL/NTSC
4) Minimum Illumination: 0.006Lux@ F1.4, AGC ON, 0 lux with IR or better
5) Imaging: 1/3s to 1/30000s, Auto Gain Control, White Balance- Auto, Back Light Compensation, Multi zone Privacy
Masking, HLC, Digital Watermarking. 6) On Screen Display: Camera should display Camera title, Date & Time in live &
recorded video both.
7) Signal to Noise Ratio: > 50 dB
8) Lens Type & Focus: as given below.
9) Day & Night: True Day & Night High Performance Mechanical IR cut filter with auto switch, IR Source- Inbuilt IR LED's
with effective distance upto 50 Mtrs integrated IR and 30 Mtrs for colour view in night.
10) Video Compression (Minimum): H.265 or better, Audio:- G.711U/A, G.711Mu, G.726, AAC, G.723
11) Wide Dynamic Range: WDR (120dB or more)
12) Digital Noise Reduction: DNR (2D/3D) On/Off
13) Streaming: Triple streaming, configurable
14) Video Streaming & Frame Rates: Triple streaming , configurable Main stream: 5MP/6MP @25/30 fps, Sub streams:
D1@25/30 fps or better
15) Image Setting: Rotate Mode, saturation, brightness, contrast, sharpness adjustable through client software or web browser
16) Profile Management: User configuration import, export
17) Security: User Authentication, Digital Water Marking
18) Onboard Storage: Camera should support built-in Micro SD/ SDHC/ SDXC Card slot upto 512 GB. It should be supplied
with minimum 128GB memory Card.
19) Recording Management: Format SD, overwrite, storage management, video to NAS device,
199.00 20) Edge Analytics: Tripwire, Intrusion, Motion Detection 23103.75 Rupees Twenty Three Thousand each
21) Alarm Trigger : Motion/tampering detection; network disconnection detection; IP conflict detection; memory card state One Hundred Three And Paise
detection; memory space detection Seventy Five Only
22) Alarm Support: It should have 1/1 Alarm In/ Out Port
23) Audio Support: It should have 1x Built-In Mic and 1/1 Audio In/ Out Port for external Mic. and Speaker (As per site
requirement) with G.711U/A / G.711Mu/ AAC/ G.726 audio compreesion
24) Network Protocol: SFTP, IPv6, IPv4, DNS,RTCP, NTP, RTP, HTTP, HTTPS, SNMP TCP/IP, PPPoE, NFS, UDP,
ICMP, SSL, DHCP, SMTP, RTSPS, unicast,
25) System Capability: ONVIF
26) VMS: Camera shall support open source VMS
27) Cyber Security: trusted boot, AES 256-bit Encryption, Configuration encryption, trusted execution, Digest, security logs,
account lockout,
video encryption, IP/MAC filtering, HTTPS, trusted upgrade.
28) Ethernet: 1 RJ 45 10/100 Ethernet port
29) Power Input: The camera should support simultaneous dual power input—12 VDC (via power adapter) and PoE—to
ensure continuous operation in the event of a failure in one power source.
30) Power Requirement: 12VDC/24V DC/PoE (802.3af)/ePoE
31) Enclosure: IP67 weather proof, IK10
32) Operating Condition: Ambient Temperature:- (- )05°C to 50°C, humidity 95% (max) (non-condensing)
33) IR life: 40000 hours or higher
34) Video Bit rate: 32 KBPS - 8 MBPS or better
35) Standards: BIS with ER, STQC Certified, CE, FCC and RoHS - 5MP/6MP IP IR 2.7 to 4 mm ~12 to 13.5mm or better
Varifocal Motorized lens outdoor Bullet Camera
295 Supplying Installation Testing and Commissioning of following Channel Network Video Recorder (NVR) with camera
licenses to record for all channels having specifications and features etc as mentioned below :
1) Network Video Recorder Embedded/ Installed OS (Linux) along with Camera Licenses to record per NVR and to provide a
live view, storage and simultaneously Multi-channel playback of all IP camera or more and must be ONVIF with minimum
support of 384 Mbps incoming Bandwidth.
2) NVR should support video compressions : H.265 or better, H.264, MJPEG.
3) Must support 1 channel RCA Input, 2 channel RCA Output for Two-way Talk with G.711U/A, G.711u, PCM, G726 audio
4) Intelligent auto power on when power resumes after power outage.
5) Storage: It should support minimum 8 SATA Slots with 20TB capacity/ Slot and RAID support of RAID 0/1/5/6/10.
6) Connectivity Interface : 2 Nos. x 10/100/1000 Mbps Ethernet Ports, 1x RS485, 1x RS232, 1x eSATA Port
7) Backup Interface : Its should have 4 Nosx USB port (2x USB3.0, 2xUSB2.0)
8) Video Output Ports: 2x HDMI and 2 VGA
9) Alarm Ports: It should have 16/8 Ch In/ Out ports to connect various type of external sensors and output devices like
hooter/ Siren etc.
10) Email & SMS Altert options: Option for SMS/ Email Alerts to minimum 5 designated mobile number for power failure,
HDD failure, vandalism, tempring, network disconnection and panic
11) Web & Mobile Application: Web, Mobile app ( For iPhone, iPad, Android Phone) for alerts and viewing.
12) Protocols: HTTP, HTTPS, TCP/IP, IPv4/IPv6, UDP, DHCP, DNS, SMTP, UPnP, IP Filter, PPPoE, FTP, DDNS, Alarm
Server, IP Search, Multicast, Auto Registration, ONVIF (Profile T, Profile S, Profile G), CGI, SDK and OEM Cloud for
remote monitoring without any public IP need.
13) Standards: CE, FCC, RoHS, BIS Certified
14) Power Supply : Should support AC100-240V, 50/60Hz Power supply.
15) Operating Condition : -5°C to 50°C, humidity 90% (max) (non-condensing)
16) The VMS application shall support all the features & functionalities of the offered cameras.
17) VMS should consist Licenses for all channels to record Cameras with General, motion detection, intelligent, alarm and
POS recording modes. VMS should be provided with Camera Licenses, with no dependency of VMS licenses by binding with
the MAC address of the cameras to achieve the functionality.
18) The NVR OEM shall be responsible for providing a mobile application compatible with both Android and iOS devices,
enabling remote monitoring and playback of cameras/NVR footage.
19) The OEM must provide its own DDNS server hosted in India, eliminating the need for a public IP address for remote
monitoring over the Internet.
20) Must support Continuous, Alarm, Motion, Instant, Panic Recording Mode
21) It should support Resolution: 32MP; 24MP; 16MP; 12MP; 8MP; 5MP; 4MP; 1080p; 720p; D1; CIF; QCIF
22) When alarm recording is enabled and an event occurs, you can click the alarm icon on monitoring page to view the alert
details. The snapshot function is supported on monitoring and playback page
23) The Network Video Recorder (NVR) shall be configured to send email whenever a system message is created or an alarm
event occurs. The email server shall be a valid SMTP server. Each recipient email address shall be configured to receive any
combination of critical, warning, or informational messages or alarm notifications. When an alarm occurs, the email message
includes the NVR name, time of alarm and a list of camera that is configured to record upon alarm
24) It should have Web and GUI interface.
25) Built-In Artificial Intelligence: NVR should have built-in AI :-
- 2 Channel face detection and recognition, - Minimum
4 Channel perimeter protection, - Minimum 8 Channel Smart Motion Detection
7.00 26) Face Recognition Database Capacity: It should support total Blacklist and Whitelist capacity of Minimum 20,000 Faces or 55451.02 Rupees Fifty Five Thousand Four each
more with Face Detection speed of 12 face images/sec and facility to add Name, gender, birthday, address, credential type, Hundred Fifty One And Paise Two
credential No., countries & regions and state to each face image. Only
27) Face & Human Attributes Search: Search Pictures/ Video by Gender, age group, glasses, expressions, face mask, beard,
Top color, top type,
hat, bag, age, gender and umbrella.
28) ANPR Capability: It should support ANPR Camera with License plate, plate color, vehicle body, vehicle model, vehicle
logo, calling, seatbelt, vehicle registration location etc vehicle attributes.
29) Alarm Notifications based on: Motion detection, video tampering, video loss, scene changing, PIR alarm, Camera external
alarm, Face detection, face recognition, perimeter protection (intrusion and tripwire), ANPR, people counting, stereo analysis,
crowd distribution, heat map, Disk Full, Storage Error, IP Conflict and abnormal behavior of fan, cybersecurity exception.
30) Alarm Notification should be linked with Recording, snapshots, Camera external alarm output, buzzer, logs, presets and
31) General AI Based Search: Search Pictures by channel, time, event type, target classification (Fall Detection, People
Approach Detection, People No. Exception Detection, People Staying Detection, Violence Detection.
32) Smart playback function: Should support smart search for the selected area in the video and smart playback to improve the
playback efficiency
33) VCA (Video Content Analytic): Should support multiple video contented analytics based on camera analytics
34) Analytics by NVR: Perimeter protection and face recognation
32 Channel Network Video Recorder (NVR) having display split :- Main screen: 1/4/8/9/16/25/32(36), 2nd screen: 1/4/8/9/16
296 7.00 Supply, Installation, Testing and commissioning of Monitor, 55" LED high resolution monitor with high performance 79572.85 Rupees Seventy Nine Thousand each
240VAC, 50 Hz. 24x7 for spot display including all accessories as per specifications and as required to complete the system. Five Hundred Seventy Two And
Paise Eighty Five Only
297 7.00 Supply, installation, testing & commissioning of Client Workstation as per following specifications:Intel Core i7-8700K or 196836.88 Rupees One Lakh(s) Ninety Six each
better, 4.2GHz, OS - Genuine Microsoft Microsoft® Windows 10 Enterprise/IOT 64 Bit, RAM - 16GB, OS - 480 GB Thousand Eight Hundred Thirty Six
SSD/SATA, Graphic Card - In-built Processor Graphics (GPU):Intel® HD Graphics 630 or Intel Q470 Processor, supporting And Paise Eighty Eight Only
2 Monitors, 01 LAN 01GBPS, Audio IN & Out, USB3.0, Keyboard and Mouse, associated cables etc complete.
Approved Makes : Pelco / Avigilon / Axis / Allgovision / Dell / HP
298 41.00 Supplying, Installation, Testing and Commissioning following capacity Serveillance grade Hard Disk with upto 256MB/s 21225.15 Rupees Twenty One Thousand Two each
Transfer Rate, 256 MB Cache, 7200 RPM Disk Speed, 3.5 inch form factor, SATA Interface, BSMI, ICES-003/NNB-003, Hundred Twenty Five And Paise
CE, FCC, KC, Maghreb, RCM, UKCA, VCCI, CB-Scheme, TUV, UL Certifications. 10TB (Terabytes) Fifteen Only
299 7.00 Supply, Installation Testing & Commissioning 15 Mtr. HDMI Interface Cable as per the detailed Specifications supports 1777.60 Rupees One Thousand Seven each
transmission of 4K Signals as per the detailed Specifications Hundred Seventy Seven And Paise
300 Supplying, Erecting, Testing & Commissioning the passenger / stretcher lift having following main features:The Rates of the
following items are for the lift without Machine room (MRL type) (A) GENERAL DESCRIPTION OF LIFTS. [1]
GEAR LESS LIFT DRIVE (MRL) comprising of High Starting torque Lift 3 phase 440 V A. C. Permanent Magnet
Synchronous motor of proper rating with high efficiency shall be used.[2] Micro processor based / PLC, ACVVVF, vector
control drive with encoder feedback closed loop system shall be used for lift car and door operation which shall be full
collective selective operation hall call demand response, UP/DOWN hall stops, Main, Up/ Down Contactor with overload and
phase reversal relay and safety controls.[3] Car with M S platform with bracings of adequate size and to sustain the impact
load cabin + passenger with safety factor of fire for steel and side panels of Stainless steel of sheet of grade 304 duty. Car
ceiling will be S.S. finishes with aesthetic appearance with LED ceiling lights. Car flooring shall be of anti skid PVC with
choice of colour of engineer in charge. Car doors shall be of stainless steel grade 304, hairline finish with centre opening /
telescopic automatic doors. Car panel will also be S.S. 304 finished with emergency stop device, mechanical door safety
device, facility of auto/ attended mode. All car panel buttons and all floor switches must be with brail language as per lift
act.[4] All landing doors must be fire rated for 2 hour shall be fully automatic centre opening/ telescopic opening made of
hairline finish steel grade of 304 with key holes and infrared curtains with Unlocking facility from outside [5] Appropriate
battery operated emergency light in the car along with alarm switch shall be provided. Also, Emergency Light & Fan should
start immediately without any Time Delay as soon as power fails. [6] Digital scrolling indicator system for up-down arrow
along with floor position indicator shall be provided inside the car and at all floors.[7] Full height infra red curtain with
multiple cross / crossing light beams shall be provided.[8] Automatic Rescue Device (ARD) shall be provided accordingly of
passenger capacity with Manual Rescue Operation ( Manual Cranking Facility).[9] Audio visual indication in the lift car
showing over loading shall be provided such that doors kept open till excess load is removed.[10] Spring buffers/PU Buffers
shall be provided.
[11] Car fan as per passenger capacity with automatic sleep timer shall be provided.[12] Voice annunciator with suitable music
shall be provided in lift car. [13] Self diagnostics system for operational and safety parameters shall be provided in control
panel. [14] Mechanical over speed governor with governor calibration as per actual site parameters and submission of
calibration certificate submission, door key holes in the floor doors, fireman switch shall be provided.[15] Lift machine
hoisting arrangement in the lift machine room and monkey ladder for lift pit should be provided by the lift agency, along with
the other steel structure works, foundations for the machine etc…[16] In the hoist way fascia plate shall be provided without
any extra cost, where ever required as / if directed by engineer in charge.[17] Permanent wiring with necessary safety devices
like RCCB in all circuit, Over Voltage Under Voltage protection and THD eliminator in circuit for lift machine room and lift
well with proper numbers of light points, with fixtures, exhaust fan and plug points shall be provided by the agency. Only
phase Power Supply shall be made available by department in lift machine room. Necessary Earthing as per Lift Act/Rules
shall be arranged by Lift Agency. [18] Any civil/ electrical works for additional and alteration in lift shaft and machine room
related to erection of lift shall be made by lift agency without any extra cost. (granite/marble fixing around all landing door
openings are not in lift agency’s scope.)
1.00 [19] Agency has to provide all working drawings and documents and liaison services for obtaining all necessary permission 3132326.13 Rupees Thirty One Lakh(s) Thirty each
from lift inspector and other authorities.[20] acrylic transparent licence/display A4 size holder in lift car[20A] As per statutory Two Thousand Three Hundred
requirement of Govt. Of Gujarat lift & escalator act 2000, lift agency has to provide 1. Car top safety barricade 2. Push & talk Twenty Six And Paise Thirteen
communication system.3. Fireman's switch operation at Ground Floor. 4.carrying out third party lift inspection during/after lift Only
erection and provide report by third party authorized by concern licensing authority 5.agency has to provide third party
insurance upto completion of free maintenance period and submit the document for the same.[21] Car Panel Operating
Buttons with floor position indicator/buttons must be of Auto Glow type clearly visible when view from inside cabin. [22] For
Physically Handicapped person Full Length Handrails of hairline finish steel grade of 304 should be provided at appropriate
height on the Rear & Side Wall Panels in Lift Car.[23] With Necessary kVA rating voltage controlled Stabilizer suitable for
your controller, drive and all equipments of lift.
[24] Necessary rating of DP Elcb and FP Elcb required for lift is in scope of work which rating is sugested by CEICED
Department (electrical Inspector)-20 passengers . Ground plus 10 upper floors with Rated Speed of 2.0 /2.5 m/sec with
micro price/PLC control and ACVVVF. drive (B) With General PLUS ADDITIONAL SPECIAL FEATURES attached
herewith. Prem. Cat.
301 Supplying, Erecting, Testing & Commissioning the passenger / stretcher lift having following main features:The Rates of the
following items are for the lift without Machine room (MRL type) (A) GENERAL DESCRIPTION OF LIFTS. [1]
GEAR LESS LIFT DRIVE (MRL) comprising of High Starting torque Lift 3 phase 440 V A. C. Permanent Magnet
Synchronous motor of proper rating with high efficiency shall be used.[2] Micro processor based / PLC, ACVVVF, vector
control drive with encoder feedback closed loop system shall be used for lift car and door operation which shall be full
collective selective operation hall call demand response, UP/DOWN hall stops, Main, Up/ Down Contactor with overload and
phase reversal relay and safety controls.[3] Car with M S platform with bracings of adequate size and to sustain the impact
load cabin + passenger with safety factor of fire for steel and side panels of Stainless steel of sheet of grade 304 duty. Car
ceiling will be S.S. finishes with aesthetic appearance with LED ceiling lights. Car flooring shall be of anti skid PVC with
choice of colour of engineer in charge. Car doors shall be of stainless steel grade 304, hairline finish with centre opening /
telescopic automatic doors. Car panel will also be S.S. 304 finished with emergency stop device, mechanical door safety
device, facility of auto/ attended mode. All car panel buttons and all floor switches must be with brail language as per lift
act.[4] All landing doors must be fire rated for 2 hour shall be fully automatic centre opening/ telescopic opening made of
hairline finish steel grade of 304 with key holes and infrared curtains with Unlocking facility from outside [5] Appropriate
battery operated emergency light in the car along with alarm switch shall be provided. Also, Emergency Light & Fan should
start immediately without any Time Delay as soon as power fails. [6] Digital scrolling indicator system for up-down arrow
along with floor position indicator shall be provided inside the car and at all floors.[7] Full height infra red curtain with
multiple cross / crossing light beams shall be provided.[8] Automatic Rescue Device (ARD) shall be provided accordingly of
passenger capacity with Manual Rescue Operation ( Manual Cranking Facility).[9] Audio visual indication in the lift car
showing over loading shall be provided such that doors kept open till excess load is removed.[10] Spring buffers/PU Buffers
shall be provided.
[11] Car fan as per passenger capacity with automatic sleep timer shall be provided.[12] Voice annunciator with suitable music
shall be provided in lift car. [13] Self diagnostics system for operational and safety parameters shall be provided in control
panel. [14] Mechanical over speed governor with governor calibration as per actual site parameters and submission of
calibration certificate submission, door key holes in the floor doors, fireman switch shall be provided.[15] Lift machine
hoisting arrangement in the lift machine room and monkey ladder for lift pit should be provided by the lift agency, along with
the other steel structure works, foundations for the machine etc…[16] In the hoist way fascia plate shall be provided without
any extra cost, where ever required as / if directed by engineer in charge.[17] Permanent wiring with necessary safety devices
like RCCB in all circuit, Over Voltage Under Voltage protection and THD eliminator in circuit for lift machine room and lift
well with proper numbers of light points, with fixtures, exhaust fan and plug points shall be provided by the agency. Only
phase Power Supply shall be made available by department in lift machine room. Necessary Earthing as per Lift Act/Rules
shall be arranged by Lift Agency. [18] Any civil/ electrical works for additional and alteration in lift shaft and machine room
related to erection of lift shall be made by lift agency without any extra cost. (granite/marble fixing around all landing door
openings are not in lift agency’s scope.)
6.00 [19] Agency has to provide all working drawings and documents and liaison services for obtaining all necessary permission 3398847.96 Rupees Thirty Three Lakh(s) each
from lift inspector and other authorities.[20] acrylic transparent licence/display A4 size holder in lift car[20A] As per statutory Ninety Eight Thousand Eight
requirement of Govt. Of Gujarat lift & escalator act 2000, lift agency has to provide 1. Car top safety barricade 2. Push & talk Hundred Forty Seven And Paise
communication system.3. Fireman's switch operation at Ground Floor. 4.carrying out third party lift inspection during/after lift Ninety Six Only
erection and provide report by third party authorized by concern licensing authority 5.agency has to provide third party
insurance upto completion of free maintenance period and submit the document for the same.[21] Car Panel Operating
Buttons with floor position indicator/buttons must be of Auto Glow type clearly visible when view from inside cabin. [22] For
Physically Handicapped person Full Length Handrails of hairline finish steel grade of 304 should be provided at appropriate
height on the Rear & Side Wall Panels in Lift Car.[23] With Necessary kVA rating voltage controlled Stabilizer suitable for
your controller, drive and all equipments of lift.
[24] Necessary rating of DP Elcb and FP Elcb required for lift is in scope of work which rating is sugested by CEICED
Department (electrical Inspector)-20 passengers . Ground plus 12 upper floors with Rated Speed of 2.0 / 2.5 m/sec with
micro price/PLC control and ACVVVF. drive (B) With General PLUS ADDITIONAL SPECIAL FEATURES attached
herewith. Prem. Cat.
302 Supplying, Erecting, Testing & Commissioning the passenger / stretcher lift having following main features:The Rates of the
following items are for the lift without Machine room (MRL type) (A) GENERAL DESCRIPTION OF LIFTS. [1]
GEAR LESS LIFT DRIVE (MRL) comprising of High Starting torque Lift 3 phase 440 V A. C. Permanent Magnet
Synchronous motor of proper rating with high efficiency shall be used.[2] Micro processor based / PLC, ACVVVF, vector
control drive with encoder feedback closed loop system shall be used for lift car and door operation which shall be full
collective selective operation hall call demand response, UP/DOWN hall stops, Main, Up/ Down Contactor with overload and
phase reversal relay and safety controls.[3] Car with M S platform with bracings of adequate size and to sustain the impact
load cabin + passenger with safety factor of fire for steel and side panels of Stainless steel of sheet of grade 304 duty. Car
ceiling will be S.S. finishes with aesthetic appearance with LED ceiling lights. Car flooring shall be of anti skid PVC with
choice of colour of engineer in charge. Car doors shall be of stainless steel grade 304, hairline finish with centre opening /
telescopic automatic doors. Car panel will also be S.S. 304 finished with emergency stop device, mechanical door safety
device, facility of auto/ attended mode. All car panel buttons and all floor switches must be with brail language as per lift
act.[4] All landing doors must be fire rated for 2 hour shall be fully automatic centre opening/ telescopic opening made of
hairline finish steel grade of 304 with key holes and infrared curtains with Unlocking facility from outside [5] Appropriate
battery operated emergency light in the car along with alarm switch shall be provided. Also, Emergency Light & Fan should
start immediately without any Time Delay as soon as power fails. [6] Digital scrolling indicator system for up-down arrow
along with floor position indicator shall be provided inside the car and at all floors.[7] Full height infra red curtain with
multiple cross / crossing light beams shall be provided.[8] Automatic Rescue Device (ARD) shall be provided accordingly of
passenger capacity with Manual Rescue Operation ( Manual Cranking Facility).[9] Audio visual indication in the lift car
showing over loading shall be provided such that doors kept open till excess load is removed.[10] Spring buffers/PU Buffers
shall be provided.
[11] Car fan as per passenger capacity with automatic sleep timer shall be provided.[12] Voice annunciator with suitable music
shall be provided in lift car. [13] Self diagnostics system for operational and safety parameters shall be provided in control
panel. [14] Mechanical over speed governor with governor calibration as per actual site parameters and submission of
calibration certificate submission, door key holes in the floor doors, fireman switch shall be provided.[15] Lift machine
hoisting arrangement in the lift machine room and monkey ladder for lift pit should be provided by the lift agency, along with
the other steel structure works, foundations for the machine etc…[16] In the hoist way fascia plate shall be provided without
any extra cost, where ever required as / if directed by engineer in charge.[17] Permanent wiring with necessary safety devices
like RCCB in all circuit, Over Voltage Under Voltage protection and THD eliminator in circuit for lift machine room and lift
well with proper numbers of light points, with fixtures, exhaust fan and plug points shall be provided by the agency. Only
phase Power Supply shall be made available by department in lift machine room. Necessary Earthing as per Lift Act/Rules
shall be arranged by Lift Agency. [18] Any civil/ electrical works for additional and alteration in lift shaft and machine room
related to erection of lift shall be made by lift agency without any extra cost. (granite/marble fixing around all landing door
openings are not in lift agency’s scope.)
1.00 [19] Agency has to provide all working drawings and documents and liaison services for obtaining all necessary permission 3100814.13 Rupees Thirty One Lakh(s) Eight each
from lift inspector and other authorities.[20] acrylic transparent licence/display A4 size holder in lift car[20A] As per statutory Hundred Fourteen And Paise
requirement of Govt. Of Gujarat lift & escalator act 2000, lift agency has to provide 1. Car top safety barricade 2. Push & talk Thirteen Only
communication system.3. Fireman's switch operation at Ground Floor. 4.carrying out third party lift inspection during/after lift
erection and provide report by third party authorized by concern licensing authority 5.agency has to provide third party
insurance upto completion of free maintenance period and submit the document for the same.[21] Car Panel Operating
Buttons with floor position indicator/buttons must be of Auto Glow type clearly visible when view from inside cabin. [22] For
Physically Handicapped person Full Length Handrails of hairline finish steel grade of 304 should be provided at appropriate
height on the Rear & Side Wall Panels in Lift Car.[23] With Necessary kVA rating voltage controlled Stabilizer suitable for
your controller, drive and all equipments of lift.
[24] Necessary rating of DP Elcb and FP Elcb required for lift is in scope of work which rating is sugested by CEICED
Department (electrical Inspector)-16 Passengers, Ground plus 10 upper floors with Rated Speed of 2.0 / 2.5 m/sec., (B)
With General PLUS ADDITIONAL SPECIAL FEATURES attached herewith. Prem. Cat.
303 Supplying, Erecting, Testing & Commissioning the passenger / stretcher lift having following main features:The Rates of the
following items are for the lift without Machine room (MRL type) (A) GENERAL DESCRIPTION OF LIFTS. [1]
GEAR LESS LIFT DRIVE (MRL) comprising of High Starting torque Lift 3 phase 440 V A. C. Permanent Magnet
Synchronous motor of proper rating with high efficiency shall be used.[2] Micro processor based / PLC, ACVVVF, vector
control drive with encoder feedback closed loop system shall be used for lift car and door operation which shall be full
collective selective operation hall call demand response, UP/DOWN hall stops, Main, Up/ Down Contactor with overload and
phase reversal relay and safety controls.[3] Car with M S platform with bracings of adequate size and to sustain the impact
load cabin + passenger with safety factor of fire for steel and side panels of Stainless steel of sheet of grade 304 duty. Car
ceiling will be S.S. finishes with aesthetic appearance with LED ceiling lights. Car flooring shall be of anti skid PVC with
choice of colour of engineer in charge. Car doors shall be of stainless steel grade 304, hairline finish with centre opening /
telescopic automatic doors. Car panel will also be S.S. 304 finished with emergency stop device, mechanical door safety
device, facility of auto/ attended mode. All car panel buttons and all floor switches must be with brail language as per lift
act.[4] All landing doors must be fire rated for 2 hour shall be fully automatic centre opening/ telescopic opening made of
hairline finish steel grade of 304 with key holes and infrared curtains with Unlocking facility from outside [5] Appropriate
battery operated emergency light in the car along with alarm switch shall be provided. Also, Emergency Light & Fan should
start immediately without any Time Delay as soon as power fails. [6] Digital scrolling indicator system for up-down arrow
along with floor position indicator shall be provided inside the car and at all floors.[7] Full height infra red curtain with
multiple cross / crossing light beams shall be provided.[8] Automatic Rescue Device (ARD) shall be provided accordingly of
passenger capacity with Manual Rescue Operation ( Manual Cranking Facility).[9] Audio visual indication in the lift car
showing over loading shall be provided such that doors kept open till excess load is removed.[10] Spring buffers/PU Buffers
shall be provided.
[11] Car fan as per passenger capacity with automatic sleep timer shall be provided.[12] Voice annunciator with suitable music
shall be provided in lift car. [13] Self diagnostics system for operational and safety parameters shall be provided in control
panel. [14] Mechanical over speed governor with governor calibration as per actual site parameters and submission of
calibration certificate submission, door key holes in the floor doors, fireman switch shall be provided.[15] Lift machine
hoisting arrangement in the lift machine room and monkey ladder for lift pit should be provided by the lift agency, along with
the other steel structure works, foundations for the machine etc…[16] In the hoist way fascia plate shall be provided without
any extra cost, where ever required as / if directed by engineer in charge.[17] Permanent wiring with necessary safety devices
like RCCB in all circuit, Over Voltage Under Voltage protection and THD eliminator in circuit for lift machine room and lift
well with proper numbers of light points, with fixtures, exhaust fan and plug points shall be provided by the agency. Only
phase Power Supply shall be made available by department in lift machine room. Necessary Earthing as per Lift Act/Rules
shall be arranged by Lift Agency. [18] Any civil/ electrical works for additional and alteration in lift shaft and machine room
related to erection of lift shall be made by lift agency without any extra cost. (granite/marble fixing around all landing door
openings are not in lift agency’s scope.)
6.00 [19] Agency has to provide all working drawings and documents and liaison services for obtaining all necessary permission 3367335.96 Rupees Thirty Three Lakh(s) Sixty each
from lift inspector and other authorities.[20] acrylic transparent licence/display A4 size holder in lift car[20A] As per statutory Seven Thousand Three Hundred
requirement of Govt. Of Gujarat lift & escalator act 2000, lift agency has to provide 1. Car top safety barricade 2. Push & talk Thirty Five And Paise Ninety Six
communication system.3. Fireman's switch operation at Ground Floor. 4.carrying out third party lift inspection during/after lift Only
erection and provide report by third party authorized by concern licensing authority 5.agency has to provide third party
insurance upto completion of free maintenance period and submit the document for the same.[21] Car Panel Operating
Buttons with floor position indicator/buttons must be of Auto Glow type clearly visible when view from inside cabin. [22] For
Physically Handicapped person Full Length Handrails of hairline finish steel grade of 304 should be provided at appropriate
height on the Rear & Side Wall Panels in Lift Car.[23] With Necessary kVA rating voltage controlled Stabilizer suitable for
your controller, drive and all equipments of lift.
[24] Necessary rating of DP Elcb and FP Elcb required for lift is in scope of work which rating is sugested by CEICED
Department (electrical Inspector)-16 Passengers, Ground plus 12 upper floors with Rated Speed of 2.0 / 2.5 m/sec., (B)
With General PLUS ADDITIONAL SPECIAL FEATURES attached herewith. Prem. Cat.
304 Supplying, Erecting, Testing & Commissioning the passenger / stretcher lift having following main features:The Rates of the
following items are for the lift without Machine room (MRL type) (A) GENERAL DESCRIPTION OF LIFTS. [1]
GEAR LESS LIFT DRIVE (MRL) comprising of High Starting torque Lift 3 phase 440 V A. C. Permanent Magnet
Synchronous motor of proper rating with high efficiency shall be used.[2] Micro processor based / PLC, ACVVVF, vector
control drive with encoder feedback closed loop system shall be used for lift car and door operation which shall be full
collective selective operation hall call demand response, UP/DOWN hall stops, Main, Up/ Down Contactor with overload and
phase reversal relay and safety controls.[3] Car with M S platform with bracings of adequate size and to sustain the impact
load cabin + passenger with safety factor of fire for steel and side panels of Stainless steel of sheet of grade 304 duty. Car
ceiling will be S.S. finishes with aesthetic appearance with LED ceiling lights. Car flooring shall be of anti skid PVC with
choice of colour of engineer in charge. Car doors shall be of stainless steel grade 304, hairline finish with centre opening /
telescopic automatic doors. Car panel will also be S.S. 304 finished with emergency stop device, mechanical door safety
device, facility of auto/ attended mode. All car panel buttons and all floor switches must be with brail language as per lift
act.[4] All landing doors must be fire rated for 2 hour shall be fully automatic centre opening/ telescopic opening made of
hairline finish steel grade of 304 with key holes and infrared curtains with Unlocking facility from outside [5] Appropriate
battery operated emergency light in the car along with alarm switch shall be provided. Also, Emergency Light & Fan should
start immediately without any Time Delay as soon as power fails. [6] Digital scrolling indicator system for up-down arrow
along with floor position indicator shall be provided inside the car and at all floors.[7] Full height infra red curtain with
multiple cross / crossing light beams shall be provided.[8] Automatic Rescue Device (ARD) shall be provided accordingly of
passenger capacity with Manual Rescue Operation ( Manual Cranking Facility).[9] Audio visual indication in the lift car
showing over loading shall be provided such that doors kept open till excess load is removed.[10] Spring buffers/PU Buffers
shall be provided.
[11] Car fan as per passenger capacity with automatic sleep timer shall be provided.[12] Voice annunciator with suitable music
shall be provided in lift car. [13] Self diagnostics system for operational and safety parameters shall be provided in control
panel. [14] Mechanical over speed governor with governor calibration as per actual site parameters and submission of
calibration certificate submission, door key holes in the floor doors, fireman switch shall be provided.[15] Lift machine
hoisting arrangement in the lift machine room and monkey ladder for lift pit should be provided by the lift agency, along with
the other steel structure works, foundations for the machine etc…[16] In the hoist way fascia plate shall be provided without
any extra cost, where ever required as / if directed by engineer in charge.[17] Permanent wiring with necessary safety devices
like RCCB in all circuit, Over Voltage Under Voltage protection and THD eliminator in circuit for lift machine room and lift
well with proper numbers of light points, with fixtures, exhaust fan and plug points shall be provided by the agency. Only
phase Power Supply shall be made available by department in lift machine room. Necessary Earthing as per Lift Act/Rules
shall be arranged by Lift Agency. [18] Any civil/ electrical works for additional and alteration in lift shaft and machine room
related to erection of lift shall be made by lift agency without any extra cost. (granite/marble fixing around all landing door
openings are not in lift agency’s scope.)
1.00 [19] Agency has to provide all working drawings and documents and liaison services for obtaining all necessary permission 2413845.46 Rupees Twenty Four Lakh(s) each
from lift inspector and other authorities.[20] acrylic transparent licence/display A4 size holder in lift car[20A] As per statutory Thirteen Thousand Eight Hundred
requirement of Govt. Of Gujarat lift & escalator act 2000, lift agency has to provide 1. Car top safety barricade 2. Push & talk Forty Five And Paise Forty Six Only
communication system.3. Fireman's switch operation at Ground Floor. 4.carrying out third party lift inspection during/after lift
erection and provide report by third party authorized by concern licensing authority 5.agency has to provide third party
insurance upto completion of free maintenance period and submit the document for the same.[21] Car Panel Operating
Buttons with floor position indicator/buttons must be of Auto Glow type clearly visible when view from inside cabin. [22] For
Physically Handicapped person Full Length Handrails of hairline finish steel grade of 304 should be provided at appropriate
height on the Rear & Side Wall Panels in Lift Car.[23] With Necessary kVA rating voltage controlled Stabilizer suitable for
your controller, drive and all equipments of lift.
[24] Necessary rating of DP Elcb and FP Elcb required for lift is in scope of work which rating is sugested by CEICED
Department (electrical Inspector)-10 Passengers, Ground plus 10 upper floors with Rated Speed of 2.0 / 2.5 m/sec., (Fire
Lift) (B) With General PLUS ADDITIONAL SPECIAL FEATURES attached herewith. Prem. Cat.
305 Supplying, Erecting, Testing & Commissioning the passenger / stretcher lift having following main features:The Rates of the
following items are for the lift without Machine room (MRL type) (A) GENERAL DESCRIPTION OF LIFTS. [1]
GEAR LESS LIFT DRIVE (MRL) comprising of High Starting torque Lift 3 phase 440 V A. C. Permanent Magnet
Synchronous motor of proper rating with high efficiency shall be used.[2] Micro processor based / PLC, ACVVVF, vector
control drive with encoder feedback closed loop system shall be used for lift car and door operation which shall be full
collective selective operation hall call demand response, UP/DOWN hall stops, Main, Up/ Down Contactor with overload and
phase reversal relay and safety controls.[3] Car with M S platform with bracings of adequate size and to sustain the impact
load cabin + passenger with safety factor of fire for steel and side panels of Stainless steel of sheet of grade 304 duty. Car
ceiling will be S.S. finishes with aesthetic appearance with LED ceiling lights. Car flooring shall be of anti skid PVC with
choice of colour of engineer in charge. Car doors shall be of stainless steel grade 304, hairline finish with centre opening /
telescopic automatic doors. Car panel will also be S.S. 304 finished with emergency stop device, mechanical door safety
device, facility of auto/ attended mode. All car panel buttons and all floor switches must be with brail language as per lift
act.[4] All landing doors must be fire rated for 2 hour shall be fully automatic centre opening/ telescopic opening made of
hairline finish steel grade of 304 with key holes and infrared curtains with Unlocking facility from outside [5] Appropriate
battery operated emergency light in the car along with alarm switch shall be provided. Also, Emergency Light & Fan should
start immediately without any Time Delay as soon as power fails. [6] Digital scrolling indicator system for up-down arrow
along with floor position indicator shall be provided inside the car and at all floors.[7] Full height infra red curtain with
multiple cross / crossing light beams shall be provided.[8] Automatic Rescue Device (ARD) shall be provided accordingly of
passenger capacity with Manual Rescue Operation ( Manual Cranking Facility).[9] Audio visual indication in the lift car
showing over loading shall be provided such that doors kept open till excess load is removed.[10] Spring buffers/PU Buffers
shall be provided.
[11] Car fan as per passenger capacity with automatic sleep timer shall be provided.[12] Voice annunciator with suitable music
shall be provided in lift car. [13] Self diagnostics system for operational and safety parameters shall be provided in control
panel. [14] Mechanical over speed governor with governor calibration as per actual site parameters and submission of
calibration certificate submission, door key holes in the floor doors, fireman switch shall be provided.[15] Lift machine
hoisting arrangement in the lift machine room and monkey ladder for lift pit should be provided by the lift agency, along with
the other steel structure works, foundations for the machine etc…[16] In the hoist way fascia plate shall be provided without
any extra cost, where ever required as / if directed by engineer in charge.[17] Permanent wiring with necessary safety devices
like RCCB in all circuit, Over Voltage Under Voltage protection and THD eliminator in circuit for lift machine room and lift
well with proper numbers of light points, with fixtures, exhaust fan and plug points shall be provided by the agency. Only
phase Power Supply shall be made available by department in lift machine room. Necessary Earthing as per Lift Act/Rules
shall be arranged by Lift Agency. [18] Any civil/ electrical works for additional and alteration in lift shaft and machine room
related to erection of lift shall be made by lift agency without any extra cost. (granite/marble fixing around all landing door
openings are not in lift agency’s scope.)
6.00 [19] Agency has to provide all working drawings and documents and liaison services for obtaining all necessary permission 2616329.25 Rupees Twenty Six Lakh(s) Sixteen each
from lift inspector and other authorities.[20] acrylic transparent licence/display A4 size holder in lift car[20A] As per statutory Thousand Three Hundred Twenty
requirement of Govt. Of Gujarat lift & escalator act 2000, lift agency has to provide 1. Car top safety barricade 2. Push & talk Nine And Paise Twenty Five Only
communication system.3. Fireman's switch operation at Ground Floor. 4.carrying out third party lift inspection during/after lift
erection and provide report by third party authorized by concern licensing authority 5.agency has to provide third party
insurance upto completion of free maintenance period and submit the document for the same.[21] Car Panel Operating
Buttons with floor position indicator/buttons must be of Auto Glow type clearly visible when view from inside cabin. [22] For
Physically Handicapped person Full Length Handrails of hairline finish steel grade of 304 should be provided at appropriate
height on the Rear & Side Wall Panels in Lift Car.[23] With Necessary kVA rating voltage controlled Stabilizer suitable for
your controller, drive and all equipments of lift. [24] Necessary rating of DP Elcb and FP Elcb required for lift is in scope of
work which rating is sugested by CEICED Department (electrical Inspector)-10 Passengers, Ground plus 12 upper floors
with Rated Speed of 2.0 / 2.5 m/sec., (Fire Lift) (B) With General PLUS ADDITIONAL SPECIAL FEATURES attached
herewith. Prem. Cat.
306 178.00 Supplying, installation, testing & commissioning of fire fighter telephone handset complete as required. 5148.98 Rupees Five Thousand One each
Hundred Forty Eight And Paise
Ninety Eight Only
307 178.00 Supplying, installation, testing & commissioning of fire fighter phone jack complete as required. 1445.31 Rupees One Thousand Four each
Hundred Forty Five And Paise
Thirty One Only
308 178.00 Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. 3151.20 Rupees Three Thousand One each
Hundred Fifty One And Paise
309 178.00 Supplying, installation, testing & commissioning of addressable manual call point complete as required. 3477.43 Rupees Three Thousand Four each
Hundred Seventy Seven And Paise
Forty Three Only
310 7.00 Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, 214342.20 Rupees Two Lakh(s) Fourteen each
central processing unit with the following loop modules and capable of supporting not less than 240 devices (including Thousand Three Hundred Forty
detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 Two And Paise Twenty Only
character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile
memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with
automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with
analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete
with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete
as per specifications.Two Loop Panel
311 2450.00 Providing & erecting 16 gauge HGS Steel conduit pipe (as per IS) painted black surface/concealed of following size 108.07 Rupees One Hundred Eight And metre
complete to be erected on/in wall or ceiling with erected with necessary saddles, screws, bends, junction boxes etc. with Paise Seven Only
following (Nominal Bore) dia of pipes, in approved manner as directed -25 mm
312 2450.00 Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing 65.65 Rupees Sixty Five And Paise Sixty metre
surface/ recessed steel/ PVC conduit as required. -2 x 1.5 sq. mm Five Only
313 4.00 Providing & erecting open well horizontal mono block pump set with cast iron body, complete for three phase submersible 11314.02 Rupees Eleven Thousand Three each
motor having [A] For 1.5 HP 3 phase open well horizontal mono block pump set suitable for 190 LPM @ 20 mtr head suitable Hundred Fourteen And Paise Two
for 40 mm dia delivery pipe Cat.II Only
314 2.00 Providing & erecting open well horizontal mono block pump set with cast iron body, complete for three phase submersible 28586.03 Rupees Twenty Eight Thousand each
motor having [E] For 7.5 HP 3 phase open well horizontal mono block pump set suitable for 1550 LPM to 370 LPM @ 13.5 Five Hundred Eighty Six And Paise
Mtr to 42 Mtr head suitable for 65/75 mm dia delivery pipe Cat.II Three Only
315 12.00 Providing & erecting open well horizontal mono block pump set with cast iron body, complete for three phase submersible 31312.02 Rupees Thirty One Thousand Three each
motor having [F] For 10 HP 3 phase open well horizontal mono block pump set suitable for 1725 LPM to 940 LPM @ 15 to Hundred Twelve And Paise Two
36 MTR head suitable for 65/80 mm dia delivery pipe Cat.II Only
316 4.00 Supplying & erecting approved make motor control cubical panel (Direct - on - line) made from 16 G. CRCA sheet duly 7722.46 Rupees Seven Thousand Seven each
epoxy powder painted inside and outside with hinged doors and locking, arrangement consisting of suitable size of ON- OFF Hundred Twenty Two And Paise
isolator (AC - 3/23duty) main fuses, single phasing preventer, indicating lamps for R- Y - B phases, overload relay, Automatic Forty Six Only
water level controller, Ammeter, Voltmeter each with two way selector switch incoming, wires duly socket crimped, main
contactor & overload relay, start - stop push buttons, to be erected on angle iron frame grouted on wall as directed. The
isolator, overload relay & contactors will be of L & T, Siemens or BCH make only (A) DOL up to 5.0 H.P.
317 2.00 Supplying & erecting approved make motor control cubical panel [Star delta] made from 16G CRCA sheet duly epoxy 13182.52 Rupees Thirteen Thousand One each
powder painted inside and outside with hinged doors and locking with suitable size of ON - OFF isolator (AC 3 / 23 duty) Hundred Eighty Two And Paise
main fuses. Digital volt and current meter (in a single unit) with micro controller based control unit and current sensing single Fifty Two Only
phasing preventer electronic overload protection, over voltage (Programmable) protection and under voltage (Programmable)
protection, prod less dry run protection programming facility for setting of all parameter like overload current, high voltage
limit, low voltage limit, dry run limit with digital indication on seven segment LED display for any fault like over load, high
voltage, low voltage, dry running single crimped, electronic star delta timer, feather touch start / stop push buttons to be
erected on angle iron frame. Grouted on wall the contactors will be of L& T, Siemens , BCH make only) (A) S/D up to
318 12.00 Supplying & erecting approved make motor control cubical panel [Star delta] made from 16G CRCA sheet duly epoxy 13794.58 Rupees Thirteen Thousand Seven each
powder painted inside and outside with hinged doors and locking with suitable size of ON - OFF isolator (AC 3 / 23 duty) Hundred Ninety Four And Paise
main fuses. Digital volt and current meter (in a single unit) with micro controller based control unit and current sensing single Fifty Eight Only
phasing preventer electronic overload protection, over voltage (Programmable) protection and under voltage (Programmable)
protection, prod less dry run protection programming facility for setting of all parameter like overload current, high voltage
limit, low voltage limit, dry run limit with digital indication on seven segment LED display for any fault like over load, high
voltage, low voltage, dry running single crimped, electronic star delta timer, feather touch start / stop push buttons to be
erected on angle iron frame. Grouted on wall the contactors will be of L& T, Siemens , BCH make only)(B) S/D up to
319 2.00 S.I.T.C. submersible pump set for bore of 150 mm. dia. Or, more having 3 phase motor capacity not more than 15 H.P. and 54933.90 Rupees Fifty Four Thousand Nine each
discharge capacity having, Lifting and Lowering taken extra.(D) ( 8 stage) 695 to 492 L.P.M. at the head 48 to 73 mtrs suitable Hundred Thirty Three And Paise
for 65/50 mm dia. delivery pipe Cat.III Ninety Only
320 50.00 Providing and erecting ISI marked PVC insulated PVC Sheathed Flat flexible Submersible copper cable approved make of 146.45 Rupees One Hundred Forty Six MTR
following Size. (C) 3 Core x 4 Sq. mm And Paise Forty Five Only
321 400.00 Providing and erecting ISI marked PVC insulated PVC Sheathed Flat flexible Submersible copper cable approved make of 488.84 Rupees Four Hundred Eighty Eight MTR
following Size. (F) 3 Core x 16 Sq. mm. And Paise Eighty Four Only
322 2.00 Lowering of submersible motor pump set at the depth of following ,complete with required. Nos. and size of casing pipes 856.48 Rupees Eight Hundred Fifty Six Per Job
erected by means of proper chain pulley block & pipe wrenches after checking of threads of each pipe with coupling to take the And Paise Forty Eight Only
load of the pump set and pipe assembly filled up with water (D)For Open well Horizontal submersible pump set for sump
well (i) 1 HP to 5 HP
323 16.00 Lowering of submersible motor pump set at the depth of following ,complete with required. Nos. and size of casing pipes 1284.72 Rupees One Thousand Two Per Job
erected by means of proper chain pulley block & pipe wrenches after checking of threads of each pipe with coupling to take the Hundred Eighty Four And Paise
load of the pump set and pipe assembly filled up with water (D)For Open well Horizontal submersible pump set for sump Seventy Two Only
well (ii) 7.5HP to 15 HP
324 2.00 EQUIPMENTS 648962.37 Rupees Six Lakh(s) Forty Eight Set
Surface Hydro-Pneumatic System for Domestic Water supply :Compact self contained Hydro-booster system comprising of Thousand Nine Hundred Sixty Two
following :Vertical In-line/Horizontal multi-stage, centrifugal clear water pumps with AISI304 Impeller and AISI316 Shaft, And Paise Thirty Seven Only
Cast Iron (FG260) Suction and Discharge with CED coating, TEFCIP55 motor (with Mechanicalseal) Vendor to submit
performance curves and technical catalogue of the proposed model for review and information Controller with colour touch
screen display and Variable Frequency Drive(VFD) integrated in a single body with pressure sensor transmitter, programming
to indicate pump ready, pump running and fault in display and capable to communicate with other controllers following
MODBUS-RTU or BACNET Class-2 protocol through RS485 port. System should be capable to compensate for frictional
losses at lower flows. All alarms should be displayed in the controller. System should be equipped with dry running protection.
Indication of all type of faults / on-off status / electrical parameters shall be available on display and central BMS monitors.
Also able to work with pressure switch in manual mode operation. Source from same manufacturer of pump. Pre-charged
diaphragm pressure vessel with interchangeable membrane, charging connection, connected to outlet header with necessary
flanges, gaskets, isolating valves, nuts/bolts etc. complete (size of pressure vessel as per manufacturer recommendation) Set of
accessories such as G.I headers (with zink coating) for suction and discharge, control valves, non return valves, pressure
switches, pressure transducers, pressure gauge, common skid, inter connecting power and control cabling etc. Complete.
Set of Solenoid valve (IP68), control panel and y-strainer to maintain water level in OHT with float switch should be provided
Purpose of system - Domestic water supply system to each utility
Nos of system - 1set =2 working + 1 stand by
Flow rate of system (working pumps) - 650 LPM
Total Head of each pump - 60m
In Wards: - Rupees One Hundred Thirty Two Crore Sixty Three Lakh(s) Fifty Two Thousand Seven Hundred Eighty Three Only
1 The Contractor shall exhibit a board with detailed specification and details of work as directed by the Engineer-In-Charge for which NO extra payment shall be made.
2 The labour cess and Testing charge will be deducted as per prevailing rules i.e. 1% (LC) and 1% (Tsting) of the work done.
3 GST and Income tax TDS will be deducted at a source while making payments of bills
4 In all R.C.C. Items in Rate Analysis Standard Cement Consumption has been taken as per Govt. G.R.: PRC-10/2017 Cement Consumption/16/C Date:11/05/2017 as stated in S.O.R. therefore in R.C.C. items where there is
a change as per actual mix design the cost of difference of cement consumption Shall be deducted from the rate of original item at the rate of input rate mentioned in all the tender.
5 GST extra applicable in case of work based on SOR 2024-25 only.
6 Credit value For Dismentalling of Existing Strructure Rs.19,04,000.00/- must be recovered from the 1st RA Bill.
Deputy Executive Engineer Executive Engineer
P.I.U. Zone-7, Surat
P.I.U. Zone-7, Surat
Deputy Executive Engineer (Ele.) Executive Engineer (Ele.)
P.I.U. Zone-7, Surat
P.I.U. Zone-7, Surat
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Condition for cement.pdf
GR RnB Revise.pdf
GR-TMT-Lap Length.pdf
INSTRUCTIONS TO PERSON TENDERING.jpg
JPG
Performance Bond and SD-Paripatra-2023.pdf
PIU SPECIAL CONDITIONS.pdf
Inclusion of Insurance clause as per new SBD.pdf
6372 Make List HO 15.10.2025.pdf
202308-H1-S4-TYPICAL FLOOR(1ST TO 10).pdf
202308-H2-S4-TYPICAL FLOOR(1ST TO 12TH).pdf
202308-H3-S4-AP-TYPICAL FLOOR(1ST TO 12TH).pdf
202308-H4-S4-AP-TYPICAL FLOOR(1ST TO 12TH).pdf
202308-H5-S4-AP-FF.pdf
Draft Letter_7-9 tender invite day.pdf
Performance Bond and Bitumen date.pdf
Specification for Civil.pdf
Specification for Electric Works.pdf
Specification for ELV.pdf
Specification for Shuttring.pdf
Specifications for Plumbing and FFTG Work.pdf
Special Condition.pdf
Special Condition Secction 2.pdf
Schedule B.pdf
SBD.pdf
Tender Document.pdf
Contractor special note.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .