Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.4 CrAccepted-AOC 101 VRAJ APARTMENT OPP POLICE HEAD QUARTERS SARU SECTION ROAD JAMNAGAR 381008 | JAMNAGAR | 381008 | ₹1.4 Cr | L1 | Accepted-AOC Lowest bidder |
| 2 | L2₹1.5 Cr+₹4.1 L (2.84%)Rejected-Finance | ₹1.5 Cr+₹4.1 L (2.84%) | L2 | Rejected-Finance other than lowest bidder |
Tender Value
₹1.4 Cr
EMD Value
₹2.1 L
Closing Date
10 Oct 2023, 6:00 pmClosed
Col Manish Dhaka CWE
HQ CWE (AF) Chiloda Military Engineer Services P.O CRPF Campus Vayu Shakti Nagar Gandhinagar 382042
PROVN OF FIRE HYDRANT SYSTEM INCLUDING STANDBY POWER SUPPLY AND 250 KVA TRANSFORMER AT AF STN GANDHINAGAR
2023_MES_601665_2
82144/CHL/E8
Open Tender
Civil Works
Lump-sum
276 days
Gandhinagar
As per tender documents
7 documents required · 7 mandatory
₹1,000
Yes
GE (AF) Chiloda
₹2.1 L
15 Nov 2023
28 Aug 2023
16 Oct 2023
28 Aug 2023
10 Oct 2023
26 Sept 2023
29 Aug 2023 - 4 Sept 2023
Amount
NOTE: Schedule ‘A’ Part I to IX under Ser No. 1 to 8 here in after are Prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only.
Lump sum price worked out for BUILDING/ STRUCTURE as listed in Sch 'A’ Part I.
Lump sum price worked out for EXCAVATION & EARTH WORK as listed in Sch 'A’ Part II.
Lump sum price worked out for INTERNAL ELECTRIFICATION as listed in Sch 'A’ Part III.
Lump sum price worked out for CHAIN LINK FENCING as listed in Sch 'A’ Part IV.
Lump sum price worked out for HARDSTANDING as listed in Sch 'A’ Part V.
Lump sum price worked out for DG SET as listed in Sch 'A’ Part VI.
Lump sum price worked out for FIRE FIGHTING as listed in Sch 'A’ Part VII.
Lump sum price worked out for TRANSFORMER as listed in Sch 'A’ Part VIII
SCHEDULE `A' PART-IX (MISCELLANEOUS ITEMS) (Note for following items- The contractor shall quote his rate for each of these items separately. The estimated rate is left blank since the same is not prepriced by MES)
INTERNAL ELECTRIFICATION
S&F Symmetrical light LED flood light fitting 100 watts, 240 volts with suitable fixing arrangement on acoustic wall panel complete all as specified
S & F 22 watt octane LED panel round slim, compact, aluminium die cast recess mounted panel with opal diffuser in build electronic driver with all accessories internally pre wired and including connection up to electric source complete all as specified
S & F Halogen 1000-watt cool white /warm/ colored spot light to throw on stage from crowd to curtain with C clamp to hang on a bar stage complete all as specified
DG SET
Supply, install, testing and commissioning of outdoor type factory assembled diesel driven generating set conforming to latest CPCB norms with silent (acoustic) enclosure with fully wired alternator AC for ambient conditions at Gandhinagar, Gujarat for 400 KVA continuous rating at 415 volts adjustable at ± 2.5% AC 3 phase, 0.8 power factor, 4 wire, 50 Hz ± 1 %, 1500 rpm directly coupled with suitable capacity diesel engine liquid coolant based mounted on common base frame placed on & including PCC platform with floor mounted Fuel Tank of adequate capacity with fuel lines, anti vibration pads, standard control & AMF panels and other accessories etc complete all as specified & directed consisting of following;- (A) Prime Mover (Diesel Engine) : Adequate capacity diesel engine of standard design consisting of direct injection type, four stroke, liquid cooled technology conforming to BS 5514 and IS 10000 suitable for prime duty generating set of minimum 490HP @ 1500 RPM with multi cylinders to drive independently alternator and considering de rating as per site condition after generating and reducing power consumed by accessories, directly coupled through coupling having overload capacity of 10% for one hour in every 12 Hrs continuous running mounted on base frame with
following salient features and standard accessories for safe handling & operation of engine as under:- (a) The gen set should have capacity to run continuously in variable load condition for unlimited hours and should also have a 110% load capacity of 01 hours in every 12 hours of operation. (b) Air System - Inlet & Exhaust comprising (i) Dry-type paper element air Cleaner (ii) Restriction Indicator / Vacuum Indicator (iii) Intake Manifold (iv) Exhaust Manifold (v) Silencer muffler and (vi) Stainless steel Exhaust Flexible coupling (c) Cooling System comprising (i) Radiator to suit ambient conditions (ii) Cooling system piping (iii) Thermostat (iv) Pressure cap (v) Coolant Inhibitor and (vi) Engine Driven Fan. (d) Fuel System comprising (i) Fuel pump -Low pressure type (ii) Injectors (iii) Cartridge paper filters primary and secondary for Fuel. (e) Governor: - Mechanical Governor for A1 governing of engine speed from No load to full load. (f) Lub Oil System: - (i) Gear driven Lube Oil Pump, Strainer, Full-flow spin-on type Oil Filters, Oil Cooler & Oil dipstick
(g) Fuel Tank: - Draw out type integral fuel tank made of MS sheet (duly painted) of capacity min 800 ltrs or DG 8 hours running Ltrs capacity with level indicator in ltrs, provided with drain plug and air vent / breather and inlet and outlet connection (h) DEIF/DSE Controller :- Engine Monitoring, load power monitoring and Protection (kW, kV A, kV Ar, pf) suitable to following display:- (i) Lub oil Pressure (ii) Coolant Temperature (iii) Engine Speed (iv) Hours Run (v) Battery Voltage, Battery charging voltage (vi) Fuel level in percentage, (vii) AC Voltage 3 phase (viii) Current RYB 3 phase (ix) Power Factor (x) Frequency (xi) KVA (xii) Kilowatt (xiii) KWH with suitable rated CTs and suitable for (xiv) Start and Stop (xv) Common Shutdown (xvi) High coolant temp warning and shutdown (xvii) Lub oil pressure warning and shutdown
(xviii) Low fuel level shutdown (xix) Over speed shutdown (xx) Alternator Protection including over voltage, under voltage, over and under frequency, Over current”. (i) Misc Accessories i.e - (i) Flywheel Housing (ii) Flywheel (iii) Anti-vibration pads (iv) Emergency stop push button etc all as required for smooth operation of DG set as recommended by manufacturer. (j)Battery - 2 Nos Dry type suitable capacity Maintenance free Batteries (minimum 2 year warranty ) with MS Fabricated Battery Stand and Battery Leads
"(B) ALTERNATOR : Self excited, self-regulated screen protected drip proof type with IP23, Class 'H' Insulation Salient pole revolving field and electronic Automatic Voltage Regulator for voltage regulation of ± 1% from No load to full load, 400 KVA, 3 phase, 4 wire, 415 V, 0.8 PF, 1500RPM, 50Hz. Continuous rating capacity etc standard enclosure complete as per IS-13364-2 and conforming to IS-4722 or BS5000 all as required or recommended by manufacturer. (C) BASE FRAME: Made of ISMC fabricated and welded construction channel duly painted for mounting Engine and Alternator all as per manufacturer's design alongwith specially designed in built vibration pads. (D) LT Control & AMF Panel: AMF panel board made out of CRCA sheet 3mm thick totally enclosed, weather, dust and vermin proof with front opening, 440 volts, 3 phase, 4 wire, 50 Hz having copper bus bar of suitable capacity for three phases and neutral duly colour coated with coloured heat shrinkable PVC sleeves, Multifunctional digital control relay for AMF operation and display of electrical parameters, manual Start/Stop facility, Two Nos Electrically operated contactor 4 pole of suitable capacity for DG set and main supply, complete all as specified, with on/off controller indicator, Phase Indicators, engine start push button, engine stop push button and fault
FIRE FIGHTING
Supply, laying & jointing in trenches / floor etc in standard length, centrifugally cast (spun) ductile iron (DI) pressure pipe of 150mm bore, with flange ends type, Class K-9 conforming to IS 8329/2000 or latest revision, ISI marked with inside cement mortar lining and black bitumen external coating , with rubber insertion packing 3 mm thick, nuts, bolts washer etc including testing complete all as specified and directed by Engr -in- Charge. Note :- (i) DI special fittings will be measured and paid separately under relevant item of sch. (ii) The cost of joint deemed to be included in the quoted rate
M & L 250 mm bore 4 meter, MS ERW Pipe as per IS 3589 (1981), wall thickness not less than 7 mm duly welded in multiple length for making hydral point, one side flanged end (thickness of flanged not less than 10 mm) and one side welded reducer 150mm dia including three incoming branch pipe connection with welded flanged end. etc complete with including two coat of anti-corrosive paint over a coat of red oxide primer all as specified and directed.
S&F Foot valve conforming to IS 4038, made out of cast iron material one side flange end and other side strainer and floating reinforced rubber coated ball as per sample for 80 mm dia. Pipe complete all as specified and directed
S&F Foot Valve conforming to IS 4038, made out of cast iron material one side flange end and other side strainer and floating reinforced rubber coated ball as per sample suitable for 150 mm dia. pipe complete all as specified and directed
Supply and installed cubicle compartmentalised indoor type CPRI approved factory made LT section pillar box with motor starter panel, front and rear opening with locking arrangement dust and vermin proof, fabricated out of 2.0 mm thick CRCA sheet and base frame & mild steel angle iron stand, over all finished with epoxy powder coating, suitable for operation on 415 volts, 50 HZ, AC supply, including earthing stud, labeling, danger plates, cable gland etc. including fixing in position PCC, connecting with electric supply complete comprising the following switch gears (a) Incoming: - (i) Bus bar chamber having 4 aluminium bus bar strip 300 Amps capacity (ii) MCCB 4 pole 160 amps having breaking capacity of Icu=25 KA with adjustable load setting - 01 No (iii) Multifunction Meter 3 phase, 415 Volts, Accuracy Class 1.0, Flush mounting 96 x 96 mm complete including CTs- 01 Nos (iv) Indicating lamp RYB (LED type) - 0 1 Set of three (b) Outgoing: - (i) MCCB 3 pole, 415 Volts, 100 Amps with adjustable load setting - 01 No (ii) MCCB 3 pole, 415 Volts, 40 Amps with adjustable load setting - 01 No (iii) AC3 32 Amps rating ML 2 contactor - 3 Nos (iv) AC3 70 Amps rating ML 4 contactor - 3 Nos (v) Relay 14-23 Amp MN 5 type - 1Nos
(iv) Single phase prevention relay - 02 Nos (v) 3Ph LED Ammeter Cl 0.5 with CT - 02 Nos (vi) Push button for ON/OFF - 2 set (vii) Indication lamp ON/OFF/TRIP - 02 set (viii) Electronic timer - 2 Nos
Supply and lay water mist extinguisher as per IS-15683 of capacity 6 kg complete fixed on wall all as directed
Supply and lay dry chemical powder (ABC) extinguisher as per IS-15683 of capacity 6 kg complete fixed on wall all as directed
Supply and lay light weight squeeze grip type CO2 extinguisher as per IS-15683 of capacity 4.5 kg complete fixed on wall all as directed.
S & F 4 Kg Capacity Clean Agent gas based system, as per IS 15683 Cylinder filled with FK5-1-12 / HFC 236fa UL Listed clean agent Gas , with all necessary fitting, Brackets, support, accessories and fitted with Direct Low Pressure valve including end line plug and pressure switch complete all as specified and directed.
S & F 2 Kg Capacity Clean Agent gas based system, as per IS 15683 Cylinder filled with FK5-1-12 / HFC 236fa UL Listed clean agent Gas, with all necessary fitting, Brackets, support, accessories and fitted with Direct Low Pressure valve including end line plug and pressure switch complete all as specified and directed
M & L Heat sensor tube for automatic fire suppression system made by special modified Polyamide (PA), Color Black, High grade HR quality, UV Stabilized, Inner diameter 4mm, Outer Diameter 6 MM fixing in electrical panel complete all as specified and directed
S & F Health monitoring cum fire alarm panel for heat sensor tube for automatic fire suppression system, over the electrical panel complete all as specified and directed.
M&L Construction of brick masonry valve pit complete as per Chief Engineer Air Force Gandhinagar Drg No. CEAA/TD/57 sheet No.1.1, Ser No.4 Type 'D' of size 1050 x 1050 x 1000mm for Sluice / Reflex valve. Complete as specified & directed by Engr-in-Charge
M & L Cutting holes into or through Brick wall, cement concrete slabs, chajjas, etc for inserting of pipe upto 100 mm dia and making good disturbed surface of walls, floors, etc. complete all as specified and directed.
M & L Boring of holes under road, pavement, hard standing by Manually or necessary machine for inserting of water pipe up to 150 mm dia complete all as directed and specified.
TRANSFORMER
Dismantling and shifting of old transformer shifting from existing location to Torrent Power store as directed by Engr in Charge
divyarsh entrprise
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .