EE II CKHED
OFFICE OF THE EXECUTIVE ENGINEER, P.W.Dte. Central Kolkata Health Electrical Division P-12, C.I.T Road(1st floor) KOLKATA
Urgent change of air conditioning machine at Neurology OPD under NRSMC and H, Kolktat
2026_WBPWD_5015126_1
WBPWD/EE-II/CKHED/eNIT08/26-27
Open Tender
ELECTRICAL WORKS ORG
Item Rate
15 days
NRS MCH
Please refer Tender documents.
4 documents required · 4 mandatory
₹4,020
central kolkata health electrical division
20 Jul 2026
8 Jun 2026
22 Jul 2026
8 Jun 2026
20 Jul 2026
16 Jun 2026
15 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, Installation, Testing & Commissioning of Inverter Ducted/ Concealed split AC machine (a set of full metal body indoor and outdoor unit) having cooling capacity not less then 14.1 kw with veriable speed rotary/ scroll compressor, refrigerant gas R32/R410 or better , both condenser and cooling coils made of copper tube connecting chord with plug top confirming to IS 1391 (Part-I & Part-II) with all amendments.
(Make - Mitsubishi Electric/ Daikin/ OGeneral/ Hitachi/ Voltas/Blue Star) | 1 | Nos | - | - |
| 2 | Supplying & installation of M.S platform (for installation of ODU of 4 TR Concealed split AC) fabricated with two nos MS u-channel of size 75 mm x 40 mm x 40 mm, 6 mm thick at base incl. 2 nos drilled holes, horizontal angle of 40 mm x40mm x 5 mm in four outer edges and two nos angular support from bottom portion for transmitting the load centrally including 6 nos vertical MS angle of size 25 mm x 25 mm x 6 mm with 25mm x 3mm MS flat for barricading the structure properly for safe maintenance. The platform will be properly grouted inside the wall after cutting holes into the wall & grouting the same with cement concrete (1:1 ½ :3) etc. and painting. Area of the platform will be 2 Mtr. x 1.2Mtr. or as per machine configuration and load with adequate service aceess as per direction of EIC. (Approximate weight 55 kG)
Structural design should be approved by E.I.C. | 1 | Nos | - | - |
| 3Supply and fixing of refrigerant Copper pipe line of following diameter for conecting Indoor and Outdoor unit for liquid and suction line with fittings, elbows, bends, supports & brackets along with the dnp resistant nitrile rubber insulation with double insulating wrapping tape to avoid driping of condensate water. (Make- Rajco/ Royku) | |||||
| 3.1 | Suction Line (5/8" OD with 0.7mm thick) | 20 | Mtr | - | - |
| 3.2 | Liquid Line 3/8" OD with 0.7mm thick) | 20 | Mtr | - | - |
| 4Supply & Fixing Pipe Insulation in liquid & suction line with 9mm thick nitrile rubber tube (Accoflex) | |||||
| 4.1 | Suction Line (5/8" OD with 0.7mm thick) | 20 | Mtr | - | - |
| 4.2 | Liquid Line 3/8" OD with 0.7mm thick) | 20 | Mtr | - | - |
| 5Supply and fixing of Control copper Cabling from Condensing Unit to control panel (Make: polycab/finolex). | |||||
| 5.1 | 4 core 2.5 sq.mm communication cable | 24 | Mtr | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.50 MB
Tendernotice_2.pdf
PDF • 0.23 MB
2911.pdf
Tender Documents • 0.50 MB
BOQ_5083718.xls
BOQ • 0.26 MB
datecorri02.pdf
PDF • 0.23 MB
datecorri.pdf
PDF • 0.23 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .