Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹1.7 CrAccepted-AOC | ₹1.7 Cr | 1 | Accepted-AOC L1 Bidder |
| 2 | 2₹1.8 Cr+₹8.0 L (4.64%)Rejected-AOC JAGAHARIMURA AGARTALA WEST TRIPURA | AGARTALA | WEST TRIPURA | TRIPURA | ₹1.8 Cr+₹8.0 L (4.64%) | 2 | Rejected-AOC L2 Bidder |
| 3 | 3₹1.9 Cr+₹15.8 L (9.14%)Rejected-AOC AGARTALA TRIPURA W | AGARTALA | TRIPURA | ₹1.9 Cr+₹15.8 L (9.14%) | 3 | Rejected-AOC L3 Bidder |
| 4 | 4₹2.0 Cr+₹22.6 L (13.1%)Rejected-AOC COLLEGE CHOWMUHANI JIRANIA WEST TRIPURA | ₹2.0 Cr+₹22.6 L (13.1%) | 4 | Rejected-AOC L4 Bidder |
| 5 | Not Admitted-Fee/PreQual/Technical EN 62 7TH FLOOR SALTLAKE CITY KOLKATA SECTOR V WEST BENGAL 700091 | 24 PARAGANAS NORTH | WEST BENGAL | 700091 | - | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹1.8 Cr
EMD Value
₹3.6 L
Closing Date
8 Feb 2021, 2:00 pmClosed
DGM,ED-II, Bordowali
Electrical Division No-II, Bordowali, Agartala
Refer to NIT
2021_POWER_15508_1
DGM/ED-II/TSECL/2020-21/15 Dt. 07.01.2021
Open Tender
Electrical Works
Turn-key
365 days
Bordowali, Agartala
Refer to bid documents
5 documents required · 5 mandatory
₹4,000
₹3.6 L
Office of the AGM,EC-I, TSECL, Agartala,
24 Jun 2021
11 Jan 2021
10 Feb 2021
13 Jan 2021
8 Feb 2021
29 Jan 2021
13 Jan 2021 - 20 Jan 2021
22 Jan 2021
Amount
33KV UG LINE
Design, Engineering, manufacturing, Supply of Three Core, 19 /33 KV, Al, 400 Sq. mm. FRLS, XLPE insulated, screened armoured power cable as per TSECL approved design, drawing, specification and as reqd. as per direction of Eng-In-Charge and detailed herein after in the bid document.
Supply of 160 mm outer diameter HDPE pipe( PE-80 grade) of working presure 6 kgf /sq.cm. having minimum wall thickness 6.3 to 7.2 mm.
Supply of 150 mm dia best quality heavy duty GI PIPE as per ISS 1239 of different length as per requirement of engineering.
Laying of one number 400sqmm PVC insulated and PVC sheathed / XLPE power cable of 33 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Trench Size: Width-350mm, Hieght-1200mm / Sand(couhioning): Hieght-250mm, Width-350mm/ Protection: Double layer Bricks including coiling of excess cable at a depth of minimum 1200 with double layer bricks protection as per direction of Engineering In Charge.
Manually digging /drilling horizontally or diagonali direction for road crossing / Water supply line/Telcomunication line/Gas Pipe line etc. including Laying of 64 to 200mm dia GI pipe and 400sqmm power cable direct into the earth at a depth of minimum 1100mm below the ground surface with out effecting the existing road including excavation earth for entry pit as per site condition and direction of Engineering In Charge.
HDD Machine digging /drilling horizontally or diagonali direction for road crossing / Water supply line/Telcomunication line/Gas Pipe line etc. including Laying of 64 to 200mm dia GI pipe and 400sqmm power cable direct into the earth at a depth of minimum 1100mm below the ground surface with out effecting the existing road including excavation earth for entry pit as per site condition including coiling of excess cable at a depth of minimum 1200 with double layer bricks protection as per direction of Engineering In Charge.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 33 KV grade of all size in the GI Pipe/HDPE for riser including tieup of Pipe with pole by the help MS Flat Clamp (excluding cost of Clamp and Nut&Bolts) as required
Supplying and Making Outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, 400sqmm, XLPE aluminium conductor cable of 33 KV grade, as required :
Providing of Pre-cast cement concrete cable identification route marker (1 cement: 2 coarse sand : 4 graded stone aggregate 6mm nominal size) reinforced with 1.6 mm dia mild steel wire including centring and shuttering, roughening cleaning, fixing and finishing in cement mortar 1:3(1cement : 3 fine sand) etc. complete, excluding the plastering of jambs, sills and soffits as per design, drawing and specification of TSECL. The marker shall be embossed "DANGERS: TSECL, ELECTRIC POWER CABLE" with Black colour letter(both side). The visible part shall be painted with Yellow colour japan paint as per approved TSECL drawing & Specification.
Supply & Laying of 250mm wide and 100microns thick(HDDPE/LLDPE) pre-warning Yellow colour tape. The warning tape shall be printed in RED letter (in English as well as Bengali) as "COUTION: TSECL, 33KV POWER CABLE" and to be placed at about 500mm depth from ground level along the cable route.
CABLE SECTION & OVERHEAD BARE LINE:
Supply of Galvanised Steel Tubular Pole, 9.0mtr. Long (Designation 410: SP-32) ( hot dip galvanized ) conforming to ISS 2713 (P-I & II) 1980 with base plate
Supply of 11.0 mtr. long Steel Tubular Poles (Designation 410: SP-54) ( hot dip galvanized ) conforming to ISS: 2713 (P-I & II)-1980 with base plate
Supply of Galvanised Stay Set complete direct in earth with 16 mm. dia. 1.8 mtr. long GI stay rod, anchor plate of size 300 X 300 X 8 mm. thick, turn buckle of length 356 mm. with 300 mm. long threaded adjustable 16 mm. dia. GI rod , thimble, guy insulator as per IS specification, hot dip (heavy duty) galvanized stay stranded wire of size 7/3.15 mm. fastened with stay clamps as required. ( including supply of MS clamp & Nuts & Bolts with galvanization as reqd) as per tender specification.
Supply of Stranded G.I Stay wire (7/3.15mm) as per relevant IS
Supply of 33KVStay Insulator as per relevant IS
Supply and fabrication 100 X 50 X 50 X 6 mm. Galvanised channel duly galvanised as per relevant I.S. on Steel Tubular Pole with supply of clamp (made of 50x6 mm. GI flat Flat duly galvanised as per relevant I.S), nuts and bolts as required as per direction of Eng-In-Charge. (a) 0.30 mtr long
(b) 1.50mtr long
(c) 2.40mtr long
(d) 1.80mtr long
Supply and fabrication of 65 X 65 X 6 mm. Galvanised angle duly galvanised as per relevant I.S. on Steel Tubular Pole srtucture with supply of clamp (made of 50x6 mm. GI flat duly galvanised as per relevant I.S), nuts and bolts as required as per direction of Eng-In-Charge . (a) 1.8 mtr long for guard
(b) 2.80 mtr long for guard
(c) 1.8 mtr long for horizontal bracing
(d) 3.2 mtr long for cross bracing
Supply of 33KV Polymeric Disc Insulators ( 70 KN as per rlelevant IS) with fittings(3/4U Bolt type)
Supply of 33KV Polymeric Pin Insulators as per rlelevant IS) .
Supply of ACSR DOG Conductor (6/4.72+7/1.57 mm) as per relevant IS.
Supply of 8 S.W.G G.I wire as per relevant IS.
Erection of Steel Tubular Pole, 9.0mtr. Long (Designation 410: SP-32) ( hot dip galvanized )conforming to ISS 2713 (P-I & II) 1980 with base plate direct in earth including excavation, refilling and ramming etc. as required complete (1 /6th of the length of the pole to be embedded in earth).
Erection of 11.0 mtr. long Steel Tubular Poles (Designation 410: SP-54) ( hot dip galvanized ) conforming to ISS: 2713 (P-I & II)-1980 with base plate direct in earth including excavation, refilling and ramming etc. as required (1/6th length of the pole to be embedded in earth).
Erection of Galvanised Stay Set complete direct in earth with 16 mm. dia. 1.8 mtr. long GI stay rod, anchor plate of size 300 X 300 X 8 mm. thick, turn buckle of length 356 mm. with 300 mm. long threaded adjustable 16 mm. dia. GI rod , thimble, guy insulator as per IS specification, hot dip (heavy duty) galvanized stay stranded wire of size 7/2.5 mm. fastened with stay clamps as required. ( including supply of GI clamp & Nuts & Bolts as reqd).
Erection of fabrication 100 X 50 X 50 X 6 mm. Galvanised channel duly galvanised as per relevant I.S. on Steel Tubular Pole with supply of clamp (made of 50x6 mm. GI flat Flat duly galvanised as per relevant I.S), nuts and bolts as required as per direction of Eng-In-Charge. (a) 0.30 mtr long
(b) 1.50mtr long
(c) 2.40mtr long
(d) 1.80mtr long
Erection of fabrication of 65 X 65 X 6 mm. Galvanised angle duly galvanised as per relevant I.S. on Steel Tubular Pole srtucture with supply of clamp (made of 50x6 mm. GI flat duly galvanised as per relevant I.S), nuts and bolts as required as per direction of Eng-In-Charge . (a) 1.8 mtr long for guard
(b) 2.80 mtr long for guard
(c) 1.8 mtr long for horizontal bracing
(d) 3.2 mtr long for cross bracing
Erection of 33KV Polymeric Disc Insulators ( 70 KN as per rlelevant IS) with fittings(3/4U Bolt type)
Erection of 33KV Polymeric Pin Insulators as per rlelevant IS) .
Laying, hoisting, binding & Jumpering of of ACSR DOG Conductor (6/4.72+7/1.57 mm) as per relevant IS.
Laying, hoisting, binding & Jumpering of 8 S.W.G G.I wire for continuous earth connection,guarding, craddling & Earthing
Providing 33KV Craddle guard making of 8SWG GI Wire
Supply of Earthing set as per ISS : 3043 of 1966 and with latest amendment if any, 2.5 mtr long G.I. pipe (ISI marked) of 40 mm diameter with suitable holes on pipe circumference including a pair of clamps (made of 50 X 6 GI flat), galvanized nuts & bolts including supply of 4.0 mtr long, 12mm dia PVC pipe for each earthing set etc. as required and as per direction of Engineer-in-charge.
Providing of 33KV Danger Plates
Providing of Barbed wire (Anti Climbing device)
Providing Name Plate made of 2mmthick MS Sheet including fastend with Pole(33KV Budhjungnagar-Drid Line)
Replacement of Partial damaged 9.0Mtr Steel Tubular Pole single pole Structures by New 11mtr. Long including all other materials and damaged materials shall be return from site to ESD stack yard as per direction of Engineering Incharge.
Replacement of Partial damaged 10/11.00Mtr long Steel Tubular Pole single pole Structures by New 11mtr. Long including all other materials and damaged materials shall be return from site to ESD stack yard as per direction of Engineering Incharge.
Replacement of Partial damaged 9.0Mtr PCC Pole single pole Structures by New 11mtr. Long including all other materials and damaged materials shall be return from site to ESD stack yard as per direction of Engineering Incharge.
Replacement of Partial damaged 9.0Mtr Steel Tubular Pole double pole Structures by New 11mtr. Long including all other materials and damaged materials shall be return from site to ESD stack yard as per direction of Engineering Incharge.
Replacement of Partial damaged 10/11Mtr Steel Tubular Pole double pole Structures by New 11mtr. Long including all other materials and damaged materials shall be return from site to ESD stack yard as per direction of Engineering Incharge.
Replacement of Partial damaged 9Mtr PCC Pole double pole Structures by New 11mtr. Long including all other materials and damaged materials shall be return from site to ESD stack yard as per direction of Engineering Incharge.
Replacement of Partial damaged/Old 33KV Pin Insulator by New Pin insulator with GI Pin and damaged materials shall be return from site to ESD stack yard as per direction of Engineering Incharge.
Replacement of Partial damaged/Old Disc Insulator Insulator by New Disc insulator with Fittings and damaged materials shall be return from site to ESD stack yard as per direction of Engineering Incharge.
Uprotting of 9.0Mtr PCC Pole including excavation of earth, refilling, rammiang etc and dismanttaled materials shall be return from site to ESD stack yard as per direction of Engineering Incharge.
Uprotting of 9.0Mtr Steel Tubular Pole including excavation of earth, refilling, rammiang etc and dismanttaled materials shall be return from site to ESD stack yard as per direction of Engineering Incharge.
Uprotting of 10/11Mt rSteel Tubular Pole including excavation of earth, refilling, rammiang etc and dismanttaled materials shall be return from site to ESD stack yard as per direction of Engineering Incharge.
Dismantalling of Rabbit conductor including oppening of binding, Jupering and coiling of dismanataled Conductor and dismanttaled materials shall be return from site to ESD stack yard as per direction of Engineering Incharge.
KAJAL DAS
M/s Bhattacharjee Construction
Asish Debnath
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .