| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.9 LAccepted-AOC MUKALATH VALAYANCHIRANGARA PO PERUMBAVOOR ERNAKULAM KOCHI 683556 | PERUMBAVOOR | ERNAKULAM | KERALA | 683556 | ₹6.9 L Quoted ₹7.1 L | L1 | Accepted-AOC lowest tender |
| 2 | L2₹8.2 L+₹1.1 L (15.4%)Rejected-Finance EDALAKADU THABORE P O MOOKANNOOR ERNAKULAM DIST KERALA 683 577 | MOOKANNOOR | ERNAKULAM | KERALA | 683577 | ₹8.2 L+₹1.1 L (15.4%) | L2 | Rejected-Finance OTHER THAN LOWEST TENDER |
Tender Value
₹9.6 L
EMD Value
₹19,200
Closing Date
28 Jan 2021, 6:00 pmClosed
GE NS KOCHI
Military Engineer Services Garrison Engineer (Naval Services) Kataribagh, Naval Base Post Kochi, 682 004
REPAIR/MAINTENANCE OF LIGHTNING CONDUCTORS AND CEILING FAN, EXHAUST FAN, ELECTRIC SUPPLY, GEYSER AND COOLING APPLIANCES, SPLIT/WINDOW TYPE AC UNDER AGE B/R ALWAYE
2021_MES_409764_1
8760/E8
Open Tender
Electrical and Maintenance Works
Item Rate
330 days
ALUVA
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE NS KOCHI
₹19,200
Yes
21 May 2021
8 Jan 2021
30 Jan 2021
8 Jan 2021
28 Jan 2021
16 Jan 2021
9 Jan 2021 - 15 Jan 2021
Amount
Taking down carefully copper / aluminium point wiring (light, fan, socket or power) complete and making good disturbed surfaces of walls, floors, ceiling etc all as specified and directed.
Attending internal/External electric complaints for maintenance/breakdown round the clock for maintenance, Checking, Fault finding and rectification of fault in LT Panels/Overhead HT/LT Lines, HT/LT underground cables, Transformers, Switchgears internal electric faults, geysers, fans etc, and carry out repairs and resume electric supply complete all as specified and directed by Engineer-in-Charge. Notes:- (a) Day to day complaint rectified by the electrician shall be written in complaint register and complaint document slip, rectified complaints only shall be measured and paid. Complaint attender shall have minimum qualification of ITI electrician cum plumber having 2 years experience of same nature of work is to be employed. (b) The Spares required for rectification of faults shall be measured under relevant items. (c) All necessary Tools shall be available with the contractor while executing the compliant. (d) All consumables other than mentioned in Schedules are deemed to be included in the rate quoted. (e) All kind of transport for the complaint attender/materials and mobile / cell charges are deemed to be included in the rate quoted. (f) All safety aspects are to be taken and if any accident/hazardous incidents happen during execution shall be the sole responsibility of the Contractor.
Material and labour for point wiring with 1.5 Sqmm PVC insulated unsheathed single core multistranded copper conductor cable, FRLS, ISI marked drawn through and including PVC conduit of suitable size and all accessories, not less than 20mm thick, fire resistant, ISI marked including 2 mm thick and 4cm depth GI sheet pressed terminal box ( recessed) with 3 mm thick laminated hylum sheet top cover including 1.50 Sqmm PVC insulated unsheathed multistranded single core copper conductor FRLS, ISI marked cable as earth continuity conductor and making good the disturbed surfaces of walls, floors, ceiling etc all as specified and directed for One light point controlled by one switch.
Ditto All as per Serial item No 3 but for One ceiling fan point controlled by one switch.
Ditto All as per Serial item No 3 but for One 3 pin 5 Amps socket outlet controlled by one switch on independent board.
Ditto All as per Serial item No 3 but for One 3 pin 5 Amps socket outlet controlled by one switch in the same board with other switches.
Ditto All as per Serial item No 3 but for One bell point controlled by one bell push
Ditto All as per Serial item No 3 but for One light point controlled by 2 Nos two way switches
Ditto All as per Serial item No 3 but with 2.5 Sq mm cable for wiring and 1.50 Sqmm cable as earth continuity conductor for one 16 Amps switch socket outlet on independent board.
Material and labour for point wiring with 1.5 Sqmm FRLS single core multi stranded copper conductor cable drawn through and including ERW steel conduit of suitable dia including 1.5 Sqmm FRLS copper conductor cable as earth continuity conductor with and including 2 mm thick and 4cm depth GI sheet pressed terminal box (recessed) with 3 mm thick laminated hylam sheet top cover complete for one light/fan/exhaust fan point controlled by one switch.
Ditto All as per Serial item No 10 but for One 3 pin socket outlet, 15 amps, independent, with cables of 4 Sqmm size.
Supply & Fix Switch flame proof rotary type with termination box in LM6, 16A, single pole 250V complete all as specified directed.
Supply and fix in repairs switch piano, flush type, 6 Amps, SP, one way, all as specified and directed.
Supply and fix in repairs switch piano, flush type, 6 Amps, SP, two way, all as specified and directed.
Supply and fix in repairs bell push, flush type, 6 Amps, all as specified and directed.
Supply and fix in repairs socket outlet, flush type, 6 Amps, 2/3 pin, all as specified and directed.
Supply and fix in repairs switch socket combination, 2/3 pin, 06 Amps, flush type, all as specified and directed.
Supply and fix in repairs switch socket combination 6 pin 6/16Amps, flush type, multipurpose, all as specified and directed.
Supply and fix in repairs ceiling rose, surface type, bakelite, 65x50mm, 3 terminals, all as specified and directed
Supply and fix in repairs plug top, 3 pin 16 Amps, 240V, Bakelite body, all as specified and directed.
Supply and fix in repairs call bell, AC, 230 Volts, single pole, all as specified and directed.
Supply and fix in repairs, fan regulator, electronic socket type, hum proof, AC, 240 Volts, 5 step, all as specified and directed.
Supply and fix in repairs lamp holder, pin type, insulated body with back plate suitable for batten fittings, AC, 240V, all as specified and directed.
Material and labour for sub main wiring with 2 runs of 4 Sq mm PVC insulated unsheathed single core multistraded copper conductor cable, FRLS, ISI marked and one run of 4 Sqmm multistranded insulated copper conductor cable, FRLS, ISI marked as earth continuity conductor drawn through and including PVC conduit of suitable size and all accessories, not less than 25mm thick, fire resistant, ISI marked and making good the disturbed surfaces of walls /floors/ceiling etc and including removing the existing aluminium sub main wiring cable, all as specified and directed.
Supply and fix in repairs sheet metal enclosure for MCB DB TPN 4 ways, 415V with 200 Amps bus bar, double door, all as specified and directed.
Supply and fix in repairs sheet metal enclosure for MCB DB SPN, 4 ways, and 240V with 200 Amps bus bar, double door, all as specified and directed.
Supply and fix in repairs sheet metal enclosure for MCB DB SPN 8 ways, 240V, with 200 Amps bus bar, double door, all as specified and directed.
Supply and fix in repairs sheet metal enclosure for MCB DB SPN 12 ways, 240V, with 200 Amps bus bar, double door, all as specified and directed.
Supply and fix in repairs MCB SP 6 to 32 Amps, 'C' series all as specified and directed.
Supply and fix in repairs MCB SPN 32 Amps, 'C' series all as specified and directed.
Supply and fix in repairs MCB TPN 40 Amps , 'C' series all as specified and directed.
Supply and fix in repairs MCB TPN 63 Amps, 'C' series all as specified and directed.
Supply and fix in repairs Isolator, DP 40 Amps,‘C’ series all as specified and directed.
Supply and fix in repairs SPN sheet metal enclosure with a two in and earth plug and socket complete with one MCB SP 10 Amps, 240V and connecting complete, all as specified and directed.
Supply and fix in repairs RCCB, double pole, 40A, 30mA, and 240V, all as specified and directed.
Supply and fix in repairs RCCB, four pole, 63A, 30mA, and 415V, all as specified and directed.
Supply and fix LED Tube light suitable for 4 feet long 18/22 W Florescent Tube light fittings all as specified and directed.
Supply and fix in repairs spring loaded, rotary type bipin holder suitable for 1x28/36/40W FTL, all as specified and directed.
Supply and connect in repairs, 1100V grade, PVC insulated flexible twisted twin core cable with multistranded copper conductor of size 23/0-0076 Sqmm, all as specified and directed.
Material and Labour Earthing of Poles with GI wire 4mm dia with galvanised MS earth plate of size 600 x 600 x 6 mm buried directly in ground vertically to a depth not less than 2.25 metre below ground level, earth plate shall be packed on all side with charcoal mixed with salt to a thickness of 150mm in layers, connected to GI earth wire 4mm dia (8 SWG) protected by GI pipe 15mm bore (light grade) and watering pipe 20 mm dia (light grade) of suitable length, with necessary earth work including disposal of surplus soil to a distance not less than 50 metre, PCC pit chamber with RCC cover frame, funnel, wire mesh. The GI earth wire 8 SWG under the earth and on the pole up to a height of 1.5 metre shall also be protected by 15mm dia GI pipe (light grade) & GI pipe to be fixed with poles by the means of 2 Nos flat iron clamp 25 x 3 mm size complete with bolts, nuts and washers etc. all as specified and shown in electrical plate No 3 of SSR Part I - 2009 including testing on completion. Note: - Main earthing lead from earth plate to test point & up to 7.5 Metre to be provided. The cost for the same shall be deemed to be included in the above quoted rate.
Supply & Fix fluorescent LED tube light fitting, 1x22W, 230V, with aluminium housing and integrated electronic driver complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size. Make Havells Cat No LUMILINEPLUSBS22WLED865SPCSS or equivalent in Philips/Crompton
Disconnecting and taking down Ceiling Fan 1200mm/1400 mm Sweep, any size, any make, from various satellite area locations, for repair /painting / replacement of defective parts and re-hanging / re-fixing in its original location after reconditioning, complete as specified and directed Note :- Items for reconditioning will be measured and paid separately.
Ditto All as per Serial item No 42 but for Wall Fan 450mm Sweep.
Ditto All as per Serial item No 42 but for Exhaust Fan 300mm Sweep.
Ditto All as per Serial item No 42 but for Exhaust Fan 450mm Sweep.
Material and Labour for removing the burnt out winding, cleaning slots, re-winding the motor with super enameled copper wire of size equivalent to the original winding including insulated packing materials, varnishing, drying etc., replacement of body screws, testing and commissioning on full load for 8 hours continuous running, for Ceiling Fan 1200mm Sweep complete as specified and directed.
Ditto All as per Serial item No 46 but for Wall Fan 450mm Sweep.
Ditto All as per Serial item No 46 but for Exhaust Fan 300mm Sweep.
Ditto All as per Serial item No 46 but for Exhaust Fan 450mm Sweep.
Material and Labour for Preparing the surface by scraping and removing the existing painting, cleaning, filling the cavities and applying two coats of spray paint of synthetic enamel white / brown colour over a coat of red oxide zinc chromate primer, including writing the MES Nos. for the Ceiling Fan 1200mm Sweep complete all as specified & directed.
Ditto All as per Serial item No 50 but for Ceiling Fan 1400mm Sweep.
Ditto All as per Serial item No 50 but for Wall Fan 450mm Sweep.
Ditto All as per Serial item No 50 but for Exhaust Fan 300mm Sweep.
Ditto All as per Serial item No 50 but for Exhaust Fan 450mm Sweep.
Supply and replace, Condenser / Capacitor of 2.5 MFD, 240V, AC suitable for fans, all as specified and directed.
Supply and replace, Condenser / Capacitor of 4 MFD, 240V, AC suitable for fans, all as specified and directed.
Supply and replace ball bearing made out of high carbon steel, equivalent to the original, suitable for any type, any make, any size fan, all as specified and directed
Supply and replace bush bearing, made out of brass alloy, equivalent to the original, suitable for any type, any make, any size fan, all as specified and directed.
Supply and replace down rod, suitably holed, made out of 15mmdia GI tubes, duly painted, 300mm long, suitable for ceiling fans any type, any make, any size, all as specified and directed.
Supply and replace nut bolt with rubber reel insulator including split pin and washer, suitable for ceiling fans any type, any make, any size, all as specified and directed.
Supply and replace, bakelite body nichrome connectors, 2 way, with fixing screws of suitable size for ceiling fans of any type, any make, all as specified and directed.
Supply and replace 1100 Volts grade PVC flexible twisted twin core cable with multistranded copper conductor of size 23/0.0076, all as specified and directed.
Taking down defective Geyser of capacity 25 liters of any make from its existing position after disconnecting inlet/outlet water connection and opening of geyser for checking and repairing the defective parts including testing and commissioning the same after successful repairing painting with synthetic enamel paint(duco) by spraying after preparation of the steel surfaces and re fixing the same on its existing position and making connection inlet/outlet water connection complete all as specified and directed. Note:- (i) The replaced defective parts will be measured and paid separately as supply only items under the relevant items of this BOQ (ii) Labour charges required for replacement of spares shall deemed to be included in the unit rate quoted by the tenderer.
Ditto All as per Serial item No 63 but for Geyser of capacity 50 liters.
Supply and replace Heating element of capacity 1.5KW of any type, 240V, AC, with heat resistant rubber washer and connecting complete all as specified and directed.
Ditto All as per Serial item No 65 but for Heating element of capacity 2.0KW.
Supply and replace Thermostat control unit suitable for 25/50 Litres capacity geysers, 30-90 degree rating, any type, 240V, AC and connecting complete all as specified and directed.
Supply and replace indicator lamp round / rectangular type, standard quality, AC, SP, 230V, Red or Green and connecting complete, all as specified and directed.
Supply and replace fusible plug with internal or external threading suitable for geysers of capacity 25/50 liters, all as specified and directed.
Supply and replace non-return valve, made out of brass 15mm bore, all as specified and directed.
Supply and replace PVC sheathed, multi stranded copper conductor, 3 core, flexible cable, 1100 V grade, size 40/0.0076, AC and connecting complete all as specified and directed.
Fabricate and replace, GI bottom cover / inspection plate, 2 mm thick, split type, as per sample, duly painted with 2 coats synthetic enamel paint over a coat of red oxide zinc chromate primer to match with the existing colour for any type/size of Geysers all as specified and directed.
Preparing the surface by scraping and removing the existing painting, cleaning, filling the cavities and applying two coats of spray paint with synthetic enamel white paint over a coat of red oxide zinc chromate primer, including writing the MES Nos. complete as specified & directed for capacity of geyser 25 litre
Ditto All as per Serial item No. 73 but for capacity of geyser 50 litre.
Material and labour for making 4 Nos of holes in wall, grouting 4 Nos rag bolts of size 125mm long x 12mm dia with PCC including necessary nuts and washers for fixing geysers on wall complete all as specified and directed.
Supply and replace inner assembly made out of brass with chromium plating, suitable for Geysers capacity 25 litre complete all as specified and directed .
Ditto All as per Serial item No. 76 but for capacity of geyser 50 litre.
Replacement of geyser bottom main terminal, synthetic gasket, fixing clamps, cleaning inner container/tank and assembly complete all as specified and directed.
Material and labour for filling the glass wool between outer cover and inner tank of Geysers, 50/25 litres capacity, horizontal / vertical, complete all as specified and directed.
Supply and fix metallic outer cover including bottom and top cover duly spray painted with two coats of synthetic enamel paint over a coat of red oxide chromate primer, suitable for any type of geyser for the capacity 25 litre complete all as specified and directed.
Ditto All as per Serial item No. 80 but for capacity of geyser 50 litre.
Supply and replace inner tank made out of copper alloy, suitable for any type of geyser, for the capacities 25 litre complete all as specified and directed.
Ditto All as per Serial item No. 82 but for capacity of geyser 50 litre.
Material and labour for repairs to metallic inner tank, arresting the leakage by welding, brazing etc, pressure testing after repairs, for any type of geyser for capacity 25/50 litres complete all as specified and directed.
Supply and replace pressure / air release valve suitable to fix in inlet of geyser, made out of brass 15mm bore complete all as specified and directed.
Material and Labour for disconnecting from position, transporting to local workshop for servicing including cleaning of interior parts and body with solvent materials, replacement of unserviceable spares/parts if required, necessary repairs, transporting back, Installing at its original location, Connecting, Testing and commissioning of water Cooler of capacity 40/40, 40/80 or 60/120 complete all as specified & directed. Note:- Spares will be measured and paid separately.
Ditto All as per Serial item No. 86 but for Ozone based filter type Hot & Cold Water cooler of capacity 85 Litres.
Ditto All as per Serial item No. 86 but for Refrigerator of capacity 165Ltrs to 310 Litres.
Material and Labour for disconnecting from position of electric supply, servicing at same location including cleaning of interior parts and body with solvent materials, replacement of unserviceable parts, necessary repairs, re-Connecting, testing and commissioning of Water Cooler of capacity 40/40, 40/80 or 60/80 complete all as specified & directed.
Ditto All as per Serial item No. 89 but for Ozone based filter type Hot & Cold Water cooler of capacity 85 Litres.
Ditto All as per Serial item No. 89 but for Refrigerator of capacity 165Ltrs to 310 Litres.
Supply & Fix Hermetically sealed compressor unit suitable for Water Cooler of capacity 40/40, 40/80 Litres including initial charging of gas and oil and taking down old unserviceable sealed compressor unit, connecting up complete all as specified & directed.
Ditto All as per Serial item No. 92 but for Water Cooler of capacity 60/120 Litres.
Ditto All as per Serial item No. 92 but for Refrigerator of capacity 165 to 210 Litres.
Ditto All as per Serial item No. 92 but for Refrigerator of capacity 290 to 310 Litres.
Supply & Fix Condensing coil made out of copper tube and aluminium fins suitable for Water cooler of capacity 40/40, 40/80 Litres including necessary brazing, gas charging, leak testing, vacuumnising etc complete all as specified and directed.
Ditto All as per Serial item No. 96 but for Water Cooler of capacity 60/120 Litres.
Ditto All as per Serial item No. 96 but for Refrigerator of capacity 165 to 210 Litres.
Ditto All as per Serial item No. 96 but for Refrigerator of capacity 290 to 310 Litres.
Supply & Fix Evaporator coil of made out of Copper tube suitable for Refrigerator of capacity 165 to 310 Litres.
Supply & Fix D S Candle suitable for Hot and Cold water cooler
Supply & Fix Filter Carbon suitable for Hot and cold water cooler
Supply & Fix main board suitable for Hot and cold water cooler
Supply & Fix power supply DCB suitable for Hot and Cold water cooler
Supply & Fix Transformer suitable for Hot and cold water cooler
Supply & Fix Solenoid valve suitable for Hot and cold water cooler
Supply & Fix Pressure Pump suitable for Hot and cold water cooler
Supply & Fix Push cock suitable for Hot and cold water cooler
Supply & Fix Heater coil suitable for Hot and cold water cooler
Supply & Fix Thermostat set suitable for Hot and cold water cooler
Supply & Fix Compressor suitable for Hot and cold water cooler
Supply & Fix Cooling Thermostat for Hot and cold water cooler
Supply & Fix 3 Core multistranded Copper Conductor PVC insulated sheathed flexible cable of size 2.5 Sqmm.
Supply & Fix 3 Core multistranded Copper Conductor PVC insulated sheathed flexible cable of size 4 Sqmm.
Material & Labour for testing of earth resistance between conductor and earth value earthing connected to building, lightening conductors , etc, twice in a year including painting/ writing the date of testing and next due date in the space provided in the board / wall with stencil complete all as directed .
Supply & Fix Air termination, single pointed aluminium rod 12 mm dia and 300 mm long including dismantling old unserviceable air termination.
Supply & Fix in repair GI earth strip of size 32 x 6 mm with saddles/fasteners/insulators and fixing screw etc.
Supply & Fix in repair test terminal block made of gun metal or phosphorus bronze size 75 x 75 x 25 mm, drilled and screwed with 3 nos 8 mm dia 25 mm long hexa head screw including dismantling old unserviceable test terminal block.
Labour only in repair earth test point after dismantling the conductor, cleaning and re fixing the same with new screws 8 mm dia 25 mm long hexa head screw complete all as directed.
Material & labour for earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6mm buried directly in ground (earth pit not less than 2.25 metre deep below ground level) vertically, with top edge of the plate not less than 1.5 metre below normal ground level, connected to galvanized iron earth lead strip 32mm x 6mm earth strip by means of nuts, bolts, washers of GI steel all as shown on electrical plate No 3 of MES schedule part I-2009 connected to earthing test point to main switch board and testing on completion with and including necessary excavation and earth work in any type soil, earth lead connected to earth test point to main switch board etc with & including adequate quantity of charcoal dust and common salt, test point, PCC (1:3:6) type C-1 (using 20mm graded black trap/granite/Basalt stone aggregate) for earth pit with 40 x 40 x 6mm mild steel angle iron frame for cover, internal surface of concrete shall be given 10mm thick plaster in CM 1:4, pre cast RCC (1:2:4) type B-1(using 20mm graded black trap/granite/Basalt stone aggregate) 40mm thick cover, reinforced with 8mm dia deformed or TMT bars 3 Nos both way with 8mm dia round bar handle, GI light grade watering pipe 20 mm dia with funnel and wire mesh and 40mm dia GI light grade earth lead protection pipe etc complete all as specified and directed. NOTE (i) The cost of earth lead and its protection pipe upto and including 7.5 metre only from the top of earth electrode are deemed to be included under this item.
Amount of Credit Schedule shall be deducted to arrive the Contract Sum.
Sreema Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .