Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹35.3 LAccepted-AOC | ₹35.3 L Quoted ₹36.0 L | L1 | Accepted-AOC L1 |
| 2 | L2₹37.5 LRejected-AOC 39 359 B PULICKAL THIRUVAMBADY POST ALAPPUZHA KERALA PIN 688 002 | ALAPPUZHA | ALAPPUZHA | KERALA | 688002 | ₹37.5 L | L2 | Rejected-AOC L2 |
| 3 | L3₹38.4 LRejected-AOC | ₹38.4 L | L3 | Rejected-AOC L3 |
| 4 | L4₹40.1 LRejected-AOC | ₹40.1 L | L4 | Rejected-AOC L4 |
| 5 | L5₹44.3 LRejected-AOC 22 1755A SANCHU JOHN KANNANKATTU TEMPLE ROAD EDAKOCHI ERNAKULAM KERALA 682010 | ERNAKULAM | KERALA | 682010 | ₹44.3 L | L5 | Rejected-AOC L5 |
| Sl No | Description | Qty | Unit | Phejays Agencies L3 | St George Engineering Works L2 | sanjay Traders L5 | PASAYDAN ELECTRICALS L4 | V V BHARATH ENTERPRISES L1 | ELAN ENGINEERS L6 |
|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Material and labour for general servicing / maintenance of LT ACBs of any make, type installed at various locations by drawing out breaker assembly carefully, disconnecting the electric supply, cleaning the contact points with cleaning solvents recommended by the manufacturer, adjusting/ tightening of fastener /springs etc, lubricating of ON -OFF mechanism and all the moving parts, checking of all electrical connections/tripping device etc. Ensure that all contacts are clean, smooth, and in proper alignment and spring pressures are maintained according to manufacturer’s specifications. on the circuit breaker and the stationary contacts in the cubicle should be cleaned and inspected for overheating, alignment, and broken or weak springs. Coat contact surfaces with contact lubricant to ease mating. Clean all ceramic materials of loose dirt and examine for signs of moisture, make sure the assemblies are clean and dry engage the breaker with supply system and testing for the capacities upto 1250 Amp complete all as specified and directed by the Engineer-in-charge. | 105 | Each Job | 2,000 ₹2.1 L | 1,350 ₹1.4 L | 2,500 ₹2.6 L | 1,500 ₹1.6 L | 2,555 ₹2.7 L | 2,000 ₹2.1 L |
| 2.00 | All as per item No.1 here-in-before, but above 1250 Amp to 2500 Amp capacity ACBs complete all as specified and directed | 35 | Each Job | 2,000 ₹70,000 | 1,500 ₹52,500 | 2,500 ₹87,500 | 2,000 ₹70,000 | 2,750 ₹96,250 | 2,500 ₹87,500 |
| 3.00 | All as per item No.1 here-in-before, but above 2500 Amp to 3200 Amp capacity ACBs complete all as specified and directed
Note for serial item nos. 1 to 3:-
(i) Cost of the lubrication material, gels, cleaning materials, etc are deemed to be included in the quoted rate
(ii) All minor spares below the cost of Rs.250.00 deemed to be included in the quoted rate. | 15 | Each Job | 2,000 ₹30,000 | 1,600 ₹24,000 | 2,500 ₹37,500 | 2,100 ₹31,500 | 2,750 ₹41,250 | 3,000 ₹45,000 |
| 4.00 | Material and labour for general servicing /Maintenance of existing LT panel board of any size after necessary shut down of electric supply, Checking the all incoming/out going cable including replacement of unserviceable cable end sockets by sufficient crimping with crimping tools and replacement of nut, bolt, and washers where ever necessary, Providing additional sleeves on the cable where ever necessary, Repairs to unserviceable door hinges including welding works as required, locking arrangements, Removing all dust/dirt, spider web etc from inside the panel by using hot air blower carefully without affecting the internal wiring, Removing the unserviceable burned bus bar sleeves and its supports and replace the same by new one with colour coded. Tightening of all nuts, bolts and washers, tightening of bus bar and testing complete all as specified and directed by the Engineer-in-Charge.
Note:-The cost of thimble, nut, bolt, washer, bus bar sleeves and rent for tools shall be deemed to be included in the quoted rate. | 85 | Each Job | 2,000 ₹1.7 L | 1,200 ₹1.0 L | 2,500 ₹2.1 L | 1,500 ₹1.3 L | 1,750 ₹1.5 L | 2,000 ₹1.7 L |
| 5.00 | Material and labour for repairs to Stainless steel LT Panel doors by replacing door hinges,welding the damaged portions of door, making good broken/bent surfaces, aligning the damaged doors in position and refixing to the LT panel complete all as specified and directed | 40 | Each Job | 1,500 ₹60,000 | 800 ₹32,000 | 2,500 ₹1 L | 1,500 ₹60,000 | 1,500 ₹60,000 | 2,000 ₹80,000 |
| 6.00 | Material and labour for Copper Earthing of cope boxes/feeder pillar boxes installed at jetty, using copper plate 600x600x3.15mm thick electrode and 32 x 6 mm copper strip through GI pipe medium grade 40mm dia duly fixed on wall/floor. The top portion of the earth electrode will kept up to 2.25 metre below the water bed at the jetty including making test point complete all as specified and as directed. Copper strip up to 8 metre length shall be included in quoted rate. | 6 | Each Job | 17,000 ₹1.0 L | 25,000 ₹1.5 L | 18,000 ₹1.1 L | 5,000 ₹30,000 | 10,500 ₹63,000 | 18,000 ₹1.1 L |
| 7.00 | Material and labour for laying of earth strip 32 x 6 mm copper strip through GI pipe medium grade 40mm dia duly fixed on wall/floor all as specified and as directed. | 40 | RM | 700 ₹28,000 | 2,000 ₹80,000 | 800 ₹32,000 | 150 ₹6,000 | 850 ₹34,000 | 1,500 ₹60,000 |
| 8.00 | Supplying and laying insulated mats for LT Panels and APFC Panels of sizes 1m x 2m ISI marked for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety complete all as specified and directed | 35 | Each | 2,300 ₹80,500 | 2,000 ₹70,000 | 2,750 ₹96,250 | 2,000 ₹70,000 | 2,500 ₹87,500 | 1,700 ₹59,500 |
| 9.00 | Material and labour for general servicing /Maintenance of existing cope boxes of any size inside jetty after necessary shut down of electric supply, Checking the all incoming/outgoing cable including replacement of unserviceable cable end sockets by sufficient crimping with crimping tools and replacement of nut, bolt, and washers where ever necessary, Providing additional sleeves on the cable where ever necessary, Repairs to unserviceable door hinges including welding works as required, locking arrangements, Removing all dust/dirt, spider web etc from inside the panel, Removing the unserviceable burned bus bar sleeves and its supports and replace the same by new one with colour coded, Tightening of all nuts, bolts and washers, tightening of bus bar and testing complete all as specified and directed by the Engineer-in-Charge.
NOTE:-The cost of thimble, nut, bolt, washer, bus bar sleeves and rent for tools shall be deemed to be included in the quoted rate. | 30 | Each Job | 1,500 ₹45,000 | 1,100 ₹33,000 | 3,000 ₹90,000 | 2,000 ₹60,000 | 1,525 ₹45,750 | 2,000 ₹60,000 |
| 10.00 | Supply and fix under voltage release 240 volt to 440 volt AC, complete all as specified and directed | 2 | Each | 5,000 ₹10,000 | 1,300 ₹2,600 | 5,000 ₹10,000 | 1,800 ₹3,600 | 2,500 ₹5,000 | 4,000 ₹8,000 |
Tender Value
Refer Docs
EMD Value
₹94,420
Closing Date
19 Jul 2025, 6:00 pmClosed
GE NS KOCHI
Military Engineer Services Garrison Engineer (Naval Services) Kataribagh, Naval Base Post Kochi 682004.
REPAIR/MAINTENANCE/SERVICING OF LT ACBS AND LT SWITCH GEARS, LT PANELS AND APFC PANELS, FIXED CAPACITOR PANELS AND ALLIED ELECTRIC WORKS AND CONNECTED ACCESSORIES IN E M INSTALLATIONS IN KATARIBAGH, NAY, SFNA, GARUDA AND ALL OTHER AREAS
2025_MES_715559_1
8519/E8
Open Tender
Electrical and Maintenance Works
330 days
KOCHI
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE NS KOCHI
₹94,420
Yes
12 Feb 2026
19 Jun 2025
21 Jul 2025
19 Jun 2025
19 Jul 2025
4 Jul 2025
19 Jun 2025 - 20 Jun 2025
Amount
Material and labour for general servicing / maintenance of LT ACBs of any make, type installed at various locations by drawing out breaker assembly carefully, disconnecting the electric supply, cleaning the contact points with cleaning solvents recommended by the manufacturer, adjusting/ tightening of fastener /springs etc, lubricating of ON -OFF mechanism and all the moving parts, checking of all electrical connections/tripping device etc. Ensure that all contacts are clean, smooth, and in proper alignment and spring pressures are maintained according to manufacturer’s specifications. on the circuit breaker and the stationary contacts in the cubicle should be cleaned and inspected for overheating, alignment, and broken or weak springs. Coat contact surfaces with contact lubricant to ease mating. Clean all ceramic materials of loose dirt and examine for signs of moisture, make sure the assemblies are clean and dry engage the breaker with supply system and testing for the capacities upto 1250 Amp complete all as specified and directed by the Engineer-in-charge.
All as per item No.1 here-in-before, but above 1250 Amp to 2500 Amp capacity ACBs complete all as specified and directed
Material and labour for repairs to Stainless steel LT Panel doors by replacing door hinges,welding the damaged portions of door, making good broken/bent surfaces, aligning the damaged doors in position and refixing to the LT panel complete all as specified and directed
Material and labour for laying of earth strip 32 x 6 mm copper strip through GI pipe medium grade 40mm dia duly fixed on wall/floor all as specified and as directed.
Supplying and laying insulated mats for LT Panels and APFC Panels of sizes 1m x 2m ISI marked for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety complete all as specified and directed
Supply and fix under voltage release 240 volt to 440 volt AC, complete all as specified and directed
Supply and fix draw out handle for ACB, complete all as specified and directed
Supply and fix closing/tripping coil/shunt release upto 415 volt AC, complete all as specified and directed
Supply and fix earth fault relay for ACB, complete all as specified and directed
Supply and fix door interlock kit suitable for fixed or Draw out ACBs, complete all as specified and directed
Supply and fix auxiliary contact block 6/7NO+6/7NC suitable for all rating, complete all as specified and directed
Supply and fix and moving arcing contacts set per pole upto capacity 2000 Amp ACB, complete all as specified and directed
Supply and fix main isolating contacts (Jaw contact) per pole upto 2000 Amp ACB, complete all as specified and directed
Supply and fix SS enclosure with louvers with provision to mount MCCB upto 400 Amps, 50 kA suitable for wall mounting all as specified and directed.
Supply and fix CRCA sheet steel powder coated with provision to mount MCB enclosure 6 way suitable for wall mounting all as specified and directed.
Supply and fix CTs of capacity 400A/630A/800A for thermal over load relay for ACB, complete all as specified and directed
Supply and fix CTs of capacity 1000A for thermal over load relay for ACB, complete all as specified and directed
Supply and fix CTs of capacity 1600A for thermal over load relay for ACB, complete all as specified and directed
Supply and fix only spring charged indication switch for ACB complete all as specified and directed
Supply and fix Key Interlock (Consisting of 2-Key Locks with 1 Key (same No.) fitted on 2 ACBs) complete all as specified and directed
Supply and fix arc chute for ACB per pole upto 2000 Amp complete all as specified and directed
Supply and fix spring charging motor for ACB 220 V AC complete all as specified and directed
Supply and fix control relay for spring charging motor for ACB 220 V AC complete all as specified and directed
Supply and fix micro switch for motor cut off for ACB complete all as specified and directed
Supply and fix manual charging handle for ACB complete all as specified and directed
Supply and fix draw out telescopic rail left or right for ACB complete all as specified and directed
Supply and fix MCB FP 40 Amp, C-Curve, 10kA, 230 volt AC including taking down old unserviceable items, complete all as specified and directed
Supply and fix Isolator, 40 Amp, 4 pole, 415 volt AC including taking down old one, complete all as specified and directed
Supply and fix HRC fuse 2 to 16 Amps, size F1, including taking down old one, complete all as specified and directed
Supply and fix fuse holder suitable for bolted fuse link of 20 Amp, HD 20 B type including taking down old one, complete all as specified and directed
Supply and fix LED indicator lamp (RED, YELLOW, GREEN) complete all as specified and directed
Supply and fix LED indicator lamp (AMBER, BLUE) complete all as specified and directed
Supply and fix Spreader terminals 3 pole suitable for 400 Amp MCCBs including taking down of old one, complete all as specified and directed
Supply and fix Spreader terminals 3 pole suitable for 630 Amp MCCBs (set of 6) including taking down of old one, complete all as specified and directed
Supply and laying or passing through duct/ GI pipe or fixing on wall XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable, heavy duty with aluminium conductor, 1100 Volt grade of size 3.5 core 185 sq mm with suitable size thimbles including taking down old one, complete all as specified and directed
Supply and laying or passing through duct/ GI pipe or fixing on wall XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable, heavy duty with aluminium conductor, 1100 Volt grade of size 3.5 core 300 sq mm with suitable size thimbles including taking down old one, complete all as specified and directed
Design, Fabrication, Supply and installation in repair of cubicle type, totally enclosed, double door Outdoor type (CPRI Approved vendor IP65) floor mounted, fully stainless steel of SAE 316 grade built forced cooling feeder pillar fabricated in compartmentalised design made out of 2.0 mm thick stainless steel sheet of 316 Grade, suitable for operation on 415 Volt, 3 phase, 3 wire, 50 Hz AC supply, 400Amp, TPN aluminium bus bars of high conductivity, DMC/SMC bus bar supports with bottom base channel, Including necessary foundation of minimum 0.6 metre, making necessary holes on jetty for laying of cables using core cutting machine/equipment stickering of feeder names, reconnection of existing/new incoming and outgoing cables, and with the following incomers & Outgoings complete all as specified and directed by Engineer-in-charge. (A) Incomer :- (a) 250Amps, 4P, 36kA MCCB with Thermal magnetic release having O/L & S/C protection - 1 No. (B) Outgoing :- (a) 200A 4P MCCB 25Ka – with Thermal magnetic release having O/L & S/C protection – 1 No (b) Digital MF Meter with suitable ratio CTs -1 Set. (d) LED Phase Indication lamp with control MCBs - 1 Set.
Cutting existing concrete/metal/ bituminous road/PCC hard standing or tile walk way any type n.exc 45 cm width and n.exc 20 cm in depth in hard strata and making good disturbed surfaces, matching with PCC(1:4:8) type D2 using 40mm graded stone aggregate including disposal of surplus material to a distance n.exc 50 m, complete all as specified and directed
Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth and getting out in soft / loose soil for laying of cable complete all as specified and directed
Returning filling in including, spreading, leveling, watering and well ramming in layers not exceeding 25 cm in soil , complete all as specified and directed
Removing excavated soil to a distance not exceeding 50 metre and depositing where directed at a level, not exceeding 1.5 metre above the starting point, complete all as specified and directed.
Material and labour, filling river sand as cushioning for underground cables, complete all as specified and directed
Supply and laying un-reinforced precast concrete cable cover of class LV, type - 1, flat , size 250 mm X 150 mm X 40 mm laid in trenches for protection of cable complete all as specified and directed .
Material and labour for painting to LT panel/LT Feeder Pillar box with two coats of synthetic enamel paint or aluminium paint by using spray paint machine after removing the electric supply, then thoroughly cleaning the surface to remove dirt, grease, oil and preparation of old painted surfaces, etc, Making the surface ready to paint including marking/ writing incomer/outgoing feeders name and connection of the electric supply, complete all as specified and directed
Material and labour 100 mm bore steel tubes, "light grade” galvanised with all fittings, laid in trenches or fixing on wall/roof/floor, including taking down old one, complete all as specified and directed
Material and labour 80 mm bore steel tubes, "light grade” galvanised with all fittings, laid in trenches or fixing on wall/roof/floor, including taking down old one, complete all as specified and directed
Supply and fixing MCCB 100 Amp, breaking capacity Icu=Ics=25 kA, three pole, 415 volt AC with thermal release range 80 - 100 Amp with spreader complete all as specified and as directed.
Supply and fixing MCCB 125 Amp, breaking capacity Icu=Ics=25 kA, three pole, 415 volt AC with thermal release range 100 - 125 Amp with spreader complete all as specified and as directed.
Supply and fixing MCCB 160 Amp, breaking capacity Icu=Ics=25 kA, three pole, 415 volt AC with thermal release range 125 - 160 Amp with spreader complete all as specified and as directed.
Supply and fixing MCCB 200 Amp, breaking capacity Icu=Ics=25 kA, three pole, 415 volt AC with thermal release range 160 - 200 Amp with spreader complete all as specified and as directed.
Supply and fixing MCCB 250 Amp, breaking capacity Icu=Ics=25 kA, three pole, 415 volt AC with thermal release range 200 - 250 Amp with spreader complete all as specified and as directed.
Supply and fixing MCCB 400 Amp, breaking capacity Icu=Ics=36 kA, three pole, 415 volt AC with thermal release range 320-400 Amp with spreader complete all as specified and as directed.
Supply and fixing MCCB 630 Amp, breaking capacity Icu=Ics=36 kA, three pole, 415 volt AC with thermal release range 500-630 Amp with spreader complete all as specified and as directed.
Supply and fixing MCCB 100 Amp, breaking capacity Icu=Ics=25 kA, four pole, 415 volt AC with thermal release range 67-100 Amp with spreader complete all as specified and as directed.
Supply and fixing MCCB 160 Amp, breaking capacity Icu=Ics=25 kA, four pole, 415 volt AC with thermal release range 125-160 Amp with spreader complete all as specified and as directed.
Supply and fixing MCCB 200 Amp, breaking capacity Icu=Ics=25 kA, four pole, 415 volt AC with thermal release range 160-200 Amp with spreader complete all as specified and as directed.
Supply and fixing MCCB 250 Amp, breaking capacity Icu=Ics=25 kA, four pole, 415 volt AC with thermal release range 200-250 Amp with spreader complete all as specified and as directed.
Supply and fixing MCCB 400 Amp, breaking capacity Icu=Ics=36 kA, four pole, 415 volt AC with thermal release range 320 - 400 Amp with spreader complete all as specified and as directed.
Supply and fixing MCCB 630 Amp, breaking capacity Icu=Ics=36 kA, four pole, 415 volt AC with thermal release range 500 - 630 Amp and adjustable magnetic with spreader complete all as specified and as directed.
Supply and fix heavy duty industrial Exhaust fan 450 mm sweep, 1400 RPM, four blades ISI marked, metallic, 230 volts, 50 Hz with frame and mounting accessories all as specified and as directed.
Material and labour for Control wiring along with earth wire with the FR LS insulated copper conductor, multistranded, single core cable of size two run of 4 sq mm and one run of 4 sq mm as earth wire in existing conduit including taking down of old one, all as specified and as directed .
Supply and laying or passing through duct/ GI pipe or fixing on wall LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable, heavy duty with aluminium conductor of size 4 core 25 sq mm with suitable size thimbles, glands including taking down old one, complete all as specified and as directed .
Material and labour in repair two pole power contactor 25 Amp, type MNX, complete all as specified and as directed.
Material and labour in repair digital time switch 12VDC1 C/O Base/DIN 25 ON/ OFF or FMI / Quart Daily, 240 volt AC, complete all as specified and as directed.
Material and labour in repair, MCB SP 6 Amp to 32 Amps, "C" Curve, complete all as specified and as directed.
Supply and laying or passing through duct/ GI pipe or fixing on wall LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable, heavy duty with aluminium conductor of size 2 core 10 sq mm with suitable size thimbles, glands including taking down old one, complete all as specified and as directed .
Materials and labour for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, buried directly and preferably vertically in ground, earth pit not less than 2.25 Metre deep below ground level with top edge of the plate not less than 1.5 m below ground level connected with galvanised strip of size 32 x 6 mm by means of nuts, bolts, check nuts and washers including welding of each joints made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe 40 mm bore (medium grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded stone aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C both ways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 metre etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion all as specified and as directed.
Supply and fix Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for loop earthing etc as required of size 32x6 mm GI strip complete all as specified and directed
Supply and fixing 03 CT 300/5 Amp, insulated, class 1.0 complete all as specified and as directed.
Supply and fixing 03 CT 600/5 Amp, insulated, class 1.0 complete all as specified and as directed.
Supply and fixing 03 CT 500/5 Amp, insulated, class 1.0 complete all as specified and as directed.
Supply and fixing 03 CT 400/5 Amp, insulated, class 1.0 complete all as specified and as directed.
Supply and fixing 03 CT 200/5 Amp, insulated, class 1.0 complete all as specified and as directed.
Supply and fixing 03 CT 100/5 Amp, insulated, class 1.0 complete all as specified and as directed.
Material and labour in repair for sub main wiring with 2 runs of 6 Sqmm single core, PVC insulated, unsheathed, multistranded copper conductor FRLS cable 1100 volts grade drawn through and including concealed PVC conduit pipe of medium duty not less than 25 mm dia including necessary PVC conduit specials and one run of 6 Sqmm cable single core PVC insulated, unsheathed, ,1100 Volts grade multistranded copper conductor FRLS cable as earth continuity conductor and connecting with suitable size thimble including cutting the chases etc and making good the disturbed surface to match with the existing complete all as specified and as directed. Note:-Three runs of 6 Sqmm size PVC copper cable and one run of PVC conduit shall be measured as one unit length.
Material and labour in repair for sub main wiring with 4 runs of 10 Sqmm single core, PVC insulated, unsheathed, multistranded copper conductor FRLS cable 1100 volts grade drawn through and including concealed PVC conduit pipe of medium duty not less than 32 mm dia including necessary PVC conduit specials and one runs of 10 Sqmm cable single core PVC insulated, unsheathed ,1100 Volts grade multistranded copper conductor FRLS cable as earth continuity conductor and connecting with suitable size thimble including cutting the chases etc and making good the disturbed surface to match with the existing complete all as directed. Note:-Five runs of 10 Sqmm size PVC copper cable and one run of PVC conduit shall be measured as one unit length.
Supply and fixing in repair sub main wiring with 2 x 2.5 Sqmm FR PVC insulated copper conductor along with 1 x 2.5 Sqmm PVC insulated copper conductor as earth continuity conductor in existing PVC Conduit complete all as specified and as directed.
Supply and fixing in replacement and testing of LED street light of 45W capacity made up of pressure die cast housing and high power LEDs as light source and lens embedded PC cover with IP 66 complete all as specified and as directed.
Supply and fixing in replacement and testing of LED high bay luminaries of 120W capacity integral driver, frame, toughened glass & IP 65 including mounting bracket of suitable size with necessary civil work and copper wire of suitable size for making electric connection all as specified and directed
Supply and fix sheet metal enclosure TPN for DB's when MCB's to be used 12 way with 200 amps bus bar and double door complete all as specified and directed.
Supply and fix MCB FP 63 Amps,440 Volts,10 KA 'C' series with all incoming/outgoing connections with proper size of lugs complete all as specified and directed.
Supply and fix MCB DP 40 Amps,240 Volts,10 KA 'C' series with all incoming/outgoing connections with proper size of lugs complete all as specified and directed.
Supply and fix 5mm thick plain or chequered Mild steel plates for LT Panels and APFC panel cable ducts, Fe-410- W(Grade- E-250) quality-B or over in thickness in available sizes complete all as specified and directed. Note:- (a) Rate quoted shall be inclusive of minor repairs such as cutting existing PCC and making good with necessary PCC/ cementing work to the existing trenches inside substations so that chequered mild steel plates will be fitted properly. (b) Rated quoted shall be inclusive of material and labour for relaying the cables inside the trenches completely covered by the chequered plates.
Supply and fix plain channels/angles/bars square cut or notched Fe-410- W(Grade-E-250)quality-B (ordinary and counter sunk) forming holes, without any attachment complete all as specified and directed.
Supply and fix thermal magnetic release for ACB, complete all as specified and directed
Supply and fix microprocessor based release with earth fault, over current and shirt circuit protection with time settings for ACB, complete all as specified and directed
Supply and fix three phase over current and earth fault relay 5A with high set having IDMT and definite time characteristics, 240 V AC auxiliary supply including necessary cutting/alteration in panel board complete all as specified and directed
Supply and fix OCR(Fault) Alarm switch (for fault indication in ACB with MP & TM release) complete all as specified and directed
Supply and fixing MCCB 800 Amp, breaking capacity Icu=Ics=36 kA, Four pole, 415 volt AC with thermal release range 500-800 Amp with spreader complete all as specified and as directed.
Supply and installation of higher rating joint block 2500 Amps, 3P4w 5mm Thk SP for S-Line busbar trunking system(02 Joint blocks) alongwith necessary horizontal hanger supports of size 40mmx40mmx2mm for mounting BBT, Hanger rod(12mm dia) with hardwares for mounting BBT support up to 100mm, Extra hanger rod(12mm dia) of 100mm long without hardwares including dismantling of existing joint blocks complete all as specified and as directed by the Engineer-in-charge.
Material and labour for fixing in repairs of double compression cable glands suitable for XLPE insulated armoured UG cable for following sizes:-
All as per item No 99 here-in-before but double compression cable gland for XLPE UG cable of size 185 Sqmm 3.5 core flameproof type as per IS:2148 with IP:13947 complete all as specified and directed
All as per item No 99 here-in-before but double compression cable gland for XLPE UG cable of size 300 Sqmm 3.5 core flameproof type as per IS:2148 with IP:13947 complete all as specified and directed
All as per item No 99 here-in-before but double compression cable gland for XLPE UG cable of size 400 Sqmm 3.5 core flameproof type as per IS:2148 with IP:13947 complete all as specified and directed
Material and labour for welding of broken or damaged earth strip including placing new porcelain insulator after welding complete all as specified and directed
Material and labour for removing/taking down/cutting/drilling old unserviceable broken/damaged earth strips from the substation complete all as specified and directed
Material and labour for removing/taking down/cutting/drilling old unserviceable broken/damaged LT UG cables from the substation complete all as specified and directed
Material and labour for meggering of all the earth resistances of earthings of LT and APFC Panels and other control panels inside the MES Substations including marking of the measured resistance with black paint on the earth pit at the substation all as specified and as directed. The test reports of all the earth resistances, Earth to neutral voltages measured shall be submitted to the Engineer-in-charge.
Servicing of Automatic Power Factor Correction (APFC) panel of the capacity 100 kVAr complete comprising MDXL type heavy duty capacitor having low watt loss, APFC relay, MCCB, Cooling fan, Voltmeter, Ammeter, CTs with all other connected accessories, checking of serviceability of each component, cleaning all contact points, tightening of all connections including replacement of unserviceable components, thimbles, nut bolt and washers, etc if necessary, cleaning the entire panel by using hot blower complete all as specified and directed by Engineer-in-Charge.
All as per item No.104 here-in-before but capacity 125 kVAr complete all as specified and directed
All as per item No.104 here-in-before but capacity 250 kVAr complete all as specified and directed
All as per item No.104 here-in-before but capacity 300 kVAr complete all as specified and directed
All as per item No.104 here-in-before but capacity 375 kVAr complete all as specified and directed
Supply and fixing in repairs of Heavy duty capacitors 3 kVAr, voltage 440 volt, 3 Phase, cylindrical, having operating losses 0.35 W/kVAr complete all as specified and directed
Supply and fixing in repairs of Heavy duty capacitors 5 kVAr, voltage 440 volt, 3 Phase, cylindrical, having operating losses 0.35 W/kVAr complete all as specified and directed
Supply and fixing in repairs of Heavy duty capacitors10 kVAr, voltage 440 volt, 3 Phase, cylindrical, having operating losses 0.35 W/kVAr complete all as specified and directed
Supply and fixing in repairs of Heavy duty capacitors 12.5 kVAr, voltage 440 volt, 3 Phase, cylindrical, having operating losses 0.35 W/kVAr complete all as specified and directed
Supply and fixing in repairs of Heavy duty capacitors 25 kVAr, voltage 440 volt, 3 Phase, cylindrical, having operating losses 0.35 W/kVAr complete all as specified and directed
Supply and fixing in repairs APFC relay, 4 Stage, auto set function, having digital display complete all as specified and directed
Supply and fixing in repairs APFC relay, 6 Stage, auto set function, having digital display complete all as specified and directed
Supply and fixing in repairs APFC relay, 8 Stage, auto set function, having digital display complete all as specified and directed
Supply and fixing in repairs APFC relay, 12 Stage, auto set function, having digital display complete all as specified and directed
Supply and fixing in repairs thyrister switching module, 440 volt, 50 Hz, having high peaking inverse voltage of 2.2 kV suitable for 10 kVAr rating complete all as specified and directed
Supply and fixing in repairs thyrister switching module, 440 volt, 50 Hz, having high peaking inverse voltage of 2.2 kV suitable for 25 kVAr rating complete all as specified and directed
Supply and fixing in repairs thyrister switching module, 440 volt, 50 Hz, having high peaking inverse voltage of 2.2 kV suitable for 50 kVAr rating complete all as specified and directed
Supply and fixing in repairs capacitor duty contactor, 415 volt, 3 phase, 50 Hz, 1 NO+NC, suitable for kVAr rating upto 5 kVAr complete all as specified and directed
Supply and fixing in repairs capacitor duty contactor, 415 volt, 3 phase, 50 Hz, 1 NO+NC, suitable for kVAr rating upto 12.5 kVAr complete all as specified and directed
Supply and fixing in repairs capacitor duty contactor, 415 volt, 3 phase, 50 Hz, 1 NO+NC, suitable for kVAr rating upto 15 kVAr complete all as specified and directed
Supply and fixing in repairs capacitor duty contactor, 415 volt, 3 phase, 50 Hz, 1 NO+NC, suitable for kVAr rating upto 20 kVAr complete all as specified and directed
Supply and fixing in repairs capacitor duty contactor, 415 volt, 3 phase, 50 Hz, 1 NO+NC, suitable for kVAr rating upto 25 kVAr complete all as specified and directed
Supply and fixing in repairs capacitor duty contactor, 415 volt, 3 phase, 50 Hz, 1 NO+NC, suitable for kVAr rating upto 50 kVAr complete all as specified and directed
Supply and fixing in repairs 3 pole contactor 70 amp, type MNX 70, 415 volt, 3 phase, 50 Hz, 2 NO+2NC complete all as specified and directed
Supply and fixing in repairs 3 pole contactor 110 amp, type MNX 110, 415 volt, 3 phase, 50 Hz, 2 NO+2NC complete all as specified and directed
Supply and fixing in repairs 3 pole contactor 140 amp, type MNX 140, 415 volt, 3 phase, 50 Hz, 2 NO+2NC complete all as specified and directed
Supply and fixing in repairs electronic time switch complete all as specified and directed
Supply and fixing in repairs side mounting Add-On block on auxiliary contact block suitable for MOC, 1NO+1NC complete all as specified and directed
Supply and fixing in repairs HRC fuse, DIN type fuse links, 250 Amps complete all as specified and directed
Supply and fixing in repairs HRC fuse, DIN type fuse links, 160 Amps complete all as specified and directed
Supply and fixing in repairs HRC fuse, DIN type fuse links, 125 Amps complete all as specified and directed
Supply and fixing in repairs HRC fuse, DIN type fuse links, 80 Amps complete all as specified and directed
Supply and fixing in repairs PVC Cooling fan for APFC panel 6" Sweep complete all as specified and directed
Material and labour for painting to APFC panel with two coat of synthetic enamel paint by using spray paint after isolating the electric supply then thoroughly cleaning the surface to remove dirt, grease, oil stains and preparation of old painted surfaces, etc and making the surface ready to paint including re-connection of electric supply complete all as specified and directed by Engineer-in-Charge
Trimming of tree branches upto 150 mm dia inside the MES sub stations using all the necessary tools and taking out the cut branches from the sub station premises and cleaning all the sub station premises complete all as specified and directed by Engineer in Charge
Supply and fixing of MCCB handles for MCCBs rated above 100 Amps and up to 250 amps including taking down old item complete all as specified and directed
Supply and fixing of MCCB handles for MCCBs rated above 250 Amps and up to 800 amps including taking down old item complete all as specified and directed by Engr in charge.
St George Engineering Works (BID ID -3362081)
Phejays Agencies (BID ID -3355136)
PASAYDAN ELECTRICALS (BID ID -3354124)
sanjay Traders (BID ID -3363103)
ELAN ENGINEERS (BID ID -3363543)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid