Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.1 LAccepted-AOC | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹24.9 L+₹1.0 L (4.37%)Rejected-Finance FLAT NO C 401 LORD KRISHNA GREEN OPPOSITE DOON SCHOLAR SCHOOL KEDARPUR DEHRADUN UK 248001 | DEHRADUN | DEHRADUN | UTTARAKHAND | 248001 | L2 | Rejected-Finance Being 2nd Lowest | |
| 3 | L3₹29.6 L+₹5.7 L (23.8%)Rejected-Finance | L3 | Rejected-Finance Being 3rd lowest |
Tender Value
Refer Docs
EMD Value
₹55,400
Closing Date
29 Dec 2022, 6:00 pmClosed
MMD PRAVEEN NANDIKATTI GE AF SARSAWA
Garrison Engineer (AF) Sarsawa, Distt. Saharanpur (U.P)
REPAIRS TO LT/HT UG/OH LINES, EARTHING, LIGHTENING ARRESTORS, DG SETS, ALTERNATORS, LT PANELS ETC AND SURVEY OF ENERGY AUDIT AT 1 AFSB DEHRADUN UNDER GE (AF) SARSAWA
2022_MES_563178_2
8122/SAR-34/2022-23
Open Tender
Civil Works
Item Rate
183 days
GE(AF) SARSAWA
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE(AF) SARSAWA
₹55,400
Yes
21 Jan 2023
15 Dec 2022
31 Dec 2022
15 Dec 2022
29 Dec 2022
15 Dec 2022
Amount
M&L for Excavation in trenches in soft/loose soil n.exc 1.5mtr deep and n excl 1.5 mtr wide for laying of HT cable ,pole, etc and gettting out including of dressing / trimming sides and levelling, grading and ramming of bottom excavation complete all as specified and as directed.
Returning filling in including spreading, leveling watering and well ramming in layers not exc 25 cm thick each layer in soft/loose soil complete all as specified and as directed.
Removing excavated materials (soils) not exc. 50 m and depositing where directed at a level not exc.1.5 mtr above the starting point complete all as specified and as directed.
M & L for fine dry sand cushioning for underground cable by providing a layers of sand 8 cm deep before laying and 15 cm deep after laying the cable including streching the cable complete al as specified and as directed.
M & L forlaying of bricks sub class 'B' old size laid flat perpendicular to the direction of cables for protection complete all as specified and as directed.
M&L PCC 1:4:8 type D2 using 40 mm graded stone aggregate as in foundation, filling mass concrete including necessary form work.
M&L for PCC 1:3:6 type C 1 using 20 mm graded aggregate block masonry with solid block ,exc 10 cm in width and setting in mortar complete for coping of pole including necessary from work and fair finish to the exposed surface area without using extra cement complete all as specified and directed.
M&L for PCC 1:2:4 type using 20 mm aggregate block masonry with solid block for copping above ground level all as specified annd directed.
S&F HDPE of Pressure rating 6kgf/cm2 pipe of 40 mm dia including necessary bends,elbows,Tees etc on cable protection complete all as directed.
Taking down old unserviceable GI tubes any size.
Supply & lay G I tubing light grade in replacement for protection of cable at road crossing /hard standing/pole protection fixed with clamps as per site requirement etc all as specified and directed for:- 50 mm dia bore
All as per item No 11.00 here in before but 80 mm dia bore
Material and labour for cutting of road/ hard standing up to a size not exceeding 20cm width and not exceeding 60cm in depth for laying of cable protection pipe including making good the disturbed road/hard standing by providing PCC (1:2:4) type B1 to much the existing surface level complete all as directed.
Labour only for Dismantling air break gang operated switches, vertical/horizontal mounted including insulators and operating mechanism for repair/ replacement of broken/worn out components and insulators etc. complete all as specified and directed
Material and labour for switches, Gang operated Triple pole mechanically operated vertical type12 insulators and with carrying capacity 200 Amps, 11000 Volts fixed with nut,bolt and washers of required quqntity, compete all as specified and as directed
M & L for single pole lightning arrestor expulsion type complete with all fittings suitable for 11000 Volt grade of discarge capacity 65 KA, connecting with HT line complete all as specified and as ddirected including dismantling of existing unserviceable.
Material and labour for pin type, porcelain, vitreous, white, brown or green insulator 11000 volts grade of size 150 mm height, 150 mm dia, including one galvanized mild steel spindle with two galvanized iron washers and one galvanized nut bolt complete all as specified as directed.
Supply and filling of transformer oil for transformers installed at various site for topping up after dehydration to achieve the dielectric strength 60 KV at 4 mm gap complete as per IS 335-1993 complete all as specified and directed.
Earthing complete with galvanised steel earth electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than1.5 metres below normal ground level, connected togalvanised earth lead wire 4.0mm dia by means ofbolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 03 connected to earth test point all as specified or indicated including testing on completion.
S&F of copper strip 20x3.15 mm on porcelain base insulator of suitable size with saddles and fixing screws etc. for roof conductors or down conductors above ground complete all as specified and directed.
Supply, laying in replacement of UG cable XLPE insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 10 sqmm, 3.5 core stranded conductor and including necessary cable lugs, bolts, nuts and washers complete all as specified and directed.
Supply, laying in replacement of UG cable XLPE insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 70 sqmm, 3.5 core stranded conductor and including necessary cable lugs, bolts, nuts and washers complete all as specified and directed.
Supply, laying in replacement of UG cable XLPE insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 95 sqmm, 3.5 core stranded conductor and including necessary cable lugs, bolts, nuts and washers complete all as specified and directed.
M&L for carrying out the servicing of DG set of capacity 15 KVA to 200 KVA, Make - Kirloskar at 1 AFSB by taking down old/UNSV spare parts, drain out burnt engine oil and cleaning the oil chamber by cleaning solution, Cleaning and servicing of radiator from inside and outside thoroughly with cleaning solution K-Clean, including replacement of ,spare parts checking/rectify all the electrical connection and tightening of loose nut & bolts including carrying out minor addition/alternation for fixing the parts for smooth functioning of DG Sets complete up to entire satisfaction of Engr-in-charge. Note : Servicing of DG set shall be carried out by authorised service dealer of Kirloskar and supply of spare parts shall be measured and paid separately under relevent items.
Supply only K oil super 15 W 40 suitable for kirloskar DG Set.
Supply only K cool Super plus 50-50 premix cat part no.82.020.35.1.25
Supply only spin on filter for lubricating oil cat part no. 06.436.01.0.00
Supply only primary element cat part no. 3H.132.01.0.00
Supply only secondary element cat part no. 3H.132.02.0.00
Supply only V fan belt for alternator of capacity 50 to 200 KVA DG Set
Supply only of primary and secondary air filter suitable for 50 to 200 KVA DG Set.
Supply and replacement of secondary fuel fillter of generator 50 KVA to 200 KVA
Supply and replacement of primary fuel filter of generatior 50 KVA to 200 KVA
Supply and replacment of oil filter of generator 50 KVA to 200 KVA
Supply and fixing indication lamp R,Y,B complete set,complete all as specefied and as directed.
S&F oil sump gasket set suitable for 15 to 200 kva DG Set complete all as specefied and as directed.
S & F contact element NO cat pt RB2-BE-101
Taking down old/unserviceable relay and its adaptor/mounting of any capacity and supply and fix in repair new relay of suitable capacity in AMF panel of capacity upto 200 KVA complete all as specified and directed.
S & F integrated LED pilot lamp type of voltage AC/DC to be specified suitable for operating at 110 and 240 volt.
Taking down old/unserviceable street light timer set of any type and capacity and supply,fixing and testing complete set of automatic street light switch uising digital/analog timer for three phase load upto 25kw, complete all as specified and directed.
Supply and fixing 415 volt AC digital AMP meter complete all as specefied and as directed.
Supply and fixing 415 volt AC digital Volt meter complete all as specefied and as directed.
Taking down old/unserviceable multi function meter from existing ABB RMU panel and supply, fixing, commissioning multi function digital panel meter as existing & complete testing all as specilfied and directed.
Supply & fixing LED Flood Light fitting 120 Watt made out of pressure dia aluminium hosing with heat resistant toughened glass and IP-66 protection complete all as specified and directed.
Taking down old unserviceable street light fitting of any make and capacity Supply and fixing in repair LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed.
Taking down old unserviceable driver from street light of any capacity and supply and fixing in repair driver, 240 Volts, 50 Hz suitable for street lights upto 70 watt capacity, complete fixing, testing all as specified and dorected.
Taking down old unserviceable LED panel from street light of any capacity and supply and fixing in repair led panel of suitable capacity, complete fixing, testing all as specified and dorected.
Supply & fix FRP junction box (weather proof) of size 250 x 250 x 160mm including three phase four nos busbarstrip of 150x30x30mm alongwith suitable clamps including MCB SP 6 Amps 10 KA rating,fixing with flat iron clamps, nuts and bolts complete all as specified and directed.
Supply and fixing in replacement of MCCB Triple Pole 63 Amp 415 Volt rupturing capacity not less than 25 KA complete all as specified and as directed.
Supply and fixing in replacement of MCCB Triple Pole 200 Amp 415 Volt rupturing capacity not less than 35 KA complete all as specified and as directed.
Supply and fixing in replacement of MCCB Triple Pole 250 Amp 415 Volt rupturing capacity not less than 35 KA complete all as specified and as directed.
Supply and replacement of change over switch 100 Amp 415V four pole in sheet enclosure with side handle operation, off load change over complete all as specified and as directed.
S&F in replacement of power contactor 3 pole 415 volt long life suitable for 65 Amps
Supply and fix four pole power contactors TYPE- ML-6, AC 3 P RATING 110 A CAT PT NO SS90921 INCLDING WITH 2 no + 2nc AUX CONTACT .
Supply and fixing power contactors 415 volt 50 Hz complete all as specefied and as directed.model no-MCX 41 of L&T or , C&S.SIEMENS
M&L replacement of battery lead set of two,suitable for suitable upto 180AH capacity 1.5mtr long incuding GM Terminals one end, copper lugs other end complete all as specefied and as directed.
Opening,checking,adjusting and tightning of tappet cover complete by torque wrench by applying proper pressure of tappet cover gas kit of the 15 KVA DG Set to-75 KVA DG Set capacity
Supply and fixing in repair of breather assembly with 500 Grams silica gel for outdoor type transformers of any capacity upto 315 KVA complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in repair of thermometer(oil temperature gauge) for outdoor type transformer, all as specified and directed by Engineer -in -Charge.
Repair and reconditoning of AMF Panel of DG Set Capacity of 15 to 200 KVA complete all specified and directed by Engineer -in-charge.(Rate quoted including necessary minor spares)
Supply only Capacitor bank 3 KVAr, Heavy duty type,415Volts,50Hz AC supply in existing panel complete as specified and directed by Engr-in-charge.
Ditto all as per item No.63 but of rating 5 KVAR
Ditto all as per item No.63 but of rating 7.5 KVAR
Ditto all as per item No.63 but of rating 10 KVAR
Ditto all as per item No.63 but of rating 25KVAR
Ditto all as per item No.63 but of rating 50KVAR
Material and labour for fault finding on HT/LT cables of any size and any length with fault detective machine by thumbing method and suitable high voltage complete all as specified and directed.
All as per item No 69.00 here in before but search for an additional fault
Supply and fix cable jointing STRAIGHT THROUGH JOINT for 11KV grade cable for straight through joint complete with Jointing material (Heat shrinkable)and accessories suitable for 3 core XLPE armoured, alluminum conductor cable of size upto 95 sq mm and all as directed by Engineer-In-Charge.
Supply and fix cable jointing END TERMINATION JOINT for 11KV grade cable for End termination joint complete with Jointing material (Heat shrinkable)and accessories suitable for 3 core XLPE armoured, alluminum conductor cable of size upto 95 sq mm and all as directed by Engineer-In-Charge.
Supply and fix cable jointing STRAIGHT THROUGH JOINT for 1100V grade cable for straight through joint complete with Jointing material (Heat shrinkable)and accessories suitable for 3.5 core XLPE armoured, alluminum conductor cable of size upto 120 sq mm and all as directed by Engineer-In-Charge.
M&L for complete servicing and caliberation of compact switch gear Vaccum Circuit Breaker (VCB) 11 KV 630Amp,breaking capa 20 KA, indore type both side extensible M+VVV (VCB incomer =02 nos,VCB out going =05 Nos) . Required T & P including taking down old unsv minor spare parts of any nature and repace with new and making functional up to the satisfaction, working with all functions like OC, UV,EF,instant tripping on fault including testing with required instruments omplete all as directed by Eng-in-chaarge.The serving covers the following :- (a) Through cleaning of break chamber (b) Lubrication of shutter mechanism/moving parts (c) Checking of shutter movement (d) Checking door interlocks with panel door (e) Checking of breaker interlocks with panel door (f) Checking of breaker rack in/out inside the panel(g) Coiling of closing and tripping coil (h) Checking of gear box operation operation (j) Checking of Test/Service Aux. Switch operation (k) Checking of tripping mechanism operation (l) Spring charging limit switches operation (m)Checking of SF 6 Gas pressure healthiness of all three poles (n) Checking of damping device and setting (o) Tightness,checking of power connection (p) Checking of breaker ON/OFF operation manuallyand electrically (q) Checking of closing timings (r) Checking and re-setting of IDMT relay with trip command and measure the timings (s) Cleaning of male and female contact assembly by using jelly (t) Checking,meggering of CT and control wiring (u) Replacement of dameged control wiring where required by using same guage and size including required size of cable lugs etc. Note: (a) Minor spares required for repair and calibration of VCB shall deemmed to be include in the quoted rate. (b) The servicing team of VCB shall be the orginal equipment manufacturer of his authorised representative.(c) The contractor shall submit the testing report showing complete parameters for record.
Taking down old unserviceable self powered relay and supply and fix new self powered relay as existing, including complete testing all as specified and directed.
M&L for servicing of self starter 12/24 volts including replacement of minor parts and testing of DG set capacity upto 200 KVA completee all as specified and directed. Note-Major parts will be measured and paid under respective items.
All as per item No 76.00 here in before but Solenoid contacts
All as per item No 76.00 here in before but Solenoid winding
All as per item No 76.00 here in before but Plunger
All as per item No 76.00 here in before but Armature
All as per item No 76.00 here in before but Bushes
All as per item No 76.00 here in before but Field winding
All as per item No 76.00 here in before but Arnature shaft rear bushing
All as per item No 76.00 here in before but Commutator
All as per item No 76.00 here in before but Lever Fork
All as per item No 76.00 here in before but Pinion stop
All as per item No 76.00 here in before but Drive pinion
All as per item No 76.00 here in before butComplete housing as existing
Taking down old unserrviceable deteriorated AMF panel and supply and fix in repair new AMF panel suitable for DG set of capacity 50 KVA with sheet enclosure factory made powder caoted along with suitable rated MCCB's, relay, batterry charger, relay cards, fuel sensing,oil pressure, oil temp, radiator water temp control function complete along with safety features like voltage surge, engiene protection, delay timer etc complete all as specified and directed.
Supply and fix in repair/replacement integral pole mounted decorative pressure die cast aluminium housing with specially designed optics for providing uniform light distribution for outdoor enhanceLED post top light 35 Watt with IP66 protection including all fittings suitable for 80 mm Gi pipe complete all as specified and directed.
Taking down old burnt/unserviceable PCB/PLB card from voltage stabilizer upto capacity 250 KVA and supply,fix, testing and commission new PCB/PLB compitable as existing complete all as specified and directed.
Taking down old unserviceable AVR unit from DG set of various capacity and Supply, installation, testing and commissioning in replcement of AVR unit suitable for 3 phase 50 Hz alternator of capacity upto 200 KVA DG set completer all as specified and directed.
Taking down old unserviceable voltage surge protector relay from existing AMF panel of capacity upto 200 KVA DG set and supply and fix new voltage surge preotection relay complete all as specified and diected.
Taking down old unsserviceable single phase preventer of any make and capacity and supply and fix in replacement single pahaase prevventer complete all as specified and directed.
M&L for servicing of turbo charger of DG sets of capacity upto 200 KVA complete specified and directed. Note:- Spare required will be measured and paid separately.
All as per item No 96.00 here in before but Actuatuor
All as per item No 96.00 here in before but Compressor
All as per item No 96.00 here in before but Compressor housing
All as per item No 96.00 here in before but Centre housing
All as per item No 96.00 here in before but Turbine wheel
All as per item No 96.00 here in before but Turbine housing
All as per item No 96.00 here in before but Wastage assembly
All as per item No 96.00 here in before but Outlet elbow
Taking down old/unserviceable charging motor from VCB of any make and capacitya and ssupplya nd fix in repair new charging motor as existing complete all as specified and directed.
Supply and fix battery 12 Volt 80 AH for DG set operation complete all as specified and directed.
Supply and fix battery 12 Volt 150 AH for DG set operation complete all as specified and directed.
M&L for Hard core/broken stone of gauge not exc. 63mm thick, deposited, spread and levelled in layers not exc 15 cm thick, watered and rammed to a true surface complete as specified and directed.
Material and labour for painting and numbering of electric poles including street light brackets, cross arms,, GOD system, four pole structure, two pole structure, LT panels from outside with two coats of aluminium duco paint after cleaning and preparing the surface of poles of any size complete all specified and directed.
Material and labour for painting and numbering of LT panels from outside with two coats of aluminium duco paint after cleaning and preparing the surface of poles of any size complete all specified and directed.
Supply only manually operated handle for ABB VCB as existing complete all as specified and directed.
Disconecting HT/LT cable and Earthing connections of burnt/defective transformers of capacity upto 315 KVA , 11 kv/433 volts 3 phase from pole/floor mounted, taking down from site of installation carefully with the help of crane and transportation of the same to workshop for repairs, draining out the transformer oil, dismantling complete and taking out the core assembly and removing brunt out windings, dehydrating the core assembly, reassembling transformer after repair, filtred/ dehydrated, topping up new with new oil, carrying out routine tests, including transportation back to site, testing full load after making cable and earthing connections complete all as specified & as directed. (Note :- New transformer oil, Dehydration of transformer oil shall be measured and paid separately.)
M&L for rewinding of LT winding with copper strip of suitable size/gauge, fixing the coil in the position in core assembly and making connection as per original pattern including providing insulation, complete all as specified and as directed.
M&L for rewinding of HT side coil with super enameled copper wire of suitable size/gauge, fixing the coil in the position in core assembly and making connection as per original pattern including providing insulation, complete all as specified and as directed.
Supply and fixing in replacement 433 volt procelain bushing insulators for LT side of out door/ indoor type transformer of capacity capacity upto 315 KVA complete all as specified and as directed
Supply and fixing in replacement 11 KV procelain bushing insulators for HT side of out door/ indoor type transformer of capacity capacity upto 315 KVA complete all as specified and as directed
Supply and fixing in replacement of worn out LT bush assembly made out of brass with heavy duty brass complete with brass spindle, nuts, bolts, washers etc without bushing insulators all as per existing size, shape and length, suitable for capacity upto 315 KVA capacity transformers complete all as specified and as directed
Supply and fixing in replacement of worn out HT bush assembly made out of brass with heavy duty brass complete with brass spindle, nuts, bolts, washers etc without bushing insulators all as per existing size, shape and length, suitable for capacity upto 315 KVA capacity transformers complete all as specified and as directed
Supply and fixing cork sheet gasket, 6 mm thick, superior quality, on top cover plate of the transformer 50 to 315 KVA after taking down/out gasket as existing at site complete all as specified and as directed.
Supply, installation, commissioning and testing of Advance Manitenance Free environment friendly ring earthing system. Each set consisting of 3 Nos of 6 feet length, 17 mm dia earth electrode made of high tensile low carbon steel circular rods, molecularly bonded cooper on outer surface ( minimum copper bonding thickness - 250 microns) with terminals to connect incoming strip with 3 bags (25 Kg each ) of environment friendly backfill compound as per manufacturing instructions with ROHs test certificate for each 150 x 25 x 6 mm Copper Bar with 4 hole shall be exothermically welded ontop to copper bonded rod to make terminal laid in minimum 80 mm dia bore. Manufacturer name shall be embossed on rod. 25 x 3 mm copper shall be used to interconnected the earths and to make the ring. The earth pit cover polypropeline (300 mm x 300 mm) shall be included in the scope of work. Make: OBO/JEF ECO SAFE/ENNOV Note: (i) Earthing shall be tested after completion of work by contractor in presence of Engr-in-Charge and proper record shall be maintained duly signed by all concerned. On testing if the desired earth resistance of less than 1.0 Ohm is not obtained the earthing will be redone at no extra cost to Govt. (ii) The cooper strip from test point to euipment or entire earting system to Eqpt/bldg only shall be measured and paid under relevant item.
Taking down old unserviceable exhaust pipe from DG set of 50 KVA cpacity and supply and in fix in reeplacement new exhaust pipe of exisitng dila and lenghth, complete all as specified and diercted.
Material and labour for painting of DG set of capacity upto 200 KVA with two coats of synthetic enamel paint as existing colour and exhaust with silver paint after cleaning and preparing the surface of DG complete all specified and directed.
Supply and fix in repair/replacement 10 Watt garden light with pressure die cast powder coated housing with PC diffuser, efficient high out put LED with IP 66 protection complete all as specified and directed. Make Crompton Cat Part No LABLA1-10-CDL or equivalent in Philips, Crompton.
Supply & fix I nrepair/replacement LED Flood Light fitting 30 W made out of pressure dia aluminium hosing with heat resistant toughened glass and IP-65 protection complete all as specified and directed.
Taking down old unserviceable copper wire of any size /type from street/security light poles & supply and fix in replacement PVC round sheathed multicore copper cable of size 1.5 Sqmm 3 core for working voltage upto and including 1100 Volts complete all as specified and directed.
Survey of the entire electrical distrubution network starting from main receiving station 11 KV in both technical and domestic area to include survey of the faccility/plants and other current energy consumption pattern and submit in form of comprehensive survey report in duplicate complete all as specified and directed. The survey includes following :-(a) Checking the strength of primary/secondary aspects, insulation level power efficiency & power factor.(b) Bench making of energy performance and matching of energy use to the requirement way to maximum system efficiencies, optimizing the input energy requirement etc.(c) Target to achieve energy cost reduction & identify energy conservation technologies retrofits energy audit procedure and alignment current consumption with current industry benchmarks.(d) Investigation the existing system to bringing out basic five aspects as given below :-(i) How much energy is consumed. (ii) How is the energy consumed.(iii) Where is the energy consumed. (iv) When is the energy consumed. (v) What is the quality of the energy consumed. (e) Give recommendation on the basis of the survey report to include cost effective measures to optimise energy resources and methods to achieve maximum energy efficiency of all assets along with financial calculation/specifications/approved brands etc so as to aid in preparation of DPR and conclusive of contracts in near future. Notes :-(a) Areas coverted by the Electrical Energy Audit Survey :-(i) Complete energy distribution network showing grid substation with all power transformers and distribution transformers.(ii) Analysis of electrical parameters i.e voltage, current, frequency, power factors etc.(iii) Health status of all electrical measuring /controlling and tripping system of MRS.(b) Details of electrical assets mentioned here-in-after, however the firm interested to bid for the subject work is expected to clear the aspects regarding quantum of total assets once again for GE(AF)Sarsawa before submitting the bid and no representation in this regard at the later stage will be entertained.(c) The energy to include will be deemed to considered complete on sucessful submission of Survey report to include specific recommendations on each aspects as bought out above along with duly recommended by GE. For final final technical check and completion.(d) The job shall be carried out through the approved consultant/Energy auditions of MES by E-in-C branch and further shall approved by Accepting Officer. The contractor shall submit the name of approved consultants of their choice and one of the Consultant shall got approved by Accepting Officer through GE.(e) The survey report shall be submitted by contractor to Accepting Officer for approval through GE and after approval twop sets of Survey report shall be submitted by contractorto GE.(f) The Payment of this item shall be made only after approval of survey report.(g) Details of Assests :-(i) Electrical Distribution Network & HT step down transformer-10 Each (ii) HT Breakers-07 Each(iii) MCCB's/ACB's-107 Each (iv) Motors three phase-01 Each (v) Submersible pumps three phase-04 Each (vi) Chloronome plants/dosing pumps-03 Each (vii) DG Sets of different Capacity-06 Each (viii) Servo Voltage Stabilizer (3 Phase)-05 Each (ix) Summer Cooling/Air Conditioning system-108 Each (h) Any other electrical items/equipment/Plants as directed by GE in writing which are not mentioned in above may also part of the work.(j) The cost of all above aspects shall include in quoted rates.
Ansh Enterprises
SHRI RAM ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .