Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹64.8 LAccepted-AOC | L1 | Accepted-AOC Lowest | |
| 2 | L2₹71.0 L+₹6.1 L (9.39%)Rejected-Finance VILLAGE P O MANSIMBLE TEHSIL PALAMPUR DISTRICT KANGRA HP | KANGRA | HIMACHAL PRADESH | 175013 | L2 | Rejected-Finance Highest Amount | |
| 3 | L3₹72.8 L+₹7.8 L (12.1%)Rejected-Finance | L3 | Rejected-Finance Highest Amount |
Tender Value
₹75.2 L
EMD Value
₹1.1 L
Closing Date
15 Jun 2022, 11:00 amClosed
Er. Rahul Dhiman EE
JSV Division Nagrota Bagwan
Providing LWSS Luhna Mangrella in Tehsil Baroh Distt.KangraSH_Supply and Errection of Pumping machinery Laying jointing and testing of Rising main construction of Pump house cum chowkidar qtr at vill Garli
2022_HPIPH_61469_1
NGB-KNG01-773
Open Tender
Civil Works - Others
Item Rate
180 days
Nagrota Bagwan
Please refer Tender documents.
8 documents required · 8 mandatory
₹800
₹1.1 L
18 Jan 2023
6 Jun 2022
15 Jun 2022
6 Jun 2022
15 Jun 2022
6 Jun 2022
Amount
Supply of submersible pumping set of (KSB / Kalama/ Kirloskar/ Johnston/ Cromption/ BS) make conforming to IS; 5659-1970 latest suitable for lifting raw water (latest with uptodate ammendments) fitted with bronze impellers/ suitable alloy directly coupled to squirrell case electric induction motor of same make as (manufacurer standard) conforming to IS; 9283-1979 (latest with uptodate ammendments) and totally water proof for submersible duty, isolated from the pump by intermediate casing with double mechanical seal in oil chamber, grease packed lubricated bearings & provided with stainless steel thrust bearing plate to with stand vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor including water level guard,errection clamps,cable clips & depth gauge etc. The pump shall be suitable for operation on data given below:-
Total Head : 18.44 Mtrs
Discharge required from each pump. : 5.34 LPS
No. of pump required : 2.00 No. Set (one act stand by)
Location of the site of installation of machinery. : About 12 KM from Nagrota Bagwan.
The Altitude of installation. : The altitude of place is 878 mtrs above MSL
Type of current. : AC Three phase supply with frequency of 75 cycles/second
Rate Voltage : 415+ 10%
Type of water and its source : Raw water from S/Well
Charactristics of water. :
a)Ambient Temperature dig.c : 20 dig. C
b)Turbidity NTU :
c)Hardness260Mg/Ltrs(as CaCO3) : -
e)total solid Mg /Ltrs : -
f)Other : -
Depth of Sump well : -
LWL in Sump well : 870.00 mtrs.
Center line level of Pump : 869.00 mtrs
Discharge level of highest point : 881.50 mtrs
Static head in Mrs : 14.50 mtrs.
Length of R/Main : 90 mtrs.
Dia of Rising main : 80 mm (medium class)
No of working hours per day : 8 Hours
Limit of pump operation. : (-) 15 % (+) 10% of total head
R.P.M. of pumping set. 2900 RPM ( or to be specified by the tenderer)
Test run. : 8 Hours continueously for 7 days
Dia of Sump well : -
Supply , Installation, Testing and Commissioning of Star Delta Starter panel for Submersible pump made out of 16 Gauge sheet, powder coated dust and vermin proof, wall/base mounted and front opening door type with copper insulated wiring suitable to operate 2 Nos. pump of rating 5 HP through Star Delta Starter mechanism. Starter should be capable enough to handle the following faults like short circuit, over current, under current, over voltage, under voltage, dry run protection and phase loss with LED ON/OFF & TRIP indicators. Make: Aarmation Electric Private Limited/MAS/ELLES/Adlec/L & T and any other make approved state level Technical Committee JSV complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Star, Delta and Mains Power Contactors of required ratings as per type-2 co-ordination for 5 HP starter complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Voltage Protection device to protect panel from over voltage and under voltage complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Single phasing and phase reversal protection device to safeguard system from single phasing and phase reversal of the supply voltage complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc with RS 485 communication Make Aarmation Electric/MAS/Elle/L & T and any other make approved state level Technical Committee JSV complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Main incomer MCCB/MCB of suitable capacity of L&T / Schnieder/ABB make on the feeder for pumping set confirming to BIS 2516-1985 ( Latest edition) complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
LED On / Off & Trip indicator and push buttons, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Bus Bar, i.e.Bolt, insulator, etc. complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Surge supressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Control Transformer to provide a stable control volatge to safegaurd the control circuit of all the components from the voltage surges and spikes complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Providing & laying PVC insulated jointless, flat water proof 2.5mm² copper cable of Siemens/ Finolex/ Grandlay/Gloster make conforming to BIS:1554 (Part I) -1988 or latest with up to date ammendments of suitable size for the pump sets offered(one cable carrying all three phases) including all other electrical equipment /accessories such as thimbles ,flexible pipe, solder, nuts & bolts cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Providing and fixing of Kirloskar/Leader/Kilburn and any other make approved state level Technical Committee JSV Cast Iron double flanged Non Return valve (NRV) 80 mm dia PN-1.0 confirming to BIS-780-1984 (P-I) complete in all respect including all leads and lift as per the direction and to the entire satisfaction of Engineer-in-Charge.
Stage -2nd Supply of horizontal spindle,horizontal/radial split casing and suction (backpull out arrangement) single/ double / multistage centrifugal pumps or combination of pumps in series /parallel of KSB / Mather & Platt/ Jyoti /Kirloskar /BE /Maxflow/ Beaconweir Sabar make conforming to BIS: 1520-1980 (latestwith upto date ammendments) read with BIS: 9137-1978 (latest edition) suitable for lifting water of under mentioned charactristics with impellers of bronze/suitable alloy, priming funnels,casing ring & shaft sleeves of bronze/ suitable alloy, shaft of sutable steel grade with cast iron casing coupled directly through a flexible coupling on a common C.I. / Cast steel base plate (base plate to be from the principle manufacturer of pumping set) to slippering/squirrel cage screen protected drip proof electric induction motor of Kirlokar /NGEF/Crompton / Siemen /Jyoti /BHEL /GEC /ABB conforming to BIS: 325-1978 read read with BIS: 900-1968 (latest with upto date ammendments) It should include the cost of bearings, nuts & bolts,painting etc. and shall be suitable for operation as per data given below:-
Total Head : 264.47 Mtrs.
Discharge required from each pump. : 5.01 LPS
No. of pump required : 2.00 Set (One act as stand by)
Location of the site of installation of machinery :
The altitude of installation. : 900 mtrs above MSL.
Type of current. : AC three phase supply with freqduency of 75cycle per second.
Rate Voltage : 415V + 10%
Type of water and its source : Clear water.
Shaft level :
Level of discharge point : 1087.00
Static Head : 219.02
Charactristics of water. :
a)Ambient Temperature dig.c : 21 dig. C
b)Turbidity NTU :
c)Hardness260Mg/Ltrs(as CaCO3) : -
e)Total solid Mg /Ltrs : -
f)Other : -
Depth of well assembly : -
No. of working hours per day : 8 Hours.
Length of Rising main : 4500 Rmts.
Dia of Rising main : 100 mm (Medium class)
Limit of pump operation. : In the completem Range of (-)75% .
R.P.M. of pumping set. : 2900 RPM (or to be specified by the tenderer).
Test run. : 8 Hours contineously for 7 days.
Supply , Installation, Testing and Commissioning of Star Delta Starter panel for centrifugal pump made out of 16 Gauge sheet, powder coated dust and vermin proof, wall/base mounted and front opening door type with copper insulated wiring suitable to operate 2 Nos. pumps (1 working & 1 stand by) each of the rating 30 HP through Star Delta Starter mechanism. Starter should be capable enough to handle the following faults like short circuit, over current, under current, over voltage, under voltage, dry run protection and phase loss with LED ON/OFF & TRIP indicators. Make: Aarmation Electric Private Limited/MAS/ELLES/Adlec/L & T and any other make approved state level Technical Committee JSV complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Star, Delta and Mains Power Contactors of required ratings as per type-2 co-ordination for 30HP starter complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Voltage Protection device to protect panel from over voltage and under voltage complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Single phasing and phase reversal protection device to safeguard system from single phasing and phase reversal of the supply voltage complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc with RS 485 communication Make Aarmation Electric/MAS/Elle/L & T and any other make approved state level Technical Committee JSV complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Main incomer MCCB/MCB of suitable capacity of L&T / Schnieder/ABB make on the feeder for pumping set confirming to BIS 2516-1985 ( Latest edition) complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Individual Starter incomer MCCB/MCB of suitable capacity of L&T / Schnieder/ABB make on the feeder for pumping set confirming to BIS 2516-1985 ( Latest edition) complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
LED On / Off & Trip indicator and push buttons, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Bus Bar, i.e.Bolt, insulator, etc. complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Surge supressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Control Transformer to provide a stable control volatge to safegaurd the control circuit of all the components from the voltage surges and spikes complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Mini PLC (Programmable logic controller) with appropriate digital and analog inputs and outputs to give automatic command to Star Delta Starter Panel/ Energy Saving Variable Frequency Starter Panel Make Aarmation Electric/Bechoff Automation/Rockwell Automation/L & T and any other make approved state level Technical Committee JSV complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Electronic relay card 8 channel complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
SMPS 4.5 Amps to energise PLC system complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
HMI (Human Machine Interface) 7" display for Monitoring and Controlling of Centrifugal pumps Make: Aarmation Electric/Bechoff Automation/Roackwell/L & T and any other make approved state level Technical Committee JSV complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Control MCB for Automation System complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Level Sensor to indicate the water level of tank remotely complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Shielded Data Cable for Communication of Level Sensor with PLC complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Installation, Commissioning and Software Development complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Providing and fixing of Kirloskar/Leader/Kilburn and any other make approved state level Technical Committee JSV Cast Steel double flanged Sluice valve 100 mm dia ASA-300 confirming to BIS-1868/API-600 complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Providing and fixing of Kirloskar/Leader/Kilburn and any other make approved state level Technical Committee JSV Cast Steel double flanged Sluice valve 80 mm dia ASA-300 confirming to BIS-1868/API-600 complete in all respect including all leads and lift as per the direction and to the entire satisfaction of Engineer-in-Charge.
Providing and fixing of Kirloskar/Leader/Kilburn and any other make approved state level Technical Committee JSV Cast Steel double flanged Non Return valve (NRV) 80 mm dia ASA-300 confirming to BIS-1868/API-6D complete in all respect including all leads and lift as per the direction and to the entire satisfaction of Engineer-in-Charge.
Stage-3rd Supply of horizontal spindle,horizontal/radial split casing and suction (backpull out arrangement) single/ double / multistage centrifugal pumps or combination of pumps in series /parallel of KSB / Mather & Platt/ Jyoti /Kirloskar /BE /Maxflow/ Beaconweir Sabar make conforming to BIS: 1520-1980 (latestwith upto date ammendments) read with BIS: 9137-1978 (latest edition) suitable for lifting water of under mentioned charactristics with impellers of bronze/suitable alloy, priming funnels,casing ring & shaft sleeves of bronze/ suitable alloy, shaft of sutable steel grade with cast iron casing coupled directly through a flexible coupling on a common C.I. / Cast steel base plate (base plate to be from the principle manufacturer of pumping set) to slippering/squirrel cage screen protected drip proof electric induction motor of Kirlokar /NGEF/Crompton / Siemen /Jyoti /BHEL /GEC /ABB conforming to BIS: 325-1978 read read with BIS: 900-1968 (latest with upto date ammendments) It should include the cost of bearings, nuts & bolts,painting etc. and shall be suitable for operation as per data given below:-
Total Head : 252.93 Mtrs.
Discharge required from each pump. : 5.01 LPS
No. of pump required : 2.00 Set (One act as stand by)
Location of the site of installation of machinery :
The altitude of installation. : 900 mtrs above MSL.
Type of current. : AC three phase supply with freqduency of 75cycle per second.
Rate Voltage : 415V + 10%
Type of water and its source : Clear water.
Shaft level :
Level of discharge point : 1197.00
Static Head : 217.50
Charactristics of water. :
a)Ambient Temperature dig.c : 21 dig. C
b)Turbidity NTU :
c)Hardness260Mg/Ltrs(as CaCO3) : -
e)Total solid Mg /Ltrs : -
f)Other : -
Depth of well assembly : -
No. of working hours per day : 8 Hours.
Length of Rising main : 1160 Rmts.
Dia of Rising main : 80 mm (Medium class)
Limit of pump operation. : In the completem Range of (-)75% .
R.P.M. of pumping set. : 2900 RPM (or to be specified by the tenderer).
Test run. : 8 Hours contineously for 7 days.
Supply , Installation, Testing and Commissioning of Star Delta Starter panel for centrifugal pump made out of 16 Gauge sheet, powder coated dust and vermin proof, wall/base mounted and front opening door type with copper insulated wiring suitable to operate 2 Nos. pumps (1 working & 1 stand by) each of the rating 30 HP through Star Delta Starter mechanism. Starter should be capable enough to handle the following faults like short circuit, over current, under current, over voltage, under voltage, dry run protection and phase loss with LED ON/OFF & TRIP indicators. Make: Aarmation Electric Private Limited/MAS/ELLES/Adlec/L & T and any other make approved state level Technical Committee JSV complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Star, Delta and Mains Power Contactors of required ratings as per type-2 co-ordination for 30HP starter complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Voltage Protection device to protect panel from over voltage and under voltage complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Single phasing and phase reversal protection device to safeguard system from single phasing and phase reversal of the supply voltage complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc with RS 485 communication Make Aarmation Electric/MAS/Elle/L & T and any other make approved state level Technical Committee JSV complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Main incomer MCCB/MCB of suitable capacity of L&T / Schnieder/ABB make on the feeder for pumping set confirming to BIS 2516-1985 ( Latest edition) complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Individual Starter incomer MCCB/MCB of suitable capacity of L&T / Schnieder/ABB make on the feeder for pumping set confirming to BIS 2516-1985 ( Latest edition) complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
LED On / Off & Trip indicator and push buttons, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Bus Bar, i.e.Bolt, insulator, etc. complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Surge supressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Control Transformer to provide a stable control volatge to safegaurd the control circuit of all the components from the voltage surges and spikes complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Mini PLC (Programmable logic controller) with appropriate digital and analog inputs and outputs to give automatic command to Star Delta Starter Panel/ Energy Saving Variable Frequency Starter Panel Make Aarmation Electric/Bechoff Automation/Rockwell Automation/L & T and any other make approved state level Technical Committee JSV complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Electronic relay card 8 channel complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
SMPS 4.5 Amps to energise PLC system complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
HMI (Human Machine Interface) 7" display for Monitoring and Controlling of Centrifugal pumps Make: Aarmation Electric/Bechoff Automation/Roackwell/L & T and any other make approved state level Technical Committee JSV complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Control MCB for Automation System complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Level Sensor to indicate the water level of tank remotely complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Shielded Data Cable for Communication of Level Sensor with PLC complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Installation, Commissioning and Software Development complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Providing and fixing of Kirloskar/Leader/Kilburn and any other make approved state level Technical Committee JSV Cast Steel double flanged Sluice valve 80 mm dia ASA-300 confirming to BIS-1868/API-600 complete in all respect including all leads and lift as per the direction and to the entire satisfaction of Engineer-in-Charge.
Providing and fixing of Kirloskar/Leader/Kilburn and any other make approved state level Technical Committee JSV Cast Steel double flanged Sluice valve 65 mm dia ASA-300 confirming to BIS-1868/API-600 complete in all respect including all leads and lift as per the direction and to the entire satisfaction of Engineer-in-Charge.
Providing and fixing of Kirloskar/Leader/Kilburn and any other make approved state level Technical Committee JSV Cast Steel double flanged Non Return valve (NRV) 65 mm dia ASA-300 confirming to BIS-1868/API-6D complete in all respect including all leads and lift as per the direction and to the entire satisfaction of Engineer-in-Charge.
Excavation in foundation and trenches (for pipes and pits) up to all depths and in all clasification of earth work such as pick Work, jumper work, chiselling or Wedging out of soft and hard rock where the blasting work is prohibited saturated soil including pumping or bailing out water in all lifts including trimming and dressng of sides, levelling of beds to correct grade including shoring strutting planking timbering and dewatering where ever required. Stacking usable and unusable matrial/soil separetaly and after laying, jointing and testing of pipes (for pipes, pipe duct, chambers, x-signs etc.) returning the usable soil in 15 cm layers by ramming and wetering and then desposing of all surlus excavated soil/un usable material as directed wirhin all leads/lifts includng restoration of unmetalled surfaces to its original conditionn and includng cost of divresion for traffic, night signal boards, fixing custion boards, crossing over tranches for access to houses, fencing etc. complete in all respect as per the direction and to be entire of Engineer-in-Charge within all leads and lifts.
Laying, jointing & testing of bevelled ended GI pipe with circumfrential butt welded joints by electrical arc welding (welding thickness shall be equal to pipe wall thickness) and testing of GI pipe of Jindal/Surya Roshni/Tata/AST make of following dia meters conforming to IS 1239-1990 (Part-III), having wall thickness as specified below capable of withstanding required test pressure, including manufacturing and febrication of reducers/ tapers, all short pieces, bends etc. as per site requirement made from parent tubes. The laying of pipe shall also include welding of flanged joints wherever required duly welded in three layers (two inner & one outer) and all operations such as cutting, welding, jointing, fefurication of bends, tees, making bevelled pipe ends suitable for butt welding , lowering & laying in excavated trenches to ensure required level complete in all respects to the best satisfaction of the Engineer-in-charge (Earth work in trenches and the cost of providing flanges i/c nut & bolts, gasket will be measured and paid for separately). The fabricated bends shall have three or four cuts having its radius not less than five times the dia of pipe. The welding electrodes shall be as per IS 814 of Advani Oerlikon/ L&T or ISI marked make. The damaged portion of the pipes ( If damaged during laying & jointing operation of pipe) and all other specials made from the parent tube shall be provided with anticorrosive treatment by applying two coats of anticorrosive bituminous paint over a priming coat as per AWWA specifications C-203-1978. The rates also includes entire carriage of material, flushing, cleaning & hydraulic testing of pipes, D.P. test of butt welded joints complete in all respect and to the best satisfaction & direction of Engineer in charge with in all leads and lifts. (For the fire fighting providing and laying of pipes also included G.I. Nipple, Tee, Reducer, Bends, Union, Gass Weling etc.).
80mm dia (M-class), Stage 1st RD 0 to 90 = 90 Rmts. (Flange Table-5)
100mm dia (M-class), Stage 2nd RD 0 to 650 = 650 Rmts. (Flange Table-28)
100mm dia (M-class), Stage 2nd RD 650 to 1500 = 850 Rmts. (Flange Table-17)
100mm dia (M-class), Stage 2nd RD 1500 to 4500 = 3000 Rmts. (Flange Table- 5)
80mm dia (M-class), Stage 3rd RD 0 to 500 = 500 Rmts. (Flange Table-28)
80mm dia (M-class), Stage 3rd RD 500 to 1000 = 500 Rmts. (Flange Table-17)
80mm dia (M-class), Stage 3rd RD 1000 to 1160 = 160 Rmts. (Flange Table-5)
Providing MS flanges (In pairs) for the joints of GI pipes mentioned as below and same shall conform to BIS 6392-1971 ( latest with up to date amendments) including the cost of nuts and bolts of required sizes, 3mm thick compressed asbestos fiber/synthetic rubber gaskets conforming to relevant BIS standards and it shall also include carriage of materials within all leads and lifts complete in all respect to the best satisfaction and direction of Engineer in charge.
80mm dia (M-class), Stage 1st RD 0 to 90 = 90 Rmts. (Flange Table-5)
100mm dia (M-class), Stage 2nd RD 0 to 650 = 650 Rmts. (Flange Table-28)
100mm dia (M-class), Stage 2nd RD 650 to 1500 = 850 Rmts. (Flange Table-17)
100mm dia (M-class), Stage 2nd RD 1500 to 4500 = 3000 Rmts. (Flange Table- 5)
80mm dia (M-class), Stage 3rd RD 0 to 500 = 500 Rmts. (Flange Table-28)
80mm dia (M-class), Stage 3rd RD 500 to 1000 = 500 Rmts. (Flange Table-17)
80mm dia (M-class), Stage 3rd RD 1000 to 1160 = 160 Rmts. (Flange Table-5)
Providing and fixing of Kirloskar/Leader/Kilburn and any other make approved state level Technical Committee JSV Cast Steel double flanged Non Return valve / Sluice valve of following dia complete in all respect including all leads and lift as per the direction and to the entire satisfaction of Engineer-in-Charge.
80mm dia, Stage 1st
100mm dia, Stage 2nd
80mm dia, Stage 3rd
Providing and fixing of Kirloskar/Leader/Kilburn and any other make approved state level Technical Committee JSV Air valve 25mm dia complete in all respect including all leads and lift as per the direction and to the entire satisfaction of Engineer-in-Charge.
Excavation in foundation trenches etc. in earth work in all kinds of soil such as pick Work, jumper work, blasting hard or softs rock by chiselling where the blasting work is prohibited slushy daldal and saturated soil including pumping or bailing out water within all heights, stacking the excavated soil within all leads clear from the edge of excavation and then returning the stacked soil in 15Cm (fifteen Centimetres) layer when required into plinths, sides of foundation consolidating each depossited layer by ramming and watering and then disposing of all surplus excavated earth complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Excavation in drains and channels etc. in earth work including dressing of side and bed and disposing of excavated earth upto a lead of 20 metres and lift upto 1.50 metres disposed earth to be levelled and neatly dressed- Pick Work/jumper work complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Providing and laying cement concrete 1:3:6 (1 cement: 3 sand: 6 graded broken/crushed stone aggregate 20mm (twenty millimeters nominal size) mechanically mixed and curing complete, excluding cost of form work in foundation and plinth complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Providing and laying cement concrete 1:6:12 (One cement: Six sand: Twelve graded broken/crushed stone aggregate 40mm(forty millimeters nominal size) mechanically mixed and curing complete, excluding cost of form work in foundation and plinth complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Random rubble masonary/polygonal rubble masonry (uncoursed/brought to courses) with hard stone of approved quality in foundation and plinth including levelling up with cement concrete 1:6:12 (1 Cement: 6 Sand:12 graded stone aggregate 20mm nominal size) and plinth level in cement mortor 1:6 (1 cement:6 Sand) complete in all respect including all leads and lifts as per the direction and to the entire satiscation of Engineer-in-Charge.
Squared rubble masonary coursed with hard stone of approved quality in foundation and plinth including racking out joints in cement mortar 1:6 (1 Cement :6 Sand) complete in all respect as per direction and to the entire satisfaction of Engineer- in- charge up to all leads and lifts.
Brick work using common burnt clay building bricks in supper structure above plinth level upto floor two level in Cement Mortor 1:6 (1cement: 6sand) with 1st class bricks complete in all respect as per direction and to the entire satisfaction of Engineer- in- charge up to all leads and lifts.
Half Brick work using common burnt clay building bricks in super structure above plinth level upto floor two level in C.M 1:4 (1cement:4sand) complete excluding the cost of form work complete in all respect as per the direction and to the entire satisfaction of Engineer-In-Charge with in all leads and Lifts. (2nd class).
Providing form work with steel plates 3.15 mm thick welded with angle iron in frame 30x30x5mm so as to give a fair finish including centring, shuttering, and propping etc. with wooden batterns & ballies, height of propping and centring below supporting floor to ceiling not exceeding 4mtrs.and removal of the same for in-situ-reinforced concrete and plain concrete work in:
Flat surfaces such as soffits and suspended floors, roofs landing and the like floors etc upto 200mm in thickness complete in all respect within all leads and lifts as per the direction and to the entire satisfaction of Engineer-in-Charge.
Vertical surfaces such as walls (any thickness) partitions buttresses plinth and string courses and the like complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Providing and Laying cement concrete 1:1½:3 (1 Cement:1½ Sand:3 graded stone aggregate 20mm nominal size) and curing complete excluding the cost of form work and reinforcement for reinforced concrete work in :-
Suspended floors, roofs landing and shelves and their support balconies, beams, girders, bressumers and cantilever upto floor two level complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
In walls any thickness (but not less than 0.10mm thickness) including attached buttersses pillaster plinth and string courses etc. from top of foundation level upto floor two level complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Providing and Laying Mild steel /Tor steel reinforcement for RCC work including bending, binding and placing in position complete upto floor two level (tor steel) complete in all respect including all leads and Lifts as per the direction and to the entire satisfaction of Engineer-In-Charge.
Providing wood work in frames of door, windows, clearstorey windows and other frames wrought, framed and fixed in position in 2nd Class deodar wood as per the direction of Engineer-in-Charge with in all leads and lifts.
Providing and fixing panelled, glazed or panelled and glazed shutters for doors, windows and clearstorey windows including black enamelled iron but hings with necessary screws 40mm thick in 2nd class Deodar wood complete in all respect as per the direction and to the entire satisfaction of Engineer-in-Charge within all leads and lifts.
6mm thick cement plaster to ceiling in CM 1:3 (1cement:3 sand) complete in all respect as per direction and to the entire satisfaction of Engineer- in- charge within all leads and lifts.
15mm cement plaster in single coat on rough side of brick/ concrete /stone walls for interior plastering upto floor two level including arrises, internal rounded angles, chamfers and/or rounded angles not exceeding 80mm in girth and finished even and smooth in cement mortar 1:6(1cement:6sand) complete in all respect as per direction and to the entire satisfaction of Engineer- in- charge up to all leads and lifts.
20mm thick cement plaster in single coat on rough side of brick/stone masonary for interior plastering upto floor two level including arrises internal rounded angle chamber and orrounded angles not exceeding 80mm in girth and finished even and smooth in Cement Mortor 1:6 (1 Cement: 6 Sand) complete in all respect as per direction and to the entire satisfaction of Engineer- in- charge up to all leads and lifts.
Providing and fixing chequrred tiles 20 mm thick of reputed make with marble chips of specified size laid in floor. Tread of steps landing on a bed of 25 mm average thickness cement mortor 1:6 (1 cement :6 sand) jointed with neets cement slurry mixed with pigment to make the tiles including in rubbing and polishing complete as per the direction of Engineer-in-Charge with in all leads and lifts.
Providing and fixing M.S. grills of required pattern in wooden frames of windows etc. with M. S. flats square or round bars with round headed bolts and nuts or by screws plain grills complete in all respect as per direction and to the entire satisfaction of Engineer- in- charge up to all leads and lifts.
White washing with lime on celing / sloping un-decorated wall surface Two coats to give an even shade including throughly brooming the surface to remove all dirt, dust and other foreign matter as per the direction of Engineer-in-Charge with in all leads and lifts.
Distempering with dry distemper of approved brand and manufacture (two coats) and of required shade on undecorated wall surfaces to given an even shade sand papered smooth complete in all respect as per the direction and to the entire satisfication of Engineer-in-Charge with in all leads and lifts.
Applying priming coat over new wood and wood based surfaces after and including preparing the surface by thoroughly cleaning oil grease dirt and other foreign matter, sand papering & knotting ready mixed paint brushing wood primer pink complete in all respect as per the direction of Engineer-in-Charge with in all leads and lifts.
Painting two coats (excluding priming coat) on new wood and wood based surfaces ready mixed paint brushing to give an even shade including cleaning of all dirt, dust and other foreign matter sand papering and slopping with ready mixed paint other than white complete in all respect as per the direction of Engineer-in-Charge with in all leads and lifts.
Applying priming coat over new steel & other metal surfaces after & including preparing the surface by thoroughly cleaning oil grease dirt and other foreign matter and scoured with wire brushes fine steel wool scrapers and sand paper complete in all respect as per the direction of Engineer-in-Charge with in all leads and lifts.
Painting two coats (excluding priming coat) on new steel and steel based & other metal surfaces under coat of ready mixed paint brushing to give an even shade including cleaning of all dirts, dust and slopping in with paint others than white complete in all respect as per the direction of Engineer-in-Charge with in all leads and lifts.
Pointing on brick work with cement mortor 1:3 (1 cement : 3 sand) (raised and cut) complete in all respect as per the direction and to the entire satisfaction of Engineer-in-Charge with in all leads and lifts.
Providing plinth protection 50mm thick in cement concrete 1:3:6 (1cement:3sand:6 stone aggregate 20mm nominal size) complete in all respect as per the direction and to the entire satisfaction of Engineer-In-Charge within all leads and Lifts.
Providing and Fixing MS Tower bolts (barrel type) anodised transparent with necessary screws etc. complete in all respect as per the direction and Satisfaction of Engineer-in-Charge with in all leads and lifts.
Providing and Fixing MS handles anodized transparent or dyed to required colour or shade with necessary screw etc. complete in all respect as per the direction and Satisfaction of Engineer-in-Charge with in all leads and lifts. (125 mm)
Providing and fixing of MS sliding door bolts anodized transparent or dyed to required colour and shade with bolts and nuts screws etc complete in all respect as per the direction and Satisfaction of Engineer-in-Charge with in all leads and lifts. (300 X 16 mm)
Providing and fixing of MS Fan Clamp type -1 of 16 mm dia M.S. bar bent to shape with hooked ends in RCC slab during laying including painting the exposed portion of loop as per standared desgin complete in all respect as per the direction of Engineer-in-Charge with in all leads and lifts.
Providing, Installation, Testing and commissioning of celling fan with regulator, including wiring the down rods of standard length (upto 30 cm) with 16/0.20 mm twin twisted flexible, cotton braided, copper cable, including providing and fixing phenolic laminated sheet cover on the fan box and earthing etc. complete in all respect as per the direction of Engineer-in-Charge with in all leads and lifts. (Celling fan 1200 mm sweep, Catagory -A). Make:- USHA/ Crompt/ Havells)
SANJAY SAINI
Saurabh Vasudeva
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .