Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.4 LAccepted-AOC | L1 | Accepted-AOC AOC | |
| 2 | L2₹20.8 L+₹33,843 (1.66%)Rejected-Finance BAGDAH NORTH 24 PARGANAS | L2 | Rejected-Finance Rejected as L2 | |
| 3 | L3₹20.8 L+₹37,215 (1.82%)Rejected-Finance 14 SURI LANE KOLKATA 700 014 | KOLKATA | KOLKATA | WEST BENGAL | 700014 | L3 | Rejected-Finance Rejected as L3 | |
| 4 | L4₹23.1 L+₹2.7 L (13.0%)Rejected-Finance | L4 | Rejected-Finance Rejected as L4 |
| Sl No | Description | Qty | Unit | T.D.K. ENTERPRISE L3 | Messrs HI- Q - ENTERPRISE L4 | DECADON ENGINEERING L1 | MALLICK ENTERPRISE L2 |
|---|---|---|---|---|---|---|---|
| 1.00 | Dismantling the existing electrical accessories like all kinds of old wiring, batten, wooden block, conduit pipe, main switche, net guard, iron clad DB, MCB DB, Bus bar, light fittings, fans, fan clamps, power board, different sizes cable, gland, nail, fastener, damaged panel, incoming & out going cable etc. at working site and deposit the dismantles items at section store with mending good the damages as per direction. | 1 | Job | 2,750 ₹2,750 Lowest | 10,000 ₹10,000 | 6,000 ₹6,000 | 2,800 ₹2,800 |
| 2.00Supply & delivery of cubicle type 415 V, LT distribution panel board of required size, compartmentalised with maple arrangement, having rigid & self-supporting structure fabricated by 2 mm thick CRCA sheet steel with M/S angle/flat frame. The panel board consists of the following switches. Incoming: Switch dis-connector fuse unit in open execution, TPN, 50 HZ, 415 V, 315 Amp with 3 nos. 315 Amp Din type HRC fuse link - 1 no. [Make - Siemens / ABB / Schneider] Bus Section: 415 V, 500 A, electrolytic graded Al. bus bar Ph. & N. (Size of bars - 4 x 80 mm x 6 mm). The bus bar shall be fixed with FRP chairs, and all bars shall be insulated with PVC heat-shrinkable sleeves of suitable size and different colours, as per the norms and directions of E.I.C. All interconnections should be done with appropriately sized aluminium bars. Outgoing: SDFU in open execution TPN 50 HZ, 415 Volt - i) 200 Amp - 1 no., ii) 125 Amp - 4 nos. with Din type HRC fuse link as per rating of each SFUs [Make - Siemens / ABB / Schneider]. All SFUs should be connected with the required size/equivalent rating Al. flat. | |||||||
| 2.10Metering, Control & Indication Arrangement :- a) Digital display Multifunction Meter (Make - Siemens / ABB / Schneider) - 1 no. b) CT, 300/5 A (Make - Kappa) - 3 nos. c) Indicating LED lamps for Red/Yellow/Blue (Make - L&T/ABB/Siemens) - 3 nos. d) 6 A SP MCB - 3 nos. e) Danger Board 18 SWG (12" x 8") - 1 no. Cable Alley: Cable entry arrangement will be provided on the back side of the cubicle panel, positioned at the bottom end in a vertical orientation, with a 630 Amp capacity and 4-way extended Al. flat Bar. A flat terminal indicating phase & neutral for each outgoing main switch, including the gland plate, must be placed at the bottom of the panel with a detachable type, as per the direction of E.I.C. Additionally, provide 1 no. Bus Alley in vertical, 2 nos. cable alley. Painting: The complete panel board shall be painted by 2 coats of powder-coated synthetic enamel Paint over two coats of R.O. primer of Approved make, brand & color as per the direction of E.I.C. | |||||||
| 2.20 | Constructional Details: All incoming & outgoing panel-mounted cubical Switch Disconnector fuse shall be housed in a respective compartment with a hinged & gasket Door at the front. All doors shall have a Panel lock Arrangement. The panel shall be properly gasket to prevent ingress of dust & moisture & Remain. Bus bar will be properly arrange & all Switches shall be fixed by M.S. nuts & bolts and also all SFU/SDFU units should be connected with the proper size electrolyting graded tinned Al. flat / Bar / as per direction of E.I.C.
Installing the LT panel in position with the necessary items required and making a brick foundation for levelling up the LT panel, such that the incoming cable can be connected in the proper way without stress.
Proper size of panel, length of BBC, construction details, arrangements of all I/C and O/G SFUs and others with drawing should be approved by the EIC before construction of this Panel. | 1 | No | 1,95,750 ₹1,95,750 | 1,50,000 ₹1,50,000 | 1,25,300 ₹1,25,300 | 30,000 ₹30,000 Lowest |
| 3.00Supply & delivery of cubicle type 415 V, LT distribution panel board of required size, compartmentalised with maple arrangement having rigid & self-supporting structure fabricated by 2 mm thick CRCA sheet steel with M/S angle/flat frame. The panel board consists of the following switches. Incoming: i) SDFU in open execution, TPN, 50 HZ, 415 V, 200 Amp with 3 nos. 200 Amp Din type HRC fuse link - 1 no. [Make - Siemens / ABB / Schneider], ii) 415 V, 200 Amp on load front-operated Changeover Switch-Disconnector (Conforms to IEC 60947-3, IS/IEC 60947-3) - 1 no. [Make - LK, Cat. No. - CO22000OOOA or a similar type of Siemens / ABB / Schneider] Bus Section: 415 V, 300 A, electrolytic graded Al. bus bars for Phs. & N. (Size of bars - 4 x 60 mm x 5 mm). The bus bar shall be fixed with FRP chairs, and the entire bars are insulated with PVC heat-shrinkable sleeves of suitable size and different colours, as per the norms and directions of E.I.C. All interconnections should be done with appropriately sized Copper bars. Outgoing: Switch disconnector fuse unit in open execution TPN 50 HZ, 415 Volt - i) 125 Amp - 3 nos.., ii) 63 Amp - 1 no. with Din type HRC fuse link as per rating of each SFUs [Make - Siemens / ABB / Schneider]. All SFUs should be connected with the required size / equivalent rating tinned Cu. flat bar. | |||||||
| 3.10Metering, Control & Indication Arrangement :- a) Digital display Multifunction Meter (Make: Siemens / ABB / Schneider) - 1 no. b) CT, 200/5 A, Make - Kappa - 3 nos. c) Indicating LED lamps for Red/Yellow/Blue (Make - Schneider/ABB/Siemens) - 3 nos. d) 6 A SP MCB - 3 nos. e) Danger Board 16 SWG (6" x 4") - 1 no. Cable Alley: Cable entry arrangement will be provided in the back side of the cubical panel in the bottom end vertical position, 630 Amp capacity 4-way extended Cu. flat terminal indicating phase & neutral for each outgoing main switches including gland plate must be placed at the bottom of the panel with detachable type as per direction of E.I.C. and also to be provided 1 no Bus Alley in vertical, 2 nos. cable alley. Painting: The complete panel board shall be painted by 2 coats of powder-coated synthetic enamel Paint over two coats of R.O. primer of Approved make & brand & color as per Direction of E.I.C. | |||||||
| 3.20 | Constructional Details: All incoming & outgoing panel-mounted cubical switch disconnector fuses shall be housed in a respective compartment with a hinged & gasketed door at the front. All doors shall have a Panel lock Arrangement. The panel shall be properly gasketed to prevent ingress of dust & moisture & remain. Bus bar will be properly arranged & all Switches shall be fixed by M.S. nuts & bolts, and also all SFU/SDFU units should be connected with the proper size electrolytic graded tinned Al. Flat Bar / as per direction of E.I.C.
Installing the LT panel in position with the necessary items required and making a brick foundation for levelling up the LT panel such that the incoming cable can be connected in a proper way without stress.
Proper size of panel, length of BBC, construction details, arrangements of all I/C and O/G SFUs and others with drawing should be approved by the EIC before construction of this Panel. | 1 | No | 1,56,300 ₹1,56,300 | 1,50,000 ₹1,50,000 | 1,24,500 ₹1,24,500 | 1,20,000 ₹1,20,000 Lowest |
| 4.00 | S & F of 415 V, up to 160 A capacity MCCB incomer, 63 A SP/TP MCB outgoing, double door, following ways VTPN MCB DB (Make - Legrand / Siemens) with IP-43 protection on angle iron frame on wall including mending good the damages to original finish, inter connection with suitable size of copper wire & neutral link and provision for earthing attachment. [15/D-11]
4 Way | 1 | Nos | 9,355 ₹9,355 | 8,500 ₹8,500 | 7,000 ₹7,000 Lowest | 1,36,000 ₹1,36,000 |
| 4.10 | 6 Way | 1 | Nos | 8,841 ₹8,841 Lowest | 9,850 ₹9,850 | 9,100 ₹9,100 | 12,000 ₹12,000 |
| 5.00 | S & F of 415 V, 32 A per way following ways double door HTPN MCB Distribution Board with IP-43 protection (Make - Legrand / Siemens), concealed in the wall after cutting the wall & mending well the damages to original finish incl. interconnection with a suitable size of copper wire and neutral link & provision for earthing attachment. [14/D-10]
4 Way | 4 | Nos | 3,089 ₹12,356 | 6,500 ₹26,000 | 2,965 ₹11,860 | 2,908 ₹11,632 Lowest |
Tender Value
Refer Docs
EMD Value
₹47,345
Closing Date
23 Mar 2026, 1:00 pmClosed
Executive Engineer
Dist Hospital Campus Saktinagar Krishnagar Nadia
Renovation of Electrical Installation at First Floor of the Administrative Building, Govt. ITI. Kalyani.
2026_WBPWD_1018064_1
WBPWD/EE/NED/NIQ/e-T/69/ (1st Call)25-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
Dist Hospital Campus Saktinagar Krishnagar Nadia
Please refer Tender documents.
6 documents required · 6 mandatory
₹47,345
Nadia Electrical Division
15 Jun 2026
5 Mar 2026
25 Mar 2026
5 Mar 2026
23 Mar 2026
9 Mar 2026
9 Mar 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Dismantling the existing electrical accessories like all kinds of old wiring, batten, wooden block, conduit pipe, main switche, net guard, iron clad DB, MCB DB, Bus bar, light fittings, fans, fan clamps, power board, different sizes cable, gland, nail, fastener, damaged panel, incoming & out going cable etc. at working site and deposit the dismantles items at section store with mending good the damages as per direction. | 1 | Job | - | - |
| 2Supply & delivery of cubicle type 415 V, LT distribution panel board of required size, compartmentalised with maple arrangement, having rigid & self-supporting structure fabricated by 2 mm thick CRCA sheet steel with M/S angle/flat frame. The panel board consists of the following switches. Incoming: Switch dis-connector fuse unit in open execution, TPN, 50 HZ, 415 V, 315 Amp with 3 nos. 315 Amp Din type HRC fuse link - 1 no. [Make - Siemens / ABB / Schneider] Bus Section: 415 V, 500 A, electrolytic graded Al. bus bar Ph. & N. (Size of bars - 4 x 80 mm x 6 mm). The bus bar shall be fixed with FRP chairs, and all bars shall be insulated with PVC heat-shrinkable sleeves of suitable size and different colours, as per the norms and directions of E.I.C. All interconnections should be done with appropriately sized aluminium bars. Outgoing: SDFU in open execution TPN 50 HZ, 415 Volt - i) 200 Amp - 1 no., ii) 125 Amp - 4 nos. with Din type HRC fuse link as per rating of each SFUs [Make - Siemens / ABB / Schneider]. All SFUs should be connected with the required size/equivalent rating Al. flat. | |||||
| 2.1 | Metering, Control & Indication Arrangement :-
a) Digital display Multifunction Meter (Make - Siemens / ABB / Schneider) - 1 no.
b) CT, 300/5 A (Make - Kappa) - 3 nos.
c) Indicating LED lamps for Red/Yellow/Blue (Make - L&T/ABB/Siemens) - 3 nos.
d) 6 A SP MCB - 3 nos.
e) Danger Board 18 SWG (12" x 8") - 1 no.
Cable Alley: Cable entry arrangement will be provided on the back side of the cubicle panel, positioned at the bottom end in a vertical orientation, with a 630 Amp capacity and 4-way extended Al. flat Bar. A flat terminal indicating phase & neutral for each outgoing main switch, including the gland plate, must be placed at the bottom of the panel with a detachable type, as per the direction of E.I.C. Additionally, provide 1 no. Bus Alley in vertical, 2 nos. cable alley.
Painting: The complete panel board shall be painted by 2 coats of powder-coated synthetic enamel Paint over two coats of R.O. primer of Approved make, brand & color as per the direction of E.I.C. | - | - | - | - |
| 2.2 | Constructional Details: All incoming & outgoing panel-mounted cubical Switch Disconnector fuse shall be housed in a respective compartment with a hinged & gasket Door at the front. All doors shall have a Panel lock Arrangement. The panel shall be properly gasket to prevent ingress of dust & moisture & Remain. Bus bar will be properly arrange & all Switches shall be fixed by M.S. nuts & bolts and also all SFU/SDFU units should be connected with the proper size electrolyting graded tinned Al. flat / Bar / as per direction of E.I.C.
Installing the LT panel in position with the necessary items required and making a brick foundation for levelling up the LT panel, such that the incoming cable can be connected in the proper way without stress.
Proper size of panel, length of BBC, construction details, arrangements of all I/C and O/G SFUs and others with drawing should be approved by the EIC before construction of this Panel. | 1 | No | - | - |
| 3Supply & delivery of cubicle type 415 V, LT distribution panel board of required size, compartmentalised with maple arrangement having rigid & self-supporting structure fabricated by 2 mm thick CRCA sheet steel with M/S angle/flat frame. The panel board consists of the following switches. Incoming: i) SDFU in open execution, TPN, 50 HZ, 415 V, 200 Amp with 3 nos. 200 Amp Din type HRC fuse link - 1 no. [Make - Siemens / ABB / Schneider], ii) 415 V, 200 Amp on load front-operated Changeover Switch-Disconnector (Conforms to IEC 60947-3, IS/IEC 60947-3) - 1 no. [Make - LK, Cat. No. - CO22000OOOA or a similar type of Siemens / ABB / Schneider] Bus Section: 415 V, 300 A, electrolytic graded Al. bus bars for Phs. & N. (Size of bars - 4 x 60 mm x 5 mm). The bus bar shall be fixed with FRP chairs, and the entire bars are insulated with PVC heat-shrinkable sleeves of suitable size and different colours, as per the norms and directions of E.I.C. All interconnections should be done with appropriately sized Copper bars. Outgoing: Switch disconnector fuse unit in open execution TPN 50 HZ, 415 Volt - i) 125 Amp - 3 nos.., ii) 63 Amp - 1 no. with Din type HRC fuse link as per rating of each SFUs [Make - Siemens / ABB / Schneider]. All SFUs should be connected with the required size / equivalent rating tinned Cu. flat bar. | |||||
| 3.1 | Metering, Control & Indication Arrangement :-
a) Digital display Multifunction Meter (Make: Siemens / ABB / Schneider) - 1 no.
b) CT, 200/5 A, Make - Kappa - 3 nos.
c) Indicating LED lamps for Red/Yellow/Blue (Make - Schneider/ABB/Siemens) - 3 nos.
d) 6 A SP MCB - 3 nos.
e) Danger Board 16 SWG (6" x 4") - 1 no.
Cable Alley: Cable entry arrangement will be provided in the back side of the cubical panel in the bottom end vertical position, 630 Amp capacity 4-way extended Cu. flat terminal indicating phase & neutral for each outgoing main switches including gland plate must be placed at the bottom of the panel with detachable type as per direction of E.I.C. and also to be provided 1 no Bus Alley in vertical, 2 nos. cable alley.
Painting: The complete panel board shall be painted by 2 coats of powder-coated synthetic enamel Paint over two coats of R.O. primer of Approved make & brand & color as per Direction of E.I.C. | - | - | - | - |
| 3.2 | Constructional Details: All incoming & outgoing panel-mounted cubical switch disconnector fuses shall be housed in a respective compartment with a hinged & gasketed door at the front. All doors shall have a Panel lock Arrangement. The panel shall be properly gasketed to prevent ingress of dust & moisture & remain. Bus bar will be properly arranged & all Switches shall be fixed by M.S. nuts & bolts, and also all SFU/SDFU units should be connected with the proper size electrolytic graded tinned Al. Flat Bar / as per direction of E.I.C.
Installing the LT panel in position with the necessary items required and making a brick foundation for levelling up the LT panel such that the incoming cable can be connected in a proper way without stress.
Proper size of panel, length of BBC, construction details, arrangements of all I/C and O/G SFUs and others with drawing should be approved by the EIC before construction of this Panel. | 1 | No | - | - |
| 4 | S & F of 415 V, up to 160 A capacity MCCB incomer, 63 A SP/TP MCB outgoing, double door, following ways VTPN MCB DB (Make - Legrand / Siemens) with IP-43 protection on angle iron frame on wall including mending good the damages to original finish, inter connection with suitable size of copper wire & neutral link and provision for earthing attachment. [15/D-11]
4 Way | 1 | Nos | - | - |
| 4.1 | 6 Way | 1 | Nos | - | - |
| 5 | S & F of 415 V, 32 A per way following ways double door HTPN MCB Distribution Board with IP-43 protection (Make - Legrand / Siemens), concealed in the wall after cutting the wall & mending well the damages to original finish incl. interconnection with a suitable size of copper wire and neutral link & provision for earthing attachment. [14/D-10]
4 Way | 4 | Nos | - | - |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.19 MB
BOQ_2501835.xls
BOQ • 0.35 MB
form2911.pdf
Tender Documents • 0.50 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .