Tender for Work of erection of 66 kV equipment, structures, control wiring, yard Lighting, Control-Room etc at 66 kV Hapa Sub Sation with Mesh earthing and furniture.
348746
2026-27 / HTC / 53
Open
Electrical and Maintenance Works
Works
Sabarkantha
16 documents required · 16 mandatory
₹1,180
GETCO,Himatnagar
24 Sept 2026
24 Sept 2026
24 Sept 2026
12 Oct 2026
24 Sept 2026
SCHEDULE B-1: MAIN ERECTION
Item code Description of work Unit
Erection of equipments of any type / make
with required all spares as per supplier's
manual & FQP, including individual &
interpole wiring for all mentioned voltage
class switchyard (as per respective technical
specifications & relevant special conditions)
suitable for all type of bus configurations.
Scope includes the dragging /loading /
unloading of same from site store to
c) 66/22 KV Breakers without crane is Set of
Erection of CT/PT/CVT on erected structure
including complete dragging/ loading/
unloading of same with crane only from site
store to erection site and fixing of required
clamps, connectors & accessories as per
instructions of Engineer-in-charge.
d) 66 KV CT/PT/CVT (without crane Per
permitted) Phase
Erection of surge arrester with counter on
erected structure including complete
dragging/loading/ unloading of the same
with crane only from site store to erection
3 9902040010 site and fixing of required clamps,
connectors instructions of Engineer-in-
d) 66 KV LA (without crane permitted) 12 415
Erection of Double break isolator (All make)
with earth blade on its erected structure
consisting of 3 base channels with solid core
porcelain insulator including interconnected
piping with operating mechanism and
accessories with final adjustment for
simultaneous mechanical & electrical
operating fro opening & closing. The rates
are inclusive of dragging / loading /
unloading of the same from site store to
erection site as per instruction of Engineer-
a) 66 KV Isolator (without crane) 2 3459
Same as Item No. 4 but without earth blade
a) 66 KV Isolator (without crane) 7 2491
Erection of Solid Core porcelain /comopsite
polymer Bus post insulator on its erected
structure complete, fixing of accessories and
shifting of same including loading/ unloading
from its site store to erection site.
Laying of any size of 11/22KV XLPE cable
including excavation of trench 300 mm wide
& 600 mm deep including laying and filling
up sand of 100mm layer from bottom &
bricks on three side of cable & refilling the
trench with Murram/soil & ramming etc.
Required bricks, sand, power cable
marker/C.I./G.I. plate etc. will have to be
supplied by the contractor. Rates are
inclusive of shifting of cable drum to the site
from S/S site store. Drum should be handled
only by jacking to avoid damage to cables.
Laying of any size of 11/22 KV XLPE cable in
ready made cable trench or in open space.
Rates are inclusive of shifting of cable drum
to the site from S/S site store. Drum should
be handled only by jacking to avoid damage
Erection of S/S & Equipment structure
including punching of nut bolts. Rates are
9 9902040027 inclusive of shifting of same up to erection
site from its s/s Store.
Erection of 66/22KV or 66/11KV, class
Power Transformer with complete mounting
of all the accessories i.e. bushings, radiators,
conservator tank etc. as per OEM approved
drawing including laying of cable between all
accessories mounted on the transformer/
marshalling KIOSK. Filling and filtration of oil
10 with filter machine as per direction of
Engineer-in-charge, manufacturer Engineer
or as per instruction manual of the
equipment. All necessary tools, tackles,
required for transformer erection shall be
provided by the contractor. Filteration of the
oil will be in the scope of the contractor for
the transformer
Stringing of Bus complete in all respect with
fixing of all fitting, insulators sag
compensating plate / spring and all
accessories as per the instruction of
Engineer-in-charge.
c) Single Moose/AL-59/Zebra conductor Per 170 63
Preparing and fixing of required length of
Jumpers in the switchyard on respective Bus
& equipments, tensioning & dressing of
jumpers complete as per instruction of
Engineer-in-charge.
c) Single Moose/AL-59/Zebra/Panther
Installation of Earthing Strips / MS Round
Bar in any kind of soil expects Rocky(HR/SR)
as per earthing philosophy of GETCO
1) Including digging of 600 mm depth and
450 mm Wide Trench.
2) Cutting, bending, laying and fixing of
Earthing grid conductor.
3) 75×10 mm / 50×6 mmGI strips: Fixing of
two bolt at each straight joints and lap
welding, removing oxide films formed during
welding, applying two coats of red oxide and
black powder after welding and applying Zinc
Rich Paint on welded joints.
4)25/32/36/40MM dia MS Rod: Lap welding
at each straight & cross joints, removing
oxide films formed during welding, applying
two coats of red oxide and black powder
after welding and applying Zinc Rich Paint on
5) Including supply of red oxide, black
powder, HDGI nuts & bolts, as per
6)Back filling of the trench with yellow /
Normal soil. Structure and
Equipment earthing:
1) Including digging of 600 mm depth and
450 mm Wide Trench.
2) Cutting, bending as per required shape,
laying and fixing of risers from Grid to
structure and Equioments. 3) Lap
welding, removing oxide films formed during
welding, applying two coats of red oxide and
black powder after welding and applying Zinc
Rich Paint on welded joints including supply
of HDGI nuts & bolts for all connections
including supporting to structures etc as per
4) Back filling of the trench with yellow /
9902040061 (a)75X10 mm GI Strip Mtr 0 52
9902040061 (b)50 X 6 mm GI Strip Mtr 3500 43
Installation of Earthing Strips / MS Round
Bar in Rocky(HR/SR) as per earthing
philosophy of GETCO Earthing Grid.
1) Including digging of 600 mm depth and
450 mm Wide Trench.
2) Cutting, bending, laying and fixing of
Earthing grid conductor.
3) 75×10 mm / 50×6 mmGI strips: Fixing of
two bolt at each straight joints and lap
welding, removing oxide films formed during
welding, applying two coats of red oxide and
black powder after welding and applying Zinc
Rich Paint on welded joints.
4)25/32/36/40MM dia MS Rod: Lap welding
at each straight & cross joints, removing
oxide films formed during welding, applying
two coats of red oxide and black powder
after welding and applying Zinc Rich Paint on
5) Including supply of red oxide, black
14 powder, HDGI nuts & bolts, as per
6)Back filling of the trench with yellow /
Normal soil. Structure and
Equipment earthing:
1) Including digging of 600 mm depth and
450 mm Wide Trench.
2) Cutting, bending as per required shape,
laying and fixing of risers from Grid to
structure and Equioments. 3) Lap
welding, removing oxide films formed during
welding, applying two coats of red oxide and
black powder after welding and applying Zinc
Rich Paint on welded joints including supply
of HDGI nuts & bolts for all connections
including supporting to structures etc as per
4) Back filling of the trench with yellow /
9902040061 (a)75X10 mm GI Strip Mtr 0 174
9902040061 (b)50 X 6 mm GI Strip Mtr 1000 164
Supply ,Installation Testing and
Commissioning of Maintenance free treated
earth electrodes suitable for Normal Soil as
per drawing no GETCO /E/STD/P-021(1 OF 2)
R3 DT 29.0.2020 and technical specification
GETCO/E/TS-maintenance free earth pits/R1
dated 04.06.2015 for 66/11 kv substation with
ground enhancement material/back
fill/grounding compound as per IEEE 80-2000
Clause 14.5(d) and as per part-7 of IEC
using copper bounded earth electrode(with
250 micron copper coating)having 24 mm
(mim) and 3000 mm length which shall be
capable of handling STC of 25 KA-1 sec. Work
also include providing BB masonry inspection
chamber(manhole) incl. light type CI cover
Installation of ground rod 20/32/24 mm dia.,
16 9902040062 3 m long vertical spike for mesh type No 30 158
earthing in Normal Soil
Erection of Control Panel Relay panel or C/R
Panel or RTCC Panel including grouting of
panel, jointing with adjoining panels
including required fabrication for entry of
17 9902080004 control cables and complete vermin
proofing. Job includes supply of required
bolts, nuts etc. and shifting of panel from S/S
site store to work site
Erection of 11 kV CB Panel of any make
including grouting, jointing with adjoining
panel and Horizontal , Vertical levelling
including required fabrication in control
panel or required stone cutting in flooring
for entry of Power Cable, Control Cable
including interpanel wiring and complete
vermin proofing, job includes supply of
required bolts, nuts etc and shifting of panel
from SS Site store to work site.
-- do -- LT panel GETCO including fixing of all
switches bus bars etc.
Erection of Battery Charger of any make as
20 9902080007 per manufacturer's instruction manual No 1 968
including grouting, vermin proofing
Erection of 100/250 AH D.C. Battery Set on
wooden stand as per instruction manual of
21 9902080009 supplier, including first filling of battery
electrolyte, proper connection of cells and
applying, charging/discharging cycles as per
manufacturer's instruction manual and
instruction of EIC
Erection of station transformer of 22KV or
11KV/430V, 63/100KVA on its plinth/DP
Structure ,grouting of foundation bolts, fixing
of channels.., D.O. fuse by fabricating str.& its
painting, danger board etc. including
connection with power cable LV cable
terminations including shifting from S/S site
store to plinth as per Engineer-in-charge.
Fabrication for erection of any Equipment
23 9902990026 /Structure /Panel or anywhere in S/S & F.B. 1 4992
at other end as per Inst. Of E.I.C.
Erection of supporting structure for 11kv
Power cable termination at 11kv bushing of
10/15/20 MVA transformer as per DRG. No.
GETCO/E/06S-STD/11KVSTR-A2-02
1) Material for supporting structure will be
supplied free of cost by GETCO.
2) Necessary wooden clamp with required
nut-bolt-washers & HDPE rubber piece for
packing etc. as per drawing shall be supplied
3) Job also include minor fabrication if
required as per instruction of E.I.C.
Providing & fixing of Set of following Items
on erected 11KV support structure system
for power cable 66/11 KV Transformer as per
DRG. No. GETCO/E/06S-STD/11KVSTR-A2-02
and instruction of E.I.C.
1) Alluminium Alloy Bus Bar of size
75X20X2000 mm. with heat shrinkable anti
tracking tubing: 03 Nos.
2) 11KV SRI of PCD 127 mm - 12 No
3) Copper laminated fusion welded flexible
jumper of size 75 X 10 X 600 mm having
2000 Amp capacity: 03 Nos.
4) BiMetalic Plate (Al/Cu): 03 Nos.
5) 11KV heat shrinkable anti tracking Sleeve
on Al Bus bar of all three phase: 06 mtrs.
6) Including required GI/SS nut-bolt and
washers of Good Quality for fitting support
7) All live parts shall be covered with heat
shrinkable MV insulated tape / sleeve.
Erection of supporting structure for Station
transformer as per GETCO drawing no :
GETCO/E/06S-STD/11KV STR A3-03.
1) Necessary wooden clamp with required
nut-bolt-washers & HDPE rubber piece for
packing etc. as per drawing shall be supplied
26 9902030018 by contractor. No 1 2196
2) Job also include erection of required 11kV
LA and D.O fuse and any minor fabrication if
required as per instruction of E.I.C.
3) Material for supporting structures, D.O.
Fuse and 11kV LA and will be supplied by
GETCO free of cost.
Erection of 11KV D.P. Structure as per
GETCO Drawing No.: GETCO/E/06S-
STD/11KV STR A1-01.
1) Job includes erection of 11KV A/B
switches, 11 KV PI, jumpering between 11kv
cable to 11kv Bus etc. on erected structures.
2) Material for DP structures, A/B switches,
27 9902030018 PI and conductor for jumper will be supplied No 5 2196
by GETCO free of cost.
3) Necessary wooden clamp with required
nut-bolt-washers & HDPE rubber piece for
packing etc. as per drawing shall be supplied
4) Job also include minor fabrication if
required as per instruction of E.I.C.
Erection of 11KV D.P. Structure as per
GETCO Drawing No.: GETCO/E/06S-
STD/11KV STR A4-04.
1) Job includes erection of 11KV A/B
switches, 11 KV PI, jumpering between 11kv
cable to 11kv Bus etc. on erected structures.
2) Material for DP structures, A/B switches,
28 9902030018 PI and conductor for jumper will be supplied No 5 2196
by GETCO free of cost.
3) Necessary wooden clamp with required
nut-bolt-washers & HDPE rubber piece for
packing etc. as per drawing shall be supplied
4) Job also include minor fabrication if
required as per instruction of E.I.C.
Providing of M15 Grade Concrete for various
equipment structure, Guy, 11kv DP, M.K.
Box, Neutral channels, cable support
channel, grouting of Pole/ Flood light
structure with cement, sand & metal in
proportion of 1:2:4 respectively.
1) Work includes muffing with smooth
cement mortar (1:6) finish.
2) Necessary sand, metal, water and cement
shall be supplied by the contractor.
Excavation in Hard Rock for excavation of
30 9901020007 earthing pits/11 KV or LT power cable cmt 100 525
trenches/Yard light poles only
Loading, Transporting & Unloading of all
material for 66 KV substation like Structure,
indoor & out door Equipments, DP
Structures, earthing materials, Battery set,
fire wedge, GI/MS Scrap, all other required
materials, etc in all respect for Substation &
opposite end feeder bay from Store(Any
store either Const. div. or R & M Store within
respective Zone) to Sub Station Site.
This job also includes crediting balance
materials at respective construction division
store at no extra cost.
Supply & laying of 1 Core X 25mm2,
Armroured Copper Cable multi-strand
flexible of approved make ISI marked in ready
made trench or PVC pipe from Battery
Charger to Battery Set including termination
at both side as per inst. of EIC.
Providing and fixing of various type of sign
Board, sticker, Big Sign Board, earthing pit
board, earthing pit Board & Single line
diagram etc as per instruction of IEC. Sticker
of red, white, black Letters are to be utilised
for various sign board.
Earthing Pit Board Size:- 6" x 6" -30 Nos.
Safety Slogan Board, Hard Sheet board size 2'
x 2'and 4mm thick (Gujarati Language)- 2 Nos.
Safety Slogan Board, Hard Sheet board size 3'
x 2'and 4mm thick (Gujarati Language) with
red and Yellow colour.-03 Nos.
Single line diagram size 5' x 3' Digital with
Alluminium frame with fitting and as per
approved diagram given by IEC.-01 No.
Big sign board size 5' x 4' and 2mm thickness
33 9901180046 indicating sub station name digital with S.S. Job 1 24957.00
rod with hole & as per approved symbol with
fitting charge.- 01 No.
Switch yard sign Board 12" X 6" with 2 mm
Thickness black & white Gujarati language.25
Safety Slogan Board size 2" x 6" in side control
Various type of control room equipment
sticker size-24 cms x 5cms.--18 Nos.
Safety picture board size :- 3' x 3' (Laminated
for O/D use)-03 Nos.
Name plate board of transformer size :- 2' x
Cable marker size:- 6" x 6", Radium, fixed on
750mm long M.S.Rod for fixing arrengement.-
P & F radium stiker for outdoor & indoor
equipment identification like LA ,Isolater,
Circuit breaker ,Transformer, CT, PT, MK Box
C&R panel ,11 kv Panel etc..
Providing and Fixing of fire stand from
75mm Gl pipe A Class ISI mark heavy duty
having 5ft width and 4ft height as per inst of
Engr. In charge
1) Work includes cutting,drilling, welding of
pipe as required. Fabrication and supply of
16mm dia meter hook size required for
2) 4 Nos.of fire buckets are to be provided
by the contractor. 3) Fire stand
should grouted with excavation of pit size
300mm x 300mm-2 Nos. of 600mm depth
with 1:3:6 mix muffing 300mm in height
including leveling of stand.
4) The fire stand is to be painted with post
box red colour of approval quality as per
instruction of EIC.
5) All required approved material including
cement, sand, metal etc are to be provided
Labour charge for fixing of 11KV XLPE Indoor
/ outdoor cable kit of any make for 11KV,
3C× 95 to 300 sq. mm. XLPE power cable.
Cable kit provided by GETCO.
Providing & Fixing of
RAYCEM/MSEAL/CABSEAL or equivalent
GETCo approved make heat shrinkable type
11KV XLPE indoor/Outdoor cable
Termination kit suitable for 11KV, 3C x
sqmm to 300 sq.mm XLPE power cable.
Providing & Fixing of Total Revival Type
Water R.O. Plant including Commissioning &
Testing and also with required peripherals
for installation of plant as per site condition
38 (2) Weight : 8 KG No 1 6889
(3) Water flow : 8 to 12 LPH
(4) Input power : 230V AC
(5) RO membrence : TFC spiral
You have to provide guarantee for the
months from installation
Providing and fixing of ISI marked Insulating
Mattysheet Suitable for 11KV Class As per
following specification.
Reference IS:15652-2006 with latest
amendment. Suitable
for Voltage Class :B
Max Use Voltage : 11KV
AC proof voltage : 22KV
Dielectric strength : 45KV
Leakage current : < 10 micro ampere
39 9902040903 Colur RED/BLUE sq.mtr 17 4492
Make : Vardhman or equivalent (
Rubberhouse India) Width
Thickness :2.5 mm.
Surface :Chequred on one side and other
side plain. NOTE:
Contractor has to supply Rubber Matty sheet
as per IS:15652-2006 with latest amendment
specification and shall submit test certificate
for routine test as per relevant IS
Providing & fixing of reputed make ISI mark
Fire Extinguisher with latest amendment in
standards as per following capacity . Note:
Contractor shall submit Test certificate for
40 routine test as per relevant IS.
9902040911 a) Chemical Powder 9 Kg No 2 6301
9902040916 d) Mechanical Foam Type : 50 Ltr No 1 14499
TOTAL: SCHEDULE B - 1
SCHEDULE B-2 : CONTROL WIRING
Description of work/Supply Unit Rate Amount
Preparing of complete schedule of wiring for
line/ transformer bays in triplicate.
necessary drawing will be provided by the
GETCO. Schedule should be approved by EE
or DE in charge.
a) 66 KV Bay 4 1996
Laying of 1.1KV PVC, armored copper/
aluminum control cable inside hume
pipe/cable trench including binding /
clamping of cable with GI wire or saddles as
per the requirement including the supply
and fixing of identification tags at both ends
and at distance of every 10 mtr of following
size.(Cable will be supplied by GETCO at free
mm2, 7C × 2.5 mm2, 4C × 4 mm2 Copper
control cable or any equivalent size of all LT
9902080038 Copper control cable 3.5 C or 4 C × 10 mm2, Mtr 2500 10
70 mm2 alluminium armoured or
unarmoured LT power cable.
Laying of 1.1KV PVC, armored copper/
aluminum cable in ground by digging trench
of suitable width and 450 mm depth in any
type of soil includingsupply and fixing of
identification tags at both ends and at
distance of every 10 mtr of following size.
43 mm2, 7C × 2.5 mm2, 4C × 4 mm2 Copper
control cable or any equivalent size of all LT
9902080025 Copper control cable 3.5 C or 4 C × 10 mm2, Mtr 150 26
70 mm2 alluminium armoured or
unarmoured LT power cable.
Providing and fixing 'B' class G.I. pipes of
following size for cable protection including
fixing with the structures.( Non SOR)
including required 'L' & 'T' band, coupling for
44 CT,PT, Transformer, M.K.Box cabling on
structure including required fabrication.
9902040142 {a} 40mm dia (weight of pipe-3.2kg/meter) Mtr 150 255
9902040142 {b} 50mm dia (weight of pipe-5.1kg/meter) Mtr 80 284
Termination of Control Cable at Panel / M.K./
Equipments including supply of required size
of double compression type metal glands,
45 lugs, ferrules, PVC Binding Tape, Buttons,
Cable ties etc for following size of cables.
9902990012 a) Up to 7 Core Control cables End 150 199
9902990011 b) As above but Above 7 Core Control Cable., End 100 349
Providing & Installation and Commissioning
of Remote Control switch Board for ON/OFF
control of all 11kv Panel from operator's table
with supply of good quality metal sheet box (
18 SWG )size 450 x 450 x 125 mm with door,
20 nos standard ISI make and rating industrial
push botton,indication lamp(LED)with
46 9902040065 installing accept/reset arrangement with Job 1 6489
required ISI marked copper flexible wire size
2.5 Sq. mm including complete wiring in PVC
pipe and fixing on wall or on floor as per inst.
of EIC.only 19/27 core x 2.5 sqmm cable
supply by GETCO.Job includes Supply of
required nos. of Disconnecting Type Terminal
for wiring at 11 kV Panel Board end
Providing and fixing of all weather proof, cold
rolled sheet steel Junction Box for CVT & PT,
CT terminations with 30 Nos. of disconnecting
47 9902990013 type, 'Elmex' make CATDM 4 or equivalent No 6 21549
type connectors and required no of fuses,
links etc.as per instruction of Engineer-in-
charge and as per drawing enclosed here with
TOTAL - 2 ( SCHEDULE B - 2 )
SCHEDULE B-3 : YARD LIGHTING
Description of work/Supply Unit Rate
Providing & fixing of all weather proof, cold
rolled sheet steel AC Panel - 2 for Yard-
Lighting, AC supply having
(1)63 A ,4P MCB : 01 NO
(2) MCX-12A Contactor : 01 NO
(3) Digital timer : 01 NO
(4) 20 A,TPN MCB : 06 NOs
(5) Indication Lamps, 03 NOS ( R , Y , B )
(6) Push Buttons : 02 Each ( Red & Green)
(7)Terminal Connectors as per site
requirement and
other detail as per drawing enclosed
including grouting & necessary fabrication of
GI Angle or fixing on GI Structure including
earthing with main grid as per instruction of
Providing & fixing of all weather proof, cold
rolled sheet floor mounted fixed type sinle
door grey color main AC Dist Box having size
900X600X250 MM with door closing
arrangement rubber gasket.
Contractor has to supply following materials
with box along with necessary mounting and
(1) L&T/Anchor/Havells Make 100A, 4P
MCCB - 1 Nos. (2)
L&T/Anchor/Havells Make 63A, 4P MCCB -
Nos. (3)100A Copper
Bus-bar link length 6 inch & 25X3mm - 4 nos.
(4) Tinned Earth Bus 25 X 3 MM length -32
Inch-1No. (5) 25 &
sqmm Cu. Flexible cable 4 & 8 mter
respectively. (6) Required nos. of
Cu. Lugs etc. as per instruction of EIC.
Supplying & laying of following size
Control/L.T power cable in readymade cable
trench or by excavating in any type of soil
cable trench size 300 mm wide 600 mm depth
and refilling the same as per the direction of
EIC. Item Includes the cable laying upto
termination box with clamps & proper
clamping of cable on gantries by GI pipe &
50 9902990006 glands as per direction. Item includes Mtr 120 292
providing & supply of bircks, sand as per
requirement. The L.T power cable to be
provided by contractor as under: ISI
(Part-I). 3.5 core × 50 mm2 Alluminium cable-
Armoured from distribution X'mer to Main
Distribution Board near dist. X'mer and from
MDB to indoor LT panel board (LTPB) - both
Supplying & laying of following size of
Control/L.T power cable of FINOLEX or
equivalent ISI mark in readymade cable
trench or by excavating in any type of soil
cable trench size 300mm wide and 600mm
depth and refilling the same as per the
direction of EIC. Item Includes the cable laying
up to termination box with clamps & proper
clamping of cable on gantries by GI pipe &
glands as per direction. Item includes
providing & fixing of bricks, sand as per
requirement to protect cables. The L.T power
cable to be provided by contractor as under
:As per ISI 1554 (Part-I). 4 Core x 25 mm2
Aluminum Cable-Armored from LT panel
board (LTPB) to Yard Light AC MK (AC Panel-
2)., AC Panel 1 in C.R. and yard AC Box
-- do -- 4C x 4mm2 Copper cable - Armoured,
from yard-light AC panel-2 to all yard-light
fixture junction boxes on LM & street light
pole & Station transformer to Colony & LT
52 9902080024 panel to watchman cabin. Mtr 600 19
Note: Cable laying work either in ready made
cable trench or by excavating in any type of
soil if required.(Only laying. Cable will be
supplied by GETCO)
-- do -- 4C x 2.5mm2 Copper cable -
Armoured, from yard-light AC panel-2 to all
junction boxes on post top lantern.
53 9902080024 Note: Cable laying work either in ready made Mtr 125 19
cable trench or by excavating in any type of
soil if required.(Only laying. Cable will be
supplied by GETCO)
Providing & fixing of 'B' class ISI marked GI.
Pipe of 32/40mm dia for cable looping & road
crossing with necessary elbow/band for each
54 9902990021 pole & J.Box for yard lighting & for Mtr 60 180
controlroom flud lights wiring work with
fixing on wall with shadles if required as per
Providing & erection of 7.0 Mtr. long swaged
type welded GI tubular street light poleon
the foundation in any type of soil as per inst.
Of E.I.C. confrirming to relevant IS and as per
attached Drawing No. GETCO/E/STD/LTG.
POLE-R2 Dt. 24-12-2019
Providing & erection of 4.5 Mtr. long swaged
type welded GI tubular street light poleon
the foundation in any type of soil as per inst.
Of E.I.C. confrirming to relevant IS and as per
attached Drawing No. GETCO/E/STD/LTG.
POLE-R2 Dt. 24-12-2019
Supply and fixing of Pole/Wall/Structure
mounted FRP junction box standard make of
required size with clamp, providing 1 SPN
MCB G class of 16 A having short ckt
breaking capacity of 10KA peak of standard
57 9902990013 ISI make like L&T/ANCHOR/MDS /HAVELLS & No 28 748
2 Nos. of stud type connector of standard
make like Connectwell. The cable glands &
lugs are ncluded for both incoming & out
going cables. MCBs shall be of standard
make like MDS/HAVELLS
Earthing to tubular pole/luminaries,by coil
type earthing of 10 SWG GI wire in earth pit
of 1.5 mtr. Depth in any type of solil by using
salt/ coke (charcole) 16 kgs each & remaining
filling with BC soil & clamping the earth wire
with pole & Junction box.
Providing and fixing of Single Piece Cast
Alluminium full frame with Acrylic Cover
integrated Energy Efficient flood light
luminaries on swaged pole / GI structure by
providing required fabrications, of
Philips/CGL/Bajaj/GE/Osram make, suitable
for 1 x 250 Watt HPSV/T with allied
accessories such as Capacitor Ignitor, Ballast,
Control Gear Box etc, 4 core 2.5 sq mm
double insulated flexible stranded wire
should be used from control gear fitting to
Providing & fixing of LED Street LightFixtures
(1x120w) (CGL Cat No. LSTO-120/CDL 120w or
Equivalant under cat- II or above as per R & B
60 9902040093 SOR) 4-core 2.5mm2 double insulated flexible No 8 9593
stranded wire should be used from control
gear fitting to approved SMC type junction
box as per inst. of EIC.
Providing & fixing of 1X 40 W LED Post Top
Lantern Fixtures (CGL Cat No. LSTO-40/CDL
40w or Equivalant under cat- II or above as
per R & B SOR) complete fitting in all respect
61 9902040070 and 4 core x 2.5 mm2 double PVC flexible No 7 7556
copper cable from control gear fitting to
SMC junction box as per instruction of EIC. (
4 No are to be provided on Main gate & 3 No
are to be provided on 4.5 Mtr Tubular pole
TOTAL - 3 ( SCHEDULE B - 3 )
SCHEDULE B-4 : CONTROL ROOM INDUSTRIAL ELECTRIFICATION
Description of work/Supply Unit Rate Amount
Providing and fixing of DBS as AC Panel -
for CR of ISI marked Powder coated Pearl
DBS of ivory color , wall mounting, Double
door Distribution board of L&T, Heggar or
higher make fitted with 63Amp Phase Bus
bar, Earth / Neutral Bars and inter
connecting wires with removable bottom
gland plates for all power cable entry from
bottom with DIN Channel ,incoming contact
and 1No - 63Amp TPN MCB 'C' Series ,6Nos-
20A SP MCB 'C' Series and 13No -10A SP
MCB 'C' Series All MCBs are L&T, Anchor or
Higher make only. Complete in all respect
and as per instruction of EIC.
Supplying & laying of following size of
Control/L.T power cable of FINOLEX or
equivalent ISI mark in readymade cable
trench or by excavating in any type of soil
cable trench size 300mm wide and 600mm
depth and refilling the same as per the
direction of EIC. Item Includes the cable
laying up to termination box with clamps &
proper clamping of cable on gantries by GI
pipe & glands as per direction. Item includes
providing & fixing of bricks, sand as per
requirement to protect cables. The L.T
power cable to be provided by contractor as
under :As per ISI 1554 (Part-I). 4 Core x
mm2 Aluminum Cable-Armored . From LTPB
to AC Panel 1 in C.R.
Supplying & Laying Sub-main lines of 3X2.5
mm2 ( two for P & N and one for
Earthing)copper PVC insulated wier of ISI
brand in suitable standard make steel
64 9902080098 conduit pipe having minimum 1.5 mm Rmtr 250 125
thickness of approved brand with ISI brand
with clmpes with it's associated accessories
for various circuits amanating from AC panel
1.as per inst. of E.I.C.
Point wiring for control room tube lights,
fans, exhaust fans, fency lights, water tight
bulck head lights with PVC insulated 660 V
grade standard copper wire in ISI make GI
conduct pipe 20 mm dia and 1.6 mm wall
thickness size fitted with sadles on the
wall/ceiling. Size of wire shall be with 3C x
1.5 sq.mm PVC insulated copper wire for
phase and neutral and earth wire [ Green]
and 5 Amp Anchor/Roma or any equivalent
65 9902980004 switch as per specification with 16 guage Point 60 1298
M.S. box. The box shall be covered with
mm thick decorative mat finish hylum sheet.
The work is all inclusive of supply and fixing
of required materials as afore said [ like
M.S.conduct pipe , sadles , swithces , M.S.
box , ceiling Rose , flexible copper wire etc]
to complete point wiring with each fixture to
be earthed by SWG-12 stranded copper
conductor having green color as per
direction and instructions of E.I.C.
Providing, fixing & termination for
emergency D.C. supply arrangement. This
job includes supply & laying of 2C x 2.5 mm2
Copper arrmoured cable from battery
charges to SBDC, fixing & providing SBDC &
complete wiring with supply of wire & D.C.
lamp (110V D.C., 100 watt-4 Nos.) in
standard steel conduit pipe.
Providing and Fixing point wiring in GI.
Conduit pipe size 20 mm dia and 1.6 mm
wall thickness with single PVC insulated
Sqmm. copper wire of ISI standard good
quality using 1.5mm thick suitable size ISI
mark Anchor brand 15 Amp. 250 Volt plug
67 9902980004 socket as separate plug point with shock Point 8 1213
proof accessories incl. indication lamp ;
erected on separate decorative mat finish
hylum sheet board on wall with providing
adequate green earthing wire as per
specification and instruction of Engineer
---- Do ---- as above but with singal PVC
insulated 3Cx1.5 sq. mm.copper wire of ISI
68 9902980003 mark plug socket for 5A domestic use Point 8 814
separate plug points per direction and
instruction of E.I.C.
---- Do ---- as above but looped on same
board i.e. no separate board, plug socket for
5A domestic use as per direction and
instruction of E.I.C.
Providing & Fixing of Ceiling Fan of 1400mm
BLDC type Bajaj/ Crompton / Orient/ usha /
Cinni make (ISI approved) flexible wiring by
using twin core double PVC 48/0.2 mm
copper flexible cord of suitable & approved
make and size from ceiling rose upto fan
terminal & supply and fixing of energy saver
regulators , extra GI pipe of required size and
length for lowering of fan if required as per
instruction of EIC.
Providing and fixing of 50W LED lighting
fixure( CGL Cat no LCTLR- 50-FO-CDL 50W of
Eqivivalant under cat - II or above as per R &
B SOR), 4-core 2.5mm2 double insulated
flexible stranded wire should be used from
control gear fitting to approved SMC type
junction box as per inst. of EIC. as per
instruction of EIC.
Providing and fixing of 41.5w LED lighting
fixtures (CGL Cat no LPFC-36-CDL- 41.5 W or
equivalent under cat- II or above as per R &
B SOR) as per instruction of EIC.
Providing and fixing of 40W (1X4) LED
lighting fixtures as per drawing (in office
73 9902980024 area) (CGL cat no LCTL-40-CDL- (1X4) 40W or No 2 3417
equivalent under cat- II or above as per R &
B SOR as per instruction of EIC.
Providing and fixing of 40W (1X4) LED
lighting fixtures as per drawing (in porch
74 9902980024 area) (CGL cat no LCTL-40-CDL- (1X4) 40W or No 2 3417
equivalent under cat- II or above as per R &
B SOR as per instruction of EIC.
Providing & fixing of industrial 30W LED
street light bulkhead (CGL Cat No LSTO -
30CDL-30W or Equivalent under Cat - II or
above as per R & B SOR) on outside C/R
building and inside cable trench in C/R
including wiring from ceiling rose to fixture
with suitable size of PVC insulated ISI marked
copper wire only as per Instruction of EIC.
Providing and fixing of heavy duty exhaust
fan in battery room size 18" of Make
GEC/KHAITAN/ CROMPTON/ BAJAJ incl. M.S.
lourex shutter of Fan & necessary wall
76 9902980012 finishing works and applying bird proof net No 1 3494
on outside wall with required arrangement
for rain water sealing and necessary
connection from ceiling rose as per direction
and instruction of EIC.
Providing earthing to Qurter with 10 SWG
copper earth wire connecting to required
installations. This work include preparation
of earth pit of size 0.5M x 1.5M depth and
back filling by using Solt, Charcoal 16 Kg.
Each. 2Mtr. Long heavy duty 19mm PVC
pipe and yellow/normal soil with C.I.
earthing plate of 10 Kg weight. as per inst. of
EIC. Required all material to be supplied by
Providing & Fixing of Electric bell with bell
78 9902980029 switch near officer's table. All materials must No 1 149
be ISI mark and approved by Engineer I/C
Providing and fixing of18W LED Lighting
fixture(CGL Cat No LCTL - CDL 18W or
79 9903190044 Equivalent under Cat - II or above as per R & No 3 1281
B SOR) of any standard ISI make and as per
instruction of EIC
TOTAL - 4 ( SCHEDULE B - 4 )
SCHEDULE -B 5-A : QUARTER RESIDENTIAL FURNITURE
Description of work/Supply Unit Rate Amount
P & F Steel table of size 54"X30"X30", one side
92 9900000003 three drawars, one side shelf 1 X 18 gauge No 1 8750
square pipe with Nova pan pre lamination top
P & F Steel rack of size 30" X 36" X 15" with
three partition, prepared with 20 gauges
P & F Steel chair 'S' type, Over hanging arm
94 9900000003 with cushion with cane seat/back 1" X 16" No 2 4600
gauge round pipe frame.
P & F Computer table made from pre
lamination Board size with Key Board facility
95 9900000003 and drawer with continues printer out facility No 1 7200
and mouse tray and also with special tray CPU
and UPS having I.D. 4 X 21 inch C 2.5 F.T.
P & F Steel revolving chair, revolving & titing,
low back high type seat with foam rubber 3"
in seat 2" in back with good quality raxine
cover, five legs, Chromium plated frame
P & F Steel cup board of size 78"X36"X19"
four partition, door and shelves 20 gauge,
body 22 gauge, color olive green as per
drawing attched
Total of Schedule (1 to 5) Rs
NET TOTAL Amount
NET TOTAL Amount
I we am / are willing to carry out the above work at_______________________________________ % above / below (percentage)
should be written in figures and words. ___________________________________________________________Percentage above /
below the tender amount work out Rs. ______________________________________________Rupees in
Signature of Contractor,
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
2026-27 53 HTC Tech Bid.pdf
2026-27 53 HTC Price Bid.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .