Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹29.2 LAccepted-AOC AMBAGAN TEZPUR TOWN PO PS TEZPUR DIST SONITPUR ASSAM | SONITPUR | ASSAM | 784001 | L1 | Accepted-AOC BEING LOWEST | |
| 2 | L2₹32.2 L+₹1.8 L (5.98%)Rejected-Finance RANGAPARA TOWN WARD NO 1 PS PO RANGAPARA DIST SONITPUR ASSAM | L2 | Rejected-Finance NOT BEING LOWEST | |
| 3 | L3₹32.5 L+₹2.1 L (6.75%)Rejected-Finance | L3 | Rejected-Finance NOT BEING LOWEST | |
| 4 | L4₹33.5 L+₹3.1 L (10.1%)Rejected-Finance P O P S MISSAMARI DIST SONITPUR ASSAM 784506 | SONITPUR | ASSAM | 784506 | L4 | Rejected-Finance NOT BEING LOWEST |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
3 Jul 2021, 6:00 pmClosed
GE MISAMARI
PO-Missamari Dist-Sonitpur Assam
REPAIR/MAINTENANCE OF LT OH LINE INCLUDING LT PANEL AND CONNECTED WORKS AT SOUTH OF RAILWAY LINE UNDER GE MISAMARI
2021_MES_449201_1
8179
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE MISAMARI
PLEASE REFER TENDER DOCUMENTS
2 documents required · 2 mandatory
₹500
Yes
GE MISAMARI
₹80,000
Yes
28 Jul 2021
7 Jun 2021
5 Jul 2021
7 Jun 2021
3 Jul 2021
21 Jun 2021
7 Jun 2021 - 14 Jun 2021
Amount
Excavation in trenches not exc 1.50 Metre wide and not exc 1.50 Metre depth for laying of UG Cable/Pole/Stays etc getting out in Soft/Loose Soil, complete all as specified and as directed.
Excavating in trenches, not exc. 1.50 Metre wide and exc. 1.50 Metre but not exc. 3.00 Metre in depth, for Foundation of Poles/ Stays, etc. and getting out in Soft/ Loose Soil, complete all as specified and as directed.
Returning, Filling in including Spreading, Leveling, Watering and Well Ramming in layers not exc. 25 Cm thick in Soils, complete all as specified and as directed.
Removing Surplus Soil to a distance not exc 50.00 Metre away and depositing where directed at a level not exc 1.50 Metre above the Starting Point, complete all as specified and as directed.
M & L Sand Cushioning (dry) in trenches/ducts for protection of UG Cables (below, above and around the UG Cable laid in Trenches) of 23 Cm Spread thickness (8 Cm in depth before laying the Cable and 15 Cm in depth after laying the Cable) and consolidated (punned) upto 180 mm thickness, complete all as specified and as directed. Note : For the purpose of Payment, Punned thickness of Sand Cushioning only shall be measured and paid for.
S & F Sub-Class ‘B’ Brick, well burnt, laid breadthwise along the length of Cable laid in trenches over Sand Cushion laid for UG Cable Protection, complete all as specified and as directed.
Dismantling unserviceable LT Poles of any description and any size including demolition of Cement Concrete (as/if required) and made good disturbed Ground complete all as specified and as directed. Note : Unsv Poles will be dismantled at Ground Level and disturbed ground will made good as directed for which Earthwork, demolition of Cement Concrete, etc. will not be measured and paid separately.
Dismantling Cross-Arms of Mild Steel Channel or Angle Sections, etc, including Mild Steel Bolts, Nuts, Washers, etc., complete all as specified and as directed.
Dismantling Insulators like Pin type, Shackle type from existing Electric Poles of any description and any size, seggregating Seviceable Insulators and keep in safe custody for re-use, complete all as specified and as directed.
Dismantling ACSR or AAC Conductors from the Disturbed Span including Line Spacer, etc., complete all as specified and as directed.
Dismantling Earth Wire, Cradle Guarding etc, complete all as specified and as directed.
Taking down/out unserviceable UG Cables of any Cross Sectional Area and Connections and joints including Pipes, Bricks, etc of any description laying in trenches or fixing with Walls/Poles, segreating serviceable Pipes, Cables etc and keep in safe custody for reuse, complete all as specified and as directed. Note : Earthwork will be measured and paid under appropriate Items.
M&L Cement Concrete 1:4:8 type D-2 (40mm graded aggregate) as Lean Concrete in Foundation of Poles, Stay Assembly, etc., including Form-work (as/if required), complete all as specified and as directed.
M&L Cement Concrete 1:3:6 type C-2 (40mm graded aggregate) as in Foundation of Poles, Stays, etc. including Formwork (as/if required) complete all as specified and as directed.
M&L Cement Concrete 1:2:4 tpe B-1 (20mm graded aggregate) as in Coping of Poles, etc. and finishing the Concrete surfaces Fair and Even including necessary Formwork required at Site(s), complete all as specified and as directed.
Supply & Erecting Steel Tubular Swaged Pole Type 410-SP-31 (9.0 Metre long) including Cast Iron Base Plate, Finial Taper Plug, Cap, Mild Steel Bolts, Nuts, Screws including applying two coats of Black Bituminous Paint Internally and Externally from bottom End of Pole upto PCC Coping and applying with two coats of Aluminium Painting over a coat of Red oxide Primer (Externally from Top of Coping) complete all as specified and as directed. Note : Earthwork, Cement Concrete, etc. will be measured and paid under approprite Items.
M & L Stay Assembly complete with Accessories as show in Electrical Plate No. 1 of MES Schedule Part-I, diameter of Stay Rod 16mm, size of Plate 230 x 230 x 6 mm complete all as specified and as directed. Note : Earthwork, Cement Concrete, Mild Steel Stay Clamps with Bolts, Nuts, Stay Strand, Loop Insulator etc. will be measured and paid under approprite Items.
Dismantling unserviceable stay assembly of LT Pole complete all as specified and as directed.Note : Unsv Stay assembly will be dismantled at Ground Level and disturbed ground will made good as directed for which Earthwork, demolition of Cement Concrete, etc. will not be measured and paid separately.
M&L Cross-arms, Bracings, Supports, Clamps and Back Plates fabricated from Structural Steel Sections including Nuts, Bolts, Washer, welding, bending cold or hot, drilling holes for Bolts, in any shape or size as indicated/ directed and inclusive of one coat of Aluminium Primer one Under Coat and One Finishing Coat of Aluminium Paint, complete all as specified and as directed.
Refixing only Cross-arms, Bracings, Supports, Clamps and Back Plates (serviceable materials i.e. Structural Steel Sections obtained from Item No. 8 here-in-before) including Nuts, Bolts, Washer, welding, bending cold or hot, drilling holes for Bolts, in any shape or size as indicated/ directed and inclusive of one coat of Aluminium Primer one Under Coat and One Finishing Coat of Aluminium Paint, complete all as specified and as directed.
S&F Insulator Pin type Porcelain, Vitreous, White, Brown or Green including one Galvanised Mild Steel Spindle, Two Galvanised Iron Washers and One Galvanised Iron Nut, 100mm Height, 65mm dia for 1100 Volt grade complete all as specified and as directed.
Fixing only Insulator Pin type Porcelain, Vitreous including one Galvanised Mild Steel Spindle Two Galvanised Iron Washers and One Galvanised Iron Nut, 100mm Height, 65mm dia for 1100 Volt grade (Serviceable Insulator obtained from Item No. 9 here-in- before) complete all as specified and as directed.
S & F Shackle type, Porcelain, Vitreous, White or Brown Insulator of size 100mm height 115mm dia including Galvanised Mild Steel 31x5mm Strap, 14mm dia Insulator Bolts, Nuts, Washers, etc. for Working Pressure 1100 Volt, complete all as specified and as directed.
Fixing only Shackle type Porcelain, Vitreous of size 100mm height 115mm dia including Galvanised Mild Steel 31x5mm Strap, 14mm dia Insulator Bolts, Nuts, Washers, etc. for Working Pressure 1100 Volt grade (Serviceable Insulator obtained from Item No. 9 here-in-before), complete all as specified and as directed.
S & F Loop Type Insulator Vitreous White, Brown or Green, large size with overall dimensions 90x65mm, clearance of hole 16mm dia, complete all as specified and as directed.
S & F Aluminium Conductor Steel Reinforced (ACSR) (sizes as ordered) with permissible Sags and providing Jumper, etc., fixing on Electric Poles and binding to Insulators with Aluminium Binding Wire as in OH Conductors including stringing, tightening, etc., complete all as specified and as directed. Note : Cost of Binding Wire is deemed to be included in the quoted Unit Rate.
Labour only for Releasing ACSR Conductor of existing OH Lines by un-binding from Insulator of any description, re-fixing after stretching, re-stringing the Conductor, removing excess Sag, maintaining proper distance between Conductors as ordered, and binding to insulators with Aluminium Binding Wire complete all as specified and as directed. Note : Cost of Binding Wire is deemed to be included in the Quoted Unit Rate.
S & F Galvanised Steel Wire 3.15 or 4.0mm dia as Earth Continuity Conductor and fixed to Pole, binding with Aluminium Binding Wire, complete all as specified and as directed. Note : Cost of Binding Wire will deem to be included in the Quoted Unit Rate.
S & F Cradles, hexagonal/rectangular fabricated with Galvanised Steel Wire with 4.00mm dia including binding with Aluminium Binding Wire, complete all as specified and as directed. Note : Cost of Binding Wire is deemed to be included in the Quoted Unit Rate.
S & F PVC/ Fibre Separator for LT Lines 1100 Volts OH Conductor 2 Wire system for horizontal spacing of Conductor, fixing with Nuts, Bolts, Washers, etc , including taking old unserviceable one. complete all as specified and as directed.
S & F PVC/ Fibre Separator for LT Lines 1100 Volts OH Conductor 4 Wire system for horizontal spacing of Conductor, fixing with Nuts, Bolts, Washers, etc.,including taking down old unserviceable one. complete all as specified and as directed.
Supply and laying and testing LT UG Cable XLPE insulated screened , PVC bedded, Galvanised steel strip or wire armoured, electric power cables (heavy duty 1100 Volts Grade with stranded aluminium conductor of size 25 sqmm 4 core laid in trenches/ surface of Wall/in GI Pipe along with Pole for connection to OH Lines etc. complete all as specified and as directed. Note : (a) Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items. Make :- Polycab/ havells/Gloster
Supply and laying and testing LT UG Cable XLPE insulated screened , PVC bedded, Galvanised steel strip or wire armoured, electric power cables (heavy duty 1100 Volts Grade with stranded aluminium conductor of size 35 sqmm 3.5 core laid in trenches/ surface of Wall/in GI Pipe along with Pole for connection to OH Lines etc. complete all as specified and as directed. Note : (a) Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items. Make :- Polycab/ havells/Gloster
Supply and laying and testing LT UG Cable XLPE insulated screened , PVC bedded, Galvanised steel strip or wire armoured, electric power cables (heavy duty 1100 Volts Grade with stranded aluminium conductor of size 50 sqmm 3.5 core laid in trenches/ surface of Wall/in GI Pipe along with Pole for connection to OH Lines etc. complete all as specified and as directed. Note : (a) Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items. Make :- Polycab/ havells/Gloster
Supply and laying and testing LT UG Cable XLPE insulated screened , PVC bedded, Galvanised steel strip or wire armoured, electric power cables (heavy duty 1100 Volts Grade with stranded aluminium conductor of size 70 sqmm 3.5 core laid in trenches/ surface of Wall/in GI Pipe along with Pole for connection to OH Lines etc. complete all as specified and as directed. Note : (a) Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items. Make :- Polycab/ havells/Gloster
Supply and laying and testing LT UG Cable XLPE insulated screened , PVC bedded, Galvanised steel strip or wire armoured, electric power cables (heavy duty 1100 Volts Grade with stranded aluminium conductor of size 95 sqmm 3.5 core laid in trenches/ surface of Wall/in GI Pipe along with Pole for connection to OH Lines etc. complete all as specified and as directed. Note : (a) Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items. Make :- Polycab/ havells/Gloster
Supply and laying and testing LT UG Cable XLPE insulated screened , PVC bedded, Galvanised steel strip or wire armoured, electric power cables (heavy duty 1100 Volts Grade with stranded aluminium conductor of size 120 sqmm 3.5 core laid in trenches/ surface of Wall/in GI Pipe along with Pole for connection to OH Lines etc. complete all as specified and as directed. Note : (a) Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items. Make :- Polycab/ havells/Gloster
Supply and laying and testing LT UG Cable XLPE insulated screened , PVC bedded, Galvanised steel strip or wire armoured, electric power cables (heavy duty 1100 Volts Grade with stranded aluminium conductor of size 150 sqmm 3.5 core laid in trenches/ surface of Wall/in GI Pipe along with Pole for connection to OH Lines etc. complete all as specified and as directed. Note : (a) Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items. Make :- Polycab/ havells/Gloster
Supply and laying and testing LT UG Cable XLPE insulated screened , PVC bedded, Galvanised steel strip or wire armoured, electric power cables (heavy duty 1100 Volts Grade with stranded aluminium conductor of size 185 sqmm 3.5 core laid in trenches/ surface of Wall/in GI Pipe along with Pole for connection to OH Lines etc. complete all as specified and as directed. Note : (a) Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items. Make :- Polycab/ havells/Gloster
Supply and laying and testing LT UG Cable XLPE insulated screened , PVC bedded, Galvanised steel strip or wire armoured, electric power cables (heavy duty 1100 Volts Grade with stranded aluminium conductor of size 240 sqmm 3.5 core laid in trenches/ surface of Wall/in GI Pipe along with Pole for connection to OH Lines etc. complete all as specified and as directed. Note : (a) Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items. Make :- Polycab/ havells/Gloster
Supply and laying and testing LT UG Cable XLPE insulated screened , PVC bedded, Galvanised steel strip or wire armoured, electric power cables (heavy duty 1100 Volts Grade with stranded aluminium conductor of size 300 sqmm 3.5 core laid in trenches/ surface of Wall/in GI Pipe along with Pole for connection to OH Lines etc. complete all as specified and as directed. Note : (a) Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items. Make :- Polycab/ havells/Gloster
Supply and laying and testing LT UG Cable XLPE insulated screened , PVC bedded, Galvanised steel strip or wire armoured, electric power cables (heavy duty 1100 Volts Grade with stranded aluminium conductor of size 400 sqmm 3.5 core laid in trenches/ surface of Wall/in GI Pipe along with Pole for connection to OH Lines etc. complete all as specified and as directed. Note : (a) Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items. Make :- Polycab/ havells/Gloster
Re-laying only LT UG Cable of size 25 sqmm / 35 sqmm (serviceable Cable obtained from Item No. 12 here-in-before), laid in trenches/ surface of Wall/in GI Pipe along with Pole for connection to OH Lines etc. and Testing complete all as specified and as directed. Note : (a) Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items.
Re-laying only LT UG Cable of size 95 Sqmm (serviceable Cable obtained from Item No. 12 here-in-before), laid in trenches/ surface of Wall/in GI Pipe along with Pole for connection to OH Lines etc. and Testing complete all as specified and as directed. Note : (a) Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items.
S & F Galvanised Iron Pipe light grade of size 50 mm dia as in protection of UG Cable laid in trenches of following sizes complete all as specified and as directed. Note : Cost of Mild Steel Clamp, Nuts, Bolts and painting is deemed to be included in the Quoted Unit Rate.
S & F Galvanised Iron Pipe light grade of size 80 mm dia as in protection of UG Cable laid in trenches of following sizes complete all as specified and as directed. Note : Cost of Mild Steel Clamp, Nuts, Bolts and painting is deemed to be included in the Quoted Unit Rate.
S & F Galvanised Iron Pipe light grade of size 40 mm dia as in protection of UG Cable laid in trenches of following sizes complete all as specified and as directed. Note : Cost of Mild Steel Clamp, Nuts, Bolts and painting is deemed to be included in the Quoted Unit Rate.
M & L preparing old painted surfaces by scraping and removing old paints, rust, etc. from steel tubular Pole of 09 mtr (above the Planting Depth and PCC Copings) and Mild Steel Cross Arms, etc. and applying Two Coats of Synthetic Enamel Painting in alternate Yellow & Black Strips Painting (4 No. Each Strip 200 mm wide) from above coping and remaining portion of Pole treated with Two Coats of Aluminum paint and Mild Steel Cross Arms, etc. treated with Two Coats of Aluminium Paint complete all as specified and as directed.
M & L preparing old painted surfaces by scraping and removing old paints, rust, etc. from Pre-stressed Concrete of 09 mtr (above the Planting Depth and PCC Copings) and Mild Steel Cross Arms, etc. and applying Two Coats of Synthetic Enamel Painting in alternate Yellow & Black Strips Painting (4 No. Each Strip 200 mm wide) from above coping and remaining portion of Pole treated with Two Coats of Exterior Weather Proof Paint and Mild Steel Cross Arms, etc. treated with Two Coats of Aluminium Paint complete all as specified and as directed.
M & L Writing Letter on Steel Tubular/Pre-stressed Concrete Pole (8 Cm in height) with Synthetic Enamel Paint (White) on base of Black Paint in round shape of 15 Cm dia, complete all as specified and as directed.
Trimming of Tree Branches upto 3.00 Metres around the OH Electric Lines, removing the trimmed Branches from Site and stacking as ordered, complete all as specified and as directed by engr in charge.
Cutting unaxious green growth and wild grass by manual labour or by machine at Electrical Installation Premises, around Pole, along the boundary Fencing, removing rubbish from the Site of Work and deposting where directed not exc. 100 Metre from the starting Point, complete all as specified and as directed. Note : The Item shall be operated maximum 2 times in the entire period of the Contract and the measurement will be taken every time independently for Payment.
Supply, installing out door type Feeder Pillar Box of size 750 x 600 x 450mm, padestal mounted, CPRI approved factory made totally enclosed, dust and vermin proof, shutter in front side made of 3.15 mm thick CRCA sheet, duly fabricated and having proper locking arrangement and painted with powder coating paint and mounted on PCC Platform all round the Feeder Pillar Box complete including copper bus bar TPN 415 Volts, 50 Hz, 100 to 300 Amp duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and rating as per site requirment and good insulation resistance with removal of old unseviceable pedestal type Feeder Pillar Box, complete all as specified and as directed.
Supply,installing, testing and commissioning Outdoor type LT panel of suitable size, padestal mounted, CPRI approved factory made totally enclosed, dust and vermin proof, double leaf shutter in rear side made of 3.15 mm thick CRCA sheet, duly fabricated and having proper locking arrangement in rear door and painted with powder coating paint and suitable for 440 volts, 50 Hz, 3 phase 4 wire internal wiring system and comprising with and including following accessories and mounted on PCC Plat form all round the panel board complete including removal of old unseviceable pedestal type panel with the following items housed in :- Location - 400 KVA , Govind nagar (a) 1000 Amps rated copper bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code (b) Incomer ACB 4 Pole 630 Amps, 415 Volts Microprocessor release type breaking capacity Icu=Ics=Icw (01 Sec) 50 KA, MDO Version C-Power draw out ACBs will have inbuilt -02NO+02NC Aux contact for MDO including Shafety shutter assembly, racking handle , door sealing frame , push button cover & rating error preventor , Type C-power S-1 MDO version Make :- L&T catpart No.SL96061 - 01 Nos (c) Outgoing MCCB 4 Pole 250 Amps, thermal magnetic type breaking capacity 25 KA with thermal magnetic release at 415 volts, Type DN1-250C Make :- L&T catpart No. CM90642OOPO -04 Nos (d) Incomer MCCB 4 Pole 200 Amps, thermal magnetic type breaking capacity 25 KA with thermal magnetic release at 415 volts, Type DN1-250C Make :- L&T catpart No. CM90642OONO - 01 nos (e) LED frequency meter CI 0.2 - 01 Nos (f) Three Phase Voltmeter CI 0.5 Input voltage measurement range 50-520 Make L&T Catpart No. WL132020OOOO - 01 Nos (g) Three phase Ammeter CI 0.5 with CT copper wound CT Coil Make :- L&T Catpart No. WL132020OOOO - 01 Nos (h) Indicator Lamps (LED type) & bakelite fuse showing R,Y, B phase - 01 Set Note :-(1) All switchgear shall be confirming to IS/IEC 60947-2 including adjustable overload setting : 0.8 x1.0 x In, adjustable short circuit setting : 6 - 10 X In and 100 % Ics of Icu. (2) All switchgear shall be connected with copper bus bar with extended spreader Link . (3) Rotatary switch shall be provided for operation of switch gears
Supply,installing, testing and commissioning Outdoor type LT panel of suitable size, padestal mounted, CPRI approved factory made totally enclosed, dust and vermin proof, double leaf shutter in rear side made of 3.15 mm thick CRCA sheet, duly fabricated and having proper locking arrangement in rear door and painted with powder coating paint and suitable for 500 volts, 50 Hz, 3 phase 4 wire internal wiring system and comprising with and including following accessories and mounted on PCC Plat form all round the panel board complete including removal of old unseviceable pedestal type panel with the following items housed in :- Location - 150 KVA , 4 Corps OMC (a) 400 Amps rated copper bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code (b) Incomer MCCB 4 Pole 250 Amps, thermal magnetic type breaking capacity 25 KA with thermal magnetic release at 415 volts, Type DN1-250C Make :- L&T catpart No. CM90642OOPO - 01 Nos (c) outgoing MCCB 4 Pole 200 Amps, thermal magnetic type breaking capacity 25 KA with thermal magnetic release at 415 volts, Type DN1-250C Make :- L&T catpart No. CM90642OONO - 02 Nos (d) ougoing MCCB 4 Pole 100 Amps, thermal magnetic type breaking capacity 25 KA with thermal magnetic release at 415 volts, Type DN0-100 C Make :- L&T catpart No. CM91712OOKOOG - 02 Nos (e) Outgoing MCB 4 Pole 32 Amps, C-curve Make :- L&T catpart NO.BB40320C - 01 Nos (f) LED frequency meter CI 0.2 - 01 Nos (g) Three Phase Voltmeter CI 0.5 Input voltage measurement range 50-520 Make L&T Catpart No. WL132020OOOO - 01 Nos (h) Three phase Ammeter CI 0.5 with CT copper wound CT Coil Make :- L&T Catpart No. WL132020OOOO - 01 Nos (j) Indicator Lamps (LED type) & bakelite fuse showing R,Y, B phase - 01 Set Note :-(1) All switchgear shall be confirming to IS/IEC 60947-2 including adjustable overload setting : 0.8 x1.0 x In, adjustable short circuit setting : 6 - 10 X In and 100 % Ics of Icu. (2) All switchgear shall be connected with copper bus bar with extended spreader Link . (3) Rotatary switch shall be provided for operation of switch gears
S & F and testing MCCB 4 pole 63 Amps of breaking capacity 25 KA suitable for 415 volts, 50 Hz, with extended terminal in existing LT Panel , including removal of existing unsv one complete all as specified and directed :- Make :- L&T Catpart No.CM9712OOHOOG /Havells/legrand
S & F and testing MCCB 4 pole 100 Amps of breaking capacity 25 KA suitable for 415 volts, 50 Hz, with extended terminal in existing LT Panel , including removal of existing unsv one complete all as specified and directed :- Make :- L&T Catpart No.CM90642OOLO /Havells/legrand
S & F and testing MCCB 4 pole 160 Amps of breaking capacity 25 KA suitable for 415 volts, 50 Hz, with extended terminal in existing LT Panel , including removal of existing unsv one complete all as specified and directed :- Make :- L&T Catpart No.CM90642OOMO /Havells/legrand
S & F and testing MCCB 4 pole 200 Amps of breaking capacity 36 KA suitable for 415 volts, 50 Hz, with extended terminal in existing LT Panel , including removal of existing unsv one complete all as specified and directed :- Make :- L&T Catpart No.CM92109OO1OG /Havells/legrand
S & F and testing MCCB 4 pole 250 Amps of breaking capacity 36 KA suitable for 415 volts, 50 Hz, with extended terminal in existing LT Panel , including removal of existing unsv one complete all as specified and directed :- Make :- Make :- L&T Catpart No.CM98403OOQOOG /Havells/legrand
S & F and testing MCCB 4 pole 400 Amps of breaking capacity 36 KA suitable for 415 volts, 50 Hz, with extended terminal in existing LT Panel , including removal of existing unsv one complete all as specified and directed :- Make :- L&T Catpart No.CM98403OOROOG /Havells/legrand
S & F connecting and testing thermal magnectic ACB in existing LT Panel of capacity 630 Amps breaking capacigty 50 KA suitable for 415 volts, 50 Hz, with extended terminals type, interlocked to prevent opening when the Switch is in ON Position, confirming to IS /IEC 60947-2, high mechanical and electrical operating life protection through thermal magnectic DN-1 and connecting and testing complete including removal of exiting unsv all as specified and directed by Engr-in-charge.Make :- L&T catpart No. SL95331 or equivallent make of havells/legrand
M & L boaring holes horizontally under Road without damaging the surface of road ( minimum 1.0 Mtr below the road surface with the help of GI tubing of any dia not exceed 80 mm bore for passing of UG cable all mas specified and as directed ( GI pipe laid shall be measured seperately).
Material and labour straight through joint (epoxy type) including jointing kit complete for making joints suitable for UG aluminium conductor cable 3 ½ core of size 35 Sqmm to 50 Sqmm complete all as specified and direcetd.Make : Denson/M-seal
Material and labour straight through joint (epoxy type) including jointing kit complete for making joints suitable for UG aluminium conductor cable 3 ½ core of size 70 Sqmm to 95 Sqmm complete all as specified and direcetd.Make : Denson/M-seal
Material and labour straight through joint (epoxy type) including jointing kit complete for making joints suitable for UG aluminium conductor cable 3 ½ core of size 120 Sqmm to 185 Sqmm complete all as specified and direcetd.Make : Denson/M-seal
Supply and fixing copper cable 16 sqmm single core , fixing in Lt panel from bus bar to switch gear as connector lead including taking down old unserviceable one complete all as specified and directed by engr - in charge. Make :- Polycab or equivallent make of havells or KEI
M & L for servicing of Lt panel by checking connection of busbar with switchgear, internal wiring system of metering devices, proper fixing of switch gear, replacing of burned/damaged insulators,connecting copper lead with held of copper lugs ,nut bolts, replacing of unserviceable copper bus bars, coplete all as specified and directed by Engr -n-charge . Note: cost of copper lead wire and copper bus bar shall be paid seperately.
Supply and fixing copper bus bar of any size in existing Lt panel , including removal of old unserviceable , coplete all as specified and directed by Engr.in.charge
Supply and fixing aluminium lug 25 sqmm in existing panel or LV side of disgtribution transformer including removal of old unserviceable one compelete all as specified and directed by engr-in-charge. Make :- Dowells
Supply and fixing aluminium lug 35 sqmm in existing panel or LV side of disgtribution transformer with help of pressure crimping tool including removal of old unserviceable one compelete all as specified and directed by engr-in-charge.Make :- Dowells
Supply and fixing aluminium lug 50 sqmm in existing panel or LV side of disgtribution transformer with help of pressure crimping tool including removal of old unserviceable one compelete all as specified and directed by engr-in-charge.Make :- Dowells
Supply and fixing aluminium lug 70 sqmm in existing panel or LV side of disgtribution transformer with help of pressure crimping tool including removal of old unserviceable one compelete all as specified and directed by engr-in-charge.Make :- Dowells
Supply and fixing aluminium lug 95 sqmm in existing panel or LV side of disgtribution transformer with help of pressure crimping tool including removal of old unserviceable one compelete all as specified and directed by engr-in-charge.Make :- Dowells
Supply and fixing aluminium lug 120 sqmm in existing panel or LV side of disgtribution transformer with help of pressure crimping tool including removal of old unserviceable one compelete all as specified and directed by engr-in-charge.Make :- Dowells
Supply and fixing aluminium lug 150 sqmm in existing panel or LV side of disgtribution transformer with help of pressure crimping tool including removal of old unserviceable one compelete all as specified and directed by engr-in-charge.
Supply and fixing aluminium lug 185 sqmm in existing panel or LV side of disgtribution transformer with help of pressure crimping tool including removal of old unserviceable one compelete all as specified and directed by engr-in-charge.Make :- Dowells
Supply and fixing aluminium lug 300 sqmm in existing panel or LV side of disgtribution transformer with help of pressure crimping tool including removal of old unserviceable one compelete all as specified and directed by engr-in-charge.Make :- Dowells
Supply and fixing aluminium lug 400 sqmm in existing panel or LV side of disgtribution transformer with help of pressure crimping tool including removal of old unserviceable one compelete all as specified and directed by engr-in-charge.Make :- Dowells
M&L for Earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below ground level connected to galvanized iron 25X4 mm as earthing lead by mean of nut/bolt and washer of galvanized iron or steel drawn through 40 mm dia light grade GI pipe as shown in electrical plate no 3 of SSR part I of 2009 including necessary excavation and earth work GI pipe 20mm dia light grade for watering PCC chamber with PCC cover in cement concrete 1:2:4 Type B1(20mm graded aggregate), funnel, wire mesh, charcoal dust, salt etc, connected to panel board / Gen Set as indicated including testing complete.
United Traders
bkgeneralstores
M/S RANA ENGINEERING ENTERPRISE
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .