Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.4 LAccepted-AOC CA 325 SA767 PWD K EL 13 1 472 CASAMARINA COMPLEX TALAP KANNUR | KANNUR | KANNUR | KERALA | 670101 | L1 | Accepted-AOC L1 | |
| 2 | L2₹24.9 L+₹51,465 (2.11%)Rejected-AOC | L2 | Rejected-AOC L2 |
Tender Value
Refer Docs
EMD Value
₹50,000
Closing Date
17 May 2023, 6:00 pmClosed
Executive Engineer
PWD Electrical Division Kannur 2
LAC ADS 2018 2019 Sri James Mathew MLA Taliparamba Constituency Nanicheri Kadavu Bridge Providing LED lights Anthoor Muncipality General Electrical Work
2023_PWD_573649_2
ELD/TN/02/23-24
Open Tender
Electrical Works
Item Rate
120 days
Nanichery Kannur
Please refer Tender documents.
7 documents required · 7 mandatory
₹2,760
₹50,000
Yes
22 Jul 2023
10 May 2023
20 May 2023
10 May 2023
17 May 2023
10 May 2023
Amount
Providing Decorative Poles
OD101639/2022-2023:Supply, conveyance, installation, testing and commissioning of 40W , 240 V LED decorative path way luminaire WW IP 65 optic Out put greater than 110 lumen/watts P.f > 0.9 ,THD ,10% with spun aluminium body, grey finish powder coated ,clear poly carbonate cover, 10 kV surge arrestor & 3 way 10 A mains terminal directly on the existing pole/ bracket and giving connections with the existing wiring etc as required (Crompton CBP 600 - 40 - 57- CP - NGR / equivalent)
OD101638/2022-2023:Supply conveyance installation, testing and commissioning of Decorative Pole 6 metre height above the ground level made out of GI, pipe section with die cast aluminium embellishments including connector foundation bolt 4 nos fixed in existing RCC foundation. The poles should have diameter 60mm to 90mm at the top and 114mm to 140mm at the bottom. The pole should should be pure polyester based powder coated with high corrosion resistance & chemical chromatised protection. The base should be made of die cast MS with holes suitable for 16/20/24 mm foundation bolts . The pole shall be with inbuilt junction looping box at bottom section with 32 A heavy duty 4 way connector for loop in & loop out and 1 no 6 A SP MCB and with MS base plate. The pole shall be suitable for wind loading's as per IS 875 part 3 1987. (Make Crompton Voila HM-DECO/equivalent)
OD101551/2022-2023:Supply conveyance installation testing and commissioning of Hot Dipped Galvanised single arm decorative bracket tightened to the pole to mount the luminaries etc as required. (Model No: Crompton HM DECO SA NS/ Equivalent)
14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
14.8:Providing and laying in position cement concrete 1 :3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required.
14.7:Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required.
OD90696/2021-2022:Providing 15mm thick cement plaster of mix 1:4 (1 cement : 4 fine sand) at all levels.
OD90695/2021-2022:Reinforcement for R.C.C works, bend tied and placed in position (plain grill requiring bend cold) using tor steel as required.
OD4503/2022-2023:Supply & providing painted clamp made from 25x5 mm GI strip with bolt nuts, screw etc for the poles cables as required..
90.6.5.11:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 1.50 sq mm
90.12.5.2:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.2 core 6 sq mm
90.12.5.3:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.2 core 10 sq mm
OD18675/2023-2024:Supply & laying of one No. PVC insulated and PVC sheathed armoured aluminium power cable of 1.1 KV grade of the following sizes in the existing RCC/HUME/STONE WVRE/GI/DWC pipe as required.2 core 16 sq mm
9.1.1:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm)
9.1.2:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 10 sq. mm (19mm)
9.1.3:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 16 sq. mm (22mm)
90.16.1.10:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.25 mm GI conductor (10 SWG)
90.12.9.2:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size
90.12.9.3:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench63/50 mm or nearest size
90.16.2.3:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.32 mm dia G.I pipe ( medium class)
OD4493/2022-2023:Supply, conveyance & installation of Hensel make Cable Junction Boxes of size 260 x 210 x 116 mm IP 66 weather proof for outdoor installation (with metric knockouts for cable entry) with terminal set 6 sq.mm/10 sq.mm 5 pole & DIN rails.
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.10.3:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Double pole
2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
OD90697/2021-2022:Supply and fixing Time switch 240V AC DIN/BASE mounting(L&T J648B1-Analog version) in the existing enclosure and giving connection as required-
OD90699/2021-2022:Supply and fixing 25A AC3, MNX 25, 2 Pole power contactor (L&T) conforming to IS/IEC 60947-4-1 & IEC60947-4-1 in the existing enclosure and giving connection as required-
OD90701/2021-2022:Supply and fixing 32A HRC fuse base with HRC fuse link-
OD90698/2021-2022:Supply and fixing of Neutral link 32 A, 2 Way neutral links mounted on DMC/SMC base-
90.6.4.1:Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.1.00 sq.mm 1 Run
1.17.20:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 4 sq. mm
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
OD90703/2021-2022:Supply and providing earth lead from the test joint to the earth electrode using the following sizes of conductors/ strips including cutting, drilling necessary holes (in case of strip) and fixing firmly with plate test joint etc as required. 25 mm X 3 mm G.I. strip
OD90700/2021-2022:Supply and providing test joint for the earthing system using 2 Nos of the following sizes of strips including cutting and bending to shape, drilling necessary holes and fixed to the watering pipe etc as required. 2 x 25 x 3 mm GI strip
OD90694/2021-2022:Supply and providing the following sizes of bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required. 25x3 mm brass nut and bolt
OD101640/2022-2023:Supply, Installation, Testing & Commissioning of 3 kWp Grid Connected Solar Power Plant With Poly crystalline base solar panels on existing structure inclined at an angle corresponding to the Solar irradiation at the point and including supply and providing suitable size UV Rated Solar cables, 3 kVA single phase Inverter/PCU (inverter and MPPT charge controller), AC distribution board with CRCA/PC enclosure with MCB, Isolators, Type 2 AC SPD, distribution blocks and provision for Energy meter and DC distribution board of IP65 box with PV Fuses, DC Isolator and Type 2 DC SPD For Lightning and over voltage protection, AC & DC cables with lightning arrestors and circuit breakers & suitable size PVC flexible pipes, including SITC of solar generation meter and single phase LT Bidirectional meter . This rate is inclusive of Cost towards Approvals and Grid Connectivity.
OD101642/2022-2023:Providing Structure work required for installation of Solar plant with purlin/single section with G I round/ rectangular pipes including cutting, hoisting, fixing in position and two coat painting with suitable paint over a coat of approved steel primer, including welding and bolted with special shaped washers etc. complete as required.
90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.<br> Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
90.14.3.1:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardA' section neoprene beeding suitable for 1.60/ 2.00 mm sheet
2.3.2:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator8 way, Double door
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
OD90702/2021-2022:Fabrication, supply, conveyance and installation of Granite name board with table rubbed, edges rounded and polished, of size 75x50 cm or nearest size deep and 1.8 cm thick , with inscription there on indicating name of project the cost involved, the dates of commencement, completion, inauguration etc , fixing it on suitable place including fixing charge etc as required .
PRADEEP KUMAR.V.K
Bidder Name
Sajju T
PRADEEP KUMAR.V.K
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_850203.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .