Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.0 LAccepted-AOC | L1 | Accepted-AOC LOWEST QUOTED BIDDER | |
| 2 | L2₹32.1 L+₹4.1 L (14.7%)Rejected-Finance | L2 | Rejected-Finance NOT THE LOWEST QUOTED BIDDER |
| Sl No | Description | Qty | Unit | Rajesh Engineering Consultants L2 | AKSHITA ELECTRICAL L1 |
|---|---|---|---|---|---|
| 1.00 | Dismantling of defective 11 KV VCB, upto 800 Amps, Indoor VCB panel (Make: Schneider / Crompton Greaves / SIEMENS etc.), Servicing, Repairing & Replacement (as required at site & as directed) of the unserviceable items such as Closing / Tripping Coil Assembly, Spring Charging Motor and Gear Assembly, Master Trip Relays, Supervision Trip Relays, OC relays, Overhauling and including rectification of the electrical & mechanical faults by the Service Engineer / Authorised Personnel of the Company after necessary cleaning and providing silicon grease to all the moving parts, also including adjustment of all springs / relays etc, commissioning of 11 KV VCB Panel CT, PT, Relays, VCB testing including CRM, Timer, IR Testing in VCB, Winding Resistance, Polarity Testing in CT and PT and Secondary Current Injection with 03 setting & Tripping test with timing in relays and applying control voltage & testing all scheme logic with ON/OFF Trip operation, also checking metering and protection and annunciation with indication kit and Testing of CT Ratio and connection of CTs by Primary Injection complete and Calibration of IDMT / OC / EF / UV Relays, Secondary Injection complete & making the VCB 100% serviceable complete in all respects complete all as specified and as directed & to the entire Satisfaction of Engr-In-Charge.
Note :- Cost of all the materials, labour and other elements to make the entire system serviceable shall be deemed to be included in the quoted rates and only payment for supply only of the items listed here-in-below shall be measured and paid for separately in case these are ordered and provided as directed. The make of the items / materials shall be as specified in the item(s) and in case not specified, the same shall be of make as approved by the Engr-In-Charge. | 20 | Each Job | 24,000 ₹4,80,000 | 16,830 ₹3,36,600 Lowest |
| 2.00 | Supply only OC & EF Relay (Make Schneider, Type Micon P111 or or as per Existing or as approved by Engr-In-Charge) perfectly matching / suitable for 11KV upto 800A VCB Panel complete all as specified and as directed & to the entire Satisfaction of Engr-In-Charge. | 3 | Each Set | 40,000 ₹1,20,000 | 32,400 ₹97,200 Lowest |
| 3.00 | Supply only Master Trip Relay (Make as per Existing or as approved by Engr-In-Charge) perfectly matching / suitable for 11KV upto 800A VCB Panel complete all as specified and as directed & to the entire Satisfaction of Engr-In-Charge. | 3 | Each | 7,000 ₹21,000 | 6,300 ₹18,900 Lowest |
| 4.00 | Supply only Supervision Trip relay / Trip Circuit Healthy (Make as per Existing or as approved by Engr-In-Charge) perfectly matching / suitable for 11KV upto 800A VCB Panel complete all as specified and as directed & to the entire Satisfaction of Engr-In-Charge. | 3 | Each | 7,000 ₹21,000 | 6,300 ₹18,900 Lowest |
| 5.00 | Supply only Single Phase PT (Make as per Existing or as approved by Engr-In-Charge) perfectly matching / suitable for 11KV upto 800A VCB Panel complete all as specified and as directed & to the entire Satisfaction of Engr-In-Charge. | 2 | Set of 3 | 58,500 ₹1,17,000 Lowest | 63,000 ₹1,26,000 |
| 6.00 | Supply only Single Phase PT fuse (Make as per Existing or as approved by Engr-In-Charge) perfectly matching / suitable for 11KV upto 800A VCB Panel complete all as specified and as directed & to the entire Satisfaction of Engr-In-Charge. | 6 | Each | 800 ₹4,800 Lowest | 990 ₹5,940 |
| 7.00 | Supply only Space Heater 230V, AC 100W (Make as per Existing or as approved by Engr-In-Charge) perfectly matching / suitable for 11KV upto 800A VCB Panel complete all as specified and as directed & to the entire Satisfaction of Engr-In-Charge. | 10 | Each | 1,200 ₹12,000 Lowest | 1,350 ₹13,500 |
| 8.00 | Supply only Multi Voltage type Indicator Lamp (Make as per Existing or as approved by Engr-In-Charge) perfectly matching / suitable for 11KV upto 800A VCB Panel complete all as specified and as directed & to the entire Satisfaction of Engr-In-Charge. | 10 | Each Set | 350 ₹3,500 Lowest | 360 ₹3,600 |
| 9.00 | Supply only Tripping Coil 110/24 VDC (Make as per Existing or as approved by Engr-In-Charge) perfectly matching / suitable for 11KV upto 800A VCB Panel complete all as specified and as directed & to the entire Satisfaction of Engr-In-Charge. | 3 | Each | 6,500 ₹19,500 | 6,300 ₹18,900 Lowest |
| 10.00 | Supply only Closing coil 110/24 VDC (Make as per Existing or as approved by Engr-In-Charge) perfectly matching / suitable for 11KV upto 800A VCB Panel complete all as specified and as directed & to the entire Satisfaction of Engr-In-Charge. | 3 | Each | 6,500 ₹19,500 | 6,300 ₹18,900 Lowest |
Tender Value
₹26 L
EMD Value
₹52,000
Closing Date
20 Jul 2026, 6:00 pmClosed
CWE (AF) Secunderabad
CWE (AF) Secunderabad
REPAIR / RENEWALS / PERIODICAL MAINT TO HT SWITCH GEARS, DEHYDERATION OF TRANSFORMERS AND OTHER MISC WORKS AT AFA HYDERABAD
2026_MES_772640_1
86816/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (AFA) Hyderabad
As per NIT
9 documents required · 9 mandatory
₹500
GE (AFA) HYDERABAD
₹52,000
Yes
13 Aug 2026
16 Jun 2026
22 Jul 2026
16 Jun 2026
20 Jul 2026
30 Jun 2026
16 Jun 2026 - 25 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Dismantling of defective 11 KV VCB, upto 800 Amps, Indoor VCB panel (Make: Schneider / Crompton Greaves / SIEMENS etc.), Servicing, Repairing & Replacement (as required at site & as directed) of the unserviceable items such as Closing / Tripping Coil Assembly, Spring Charging Motor and Gear Assembly, Master Trip Relays, Supervision Trip Relays, OC relays, Overhauling and including rectification of the electrical & mechanical faults by the Service Engineer / Authorised Personnel of the Company after necessary cleaning and providing silicon grease to all the moving parts, also including adjustment of all springs / relays etc, commissioning of 11 KV VCB Panel CT, PT, Relays, VCB testing including CRM, Timer, IR Testing in VCB, Winding Resistance, Polarity Testing in CT and PT and Secondary Current Injection with 03 setting & Tripping test with timing in relays and applying control voltage & testing all scheme logic with ON/OFF Trip operation, also checking metering and protection and annunciation with indication kit and Testing of CT Ratio and connection of CTs by Primary Injection complete and Calibration of IDMT / OC / EF / UV Relays, Secondary Injection complete & making the VCB 100% serviceable complete in all respects complete all as specified and as directed & to the entire Satisfaction of Engr-In-Charge.
Note :- Cost of all the materials, labour and other elements to make the entire system serviceable shall be deemed to be included in the quoted rates and only payment for supply only of the items listed here-in-below shall be measured and paid for separately in case these are ordered and provided as directed. The make of the items / materials shall be as specified in the item(s) and in case not specified, the same shall be of make as approved by the Engr-In-Charge. | 20 | Each Job | 1.25 | ₹25 |
| 2 | Supply only OC & EF Relay (Make Schneider, Type Micon P111 or or as per Existing or as approved by Engr-In-Charge) perfectly matching / suitable for 11KV upto 800A VCB Panel complete all as specified and as directed & to the entire Satisfaction of Engr-In-Charge. | 3 | Each Set | 1.25 | ₹3.75 |
| 3 | Supply only Master Trip Relay (Make as per Existing or as approved by Engr-In-Charge) perfectly matching / suitable for 11KV upto 800A VCB Panel complete all as specified and as directed & to the entire Satisfaction of Engr-In-Charge. | 3 | Each | - | - |
| 4 | Supply only Supervision Trip relay / Trip Circuit Healthy (Make as per Existing or as approved by Engr-In-Charge) perfectly matching / suitable for 11KV upto 800A VCB Panel complete all as specified and as directed & to the entire Satisfaction of Engr-In-Charge. | 3 | Each | 100 | ₹300 |
| 5 | Supply only Single Phase PT (Make as per Existing or as approved by Engr-In-Charge) perfectly matching / suitable for 11KV upto 800A VCB Panel complete all as specified and as directed & to the entire Satisfaction of Engr-In-Charge. | 2 | Set of 3 | 53 | ₹106 |
| 6 | Supply only Single Phase PT fuse (Make as per Existing or as approved by Engr-In-Charge) perfectly matching / suitable for 11KV upto 800A VCB Panel complete all as specified and as directed & to the entire Satisfaction of Engr-In-Charge. | 6 | Each | 10 | ₹60 |
| 7 | Supply only Space Heater 230V, AC 100W (Make as per Existing or as approved by Engr-In-Charge) perfectly matching / suitable for 11KV upto 800A VCB Panel complete all as specified and as directed & to the entire Satisfaction of Engr-In-Charge. | 10 | Each | 11 | ₹110 |
| 8 | Supply only Multi Voltage type Indicator Lamp (Make as per Existing or as approved by Engr-In-Charge) perfectly matching / suitable for 11KV upto 800A VCB Panel complete all as specified and as directed & to the entire Satisfaction of Engr-In-Charge. | 10 | Each Set | 1.25 | ₹12.5 |
| 9 | Supply only Tripping Coil 110/24 VDC (Make as per Existing or as approved by Engr-In-Charge) perfectly matching / suitable for 11KV upto 800A VCB Panel complete all as specified and as directed & to the entire Satisfaction of Engr-In-Charge. | 3 | Each | - | - |
| 10 | Supply only Closing coil 110/24 VDC (Make as per Existing or as approved by Engr-In-Charge) perfectly matching / suitable for 11KV upto 800A VCB Panel complete all as specified and as directed & to the entire Satisfaction of Engr-In-Charge. | 3 | Each | 1.25 | ₹3.75 |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.39 MB
86816TENDERPDF.pdf
Tender Documents • 0.90 MB
BOQ_865176.xls
BOQ • 0.61 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .