Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance AIMANATHU CHANGANASSERY KURICHY P O KOTTAYAM | CHANGANASSERY | KOTTAYAM | KERALA | Admitted-Finance |
| 4 | Admitted-Finance JAMMU AND KASHMIR JAMMU AND KASHMIR | JAMMU | JAMMU AND KASHMIR | 181122 | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹35,928
Closing Date
5 Dec 2024, 3:00 pmClosed
XEN JAL SHAKTI PHE MECHANICAL DIVISION UDHAMPUR
UDHAMPUR
Improvement of electric sub-station by providing, fitting, installation, testing and commissioning of 630 KVA electric transformer alongwith allied works at pumping station Baryal.
2024_PHE_264585_1
ENIT NO. 55 OF 2024-25
Open Tender
Repair and Maintenance Services
Item Rate
90 days
XEN JAL SHAKTI PHE MECHANICAL DIVISION UDHAMPUR
Improvement of electric sub-station by providing, fitting, installation, testing and commissioning of 630 KVA electric transformer alongwith allied works at pumping station Baryal.
9 documents required · 9 mandatory
₹1,000
Yes
XEN JAL SHAKTI PHE MECHANICAL DIVISION UDHAMPUR
₹35,928
Yes
7 Dec 2024
14 Nov 2024
6 Dec 2024
14 Nov 2024
5 Dec 2024
14 Nov 2024
Amount
Providing, installation, testing and commissioning of 11/0.433-0.250 KV;630 KVA;50Hz, Copper wound Distribution Transformer of latest Energy Efficiency Level-2 (New), IS1180 Part-I; 2014 as per latest upto date amendment with externally fitted MCCB with cable box and 4x4 Mtrs. Suitable cable of ratings by way of shifting the old and wornout transformer to storage side. Providing and shifting of new 630 KVA electrical transformer to site by load carrier and placing the new transformer on concrete platform with the help of crane. Making of electrical connections with the existing circuit of sub-station with proper thimbling and insulation of cables after cutting HT power supply. Replacing the old and wornout conductor / insulators of sub-station. Restoring the HT power supply and testing of 630 KVA electric transformer on no load for at-least 6 hours and then on full load. Complete job includes cost of material, labour charges, skilled and unskilled charges for installation, testing and commissioning.
M/S D.K TRADERS (BID ID -2266566)
SUNIL KUMAR SURI CONTRACTOR (BID ID -2250304)
ROYAL ENGINEERS AND CONTRACTORS (BID ID -2272198)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .