Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.0 LAccepted-AOC | L1 | Accepted-AOC L1 |
| Sl No | Description | Qty | Unit | Vinod Kumar M L1 |
|---|---|---|---|---|
| 1.00ELETRIFICATION | ||||
| 1.00 | 1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC
insulated copper conductor single core cable in surface / recessed medium class PVC conduit,
with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS
PVC insulated copper conductor single core cable etc as required.Group C | 67 | point | 1,160 ₹77,720 Lowest |
| 1.00 | OD231144/2024-2025:Wiring combined plug point together with the light point/ fan point/ exhaust fan point/ call bell point including 6 A 5 pin modular socket controlled by 6A one way modular switch in the existing switch board and giving connection to the phase, neutral and earth terminal with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable ( Green wire for earthing) etc as required. | 1 | each | 330 ₹330 Lowest |
| 1.00 | 1.33:Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required. | 50 | each | 74 ₹3,700 Lowest |
| 1.00 | 90.3.21.3:Supply & installation of light fittings on 'C/U' shaped flat iron bracket
Supply, conveyance, installation, testing and commissioning the light fittings of following types made from 0.5mm CRCA sheet complete with all accessories and lamps etc. directly on wall using 2 nos. 'C/U' brackets made from 20 x 3 mm MS flat, painting the flat iron bracket and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.1200 mm 1X20W LED Lamp with box type fixture | 14 | each | 1,270 ₹17,780 Lowest |
| 1.00 | 90.3.24.3:Supply & installation of light fittings suspended on ball & socket arrangement with 19 mm down rod <br>
Supply, conveyance, installation, testing and commissioning the light fittings of following types made of .5mm thick CRCA sheet accessories and lamps etc. including supplying and fixing ball and socket arrangements on PVC round block, suspension down rod of 19mm dia MS conduit up to 2x30cm length including painting and wiring the down rod with 16/0.20mm 3 core round copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connections etc. a required.1200 mm 1X20W LED Lamp with box type fixture | 4 | each | 1,500 ₹6,000 Lowest |
| 1.01 | 90.3.20.3:Supply & installation of light fittings on TW round block
Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 1X20W LED Lamp with box type fixture | 4 | each | 1,250.12 ₹5,000.48 Lowest |
| 1.01 | OD231027/2024-2025:Supply, conveyance, Installation, testing and commissioning of Cast aluminium stove enameled elliptical shaped bulk head fittings directly on wall including cutting necessary holes, giving connections with the extended original wiring, making good the damages, colour washing etc as required. | 5 | each | 550 ₹2,750 Lowest |
| 1.01 | 1.58:Supplying and fixing PVC batten/ angle holder including connection etc. as required. | 17 | each | 102 ₹1,734 Lowest |
| 1.01 | OD226677/2024-2025:Supply and providing the following types and power rated lamps in the existing fittings as required. B22 LED bulb 9W | 22 | each | 175 ₹3,850 Lowest |
Tender Value
₹5.1 L
EMD Value
₹12,692
Closing Date
30 Sept 2025, 6:00 pmClosed
Assisstant Executive Engineer
Office of the Assisstant Executive Engineer PWD Electrical Subdivision Thalassery
GENERAL-Pariyaram Public Health Centre Construction of New Building-Electrification of New Building for Pariyaram Public Health Centre-General Electrical Work
2025_PWD_759999_2
PWD/BLDG/TR/846/2025_6_1_1/1
Open Tender
Electrical Works
Item Rate
540 days
KANNUR
Please refer Tender documents.
7 documents required · 7 mandatory
₹1,120
₹12,692
31 Mar 2026
22 Sept 2025
3 Oct 2025
22 Sept 2025
30 Sept 2025
22 Sept 2025
Amount
ELETRIFICATION
1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
OD231144/2024-2025:Wiring combined plug point together with the light point/ fan point/ exhaust fan point/ call bell point including 6 A 5 pin modular socket controlled by 6A one way modular switch in the existing switch board and giving connection to the phase, neutral and earth terminal with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable ( Green wire for earthing) etc as required.
1.33:Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
90.3.21.3:Supply & installation of light fittings on 'C/U' shaped flat iron bracket Supply, conveyance, installation, testing and commissioning the light fittings of following types made from 0.5mm CRCA sheet complete with all accessories and lamps etc. directly on wall using 2 nos. 'C/U' brackets made from 20 x 3 mm MS flat, painting the flat iron bracket and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.1200 mm 1X20W LED Lamp with box type fixture
90.3.24.3:Supply & installation of light fittings suspended on ball & socket arrangement with 19 mm down rod <br> Supply, conveyance, installation, testing and commissioning the light fittings of following types made of .5mm thick CRCA sheet accessories and lamps etc. including supplying and fixing ball and socket arrangements on PVC round block, suspension down rod of 19mm dia MS conduit up to 2x30cm length including painting and wiring the down rod with 16/0.20mm 3 core round copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connections etc. a required.1200 mm 1X20W LED Lamp with box type fixture
90.3.20.3:Supply & installation of light fittings on TW round block Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 1X20W LED Lamp with box type fixture
OD231027/2024-2025:Supply, conveyance, Installation, testing and commissioning of Cast aluminium stove enameled elliptical shaped bulk head fittings directly on wall including cutting necessary holes, giving connections with the extended original wiring, making good the damages, colour washing etc as required.
1.58:Supplying and fixing PVC batten/ angle holder including connection etc. as required.
OD226677/2024-2025:Supply and providing the following types and power rated lamps in the existing fittings as required. B22 LED bulb 9W
90.3.18.1:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.25 mm dia with HG company fabricated clamps
90.15.4.2:Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
OD226683/2024-2025:Supply, conveyance, installation, testing and commissioning of exhaust fan in the existing opening, fixing necessary anchor bolts / bolt and nuts etc., as required including giving connections with the supplied wire along with the exhaust fan,making good the surface as required. 305 mm sweep light duty exhaust fan in metal frame
90.4.8:Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.6:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm
1.17.9:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.9 x 1.5 sq. mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.15:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 2.5 sq. mm
1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
1.17.24:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 4 sq. mm
1.17.33:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 6 sq. mm
90.12.7.40:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
90.12.5.40:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 10 sq mm
90.12.7.41:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
90.12.10.2:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation50/38 mm or nearest size
OD280733/2024-2025:Supply laying and clamping of the following sizes of B class GI pipe using stain less steel clamps spacing not exceeding 40cms making good the damages as required 32mm dia GI pipe (medium class)
9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
1.27.1:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.27.3:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.4 Module (125mmX75mm)
1.27.4:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm)
1.27.5:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
90.10.3.15:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )32A DP switch with indicator
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
90.10.3.33:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3pin Shuttered socket
90.10.3.32:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3 pin plug top with indicator
90.11.1.14:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
90.11.1.11:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - three phase double cover (IP 42/43)
2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door
OD280770/2024-2025:Supply and fixing 40A to 63A, TP MCB (C curve), 10 KA breaking capacity suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc... as required.
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.15.3:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
OD226684/2024-2025:Supply and providing the following sizes of bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required. 25x6 mm brass nut and bolt
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
OD226680/2024-2025:Supply and providing earth lead from the test joint to the earth electrode using the following sizes of conductors/ strips including cutting, drilling necessary holes (in case of strip) and fixing firmly with plate test joint etc as required. 25 mm X 3 mm G.I. strip
OD226681/2024-2025:Supply and providing test joint for the earthing system using 2 Nos of the following sizes of strips including cutting and bending to shape, drilling necessary holes and fixed to the watering pipe etc as required. 2 x 25 x 3 mm GI strip
OD292363/2024-2025:Supply and installation of switch gear units in sheet steel enclosure complete with handle assembly, door interlock and pad locking arrangement of the following ratings on existing angle iron frame work or directly to wall using necessary bolts & nuts, fixing the unit to wall, making good the damages, colour washing etc. including giving necessary connections as required. 63 Amp TPN SDF AC 23A with ISI marked HRC fuse
OD226675/2024-2025:Supply and fixing 63A, HRC Fuse with HRC Fuse link with connections, in existing meter board
OD226678/2024-2025:Supplying and fixing 63 A, 2 Way neutral links mounted on DMC/SMC base with connections, in existing meter board
OD226686/2024-2025:Supply and installation of 3 phase meter board with provision for fixing KSEB energy meter, cut out fuse unit etc.(syntex make GSMB 6535/Equivalent)
OD260790/2024-2025:Supply and fixing 32mm dia 6Kgff/cm2 PVC Pipe including fixing the pipe with clamp/clips at 60cm spacing. etc. as required (for service pipe)
OD226679/2024-2025:Supply and providing suitable Iron Hook grouted on wall for binding the service wire
OD281060/2024-2025:Supply installation of ISO certified pure sine wave Inverter with the following specifications, a. Capacity: 2 KVA b. Input voltage range 140-280 Volts AC Single phase c.Out put voltage : 230V/50Hz AC Voltage regulation +/-1% d. Wave form: True sine wave e. Indicators: Mains on, Inverter on,Battery on charger,Over load f. Battery:C Tubular C10 series 75AHx 2 nos (1Hrs backup) with painted angle iron non corrossive rack for keeping the batteries. g. Warranty : 2 Year on site warranty for inverter and 3year Warraty for tubular battery.
OD292364/2024-2025:Supply and Installation of ISO certified Luminous/ Power Tehh/ Hykon/Numeric /Delta or equivalent Tpure sine wave Off line UPS with the following specifications, a. Capacity & DC Voltage : 2 KVA/24V b. Input Voltage range : 100-285 Volt AC Single phase c. Output voltage : single phase 230V AC with voltage regulation 1% d. Maximum Charging Current: 21A e. Waveform : Prue Sine wave g. Display: Digital Display for the status of Power back-up/battery charging time in hours and minutes h. Battery : with 2 no.s 12 V ,100Ah Tubular inverter rechargeable battery Luminous/Exide/Amroon / or equivalent with rugged construction; Water Level Indicators: with painted non corrosive rack for keeping the Batteries. g. Warranty : 3 year on-site warranty for Inverter and minimum 3 years replacement warranty for Battery giving connection etc as required.
Bidder Name
Vinod Kumar M
stage.html
html • 0.03 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1327709.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.04 MB
MOM.pdf
Tender Documents • 0.20 MB
viewnit.pdf
Tender Documents • 0.02 MB
viewsbd.pdf
Tender Documents • 1.63 MB
specificconditionNEW.pdf
Tender Documents • 0.34 MB
BOQ_1327709.xls
BOQ • 0.35 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .