Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.4 LAccepted-Finance NEAR CAPITAL FILLING STATION POWERLUX INDUSTRIES PRIVATE LIMITED RAISEN ROAD PATEL NAGAR BHOPAL MADHYA PRADESH 462024 | BHOPAL | MADHYA PRADESH | 462024 | L1 | Accepted-Finance L1 bidder | |
| 2 | L2₹40.7 L+₹3.3 L (8.71%)Rejected-Finance 1 A BASEMENT 30 31 RAJA HOUSE NEHRU PALACE NEW DELHI 110 019 | SOUTH EAST | DELHI | 110019 | L2 | Rejected-Finance Not the L1 bidder | |
| 3 | Rejected-Technical PLOT NO 113 GURUSANGAT DARBAR ROAD SINDHI COLONY KHAMLA NAGPUR 440025 | NAGPUR | MAHARASHTRA | 440025 | - | Rejected-Technical As par Tender document | |
| 4 | Rejected-Technical | - | Rejected-Technical As par Tender document |
Tender Value
₹45.7 L
EMD Value
₹91,400
Closing Date
7 Apr 2025, 3:00 pmClosed
AGM(EM)
FCI RO Jaipur
SITC of 82.5, 35 ,30,25 KVA DG Set AS PER CPCB IV plus NORMS with AMF PANEL, including providing earthing, cabling work, foundation, at FCI FSD Kota, FSD Bundi, FSD Baran and FSD Bhawani Mandi respectively
2025_FCI_854141_1
ROJ/ELECT/18/2024-25
Open Tender
Electrical Works
Works
90 days
Bundi, Baran, Bhawani mandi
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹91,400
10 Jun 2025
21 Mar 2025
8 Apr 2025
21 Mar 2025
7 Apr 2025
21 Mar 2025
Amount
ELECTRICAL WORKS
1. FSD Shivpura, Kota
Supply, Installation, testing and commissioning of 82.5 kVA Silent type Liquid cooled diesel driven generating set conforming to CPCB IV+ norms comprising of radiator, 4 stroke multi cylinder engine of minimum 100 BHP to deliver rated kVA at prevailing site conditions equipped with flywheel, residential type silencer, fuel governor, fuel pump/ CRDI, built in fuel tank, electric starting equipment with required nos. of suitable AH sealed maintenance free batteries etc., directly coupled to 82.5 kVA 0.8PF (lag), alternator suitable for 3 phase, 4 wire 50Hz AC supply system with the entire system mounted on common base frame etc. on an existing foundation, exhaust piping with thermal insulation, control wiring from Alternator to control panel, acoustic enclosure, etc. as specified and consisting of the followings and AMF panel as per specification given in the detailed specifications sheet as attached in the DG set Specifications section etc. as required.; Diesel Engine: One number Diesel Engine multi-cylinder, four stroke, liquid cooled, electric start, turbo charged type engine suitable for developing the minimum 100 BHP at 1500 rpm, suitable for above output of alternator at 40º C, 50% RH and at 1000 Metre MSL and conforming to BS 5514, BS 649, IS:10000, ISO 8528 Part I with upto date amendments/ norms, capable of taking 10% over loading for one hour after 12 hours of continuous operation complete with common base frame, Anti vibration mountings, radiator, starting equipment, batteries, residential type silencer and other accessories etc. as required and as specified in the detailed specification enclosed in the DG set Specifications section. Governing Class (As per ISO 8528 part-V) ; Noise Level ≤ 75 dBA at a distance of 1m (IS 8528-10)/as per latest CPCB NORMS ; Fuel Tank Capacity-minimum 160L / to run minimum of 8hr in one time full refilling ; Weight of Gen Set with Canopy- Wet- minimum 1350 Kgs (or as per Manufacturer standards) ; Electrical Battery Starting Voltage-12 V DC Engine Specifications- Rated Output (Prime continuous Rating as per ISO 8528-1)-66 kW/ minimum 100 HP; No of Cylinders-3/4; Rated Speed at 1500 RPM Aspiration - Turbo Aspiration; Lube Oil Sump Capacity- minimum 7L; Coolant Capacity- minimum 12L Alternator: Insulation-Class H; Efficiency at (100% Load)-0.8 pf (As per Standards IS 4722, IEC 34-1)-90% with voltage regulator ±1%; Max time to build Rated Voltage at Rated RPM-Voltage Recovery TIme-6 sec
Supplying, installation, testing and commissioning of automatic mains failure control suitable for 82.5kVA including auto By pass panel of 16SWG CRCA sheet floor mounted type, weather proof, corrosion resistance, water proof, Powder coated, powder painted, 7 tank process with suitable rating of 02 nos. FP MCCB, 02 nos. FP Contactors, aluminium bus bar for Grid, DG output and common output as approved by Engineer in Charge, suitable for required capacity of silent type DG site complete with relays, timers, set of CTs for metering & protection and energy analyser indicate currents, phase and line voltages, frequency, power factor, KWH, KVARH & provision for overload, short circuit, restricted earth fault, under frequency, control cabling from AMF Panel to diesel Engine and else where if required all complete and inter locking including all the required installations as mentioned in detailed specification sheet for DG set etc. as required. The AMF Panel may be placed inside the Canopy or at the suitable outdoor location as per latest norms and site conditions.
2. FSD Bundi
Supply, Installation, testing and commissioning of 35 kVA Silent type Liquid cooled diesel driven generating set conforming to CPCB IV+ norms comprising of radiator, 4 stroke multi cylinder engine of minimum 40 BHP to deliver rated kVA at prevailing site conditions equipped with flywheel, residential type silencer, fuel governor, fuel pump/ CRDI, built in fuel tank, electric starting equipment with required nos. of suitable AH sealed maintenance free batteries etc., directly coupled to 35 kVA 0.8PF (lag), alternator suitable for 3 phase, 4 wire 50Hz AC supply system with the entire system mounted on common base frame etc. on an existing foundation, exhaust piping with thermal insulation, control wiring from Alternator to control panel, acoustic enclosure, etc. as specified and consisting of the followings and AMF panel as per specification given in the detailed specifications sheet as attached in the DG set Specifications section etc. as required.; Diesel Engine: One number Diesel Engine multi-cylinder, four stroke, liquid cooled, electric start, turbo charged type engine suitable for developing the required BHP at 1500 rpm, suitable for above output of alternator at 40º C, 50% RH and at 1000 Metre MSL and conforming to BS 5514, BS 649, IS:10000, ISO 8528 Part I with upto date amendments/ norms, capable of taking 10% over loading for one hour after 12 hours of continuous operation complete with common base frame, Anti vibration mountings, radiator, starting equipment, batteries, residential type silencer and other accessories etc. as required and as specified in the detailed specification enclosed in the DG set Specifications section. Governing Class (As per ISO 8528 part-V) ; Noise Level ≤ 75 dBA at a distance of 1m (IS 8528-10)/as per latest CPCB NORMS ; Fuel Tank Capacity-minimum 80L / to run minimum of 8hr in one time full refilling ; Weight of Gen Set with Canopy- Wet- minimum 1050 Kgs (or as per Manufacturer standards) ; Electrical Battery Starting Voltage-12 V DC Engine Specifications- Rated Output (Prime continuous Rating as per ISO 8528-1)-28 kWe/ minimum 40 HP ; No of Cylinders-3/4; Rated Speed at 1500 RPM Aspiration - Turbo Aspiration ; Lube Oil Sump Capacity- minimum 7L; Coolant Capacity- minimum 8L Alternator: Insulation-Class H ; Efficiency at (100% Load)-0.8 pf (As per Standards IS 4722, IEC 34-1)-86% with voltage regulator ±1% ; Max time to build Rated Voltage at Rated RPM-Voltage Recovery TIme-6 sec
Supplying, installation, testing and commissioning of automatic mains failure control suitable for 35kVA including auto By pass panel of 16SWG CRCA sheet floor mounted type, weather proof, corrosion resistance, water proof, Powder coated, powder painted, 7 tank process with suitable rating of 02 nos. FP MCCB, 02 nos. FP Contactors, aluminium bus bar for Grid, DG output and common output as approved by Engineer in Charge, suitable for required capacity of silent type DG site complete with relays, timers, set of CTs for metering & protection and energy analyser indicate currents, phase and line voltages, frequency, power factor, KWH, KVARH & provision for overload, short circuit, restricted earth fault, under frequency, control cabling from AMF Panel to diesel Engine and else where if required all complete and inter locking including all the required installations as mentioned in detailed specification sheet for DG set etc. as required. The AMF Panel may be placed inside the Canopy or at the suitable outdoor location as per latest norms and site conditions.
3. FSD Baran
Supply, Installation, testing and commissioning of 30 kVA Silent type Liquid cooled diesel driven generating set conforming to CPCB IV+ norms comprising of radiator, 4 stroke multi cylinder engine of minimum 35 BHP to deliver rated kVA at prevailing site conditions equipped with flywheel, residential type silencer, fuel governor, fuel pump/ CRDI, built in fuel tank, electric starting equipment with required nos. of suitable AH sealed maintenance free batteries etc., directly coupled to 30 kVA 0.8PF (lag), alternator suitable for 3 phase, 4 wire 50Hz AC supply system with the entire system mounted on common base frame etc. on an existing foundation, exhaust piping with thermal insulation, control wiring from Alternator to control panel, acoustic enclosure, etc. as specified and consisting of the followings and AMF panel as per specification given in the detailed specifications sheet as attached in the DG set Specifications section etc. as required.; Diesel Engine: One number Diesel Engine multi-cylinder, four stroke, liquid cooled, electric start, turbo charged type engine suitable for developing the required BHP at 1500 rpm, suitable for above output of alternator at 40º C, 50% RH and at 1000 Metre MSL and conforming to BS 5514, BS 649, IS:10000, ISO 8528 Part I with upto date amendments/ norms, capable of taking 10% over loading for one hour after 12 hours of continuous operation complete with common base frame, Anti vibration mountings, radiator, starting equipment, batteries, residential type silencer and other accessories etc. as required and as specified in the detailed specification enclosed in the DG set Specifications section. Governing Class (As per ISO 8528 part-V) ; Noise Level ≤ 75 dBA at a distance of 1m (IS 8528-10)/as per latest CPCB NORMS ; Fuel Tank Capacity-minimum 60L / to run minimum of 8hr in one time full refilling ; Weight of Gen Set with Canopy- Wet- minimum 750 Kgs (or as per Manufacturer standards) ; Electrical Battery Starting Voltage-12 V DC Engine Specifications- Rated Output (Prime continuous Rating as per ISO 8528-1)-24 kW/ minimum 35 HP ; No of Cylinders-3; Rated Speed at 1500 RPM Aspiration - Turbo Aspiration ; Lube Oil Sump Capacity- minimum 4.5L; Coolant Capacity- minimum 9L Alternator: Insulation-Class H ; Efficiency at (100% Load)-0.8 pf (As per Standards IS 4722, IEC 34-1)-86% with voltage regulator ±1% ; Max time to build Rated Voltage at Rated RPM-Voltage Recovery TIme-6 sec
Supplying, installation, testing and commissioning of automatic mains failure control suitable for 30kVA including auto By pass panel of 16SWG CRCA sheet floor mounted type, weather proof, corrosion resistance, water proof, Powder coated, powder painted, 7 tank process with suitable rating of 02 nos. FP MCCB, 02 nos. FP Contactors, aluminium bus bar for Grid, DG output and common output as approved by Engineer in Charge, suitable for required capacity of silent type DG site complete with relays, timers, set of CTs for metering & protection and energy analyser indicate currents, phase and line voltages, frequency, power factor, KWH, KVARH & provision for overload, short circuit, restricted earth fault, under frequency, control cabling from AMF Panel to diesel Engine and else where if required all complete and inter locking including all the required installations as mentioned in detailed specification sheet for DG set etc. as required. The AMF Panel may be placed inside the Canopy or at the suitable outdoor location as per latest norms and site conditions.
4. FSD Bhawani mandi
Supply, Installation, testing and commissioning of 25 kVA Silent type Liquid cooled diesel driven generating set conforming to CPCB IV+ norms comprising of radiator, 4 stroke multi cylinder engine of minimum 32 BHP to deliver rated kVA at prevailing site conditions equipped with flywheel, residential type silencer, fuel governor, fuel pump/ CRDI, built in fuel tank, electric starting equipment with required nos. of suitable AH sealed maintenance free batteries etc., directly coupled to 25 kVA 0.8PF (lag), alternator suitable for 3 phase, 4 wire 50Hz AC supply system with the entire system mounted on common base frame etc. on an existing foundation, exhaust piping with thermal insulation, control wiring from Alternator to control panel, acoustic enclosure, etc. as specified and consisting of the followings and AMF panel as per specification given in the detailed specifications sheet as attached in the DG set Specifications section etc. as required.; Diesel Engine: One number Diesel Engine multi-cylinder, four stroke, liquid cooled, electric start, turbo charged type engine suitable for developing the minimum 32 BHP at 1500 rpm, suitable for above output of alternator at 40º C, 50% RH and at 1000 Metre MSL and conforming to BS 5514, BS 649, IS:10000, ISO 8528 Part I with upto date amendments/ norms, capable of taking 10% over loading for one hour after 12 hours of continuous operation complete with common base frame, Anti vibration mountings, radiator, starting equipment, batteries, residential type silencer and other accessories etc. as required and as specified in the detailed specification enclosed in the DG set Specifications section. Governing Class (As per ISO 8528 part-V); Noise Level ≤ 75 dBA at a distance of 1m (IS 8528-10)/as per latest CPCB NORMS; Fuel Tank Capacity-minimum 50L / to run minimum of 8hr in one time full refilling; Weight of Gen Set with Canopy- Wet- minimum 750 Kgs (or as per Manufacturer standards) ; Electrical Battery Starting Voltage-12 V DC Engine Specifications- Rated Output (Prime continuous Rating as per ISO 8528-1)-20 kW/ minimum 32 HP; No of Cylinders-3; Rated Speed at 1500 RPM Aspiration - Turbo Aspiration; Lube Oil Sump Capacity- minimum 4.5L; Coolant Capacity- minimum 5L Alternator: Insulation-Class H; Efficiency at (100% Load)-0.8 pf (As per Standards IS 4722, IEC 34-1)-86% with voltage regulator ±1%; Max time to build Rated Voltage at Rated RPM-Voltage Recovery TIme-6 sec
Supplying, installation, testing and commissioning of automatic mains failure control suitable for 25kVA including auto By pass panel of 16SWG CRCA sheet floor mounted type, weather proof, corrosion resistance, water proof, Powder coated, powder painted, 7 tank process with suitable rating of 02 nos. FP MCCB, 02 nos. FP Contactors, aluminium bus bar for Grid, DG output and common output as approved by Engineer in Charge, suitable for required capacity of silent type DG site complete with relays, timers, set of CTs for metering & protection and energy analyser indicate currents, phase and line voltages, frequency, power factor, KWH, KVARH & provision for overload, short circuit, restricted earth fault, under frequency, control cabling from AMF Panel to diesel Engine and else where if required all complete and inter locking including all the required installations as mentioned in detailed specification sheet for DG set etc. as required. The AMF Panel may be placed inside the Canopy or at the suitable outdoor location as per latest norms and site conditions.
EARTHING WORK
Earthing with G.l. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/coke and salt as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.l. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
SUPPLY AND LAYING OF SERVICE CABLE
Supplying of XLPE Armoured cable with aluminium conductor of 1.1 KV grade confirming to IS:7098 (Part- I) 1988 with up to date ammendments of the following size as required.
3½ x 35 sq. mm
3½ x 50sq. mm
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3½ X 35 sq. mm (32mm)
3½ X 50 sq. mm (35mm)
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.
upto 35 sq. mm
above 35 sq. mm and upto 95 sqmm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
Above 35 sq. mm
above 35 sq. mm and upto 95 sqmm (clamped with 25*3 mm MS flat clamp)
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
upto 35 sq. mm
above 35 sq. mm and upto 95 sqmm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
upto 35 sq. mm
above 35 sq. mm and upto 95 sqmm
Supplying and fixing of light class G.I. pipe of 50 mm dia. (nominal) 3 metres length along the pole for protection of under ground cable as required.
CIVIL WORKS
Providing foundation and platform for the 25 kVA Silent type DG set so as to place the above mentioned DG Set conforming to clause 2.5.1 of General specifications for Electrical Works Part - VII DG Sets 2013 including PCC & suitable CC mix as recommended by OEM/ Manufacturer.
At FSD Bhawani Mandi
Providing foundation and platform for the 30 kVA Silent type DG set so as to place the above mentioned DG Set conforming to clause 2.5.1 of General specifications for Electrical Works Part - VII DG Sets 2013 including PCC & suitable CC mix as recommended by OEM/ Manufacturer.
At FSD Baran
Providing foundation and platform for the 35 kVA Silent type DG set so as to place the above mentioned DG Set conforming to clause 2.5.1 of General specifications for Electrical Works Part - VII DG Sets 2013 including PCC & suitable CC mix as recommended by OEM/ Manufacturer.
At FSD Bundi
Providing foundation and platform for the 82.5kVA Silent type DG set so as to place the above mentioned DG Set conforming to clause 2.5.1 of General specifications for Electrical Works Part - VII DG Sets 2013 including PCC & suitable CC mix as recommended by OEM/ Manufacturer.
At FSD Shivpura,kota
Mona Generator Services Pvt. Ltd. (BID ID -3198769)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .